1-1. Tools Required for Installation (not supplied)
1-2. Accessories Supplied with Unit
1-3. Optional Copper Tubing Kit
1-4. Type of Copper Tube and Insulation Material
1-5. Additional Materials Required for Installation
2.INSTALLATION SITE SELECTION ................... 4
2-1. Indoor Unit
2-2. Outdoor Unit
3.HOW TO INSTALL THE INDOOR UNIT ............ 6
3-1. Preparation for Suspending
3-2. Suspending the Indoor Unit
3-3. Placing the Unit Inside the Ceiling
3-4. Installing the Drain Piping
3-5. Checking the Drainage
3-6. How to Install the Ceiling Panel
3-7. Wiring Instructions
3-8. Recommended Wire Length and Diameter
3-9. Wiring Instructions for Inter-unit Connections
4.HOW TO INSTALL THE OUTDOOR UNIT ....... 14
4-1. Wiring Instructions for the Outdoor Unit
Refrigerant service valve size = 5/16"
Page
COOL/ DRY/HEAT Model
Model Combinations
Combine indoor and outdoor units only as listed
below.
Indoor UnitOutdoor Unit
XHS1271CH1271
Power Source:
60 Hz, single-phase, 115 V
XHS1872CH1872
Power Source:
60 Hz, single-phase, 230/208 V
Ceiling Panel
PNR-XS1872
Be sure to read the yellow instruction sheet
attached to the outdoor unit for models using the
new refrigerant R410A.
7.REMOTE CONTROL UNIT INSTALLATION
POSITION ......................................................... 21
5-1. Use of the Flaring Method
5-2. Flaring Procedure with a Flare Tool
5-3. Caution before Connecting Tubes Tightly
5-4. Connecting Tubing between Indoor and
Outdoor Units
5-5. Insulation of Refrigerant Tubing
5-6. Taping the Tubes
5-7. Finishing the Installation
The illustrations are based on the typical appearance of
a standard model. Consequently, the shape may differ
from that of the air conditioner that you are installing.
SANYO Commercial SolutionsIn Canada
A Division of SANYO North America CorporationSANYO Canada Inc.
1300 Michael Drive, Suite A1-300 Applewood Crescent, Concord
Wood Dale, IL 60191, U.S.A.Ontario, L4K 5C7, Canada
Page 2
IMPORTANT!
WARNING
WARNING
CAUTION
CAUTION
Please Read Before Starting
This air conditioning system meets strict safety and operating
standards. As the installer or service person, it is an important
part of your job to install or service the system so it operates
safely and efficiently.
For safe installation and trouble-free operation, you
must:
G
Carefully read this instruction booklet before beginning.
G
Follow each installation or repair step exactly as shown.
G
Observe all local, state, and national electrical codes.
G
Pay close attention to all warning and caution notices
given in this manual.
This symbol refers to a hazard
or unsafe practice which can
result in severe personal injury
or death.
This symbol refers to a hazard
or unsafe practice which can
result in personal injury or product or property damage.
If Necessary, Get Help
These instructions are all you need for most installation
sites and maintenance conditions. If you require help for a
special problem, contact our sales/service outlet or your
certified dealer for additional instructions.
In Case of Improper Installation
The manufacturer shall in no way be responsible for improper installation or maintenance service, including failure to
follow the instructions in this document.
SPECIAL PRECAUTIONS
When Installing…
…In a Ceiling or Wall
Make sure the ceiling/wall is strong enough to hold the
unit’s weight. It may be necessary to construct a strong
wood or metal frame to provide added support.
…In a Room
Properly insulate any tubing run inside a room to prevent
“sweating” that can cause dripping and water damage to
walls and floors.
…In Moist or Uneven Locations
Use a raised concrete pad or concrete blocks to provide a
solid, level foundation for the outdoor unit. This prevents
water damage and abnormal vibration.
…In an Area with High Winds
Securely anchor the outdoor unit down with bolts and a
metal frame. Provide a suitable air baffle.
…In a Snowy Area (for Heat Pump-type Systems)
Install the outdoor unit on a raised platform that is higher
than drifting snow. Provide snow vents.
When Connecting Refrigerant Tubing
• Use the flare method for connecting tubing.
• Apply refrigerant lubricant to the matching surfaces of
the flare and union tubes before connecting them, then
tighten the nut with a torque wrench for a leak-free
connection.
• Check carefully for leaks before starting the test run.
When Servicing
When Wiring
ELECTRICAL SHOCK CAN CAUSE SEVERE
PERSONAL INJURY OR DEATH. ONLY A
QUALIFIED, EXPERIENCED ELECTRICIAN
SHOULD ATTEMPT TO WIRE THIS SYSTEM.
• Do not supply power to the unit until all wiring and tubing
are completed or reconnected and checked.
• Highly dangerous electrical voltages are used in this
system. Carefully refer to the wiring diagram and these
instructions when wiring. Improper connections and
inadequate grounding can cause accidental injury or
death.
• Ground the unit following local electrical codes.
• Connect all wiring tightly. Loose wiring may cause overheating at connection points and a possible fire hazard.
When Transporting
Be careful when picking up and moving the indoor and outdoor units. Get a partner to help, and bend your knees when
lifting to reduce strain on your back. Sharp edges or thin aluminum fins on the air conditioner can cut your fingers.
• Turn the power OFF at the main power box (mains) before
opening the unit to check or repair electrical parts and
wiring.
• Keep your fingers and clothing away from any moving
parts.
• Clean up the site after you finish, remembering to check
that no metal scraps or bits of wiring have been left inside
the unit being serviced.
Others
• Ventilate any enclosed areas when installing or testing
the refrigeration system. Escaped refrigerant gas, on
contact with fire or heat, can produce dangerously
toxic gas.
• Confirm upon completing installation that no refrigerant
gas is leaking. If escaped gas comes in contact with a
stove, gas water heater, electric room heater or other heat
source, it can produce dangerously toxic gas.
2
Page 3
Printed on
container box
For unit & PVC
tube connection
For drain hose
connection
RemarksQ’ty
For full-scale
installation
diagram
1
2
4
1
4
4
4
2
1
For temporarily
suspending indoor
unit from ceiling
Flare
insulation
For wide /
narrow tube
connection
For wide /
narrow tube /
flare nut connection
For flare / drain
insulating
connection
For drain tube
connection
Insulation tape
Vinyl tie
Drain hose
insulation
Washer
AAA alkaline
battery
Remote
control unit
Remote control
unit holder
PartsPartsFigureRemarksQ’tyFigure
Drain hose
Full-scale
installation
diagram
5-1/2"(L140)
Hose band
Truss head screw
Truss head screw
Hex wrench
Special screw
Cushion rubber
Tapping screw
8
2
set
2
8
1
1
1
2
1/8"(T3)
3/16"(T5)
13/32"(T10)
3/32"(T2)
Truss-head Phillips
5/32 5/8"
(4 16mm)
3/16 13/32"
(5 10mm)
5/32 15/32"
(4 12mm)
3/16 1-9/16"
(5 40mm)
Packed in the
outdoor unit
Packed in the
ceiling panel
Use M10 or 3/8" for suspension bolts.
Suspension bolts and nuts (locally purchased)
1. General
CAUTION
This booklet briefly outlines where and how to install the air conditioning system. Please read over the entire set of instructions for the indoor and outdoor units and make sure all accessory parts listed are with the system before beginning.
1-1. Tools Required for Installation (not supplied)
1. Standard screwdriver
2. Phillips head screwdriver
3. Knife or wire stripper
4. Tape measure
5. Carpenter’s level
1-2. Accessories Supplied with Unit
Table 1
6. Sabre saw or key hole saw
7. Hacksaw
8. Core bits
9. Hammer
10. Drill
11. Tube cutter
12. Tube flaring tool
13. Torque wrench
14. Adjustable wrench
15. Reamer (for deburring)
1-3. Optional Copper Tubing Kit
Copper tubing for connecting the outdoor unit to the indoor unit is available in kits which contain the narrow and wide
tubing, fittings and insulation. Consult your nearest sales outlet or air conditioning workshop.
1-4. Type of Copper Tube and Insulation Material
If you wish to purchase these materials separately from a local source, you will need:
1.Deoxidized annealed copper tube for refrigerant tubing as detailed in Table 2.
Cut each tube to the appropriate lengths 1' to 1'4" (30 cm to 40 cm) to dampen vibration between units.
2.Foamed polyethylene insulation for the specified copper tubes as required to precise length of tubing. Wall thickness
of the insulation should be not less than 5/16" (8 mm).
3.Use insulated copper wire for field wiring. Wire size varies with the total length of wiring. Refer to 3-7. Wiring
Instructions for details.
Check local electrical codes
and regulations before
obtaining wire. Also, check
any specified instructions or
limitations.
Page 4
1-5. Additional Materials Required for Installation
3.3 ft.
(1m)
(1m)
(1m)
3.3 ft.
(1m)
3.3 ft.
3.3 ft.
3.3 ft.
(1m)
Tubing length (L)
Elevation difference (H)
Outdoor unit
Indoor unit
WARNING
CAUTION
1.Refrigeration (armored) tape
2.Insulated staples or clamps for connecting wire
(See local codes)
3.Putty
4.Refrigeration lubricant
5.Clamps or saddles to secure refrigerant tubing
2. Installation Site Selection
2-1. Indoor Unit
To prevent abnormal heat generation and the possibility of fire, do
not place obstacles, enclosures
and grilles in front of or surrounding the air conditioner in a way
that may block air flow.
AVOID:
G direct sunlight.
G nearby heat sources that may affect performance of the unit.
G areas where leakage of flammable gas may be expected.
G places where large amounts of oil mist exist.
DO:
G select an appropriate position from which every corner of
the room can be uniformly cooled.
G select a location that will hold the weight of the unit.
