OUTDOOR MODEL No.PRODUCT CODE No.APPLICABLE INDOOR MODEL No.V/ø/Hz
CHDX0905385403301 AHX,UHX,KHX0752
CHDX1405385403302 AHX,KHX0952OUTDOOR
XHX,AHX,UHX,THX,KHX1252208-230/3ø/60
XHX,UHX,THX,KHX1852
XHX,UHX,THX,KHX 2452INDOOR
XHX,UHX,DHX3652208-230/1ø/60
DHX4852
85464869238002
REFERENCE NO.
TD831138-02
i
Check of Density Limit
NO TE
Outdoor unit
Refrigerant tubing
Indoor unit
e.g., charged
amount (353 oz)
Outdoor unit
Indoor unit
Room A Room B Room C Room D Room E Room F
e.g., charged
amount (529 oz)
Refrigerant tubing
Outdoor unit
Very
small
room
Indoor unit
Small
room
Medium
room
Large room
Mechanical ventilation device – Gas leak detector
00
57
114
170
227
284
341
398
454
0
500
1000
1500
2000
2500
3000
3500
4000
400200600 800 1000 1200
Total amount of refrigerant
Min. indoor volume
Min. indoor floor area
(when the ceilin
g
is 8.8 ft. hi
g
h)
ft.
3
ft.
2
oz
Range above
the density limit of
0.3 oz/ft.
3
(countermeasures
needed)
Range below
the density limit of
0.3 oz/ft.
3
(countermeasures
not needed)
The room in which the air conditioner is to be
installed requires a design that in the event of refrigerant gas leaking out, its density will not exceed a set
limit.
The refrigerant (R410A), which is used in the air conditioner, is safe, without the toxicity or combustibility of
ammonia, and is not restricted by laws imposed to protect
the ozone layer. However, since it contains more than air,
it poses the risk of suffocation if its density should rise
excessively. Suffocation from leakage of refrigerant is
almost non-existent. With the recent increase in the number of high density buildings, however, the installation of
multi air conditioner systems is on the increase because of
the need for effective use of floor space, individual control,
energy conservation by curtailing heat and carrying power,
etc.
Most importantly, the multi air conditioner system is able
to replenish a large amount of refrigerant compared to
conventional individual air conditioners. If a single unit
of the multi air conditioner system is to be installed in a
small room, select a suitable model and installation procedure so that if the refrigerant accidentally leaks out,
its density does not reach the limit (and in the event of
an emergency, measures can be made before injury can
occur).
In a room where the density may exceed the limit, create
an opening with adjacent rooms, or install mechanical
ventilation combined with a gas leak detection device.
The density is as given below.
2. The standards for minimum room volume are as follows.
(1) No partition (shaded portion)
(2) When there is an effective opening with the adjacent
room for ventilation of leaking refrigerant gas (opening without a door, or an opening 0.15% or larger
than the respective floor spaces at the top or bottom
of the door).
(3) If an indoor unit is installed in each partitioned room
and the refrigerant tubing is interconnected, the
smallest room of course becomes the object. But
when mechanical ventilation is installed interlocked
with a gas leakage detector in the smallest room
where the density limit is exceeded, the volume of the
next smallest room becomes the object.
Total amount of refrigerant (lbs)
Min. volume of the indoor unit installed room (ft.3)
<
Density limit (oz/ft.3)
The density limit of refrigerant which is used in multi air
conditioners is 0.3 oz/ft.3 (ISO 5149).
1.If there are 2 or more refrigerating systems in a single
refrigerating device, the amount of refrigerant should be
as charged in each independent device.
For the amount of charge in this example:
The possible amount of leaked refrigerant gas in
rooms A, B and C is 353 oz.
The possible amount of leaked refrigerant gas in
rooms D, E and F is 529 oz.
3. The minimum indoor floor space compared with the
amount of refrigerant is roughly as follows: (When the
ceiling is 8.8 ft. high)
ii
Contents
Section 1: OUTLINE OF W-2WAY ECO-i SYSTEM ................................................................1-1
The compressor combination (DC inverter compressor + constant-speed compressor) allows smooth capacity control from 0.8
HP to 32 HP.