G select a location where tubing and drain hose have the
shortest run to the outside.
G allow room for operation and maintenance as well as unre-
stricted air flow around the unit. (Fig. 1)
G install the unit within the maximum elevation difference (H)
above or below the outdoor unit and within a total tubing length
(L) from the outdoor unit as detailed in Table 3 and Fig. 2.
G install the indoor unit more than 3.3' (1 m) away from any
antenna or power lines or connecting wires used for television,
radio, telephone, security system, or intercom. Electrical noise
from any of these sources may affect operation.
Fig. 1
Fig. 2
Air delivery will be degraded if the distance
from the floor to the ceiling is greater than
10 ft. (3 m).
Table 3
Max. Allowable Tubing Limit of TubingLimit of ElevationRequired Amount of
ModelLength at ShipmentLength (L)Difference (H)Additional Refrigerant
XHS12712565230.16
XHS18722598500.27
* If total tubing length becomes 25 to 65 ft. (Max.) or 25 to 98 ft. (Max.), charge additional refrigerant (R410A) by 0.16 or 0.27 oz./ft.
No additional charge of compressor oil is necessary. For more detailed charging information, refer to the Technical & Service Manual.
(ft.)(ft.)(ft.)(oz./ft.)*
4
Page 5
2-2. Outdoor Unit
Outdoor unit
Hot air
Heat source
Exhaust fan
NO
CAUTION
Min.
7' (2 m)
Min.
7' (2 m)
Ground
Obstacle
Obstacle above
Air discharge
Min. 4" (10 cm)
Air intake
AVOID:
G heat sources, exhaust fans, etc. (Fig. 3)
G damp, humid or uneven locations.
DO:
G choose a place as cool as possible.
G choose a place that is well ventilated.
G install in a location where at least two sides are unob-
structed, so that the flow of air at the intake port or
exhaust port is not blocked, and so that sufficient
space is ensured for maintenance to be carried out
without trouble. In general the top also must be unobstructed. (Figs. 4a and 4b)
G provide a solid base (level concrete pad, concrete
block, 4" × 1'4" (10 × 40 cm) beams or equal), a minimum of 4" (10 cm) above ground level to reduce
humidity and protect the unit against possible water
damage and decreased service life. (Figs. 5a and 5b)
(CH1271)
Air intakeMin. 2" (5 cm)
Min.
2" (5 cm)
Air discharge
Fig. 3
Valve
side
Min. 10"
(25 cm)
Min.
8" (20 cm)
Obstacle above
Min.
7' (2 m)
Air discharge
Min.
7' (2 m)
Obstacle
A solid base must not cover
the hole of the bottom plate.
G install cushion rubber under unit’s feet to reduce vibra-
tion and noise. (Fig. 5c)
G use lug bolts or equal to bolt down unit, reducing vibra-
tion and noise.
G install in a location where no antenna of a television or
radio exists within 10' (3 m).
Drain holes
Fig. 5a
Anchor bolts
(4 pcs.)
(CH1872)
Air intakeMin. 4" (10 cm)
Min.
2" (5 cm)
Air discharge
Min.
1'4" (40 cm)
Fig. 4a
Valve
side
Min. 10"
(25 cm)
Fig. 4b
Ground
Min. 2" (5 cm)
Air intake
Air intake
Concrete
or equal
Abou
t 1'4" (40 cm)
About 4" (10 cm)
Fig. 5bFig. 5c
Min. 4" (10 cm)
Cushion rubber
5
Page 6
Hole-in-anchor
ConcreteInsert
Suspension bolt (M10 or 3/8")
Hole-in-plug
(locally purchased)
1/2" — 23/32" (13~18
mm
)
Over 19/32" (15
mm
)
Supplied screw
Full-scale installation diagram
(printed on top of container box)
3. How to Install the Indoor Unit
Nuts and washers
(used for upper and lower)
Double nut
Notch
Suspension lug
Suspension bolt
1/2" — 23/32"
(13~18
mm
)
3-1. Preparation for Suspending
This unit uses a drain pump. Use a carpenter’s level to
check that the unit is level.
3-2. Suspending the Indoor Unit
(1) Fix the suspension bolts securely in the ceiling using
the method shown in the diagrams, by attaching
them to the ceiling support structure, or by any other
method that ensures that the unit will be securely
and safely suspended. (Fig. 6-1)
(2) Follow the diagram to make the holes in the ceiling.
Fig. 6-1
23-5/8"(600mm)
Ceiling opening dimensions
21-1/32"(534
Suspension bolt pitch
mm
)
(3) Determine the pitch of the suspension bolts using
the supplied full-scale installation diagram. The diagram shows the relationship between the positions
of the suspension fitting, unit, and panel. (Fig. 6-2)
3-3. Placing the Unit Inside the Ceiling
(1) Be sure to remove the fan protection (4pcs) for
transportation before hanging up the indoor unit.
(2) When placing the unit inside the ceiling, determine
the pitch of the suspension bolts using the supplied
full-scale installation diagram. (Fig. 6-3)
Tubing and wiring must be laid inside the ceiling
when suspending the unit. If the ceiling is already
constructed, lay the tubing and wiring into position
for connection to the unit before placing the unit
inside the ceiling.
(3) The length of suspension bolts must be appropriate
for a distance between the bottom of the bolt and the
bottom of the unit of more than 19/32" (15 mm) as
shown in the diagram. (Fig. 6-3)
Drain tube
connection port
(outer dia 1-1/32"( 26mm))
)
mm
)
mm
(215
8-15/32"
11-5/32"(283
)
mm
1-3/16"
(30
(4) Thread the 3 hexagonal nuts (locally purchased) and
2 supplied washers onto each of the 4 suspension
bolts as shown in the diagram. Use 1 nut and 1
washer for the upper side, and 2 nuts and 1 washer
for the lower side, so that the unit will not fall off the
suspension lugs. (Fig. 6-4)
(5) Adjust so that the distance between the unit and the
ceiling bottom is 1/2" (13 mm) to 23/32" (18 mm).
Tighten the nuts on the upper side and lower side of
the suspension lug. (Fig. 6-4)
Fig. 6-3
Fig. 6-4
6
Page 7
Drain port
Twist tie
(4 vinyl ties, supplied)
Hard PVC pipe
Position to
Drain hose
(supplied)
Hose band
(2 bands, supplied)
3/16"
(5
mm
)
3/16"
(5mm)
15/16"
(25mm)
15/16"
(25mm)
5-1/2"(140
mm
)
Drain hose
(locally purchased)
bands
(supplied)
O.D. 1-1/32" (26mm))
fasten hose
insulation
(equivalent to
Unit
Air bleeder prohibited
Support
bracket
Uphill slope
3-4. Installing the Drain Piping
1 ft.(300mm) or less
0 - 45
2.78 ft.(850
mm
) or less
* Length of supplied drain hose = 5-1/2"(140
mm
)
CAUTION
CAUTION
CAUTION
(1) Prepare standard hard PVC pipe (locally purchased O.D.
1-1/32" (26 mm)) for the drain and use the supplied hose
band to prevent water leaks. (Fig. 6-5)
(2) To install the drain hose, first place 1 of the 2 hose bands
over the unit drain port and the other hose band over the
hard PVC pipe (not supplied). Then connect both ends of
the supplied drain hose. (Fig. 6-5)
(3) On the unit drain side, grasp the hose band with pliers
and insert the drain hose all the way to the base.
G If other commercially available hose bands are used, the
drain hose may become pinched or wrinkled and there is
danger of water leakage. Therefore be sure to use the
supplied hose bands. When sliding the hose bands, be
careful to avoid scratching the drain hose.
G Do not use adhesive when connecting the supplied drain
hose to the drain port (either on the main unit or the PVC
pipe).
Reasons:a) It may cause water to leak from the connec-
tion. Since the connection is slippery just
after the adhesive has been applied, the
pipe easily slips off.
b) The pipe cannot be removed when mainte-
nance is needed.
Fig. 6-5
G Attach so that the hose band
fastener is on the side of the
drain port.
G Attach the hose bands so that
each is approximately 3/16"
(5 mm) to 15/16" (25 mm) from
the end of the supplied drain
hose.
(4) Wrap the hose with the supplied drain hose insulation
and use the 4 twist ties so that the hose is insulated with
no gaps.
G Do not bend the supplied drain hose 90° or more. The
hose may slip off.
NOTE
Make sure the drain pipe has a downward gradient (1/100 or
more) and that there are no water traps.
G In cases where it is necessary to raise the height of the
drain piping, the drain piping can be raised to a maximum
height of 2.78 ft. (850 mm) above the bottom surface of
the ceiling. Under no conditions attempt to raise it higher
than 2.78 ft. (850 mm) above the bottom surface of the
ceiling. Doing so will result in water leakage. (Fig. 6-7)
G Do not use natural drainage.
G Do not install the pipe with an upward gradient from the
connection port. This will cause the drain water to flow
backward and leak when the unit is not operating.
G Do not apply force to the piping on the unit side when
(Fig. 6-8)
connecting the drain pipe. The pipe should not be
allowed to hang unsupported from its connection to the
unit. Fasten the pipe to a wall, frame, or other support as
close to the unit as possible. (Fig. 6-9)
G Provide insulation for any pipes that are run indoors.
Fig. 6-6
G Do not install an air bleeder as
this may cause water to spray
from the drain pipe outlet.
(Fig. 6-6)
Fig. 6-7
Fig. 6-8
Fig. 6-9
7
Page 8
A
must be within the range of 1/2"(13mm) to 23/32"(18mm). (Fig. 6-11)
If not within this range, malfunction or other trouble may occur.
Ceiling opening
dimension
Ceiling side
A
Indoor unit
3-5. Checking the Drainage
CAUTION
CAUTION
2
1
Water drain
Control box
Drain pan outlet
Water
Plastic container
for water intake
Over 4"
(100
mm
)
(Approx. 16 ounces (500m ) )
Flap
NO
Latch
Air-intake grille
Ceiling panel
Air-intake grille hinge
1
1
FS
FLAP
Control box
RCIND
After wiring and drain piping are completed, use the following procedure to check that the water will drain smoothly. For this, prepare a bucket and wiping cloth to catch and wipe up spilled water.
G Be sure to do the wiring between the units before installing the
ceiling panel. (Refer to 3-9. Wiring Instructions for Inter-unit
Connections)
(1) Turn on the power. (Here, “power” refers to the power supply
from the outdoor unit.)
(2) Slowly pour approx. 16 ounces (500 ml) of water into the drain
pan to check drainage. (Fig. 6-10a)
(3) Remove the 2 screws from the control box cover, then open
the cover. Be careful not to drop the cover at this time.
(4) Disconnect the FS 3P connector (red) on the control PCB and
operate the drain pump. (Fig. 6-10b) Check the water flow
through the transparent drain pipe and see if there is any
leakage.
(5) When the check of drainage is complete, reconnect the FS
3P connector and remount the control cover.
The drain pump will continue to
operate for a minimum of 6 minutes after the FS 3P connector is
reconnected.
Fig. 6-10a
Fig. 6-10b
3-6. How to Install the Ceiling Panel
Checking the unit position
(1) Check that the ceiling hole is 23-5/8" (600 mm) × 23-5/8"
(600 mm) (Fig. 6-11)
(2) Confirm that the position of the indoor unit and the ceiling
as shown in the diagram. If the positions of the ceiling surface and unit do not match, air leakage, water leakage, flap
operation failure, or other problems may occur. (Fig. 6-11)
G Never place the panel face-down. Neither hang it ver-
tically nor place it on top of a projecting object. Placing it face-down will damage the surface.
G Do not touch the flap or apply force to it. (This may
cause flap malfunction.) (Fig. 6-12)
3-6-1. Before Installing the Ceiling Panel
(1) Remove the air-intake grille and air filter from the ceiling
panel.
a) Press on and slide the two latches of the air-intake grille
with your thumb in the direction shown by the arrow
to open the grille. (Figs. 6-13 and 6-14)
b) With the air-intake grille opened, remove the grille hinge
from the ceiling panel by sliding it in the direction shown
by the arrow . (Fig. 6-15)
Fig. 6-12
Fig. 6-14
Fig. 6-11
Fig. 6-13
2
Fig. 6-15
8
Page 9
(2) Removing the corner cover and
CAUTION
latch
Temporary latches
Temporary
DRAIN mark
Ceiling panel
Special screws
Refrigerant tubing joint
Drainage check
REF.PIPE mark
Panel installation hole
(4 locations)
Indoor unit
Ceiling panel
Ceiling surface
Do not allo
w
gaps
indicator cover
a) While lightly pressing the cen-
ter of the corner cover, pull up
the tab for the screw hole.
Use the same procedure to
remove the indicator cover.
(Fig. 6-16)
Corner cover
1
Press
2
Pull up
Indicator cover
3-6-2. Installing the Ceiling Panel
(1) Hang the temporary latches on the inside of the ceil-
ing panel to the receptacle on the unit to temporarily
attach the ceiling panel in place. (Fig. 6-17)
G The ceiling panel must be installed in the correct
direction relative to the unit. Align the REF. PIPE and
DRAIN marks on the ceiling panel corner with the
correct positions on the unit.
(2) Align the panel installation holes and the unit screw
holes. (Fig. 6-18)
(3) Tighten the supplied special screws at the 4 panel
installation locations so that the panel is attached
tightly to the unit.
G Check that the wiring connectors are not caught
between the unit and the ceiling panel.
(4) Check that the panel is attached tightly to the ceiling.
(Fig. 6-19)
G At this time, make sure that there are no gaps
between the unit and the ceiling panel, or between
the ceiling panel and the ceiling surface.
G If there is a gap between the panel and the ceiling,
leave the ceiling panel attached and make fine
adjustments to the installation height of the unit to
eliminate the gap with the ceiling.
Fig. 6-16
Fig. 6-17
Fig. 6-18
If the screws are not sufficiently tightened,
trouble such as that shown in the figure
below may occur. Be sure to tighten
the screwssecurely.
Air leakage
Air leakage from
ceilingsurface
Staining
Condensation, water leakage
If a gap remains between the ceiling
surface and the ceiling panel even
after the screws are tightened,
adjust the height of the unit again.
Adjust so that there are no gaps.
Fig. 6-20
Fig. 6-19
The height of the unit can be adjusted from the ceiling
panel corner hole, with the ceiling panel attached, to
an extent that doesnot affect the unit levelness,
the drain hose, or other elements.
9
Page 10
fit into the holes in the ceiling panel.
Place the corner cover so that the 3 tabs
Then fasten it in place with the supplied screws.
Pin
Hole for ceiling
panel hook
the grille from
dropping
Hook that prevents
Can be installed rotated 90
* The grille can be installed
with these hinges facing
in any of 4 directions.
3-6-3. Wiring the Ceiling Panel and the Indicator
FLAP
RCIND
Indicator
Indicator
7P IND and 4P RC wiring connector
7P IND and 4P RC
Ceiling panel
5P FLAP wiring connector
Clamps
Control box
Indoor unit
* Pass the wiring connectors through the clamps to fasten them in place,
as shown in the figure.
wiring connector
7P
4P
5P
5P FLAP
wiring connector
Control box
As to how to attach the indicator cover, refer to Fig.6-23.
Drain pipe side
Refrigerant tube side
Indicator cover
Power box
(1) Remove the 2 screws from the control box cover, then open
the cover. Be careful that the cover does not fall.
(2) Connect the 5P FLAP wiring connector from the ceiling
panel to the connector on the control PCB in the control box.
(Fig. 6-21)
(3) Connect the 7P IND and 4P RC wiring connector from the
indicator to the connectors on the control PCB in the control
box. (Fig. 6-21)
(4) Be sure to use the clamps to fasten the connector wires in
place. (Fig. 6-21)
(5) Tighten the 2 cover screws to
close the cover.
G Check that the wiring
connectors are not caught
between the electrical
component box and the cover.
G If the indicator connector is
not securely connected,
the remote controller
signal will not be
received.
G If the connectors are not
connected, the auto flap will not
operate. Be sure
to connect them securely.
Fig. 6-22
3-6-4. How to Attach the Corner Cover and Air-Intake Grille
A. Attaching the corner cover
(1) Check that the safety strap from the corner cover is fas-
tened to the ceiling panel pin, as shown in the figure.
(Fig. 6-23)
(2) Use the supplied screws to attach the corner cover to the
ceiling panel.
B. Attaching the air-intake grille
G To install the air-intake grille, follow the steps for 3-6-1.
Before Installing the Ceiling Panel in the reverse order.
By rotating the air-intake grille, it is possible to attach the
grille onto the ceiling panel
from any of 4 directions.
(Fig. 6-25)
G When attaching the air-intake
grille, be careful that the flap
and the indicator wiring do
not become caught.
G Be sure to attach the safety
cord that prevents the air-intake
grille from dropping off to the
ceiling panel unit as shown
in Fig. 6-24.
Fig. 6-21
Fig. 6-23
Fig. 6-24Fig. 6-25
10
Page 11
3-6-5. Checking After Installation
G Check that there are no gaps between the unit and the ceiling panel, or between the ceiling panel and the ceiling sur-
face. Gaps may cause water leakage and condensation.
G Check that the wiring is securely connected.
If it is not securely connected, the auto flap will not operate. In addition, water leakage and condensation may occur.
3-6-6. When Removing the Ceiling Panel for Servicing
When removing the ceiling panel for servicing, remove the air-intake grille and air filter, disconnect the flap and the indicator wiring connectors inside the control box, and then remove the 4 mounting screws.
3-6-7. Adjusting the Auto Flap
The air-direction flap on the ceiling panel outlet can be adjusted as follows.
G Adjust the flap to the desired angle using the remote controller. The flap also has an automatic air-sweeping mecha-
nism.
NOTE
G Never attempt to move the flap by hand.
G Proper air flow depends on the location of the air conditioner, the layout of the room and furniture, etc. If cooling or
heating seems inadequate, try changing the direction of the air flow.
3-7. Wiring Instructions
General precautions on wiring
(1) Before wiring, confirm the rated voltage of the unit as shown on its nameplate,
then carry out the wiring closely following the wiring diagram.
(2) Provide a power outlet to be used exclusively for each unit, with a power supply
disconnect and circuit breaker for overcurrent protection provided in the exclusive line.
(3) To prevent possible hazards due to insulation failure, the unit must be grounded.
(4) Each wiring connection must be done tightly and in accordance with the wiring
system diagram. Wrong wiring may cause the unit to misoperate or become
damaged.
(5) Do not allow wiring to touch the refrigerant tubing, compressor, or any moving
parts of the fan.
(6) Unauthorized changes in the internal wiring can be very dangerous. The manu-
facturer will accept no responsibility for any damage or misoperation that occurs
as a result of such unauthorized changes.
3-8. Recommended Wire Length and Diameter
Regulations on wiring diameter differ from locality to locality. For field wiring requirements, please refer to your local electrical codes. Carefully observe these regulations when carrying out the installation.
Table 4 lists recommended wire lengths and diameters for power supply systems.
NOTE
Refer to the wiring system diagram (Fig. 7a or Fig. 7b) for the meaning of (A), (B)
and (C) in Table 4.
Refer to your local codes or in the absence of local codes see the National Electric
Code: ANSI/NFPA70.