Realization of smooth capacity control
from 0.8HP to 32HP
Capacity control is possible smoothly with a DC
inverter compressor.The right graph shows the
image of the operating combination of compressors in case of 32HP system.In actual operation,
the combination will be changed by operationg
condition, operating time amount, priority of compressor and so on.
Comp. HPUnit1(main) Unit2(sub1)
DC comp.4.04.0
AC1 comp.6.06.0
AC2 comp.6.06.0
*32HP = CHDX14053 Type x2
1-6
Design of W-2WAY ECO-i SYSTEM Unit Specifications
1
2
3
4
5
6
7
8
Contents
2. DESIGN OF W-2WAY ECO-i SYSTEM
1. Model Selecting and Capacity Calculator ........................................................................2-2
2. System Design ..................................................................................................................2-17
Calculation of the corrected outdoor unit capacity
●
Capacity correction coefficient for model.................................................................... 2-11, 13, 14
●
Capacity correction coefficient for outdoor temperature conditions ..................................2-11, 13
●
Capacity correction coefficient for tubing length and elevation difference ........................ 2-11, 14
●
Heating capacity correction coefficient for frosting/defrosting .......................................... 2-11, 13
Calculation of the corrected capacity for each indoor unit
●
Capacity correction coefficient for indoor temperature conditions .................................... 2-11, 14
●
Capacity distribution ratio based on the tubing length and elevation difference .............. 2-11, 14
Calculation of the actual capacity for each indoor unit
●
Calculate the corrected indoor/outdoor capacity ratio, based on the corrected outdoor unit
capacity and the total corrected capacity of all indoor units in the same system. Use the result to
calculate the capacity correction coefficient for the indoor units.................................
2-11 ~ 2-14
●
Multiply the corrected capacity of each indoor unit by the capacity correction coefficient to calcu-
late the actual capacity for each indoor unit. .......................................................................... 2-12
Recheck of the actual capacity for each indoor unit
●
If the capacity is inadequate, reexamine the unit combinations.
Example 1: Increasing the outdoor unit capacity.................................................................... 2-18
Example 2: Increasing the indoor unit capacity ...................................................................... 2-19
●
Increasing the tubing size ...................................................................................................... 2-20
Design of tubing
●
Create a tubing design which minimizes the amount of additional refrigerant charge as much as
If tubing extension for additional unit is expected in the future, create the tubing design with
adequate consideration for this extension.
●
Select the tubing size for the main tube (LA) up to the No. 1 distribution joint based on the rated
cooling capacity of the outdoor unit. Select tubing sizes after the distribution point based on the
total rated cooling capacity of the connected indoor units.
●
Increasing the tubing size of the wide tubes can reduce the loss of capacity caused by longer
tubing lengths. (Only the main wide tube with the largest tube diameter (main tube LA and main
tubes after the distribution point that are the same size as LA) can be changed.) In this case, it is
necessary to recalculate the actual indoor unit capacities. ....................................................
2-20
Calculation of additional refrigerant charge amount
●
Calculate the additional refrigerant charge from the diameters and lengths of the refrigerant tubing. Even if the wide tubing diameter was increased, determine the additional refrigerant charge
based only on the narrow tubing size.....................................................................................
2-21
●
Check the minimum indoor capacity (limit density) with respect to the amount of refrigerant. If the
limit density is exceeded, be sure to install ventilation equipment or take other corrective steps. 2-22
Design of electrical wiring capacity
●
Select a wiring capacity according to the method of power supply. ...................................... 2-24
1. Model Selecting and Capacity Calculator
1-2. Procedure for Selecting Models and Calculating Capacity
Main distribution tubes LC – LG are selected according to the capacity after the distribution joint.
Sizes of indoor unit connection tubing 1 – 40 are determined by the connection tubing sizes on the indoor units.
Main tubing length LM = LA + LB … 262 ft
1.
2.
3. The outdoor connection main tubing ( B portion) is determined by the total capacity of the outdoor units that are connected to the tube ends.
4.
Ball valve (field supply)
T-joint (field supply)
Note: Do not use commercially available T-joints for the liquid tubing and parts.
* Be sure to use special R410A distribution joints (APR: purchased separately) for outdoor unit connections and tubing branches.