11
Page 12
Table 4
WARNING
WARNING
CAUTION
CAUTION
Cross-Sectional(A)+(B)(A) Power Supply Wiring Length (ft)(C) Control
Area (AWG)
Model(#14)(#12)(#14)
CH1271131 (Max.)230 (Max.)65 (Max.)20A
CH1872131 (Max.)230 (Max.)98 (Max.)20A
G Be sure to comply with local codes on running the
(B) Power Line Length (ft)Line Length (ft)
wire from the indoor unit to the outdoor unit (size
of wire and wiring method, etc.).
G Each wire must be firmly connected.
G No wire should be allowed to touch refrigerant
tubing, the compressor, or any moving part.
G To avoid the risk of electric shock, each air con-
ditioner unit must be grounded.
G For the installation of a grounding device,
please observe local electrical codes.
G Grounding is necessary, especially for units
using inverter circuits, in order to release
charged electricity and electrical noise caused
by high tension.
Otherwise, electrical shock may occur.
G Place a dedicated ground more than 7' (2 m)
away from other grounds and do not have it
shared with other electric appliances.
Fuse or Circuit
Breaker Capacity
# ... AWG (American Wire Gauge)
WIRING SYSTEM DIAGRAM
(CH1271)
INDOOR
UNIT
Te r mi nalTerminal
1
2
3
Disconnect
*
switch
Field supply
(C)
Grounding line
115V
115V
115V
OUTDOOR
UNIT
(B)
(B)
Fig. 7a
(CH1872)
INDOOR
UNIT
Te r mi nalTerminal
1
2
3
Disconnect
*
switch
Field supply
(C)
Grounding line
230/208V
230/208V
230/208V
OUTDOOR
UNIT
(B)
(B)
1
2
3
4
5
6
1
2
3
4
5
6
Powe r supply
(A)
L
N
Grounding
line
Powe r supply
(A)
L
1
L
2
Single phase 115V 60HZ
Single phase 230/208V 60HZ
G Be sure to connect the power supply line to the
outdoor unit as shown in the wiring diagram. The
indoor unit draws its power from the outdoor unit.
G Do not run wiring for antenna, signal, or power
lines of television, radio, stereo, telephone, security system, or intercom any closer than 3'3" (1 m)
from the power cable and wires between the
indoor and outdoor units. Electrical noise may
affect the operation.
Fig. 7b
NOTE
*
A disconnect switch may be required by
national or local codes.
Always comply with national and local code
requirements.
12
Grounding
line
Page 13
WARNING
1
32
Earth screw
Clamping strap
(Conduit)
Inter unit
Power wiring
(Locally purchased)
3-9. Wiring Instructions for Inter-unit Connections
(1) Remove the 1 screw from the terminal cover, then open the
cover. Be careful that the cover does not fall.
(2) Remove the 3 screws from the power box cover, then open
the cover. Be careful that the cover does not fall.
(3) Use the screw to securely fasten the ground wire from the
outdoor unit in place.
(4) Remove the transparent plastic cover from the 3P terminal
plate.
(5) While viewing the wiring diagram, connect the inter-unit and
power supply line to terminals 1, 2 and 3 on the 3P terminal
plate.
(6) Remount the transparent plastic cover onto the 3P terminal
plate.
(7) Be sure to use the clamping strap to fasten the wires in place.
(8) Tighten the screws to remount the terminal and the power
box cover.
Loose wiring may cause the terminal to overheat or result in unit
malfunction. A fire hazard may
also exist. Therefore, be sure all
wiring is tightly connected.
Fig. 8
When connecting each power wire to the corresponding terminal, follow the instructions “How to connect wiring to the terminal” and fasten
the wire securely tight with the fixing screw of the terminal plate.
How to connect wiring to the terminal
a) For Indoor Unit
(1) Cut the wire end with a cutting pliers, then strip the insulation to
expose the wire about 9/32" (7 mm). See the label (Fig. 9) near the
terminal plate.
(2) Using a screwdriver, loosen the terminal screw on the terminal
plate.
(3) Insert the wire and tighten the terminal screw completely using a
screwdriver.
b) For Outdoor Unit
I For solid core wiring (or F-cable)
(1) Cut the wire end with a cutting pliers, then strip the insulation to
expose the solid wire about 15/16"
(25 mm). (Fig. 10)
(2) Using a screwdriver, remove the terminal screw(s) on the terminal
plate.
9/32"
STRIP
SIZE
(7 mm)
Fig. 9
Solid wire
Strip 15/16" (25 mm)
Insulation
Fig. 10
(ACTUAL
SIZE)
Loop
(3) Using the pliers, bend the solid wire to form a loop suitable for the
terminal screw.
(4) Shape the loop wire properly, place it on the terminal plate and fix
it securely with the removed terminal screw using a screwdriver.
13
Page 14
I For stranded wiring
(1) Cut the wire end with a cutting pliers, then strip the insulation to expose the stranded wiring about 3/8" (10 mm) and
tightly twist the wire ends. (Figs. 11 and 12)
(2) Using a screwdriver, remove the terminal screw(s) on the terminal plate.
(3) Using a ring connector fastener or pliers, securely clamp each stripped wire end with a ring connector. (Fig. 11)
(4) Place the ring connector wire, and replace and tighten the removed terminal screw using a screwdriver. (Fig. 13)
Stranded wire
Ring
connector
Strip 3/8" (10 mm)
Fig. 11
Tw ist wire ends
Fig. 12
4. How to Install the Outdoor Unit
First refer to Section 2. Installation Site Selection.
4-1. Wiring Instructions for the Outdoor Unit
Regulations on wire size differ from locality to locality.
For field wiring requirements, please refer to your
local electrical codes. Make sure that the installation
fully complies with all local and national regulations.
Te r mi nal
block
Wire
Special
washer
Lock nut
Screw
Ring connector
Te r mi nal plate
Wire
Fig. 13
Cabinet
Screw and
special washer
Ring
connector
(1) Remove access panel “C”. (Fig. 14)
(2) Connect the inter-unit and power supply line
according to the drawing on the panel side.
(3) Be sure to size each wire allowing approx. 4"
(10 cm) longer than the required length for
wiring. Store excess wiring inside the cabinet.
(4) When connections are completed, check that all
connections are correct as shown in the wiring
system diagram on panel side.
(5) Be sure to ground the unit according to your
local codes.
Conduit
plate
Plug
Inter unit
(Conduit)
Access panel “C”
Power supply
(Conduit)
Fig. 14
14
Page 15
5. Refrigerant Tubing
Flare nut
Union
Deburring
5-1. Use of the Flaring Method
Many of the conventional split system air conditioners
employ the flaring method to connect refrigerant tubes
which run between indoor and outdoor units. In this
method, the copper tubes are flared at each end and
connected with flare nuts.
5-2. Flaring Procedure with a Flare Tool
(1) Cut the copper tube to the required length with a
tube cutter. It is recommended to cut approx. 12" to
20" (30 to 50 cm) longer than the tubing length you
estimate.
(2) Remove burrs at the end of the copper tube with a
tube reamer or file. This process is important and
should be done carefully to make a good flare.
(Fig. 15)
NOTE
When reaming, hold the tube end downward and be
sure that no copper scraps fall into the tube. (Fig. 16)
Before
After
Fig. 15
Copper
tubing
Reamer
Fig. 16
(3) Remove the flare nut from the unit and be sure to
mount it on the copper tube.
(4) Make a flare at the end of copper tube with a flare
tool.* (Figs. 17 and 18)
(*Use “RIDGID” or equivalent.)
NOTE
A good flare should have the following characteristics:
G inside surface is glossy and smooth.
G edge is smooth.
G tapered sides are of uniform length.
5-3. Caution before Connecting Tubes Tightly
a)Be sure to apply a sealing cap or water-proof tape
to prevent dust or water from getting into the tubes
before they are used.
b)Be sure to apply refrigerant lubricant to the match-
ing surfaces of the flare and union before connecting them together. This is effective for reducing gas
leaks. (Fig. 19)
c)For proper connection, align the union tube and
flare tube straight with each other, then screw in the
flare nut lightly at first to obtain a smooth match.
(Fig. 20)
If the special R410A
flare tool is used:
0 to 0.0196"
(0 to 0.5 mm)
If the previous flare tool
(clutch-type) is used:
0.0472" (1.2 mm)
Adjust so that the amount of tube
protrusion is asshown in the figure.
Fig. 17
Flare nut
Copper
tubing
Flare tool
Fig. 18
Apply refrigerant
lubricant here and here
Fig. 19
Fig. 20
15
Page 16
5-4. Connecting Tubing between Indoor and
IMPORTANT
CAUTION
Indoor unit
Outdoor unit
Spanner
Torque wrench
Insulation tape (supplied)
Flare insulation (3/16"(T5, supplied) )
Flare insulation (1/8"(T3, supplied) )
Tube insulation
(not supplied)
Vinyl tie (supplied)
Flare nut
The procedure used for installing
the insulation for both wide and
narrow tubes are the same.
Flare
insulation
Vinyl tie (supplied)
Insulation tape
Refrigerant tubing
and insulation
(not supplied)
Drain pipe and insulation
(not supplied)
Drain hose insulation
and vinyl tie
(supplied)
Drain hose
and hose band
(supplied)
Outdoor Units
a)Tightly connect the indoor side refrigerant tubing exten-
ded from the wall with the outdoor side tubing. (Fig. 21)
b)To fasten the flare nuts, apply specified torque as:
To prevent heat loss and wet floors due to dripping of condensation, both tubes must be well insulated with a
proper insulation material.
The thickness of the insulation should be a minimum 5/16"
(8 mm). (Fig. 22)
Min.
5/16"
(8 mm)
Fig. 21
Insulation
Thickness:
min. 5/16"
(8 mm)
Fig. 22
Taping the flare nuts
Wind the insulation tape around the flare nuts at the
tube connections. Secondly cover up the tubing connections with the flare insulation (1/8" (T3, supplied)). Then
wind the other flare insulation (3/16" (T5, supplied)).
Finally, fasten the insulation at both ends with the supplied vinyl ties. (Fig. 23)
Insulation material
The material used for insulation must have good insulation characteristics, be easy to use, be age resistant,
and must not easily absorb moisture.
After a tube has been insulated, never try to bend it into a
narrow curve because it can
cause the tube to break or
crack.
Fig. 23
Fig. 24
Never grasp the drain or refrigerant connecting outlets when moving the unit.
16
Page 17
Insulated tubes
Drain hose
Clamp
5-6. Taping the Tubes
CAUTION
CAUTION
Apply putty here
Tubing
(1) At this time, the 2 refrigerant tubes (and electrical wire
if local codes permit) should be taped together with
armoring tape. The drain hose may also be included
and taped together as 1 bundle with the tubing.
(2) Wrap the armoring tape from the bottom of the outdoor
unit to the top of the tubing where it enters the wall. As
you wrap the tubing, overlap half of each previous tape
turn. (Fig. 25)
(3) Clamp the tubing bundle to wall, using 1 clamp approx.
every 47" (120 cm).
NOTE
Do not wind the armoring tape too tightly, since this will
decrease the heat insulation effect. Also, be sure the condensation drain hose splits away from the bundle and drips
clear of the unit and the tubing.
Fig. 25
5-7. Finishing the Installation
After finishing insulating and taping over the tubing, use
sealing putty to seal off the hole in the wall to prevent rain
and draft from entering. (Fig. 26)
6. Air Purging
Air and moisture remaining in the refrigerant system have
undesirable effects as indicated below. Therefore, they must
be purged completely.
G pressure in the system rises
G operating current rises
G cooling (or heating) efficiency drops
G moisture in the air may freeze and block capillary tubing
G water may lead to corrosion of parts in the refrigerant system
I Air Purging with a Vacuum Pump (for Test Run)
(1) Check that each tube (both narrow and wide tubes)
between the indoor and outdoor units have been properly connected and all wiring for the test run has been
completed. Note that both narrow and wide tube service
valves on the outdoor unit are kept closed at this stage.
(2) Using an adjustable wrench or box wrench, remove the
valve caps from the service valve on both narrow and
wide tubes.
(3) Connect a vacuum pump and a manifold valve (with
pressure gauges) to the service port on the wide tube
service valve. (Fig. 27)
Manifold valve
(Exclusively for R410A)
Pressure
gauge
Fig. 26
Indoor unit
Outdoor unit
HiLo
The service port on the wide tube service valve
uses a Schrader core valve to access the
refrigerant system. The valve core is similar to
those used in automobile tires. Therefore, be
sure to use a vacuum hose connector which
has a push-pin inside.
Be sure to use a manifold valve for
air purging. If it is not available, use
a stop valve (field supply) for this
purpose. The “Hi” knob of the manifold valve must always be kept closed.
(4) With the “Lo” knob of the manifold valve open, run
CAUTION
CAUTION
the vacuum pump. The operation time for the vacuum pump varies with tubing length and the capacity
of the pump. The following table shows the amount
of time for evacuation:
Table 6
Required time for evacuation when
26.4 gal/h (100 liter/h) vacuum pump is used
If tubing length isIf tubing length is
less than 33 ft. (10 m)more than 33 ft. (10 m)
10 min. or more15 min. or more
(5) With the vacuum pump still running, close the “Lo”
knob of the manifold valve. Then stop the vacuum
pump.
(6) With the accessory hex wrench, turn the valve stem on
the narrow tube service valve counter-clockwise by 90
degrees (1/4 turn) for 10 seconds, and then turn the
stem clockwise to close it again. (Fig. 28)
NOTE
To prevent other refrigerants from being mistakenly
charged to units which use R410A, the size of the
charge port on the service valve is different from the
one for other refrigerant types. For servicing such as
recharging, the specified charging hose, manifold and
vacuum pump adapter (with reverse flow prevention)
for R410A must be used.
NOTE
The required time in Table 6 is calculated based on the
assumption that the ideal (or target) vacuum condition
is around 0.193 psi (10 mmHg abs.).
90° (1/4 turn)
Narrow tube
Hex wrench
Be sure to completely insert the hex
wrench before attempting to turn the valve.
(7) Leak test all joints at the tubing (both indoor and outdoors) with
soapy water. Bubbles indicate a leak. Tighten the joint more
when leaks, then check if there is no leak. Be sure to wipe off the
soap with a clean cloth.
(8) With the hex wrench, turn the wide tube service valve stem
counter-clockwise to fully open the valve.
(9) Turn the narrow tube service valve stem counter-clockwise to
fully open the valve.
(10) Loosen the vacuum hose connected to the wide tube service
port slightly to release the pressure. Then, remove the hose.
This may cause the refrigerant gas to
leak. In order to avoid this, take off the
hose quickly.
(11) Fasten the valve cap on the wide tube service port securely
with an adjustable wrench or box wrench. Next, mount the
valve cap on the service valve and tighten it to 170 lbs·in
(200 kgf·cm) with a torque wrench. This process is very
important to prevent gas from leaking from the system.
Wide tube
Valve cap
Vac uum hose to manifold valve
Fig. 28
(12) Test run the air conditioner. (See next page.)
(13) While the air conditioner is running, apply liquid soap to
check for any gas leaks around the service valves or caps.
(14) If there is no leakage, stop the air conditioner.
(15) Wipe off the soap on the tubing.
This completes air purging with a vacuum pump and the air conditioner is ready for actual operation.
18
Page 19
How to Test Run the Air Conditioner
IMPORTANT
ACL
(Reset)
button
1HR.
TIMER
button
ON/OFF
operation
button
HIGH POWER
button
OPERATION lamp
TIMER lamp
HIGH POWER lamp
REMOTE CONTROL receiver
OPERATION button
After turning on the power of the air conditioner, use the
remote controller and follow the steps below to conduct
the test run.
(1) Set the remote controller in Test Run mode. (Fig. 29)
a)Press and hold the HIGH POWER button and the
1HR. TIMER button.
b)Then press and hold the ACL (Reset) button with
a pointed object such as the tip of a pen. After 5
seconds, release the ACL button first.
c) Then release the HIGH POWER and 1HR. TIMER
buttons.
d)appears and “oP-1” blinking in the remote con-
troller clock display area. (Fig. 30)
(2) Start Cooling mode test run by pressing the ON/OFF
operation button of the remote controller. (Fig. 29)
• This starts the fan producing uncooled forced air
with the 3 indicator lamps (OPERATION lamp,
TIMER lamp, and HIGH POWER lamp) on the
main unit blinking. (Fig. 31)
• After 3 minutes, the system shifts into cooling
operation, and cool air will start to be felt. Cooling
mode test run is unaffected by the room temperature.
(3) Press the ON/OFF operation button of the remote
controller again to stop the test run. (Fig. 29)
(4) Finally press the ACL (Reset) button of the remote
controller to release it from Test Run mode to return
to normal mode. (Fig. 29)
• “” and “oP-1” will disappear from the remote
controller clock display area.
Fig. 29
NOTE
Troubleshooting:
In the event that the green OPERATION lamp is blinking
In this case, refer to the self-diagnostics procedure
which can be seen by opening the air-intake grille.
After the test run is completed, be sure to press the ACL
(Reset) button to return to normal mode. The air condi-
upon powering up the system, an error condition exists.
tioner will not operate correctly if this is not done.
Fig. 30
Fig. 31
19
Page 20
I Basic Functions of the Service Valves
PUSH
Hose with push-pin
Service valve
Close
Hex
wrench
Open
CAUTION
The basic functions of the service valves are given in Table 7 below.
Table 7
Action
Shipping
Operating and
test running
the air conditioner
Measuring pressure
and gas charging
Air purging with
a vacuum pump
Narrow Tube Service
Valve (2-Way)
CLOSED
Fully OPEN
Fully OPEN
CLOSED
Wide Tube Service
Valve (3-Way)
O-ring
*
*
Valve cap
Stem
* The service port on the wide tube ser-
vice valve uses a Schrader core valve
to access the refrigerant system.
Therefore, be sure to use a hose connector which has a push-pin inside.
(Fig. 32)
When opening or closing the service valve
stem, use the accessory
hex wrench. Be sure to
fully seat the wrench
before turning the valve.
I Pump Down
Pump down means collecting all refrigerant gas in the
system back into the outdoor unit without losing any of
the gas. Pump down is used when the unit is to be
moved or before servicing the refrigerant circuit.
Pump Down Procedure
Be sure to carry out pump down with the unit in
Cooling mode.
(1) Connect the Lo side charging hose of the manifold
valve to the service port on the wide tube service
valve.
Fig. 33
NOTE
External diameter of service port
R410A: 5/16"
Fig. 32
(2) Using a hex wrench, turn the narrow tube service
valve clockwise all the way to close the service
valve. (Be sure to confirm that the wide tube service
valve is fully open.)
(3) Press the operation button and start cooling oper-
ation.
(4) When the low pressure gauge reading falls to 14.2 to
7.1 psi (1 to 0.5 kg/cm
2
), fully close the wide tube
valve stem. Then quickly stop the unit.
(5) Disconnect all gauges and hoses, and replace the
valve caps as they were before.
20
Page 21
I Service Valve Connections
CAUTION
a)Temporary connection:
Screw in 3 – 5 turns by hand. (Fig. 34)
b)To fasten the flare nuts, apply specified torque
The remote control unit can be operated from either a
non-fixed position or a wall-mounted position.
To ensure that the air conditioner operates correctly, do
not install the remote control unit in the following places:
G In direct sunlight
G Behind a curtain or other place where it is covered
G More than 26' (8 m) away from the air conditioner
G In the path of the air conditioner’s airstream
G Where it may become extremely hot or cold
G Where it may be subject to electrical or magnetic
interference
G Where there is an obstacle between the remote con-
trol unit and the air conditioner (since a check signal
is sent from the remote control unit every 5 minutes)
Fig. 34
Torque wrench
Fig. 35
Be sure to tighten the flare nut
using the prescribed torque. If the
nut is over-tightened, refrigerant
leakage may occur.
7-1. Mounting on a Wall
Before mounting the remote control unit, press the
ON/OFF operation button at the mounting location to
make sure that the air conditioner operates from that
location. The indoor unit should make a beeping sound
to indicate that it has received the signal.
Remote control
unit mount
Mounting screws
5/32 5/8" (4 16 mm)
(included)
To take out the remote control unit, pull it forward.
Press
Set in
place
Fig. 36
Rear side
Hole
To prevent loss of the remote control
unit, you can connect the remote
control unit to the mount by passing
a string through the remote control
unit and attachment hole.
21
Page 22
ACL
(Reset)
button
1HR.
TIMER
button
ON/OFF
operation
button
HIGH POWER
button
8. Address Switch
8-1. Address Setting of the Remote Control Unit
The address can be set in order to prevent interference between remote controllers when 2 indoor units
are installed near each other. The address is normally
set to “A.” To set a different address, it is necessary to
change the address on the second remote controller.
Ta b
NOTE
Once changed, you cannot restore the original
address setting of the air conditioner.
(1) Switch on the power source.
(2) Break the address-setting tab marked “A” on the
second remote controller to change the address
(Fig. 37). When the tab is removed, the address is
automatically set to B (Fig. 38).
(3) Press and hold the remote controller HIGH
POWER button and 1HR. TIMER button. Then,
press and hold the ACL (Reset) button with a
pointed object such as the tip of a pen. After 5
seconds, release the ACL button first, then
release the HIGH POWER and 1HR. TIMER buttons. “oP-1” (Test Run) appears, blinking in the
remote controller clock display area.
(4) Each time the 1HR. TIMER button is pressed, the
display changes as shown below. Press this button 2 times to change the display to “oP-7”
(Address setting). (Fig. 39)
Fig. 37
ACL button
Fig. 38
Te st run mode
Self-diagnostic mode
Addresssetting mode
(5) “oP-7” has now been selected for address setting.
(6) Press the ON/OFF operation button on the remote
controller. (Fig. 39) Check that the “beep” signalreceived sound is heard from the second indoor
unit (approximately 5 times). The sound you hear
is the signal that the remote controller address
has been changed.
(7) Finally press the remote controller ACL (Reset)
button to cancel the blinking “oP-7” display.
(Fig. 39)
Changing of the second remote controller address is
now completed.
Fig. 39
22
Page 23
STK-RCS-7TWSU
This wired remote controller is designed for
both the “COOL/DRY/HEAT Model” and
“COOL/DRY Model” indoor unit.
Before using the remote controller, be sure
to confirm the “model type” specified on the
front cover of the INSTRUCTION MANUAL
INSTRUCTION MANUAL
Wired Remote Controller
MODE D’EMPLOI
Télécommande Filaire
supplied with the indoor unit.
Save These Instructions!
Conserver ce mode d’emploi
3. Adjusting the Fan Speed ..................................................................................................... 7
4. Fan Only..............................................................................................................................7
5. Night Setback Mode............................................................................................................ 7
SPECIAL REMARKS.......................................................................................................................... 7
SETTING THE TIMER........................................................................................................................8
USING THE 1-HOUR OFF TIMER..................................................................................................... 9
ADJUSTING THE AIRFLOW DIRECTION .........................................................................................9
Page
PRODUCT INFORMATION
If you have problems or questions concerning your wired
remote controller, you will need the following information.
Model No. __________________________________
Date of purchase _____________________________
Dealer’s address _____________________________
Phone number________________
ALERT SYMBOLS
The following symbols used in this manual, alert you
to potentially dangerous conditions to users, service
personnel or the appliance:
This symbol refers to a hazard or unsafe
practice which can result in severe
personal injury or death.
CAUTION
This symbol refers to a hazard or unsafe
practice which can result in personal
injury or product or property damage.
INSTALLATION LOCATION
We recommend that this wired remote controller be
installed properly by qualified installation technicians
in accordance with the Installation Instructions
provided with the unit.
• Do not install this wired remote
controller where there are fumes or
flammable gases, or in an extremely
humid space such as a greenhouse.
• Do not install the wired remote
controller where excessively high
heat-generating objects are placed.
Avoid:
To protect the air conditioner from heavy corrosion, avoid installing
the outdoor unit where salty sea water can splash directly onto it or
in sulphurous air near a spa.
ELECTRICAL
REQUIREMENTS
1. All wiring must conform to the local electrical codes.
Consult your dealer or a qualified electrician for details.
2. Each unit must be properly grounded with a ground (or
earth) wire or through the supply wiring.
3. Wiring must be done by a qualified electrician.
SAFETY INSTRUCTIONS
• Read this Instruction Manual carefully before using
this air conditioner. If you still have any difficulties
or problems, consult your dealer for help.
• This air conditioner is designed to give you
comfortable room conditions. Use this only for its
intended purpose as described in this Instruction
Manual.
• Never use or store gasoline or other
flammable vapor or liquid near the air
conditioner — it is very dangerous.
• This air conditioner has no ventilator
for intaking fresh air from outdoors.
You must open doors or windows
frequently when you use gas or oil
heating appliances in the same room,
which consume a lot of oxygen from
the air. Otherwise there is a risk of
suffocation in an extreme case.
CAUTION
• Do not turn the air conditioner on and
off from the power mains switch. Use
the ON/OFF operation button.
• Do not stick anything into the air outlet
of the outdoor unit. This is dangerous
because the fan is rotating at high
speed.
• Do not let children play with the air
conditioner.
• Do not cool or heat the room too much
if babies or invalids are present.
2
OI-119-2-EG
Page 25
REMOTE CONTROL UNIT (DISPLAY)
Symbols
Displayed when indoor unit
sensor is in use
Displayed when operating
NIGHT SETBACK mode
Displayed when setting temperature
Displayed when temperature is shown
Displayed when setting timer
(1) Operation mode
AUTO .....................................
(only for COOL/DRY/HEAT
Model)
HEAT ......................................
(only for COOL/DRY/HEAT
Model)
MILD DRY..............................
COOL.....................................
FAN ........................................
(2) Fan speed
Automatic operation ...............
HIGH .....................................
(3) Temperature setting
60 – 86 °F ..............................
When set to 80 °F
temperature indication...........
(4) Timer
24-hour clock with ON/OFF
program Timer .......................
ON Timer. ..............................
OFF Timer. ............................
1-hour OFF Timer..................
(5) NIGHT SETBACK..................
MEDIUM.................................
LOW.......................................
OI-119-3-EG
(6) Flap angle indication..............
Sweep indication....................
3
Page 26
REMOTE CONTROL UNIT
NOTE
The descriptions on the AUTO () or HEAT ( ) operation mode are only for the “COOL/DRY/HEAT Model,” and not for the
“COOL/DRY Model.”
Display
Information on the operating conditions is displayed while the remote control
unit is switched on. If the unit is turned off, only the mode that was set
previously is still displayed.
Temperature setting buttons (TEMP.)
Press the button to increase the set temperature.
Press the button to reduce the set temperature.
The temperature setting changes by 2 °F each time one of the TEMP. buttons
is pressed.
FAN SPEED selector button
: The air conditioner automatically decides the fan speeds.
: High fan speed
: Medium fan speed
: Low fan speed
NIGHT SETBACK button
For details, see “5. Night Setback Mode”. When you press this button in the
HEAT, DRY or COOL mode, the mark appears in the display, and the
remote control unit will automatically adjust the set temperature to save
energy.
FLAP button
Press this button either to select the setting of the airflow direction to one of
the six possible positions manually or to select the sweep function which
moves the flap up and down automatically.
: The airflow direction can be set manually. (six positions)
: The flap moves up and down automatically.
NOTE
When you press the FLAP button, the air flow direction will be changed one by
one as follows.
SWEEP
Timer and Present Time setting buttons
First, press the SET button to select the mode (ON, OFF and Present Time
settings) you want.
Each time you press the ‘‘HH’’ button, the hours advance by one.
(PM0, PM1.....PM11, AM0, AM1.....AM11)
Each time you press the ‘‘MM’’ button, the minutes advance by one when
setting Present Time and by ten when setting ON and OFF Time.
SET button
For details, see ‘‘Setting the Timer’’.
Press this button to select the mode you want to program.
ACL button (ALL CLEAR)
When you press the ACL button while the
operation button is ON, all settings are cleared.
Press the ACL button if the air conditioner is not
operating correctly.
4
OI-119-4-EG
Page 27
ON/OFF operation button
This button is for turning the air conditioner on and off.
MODE selector button
Use this button to select AUTO, HEAT, DRY, COOL or FAN mode.
(AUTO): When this setting is selected, the air conditioner calculates the difference between the
thermostat setting and the room temperature and automatically switches to the ‘‘COOL’’ or
‘‘HEAT’’ mode as appropriate.
(HEAT): The air conditioner makes the room warmer.
(DRY): The air conditioner reduces the humidity in the room.
(COOL): The air conditioner makes the room cooler.
(FAN): The air conditioner works only as a circulation fan.
1 HR. TIMER button (1-HOUR OFF TIMER)
: When you press this button, regardless of whether the unit is operating or stopping, the unit operates for
one hour and then shuts down.
TIMER SELECT button
No display :The timer does not operate.
: The air conditioner starts at the set time.
: The air conditioner stops at the set time.
: The air conditioner stops and starts, or starts and stops, at the set times every day.
Sensor
A temperature sensor inside the remote control unit senses the room temperature.
SENSOR button
When you press this button (use a small-tipped object such as a ballpoint pen), the mark will disappear at the
display. And the room temperature is detected by the sensor which is built into the remote control unit and the air
conditioner is controlled accordingly.
NOTE
If the remote control is located near a heat source, such as a space heater or in direct sunlight, press the
SENSOR button to switch to the sensor on the indoor unit.
NOTE
The indoor fan runs continuously when the system is in normal operation. It does not turn off when the desired room temperature is
reached. If Night Set Back mode is selected, the fan will turn off intermittently during cooling operation in order to control air flow.
OI-119-5-EG
5
Page 28
OPERATION WITH THE REMOTE CONTROL UNIT
1. Automatic Operation
(only for COOL/DRY/HEAT Model)
This unit automatically switches between cooling operation and
heating operation according to the difference between the room
temperature and the temperature setting.
STEP 2
STEP 1
NOTE
NOTE
Check that the circuit breaker on the power panel is
turned on.
Once mode is selected and the unit is preset by
following the steps below, you can have the air
conditioner automatically bring the room to the desired
temperature simply by pressing the ON/OFF operation
button.
STEP 1Press the MODE selector button to .
STEP 2Press the ON/OFF operation button.
To stop the air conditioner, press the ON/OFF operation
button again.
To change the temperature setting; press the
temperature setting buttons and change the setting to
the desired temperature.
2. Manual Operation
STEP 5
NOTE
Check that the circuit breaker on the power panel is
turned on.
If the automatic operation settings of the unit do not
meet your needs, press the setting buttons as
described below and change the settings as desired.
STEP 1Press the MODE selector button
and select the desired mode.
For heating operation
For dehumidifying operation
For cooling operation
For fan only operation
STEP 2To start the air conditioner, press the ON/
OFF operation button.
STEP 3Press the TEMP. setting buttons to change
the temperature setting to the desired
temperature.
Adjustable temperature range:
86 °F max.
60 °F min.
STEP 4Set the FAN SPEED selector button to the
setting you want.
STEP 5Press the FLAP button and set the airflow
direction as desired.
(Refer to “ADJUSTING THE AIRFLOW
DIRECTION” on page 9.)
To stop the air conditioner, press the ON/OFF
operation button again.
STEP 2
STEP 3
STEP 1STEP 4
→
→
→
→
6
NOTE
• Choose the best position in the room for the remote
control unit, which also acts as the sensor for room
comfort and transmits the operating instructions.
Once you’ve found this best position, always keep the
remote control unit there.
• This appliance has a built-in 5-minute time delay
circuit to ensure reliable operation. When the
operation button is pressed, the compressor will start
running within three minutes. In the event of power
failure, the unit will stop.
• The display on the remote control unit shows the
setting temperature and not the room temperature.
OI-119-6-EG
Page 29
3. Adjusting the Fan Speed
A. Automatic fan speed
Simply set the FAN SPEED selector button to the
position.
This automatically sets the best fan speed for the room
temperature.
B. Manual fan speed
If you want to adjust fan speed manually during operation,
just set the FAN SPEED selector button as desired. [,
, or ]
4. Fan Only
A. In Cooling and DRY Mode: ( and )
When the night setback mode is selected, the air conditioner
automatically raises the temperature setting 2 °F when 30 minutes
have passed after the selection was made, and then another 2 °F
after another 30 minutes have passed, regardless of the indoor
temperature when night setback was selected. This enables you
to save energy without sacrificing comfort. This function is
convenient when gentle cooling is needed.
Setting
temperature
2°F
2°F
If you want to circulate air without any temperature
control, follow these steps:
STEP 1Press the MODE selector button to switch to
the fan mode .
STEP 2Press the ON/OFF operation button.
STEP 3Press the FAN SPEED selector button to
select the fan speed of your choice (,
or ).
5. Night Setback Mode
STEP 2
STEP 1STEP 3
Press the NIGHT
SETBACK button
30 min.
30 min.
Time
B. In Heating Mode: ()
(only for COOL/DRY/HEAT Model)
When the night setback mode is selected, the air conditioner
automatically lowers the temperature setting 4 °F when 30
minutes have passed after the selection was made, and then
another 4 °F after another 30 minutes have passed, regardless of
the indoor temperature when night setback was selected. This
enables you to save energy without sacrificing comfort. This
function is convenient when gentle heating is needed.
30 min.
4°F
30 min.
4°F
Time
Setting
temperature
Press the NIGHT
SETBACK button
SPECIAL REMARKS
Night Setback Mode is used for saving energy.
Press the NIGHT SETBACK button while operation.
The mark appears in the display.
To release the night setback function, press the NIGHT SETBACK
button again.
OI-119-7-EG
Power failure during operation
• In the event of power failure, the unit will stop. When the power is
resumed within 3 hours, the unit will restart automatically within five
minutes by the remote control unit.
Remote Control Unit
• The remote control unit sends the setting condition to the air
conditioner regularly at five minute intervals.
Remote Control Unit Display
• If the display malfunctions, press the ACL button.
This resets the remote control unit back to the initial settings.
Make the settings again.
7
Page 30
SETTING THE TIMER
1. How to set the present time
(Example) To set to 9:10 pm.
3. How to set the ON time
(Example) To start operation at 7:10 am.
ON TIMEPresent time
OperationIndication
1. Press the SET button once.The timer indication alone
2. • Press the HH button until
AM 7 is displayed.
• Press the MM button until
10 is displayed.
3. Press the ON/OFF button to
start the air conditioner.
4. Press the TIMER SELECT
button once to set ON time.
flashes and the previous settime is only displayed.
The display will change
automatically back to show the
present time after about 10 sec.
The present time is displayed.
The present time and are
displayed.
OperationIndication
1. Press the SET button three
times.
2. • Press the HH button until
PM 9 is displayed.
• Press the MM button until
10 is displayed.
The time indication alone
flashes.
The display will flash for 10 sec.
and automatically stop flashing
except for the “:” symbol.
2. How to set the OFF time
(Example) To stop the air conditioner at 11:30 pm.
OFF TIMEPresent time
OperationIndication
1. Press the SET button twice.The timer indication alone
2. • Press the HH button until
PM 11 is displayed.
• Press the MM button until
30 is displayed.
3. Press the ON/OFF button to
start the air conditioner.
4. Press the TIMER SELECT
button twice to set OFF time.
flashes and the previous settime is only displayed.
The display will change
automatically back to show the
present time after about 10 sec.
The present time is displayed.
The present time and are
displayed.
4. How to set daily ON/OFF repeat timer
(Example) To start operation at 7:10 am. and stop the air conditioner
at 11:30 pm.
Present timeOFF TIME
ON TIME
9:10 pm.
Present time
7:10 am.
ON
OperationIndication
1. Set the timer ON/OFF times
as shown in 2 and 3.
2. Press the ON/OFF button to
start the air conditioner.
3. Press the TIMER SELECT
button three times to set the
ON/OFF combination timer.
The present time PM 9:10 and
are displayed.
Programmed
daily ON / OFF
11:30 pm.
OFF
8
NOTE
You can check the timer ON/OFF times after you have set them by
pressing the SET button.
OI-119-8-EG
Page 31
I How to wire the remote controller
Ceiling
panel
5P FLAP
wiring connector
7P IND and 4P RC
wiring connector
Control
box
cover
Power box cover
Indicator
(1) Turn OFF the power and remove the ceiling panel
air-intake grille. (Refer to 3-6-1 Before Installing theCeiling Panel in the Installation Instructions supplied
with the indoor unit.)
(2) Remove the 3 power box cover screws and 2 control
box cover screws, then remove both covers. At this
time, take care not to drop the covers. (Fig. 7)
(3) Disconnect the 7P (IND) terminal and 4P (RC) termi-
nal of the 7P IND and 4P RC wiring connectors and
the 5P terminal of the 5P FLAP wiring connector
from the control box PCB connectors (IND, RC,
FLAP). Disconnect each wiring connector from the
clamp that fastens it. (Fig. 7)
(4) Remove the ceiling panel. (To remove the ceiling
panel, follow the steps for 3-6 How to Install theCeiling Panel in the reverse order. Refer to the
Installation Instructions supplied with the indoor unit.)
Indicator
Fig. 7
Fig. 8-a
7P IND and 4P RC
wiring connector
7P IND and 4P RC
wiring connector
Terminal cover
Fig. 8
Clamps
Remote
controller
5P FLAP
wiring
connector
Wire harness
4P
RCIND
FLAP
7P
Control PCB
Putty
Wire harness
Clamping strap
Fig. 8-b
Indicator
Ceiling
panel
Wire harness
5P FLAP
wiring connector
(5) Remove the terminal cover screws, then remove the cover. At this time, take care not to drop the cover. (Fig. 8)
(6) Pull in the wire harness from the remote controller as shown in Fig. 8-b.
• Remove the putty before wiring. After wiring, make sure to restore the putty.
(7) Insert the wire harness 4P terminal into the control box PCB connector (RC). (Fig. 8-a)
(8) Install the terminal cover. Then install the ceiling panel. (Refer to 3-6 How to Install the Ceiling Panel in the
Installation Instructions supplied with the indoor unit.)
(9) Insert only the 7P (IND) terminal of the 7P IND and 4P RC wiring connector into the connector (IND) on the control
box PCB. Store the 4P terminal inside the control box. (Fig. 8-a)
(10) Next, insert the 5P terminal of the 5P FLAP wiring connector into the connector (FLAP) on the control box PCB.
(Fig. 8-a)
(11) When the connections are completed, fasten the wire harness and each wiring connector with the clamps.
(12) Install the power box cover and control box cover.
(13) Install the air-intake grille. (Refer to 3-6 How to Install the Ceiling Panel in the Installation Instructions supplied
with the indoor unit.)
3
Page 32
5. Cancellation of the time setting
You can cancel the time settings by pressing the TIMER SELECT
button.
The time settings cannot be canceled by pressing the ON/OFF
operation button or MODE selector button.
6. Backup function
Even if the main power supply (circuit breaker) is cut off, the
capacitor inside the remote control store the mode settings in the
memory for 3 hours after the power is off.
The mode settings are reset if the main power supply is off for 3
hours or more.
USING THE 1-HOUR OFF
TIMER
1. 1-Hour OFF Timer
ADJUSTING THE AIRFLOW
DIRECTION
The vertical airflow can be adjusted by moving the flap with the
remote control unit. Do not move the flap with your hands. Confirm
that the remote control unit has been turned on. Use the FLAP
button to set either the sweep function or one of the six airflow
direction settings.
A. Sweep function
The flap starts moving
up and down to deliver
air over the sweep
range.
This function causes the unit to operate for one hour and then
stop, regardless of whether the unit is on or off when this
button is pressed.
The indicator in the display indicates that this function is
operating.
Setting procedure:
Regardless of whether the unit is operating or stopped, press the 1
HR. TIMER button.
appears in the display.
Cancellation procedure:
Press the ON/OFF operation button to turn the unit off, wait for the
unit to stop operating, and then press the ON/OFF operation button
again.
The 1-Hour Timer function is now cancelled and the unit operates
normally.
NOTE
• If, while the 1-Hour Timer function is operating, the 1HR. TIMER
button is pressed once to cancel the function and then again, the
unit continues to operate for one hour from that point in time and
then stops.
• It is not possible to use the OFF Timer and 1-Hour OFF Timer
together. Whichever function is set last takes precedence. If the 1
HR. TIMER button is pressed while the TIMER OFF function
operates, the OFF Timer is cancelled and the unit will stop
operating one hour later.
B. Setting the airflow manually
Referring to the above
illustration, use the
FLAP button to set the
airflow direction within
the range used during
the heating, cooling, or
dehumidifying
operation.
COOL
DRY
SWEEP
SWEEP
HEAT
FAN
NOTE
• The flap automatically closes when the unit is off.
• During the heating operation, the fan speed will be very low and the
flap will be in the horizontal position (position ) until the air being
blown out of the unit begins to warm. Once the air warms up, the
flap position and fan speed change to the settings specified with
the remote control.
CAUTION
• Use the FLAP button on the remote control to adjust the
position of the flap. If you move the flap by hand, the flap
position according to the remote control and the actual flap
position may no longer match. If this should happen, shut off
the unit, wait for the flap to close, and then turn on the unit
again; the flap position will now be normal again.
• Do not have the flap pointed down during cooling operation.
Condensation may begin to form around the air vent and drip
down.
2. Operation together with the daily ON/OFF
repeat timer
The 1-Hour OFF Timer setting is given priority over the DAILY ON/
OFF REPEAT setting.
OI-119-9-EG
9
Page 33
IMPORTANT
Q'tyQ'ty
1
Parts
Wired
remote
controller
Machine
screws
Tapping
screws
2
2
2
Spacers
1
Parts
1
1
Instruction
manual
FigureFigure
Installation
Instructions
Wire
harness
5/32
15/16"
5/32
15/16"
(4
25mm)
(4
25mm)
26.2 ft. (8m)
INSTALLATION INSTRUCTIONS
W
STK-RCS-7TWSU (Wired Remote Controller)
I Parts supplied with the remote controller
Table 1
See Table 1.
I Remote controller installation guidelines
Installation location
• Mount the remote controller 3.3 to 4.9 ft. (1 to 1.5
meters) off the floor where it can sense the average
temperature of the room.
• Do not mount the remote controller in a place exposed
to direct sunlight or where it is exposed to outside air
such as near a window.
• Do not mount the remote controller behind a curtain or
other object so that it is separated from the air circulation of the room.
• Mount the remote controller inside the room being air
conditioned.
Switching the room temperature sensor
Room temperature sensors are separately incorporated in both the indoor unit and the remote controller. Either sensor can
be used to sense the room temperature. The indoor unit sensor is usually used.
If you wish the remote controller to sense the room temperature, press the SENSOR button with a ballpoint pen or tool with
a small tip. (Refer to Fig. 9 on page 4 to locate the SENSOR button.)
I How to install the remote controller
• The remote controller is set to “Cool/Dry/Heat model” at
the time of shipment from the factory. If the purchased air
conditioner is a COOL/DRY model, follow the instructions
on the label and change the switch on the reverse side of
the remote controller unit to “Cool/Dry model”. (Fig. 1)
• The remote controller is also set to “Single” at the time of
shipment from the factory. For multiple use, set the switch
on the reverse side of the remote controller unit to “Multi”.
(Fig. 1)
• After all work is completed, if any switches have been
changed, then be sure to press the ACL (Reset) button.
(Refer to Fig. 9 on page 4 to locate the ACL (Reset) button.)
SANYO Commercial SolutionsIn Canada
A Division of SANYO North America CorporationSANYO Canada Inc.
1300 Michael Drive, Suite A1-300 Applewood Crescent, Concord
Wood Dale, IL 60191, U.S.A.Ontario, L4K 5C7, Canada
Fig. 1
Page 34
A. Installing with in-wall junction box
Remote
controller
Machine
Opening
In-wall junction box
from the indoor unit
Wire harness
Spacers
Wall
screws
Back plate
Wall
Remote
controller
Wire harness
Tapping
screws
Back plate
WallWall
Cut out
Connector
Hook
PCB
Slot
Ta b
Back
plate
2-3/8"
(60mm)
In-wall junction box (locally purchased)
4-3/16"
(106mm)
3-9/32"
(83.5mm)
(1) Install the junction box (locally purchased) into the wall.
(Figs. 2-a and 3)
(2) Pass the wire harness through the junction box and
conduit. (Fig. 3)
(3) Insert a flathead screwdriver into the 5 tab locations
and disconnect the back plate of the remote controller by
lifting up slightly. (Fig. 2-b)
The tabs are thin; take care not to chip them.
(4) Pass the wire harness connector through the cord open-
ing on the back plate of the remote controller.
Use nippers or a similar tool to cut out the slots for the
remote controller back plate screws. Insert the spacers
and use the machine screws to install the remote controller back plate. (Fig. 3)
(5) Insert the connector into the PCB of the remote con-
troller unit, and wrap the wire harness around the hook.
(Fig. 4)
(6) Store the excess wire harness inside the junction box,
then hook the remote controller unit onto the top of the
back plate and install the remote controller unit.
(7) To remove the remote controller unit after it has been
installed, insert a flathead screwdriver into the slot on the
bottom of the case and turn it. (Fig. 5)
Fig. 2-a
Fig. 2-b
B. Installing directly onto the wall
(1) Insert a flathead screwdriver into the 5 tab locations and
disconnect the back plate of the remote controller by lifting up slightly. (Fig. 2-b)
The tabs are thin; take care not to chip them.
(2) Use tapping screws to directly fasten the remote con-
troller back plate onto the wall. (Fig. 6)
(3) Insert the connector into the PCB of the remote con-
troller unit, and wrap the wire harness around the hook.
(Fig. 4)
(4) Use nippers or a similar tool to cut out the slot on the top
of the remote controller unit. Pass the wire harness
through the slot, then hook the remote controller unit
onto the top of the back plate and install the remote controller unit.
(5) In order to conceal the exposed wiring, use a wire cover
(locally purchased) or similar means.
NOTE
• When installing the remote controller back plate, be sure
that it is flat and straight. Do not over-tighten the installation screws.
• Install the remote controller away from all sources of electrical noise.
• Install a noise filter or take other appropriate action if electrical noise affects the power supply circuit of the unit.
Fig. 3
Fig. 4
Fig. 5
Fig. 6
2
Page 35
ON/OFF
operation button
1 HR.TIMER
button
NIGHT SETBACK
button
ACL (Reset)
button
SENSOR button
OPERATION lamp
TIMER lamp
HIGH POWER lamp
REMOTE CONTROL receiver
OPERATION button
I How to Test Run the Air Conditioner
IMPORTANT
After turning on the power of the air conditioner, use the
remote controller and follow the steps below to conduct
the test run.
(1) Set the remote controller in Test Run mode. (Fig. 9)
a)Press and hold the NIGHT SETBACK button and
the 1HR. TIMER button.
b)Then press and hold the ACL (Reset) button with
a pointed object such as the tip of a pen. After 5
seconds, release the ACL button first.
c) Then release the NIGHT SETBACK and 1HR.
TIMER buttons.
d)appears and “oP-1” blinking in the remote con-
troller clock display area. (Fig. 10)
(2) Start Cooling mode test run by pressing the ON/OFF
operation button of the remote controller. (Fig. 9)
• This starts the fan producing uncooled forced air
with the 3 indicator lamps (OPERATION lamp,
TIMER lamp, and HIGH POWER lamp) on the
main unit blinking. (Fig. 11)
• After 3 minutes, the system shifts into cooling
operation, and cool air will start to be felt. Cooling
mode test run is unaffected by the room temperature.
(3) Press the ON/OFF operation button of the remote
controller again to stop the test run. (Fig. 9)
(4) Finally press the ACL (Reset) button of the remote
controller to release it from Test Run mode to return
to normal mode. (Fig. 9)
• “” and “oP-1” will disappear from the remote
controller clock display area.
Fig. 9
Fig. 10
NOTE
Troubleshooting:
In the event that the green OPERATION lamp is blinking
upon powering up the system, an error condition exists.
In this case, refer to the self-diagnostics procedure
which can be seen by opening the air-intake grille.
After the test run is completed, be sure to press the
ACL (Reset) button to return to normal mode. The air
conditioner will not operate correctly if this is not done.
Fig. 11
4
Page 36
SANYO Commercial Solutions
A Division of SANYO North America Corporation
1300 Michael Drive, Suite A
Wood Dale, IL 60191, U.S.A.