Table 2-1 Ranges that Apply to Refrigerant Tubing Lengths and to Differences in Installation Heights
Select the installation location so that the length and size of refrigerant tubing are within the allowable range shown in the figure below.
ItemMarkContentsLength (ft.)
L1Max. tubing length
Actual length492
Equivalent length574
L (L2 – L4)
Difference between max. length and min.
length from the No.1 distribution joint
131
LMMax. length of main tubing (at max. diameter)262
1, 2... 40
Max. length of each distribution tube98
L1+ 1+ 2... 39+
A+LE+LF+LG
Total max. tubing length including length of
each distribution tube (only liquid tubing)
984
L5
L3
Distance between outdoor units
32
H1
When outdoor unit is installed higher than indoor unit164
When outdoor unit is installed lower than indoor unit131
H2
Max. difference between indoor units49
H3Max. difference between outdoor units
13
L = Length, H=Height
Allowable tubing
length
Allowable elevation
difference
*3
6.6
Allowable length of
joint tubing
T-joint tubing (field-supply); Max. tubing length between
the first T-joint and solidly welded-shut end point
1: The outdoor connection main tubing ( B portion) is determined by the total capacity of the outdoor units that are connected to
the tube ends.
2: If the longest tubing length (L1) exceeds 295 ft. (equivalent length), increase the sizes of the main tubes (LM) by 1 rank for gas
tubes and liquid tubes. (Use a field supply reducer.) (Select the tube size from the table of main tube sizes (Table 2-5) on the
following page (LA table), and from the table of refrigerant tubing sizes (Table 2-10) on the second following page.)
3: If the longest main tube length (LM) exceeds 164 ft., increase the main tube size at the portion before 164 ft. by 1 rank for the
gas tubes. (Use a field supply reducer.)
(For the portion that exceeds 164 ft., set based on the main tube sizes (LA) listed in the table on the following page.)
4: If the size of the existing tubing is already larger than the standard tubing size, it is not necessary to further increase the size.
* If the existing tubing is used, and the amount of on-site additional refrigerant charge exceeds the value listed below, then
change the size of the tubing to reduce the amount of refrigerant.
Max. additional charge for 1 outdoor unit: 62 lbs
Max. additional charge for 2 outdoor units: 111lbs
NOTE
L5
LA
LE
LM
LBLC
L2
L4
LF
LDL3
LG
H2
H3
H1
L1
2
3
1
5
4
A
B
38
39
40
For
extension
For
extension
Max. 1.3ft
Max. 1.3ft
1. Model Selecting and Capacity Calculator
1-3. Tubing Length
2-4
1
2
3
4
5
6
7
8
2-5
Design of W-2WAY ECO-i SYSTEM Unit Specifications
1
2
3
4
5
6
7
8
1. Model Selecting and Capacity Calculator
Table 2-2 Refrigerant Charge Amount at Shipment (for outdoor unit)
DC
(oz)
Additional refrigerant charge amount is calculated from the liquid tubing total length as follows.
Table 2-3 Amount of Refrigerant Charge Per Meter, According to Liquid Tubing Size
Liquid tubing size Amount of refrigerant
(in. (mm)) charge (oz/ft.)
ø1/4" (ø6.35) 0.279
ø3/8" (ø9.52) 0.602
ø1/2" (ø12.7) 1.38
ø5/8" (ø15.88) 1.99
ø3/4" (ø19.05) 2.78
ø7/8" (ø22.22) 3.93
CHDX09053 CHDX14053
423 458
Required amount of charge = (Amount of refrigerant charge per
meter of each size of liquid tube × its tube length) + (...) + (...)
* Always charge accurately using a scale for weighing.
* If the existing tubing is used, and the amount of on-site additional
refrigerant charge exceeds the value listed below, then change the
size of the tubing to reduce the amount of refrigerant.
Max. additional charge for 1 outdoor unit : 62 lbs
Max. additional charge for 2 outdoor units : 111 lbs
Max. allowable indoor/outdoor capacity ratio 50 – 130 %
*1: Up to 2 units can be connected if the system has been extended.
*1
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
32
249,100
(73.0)
26
ø7/8"
(ø22.22)
10
95,500
(28.0)
ø1/2"
(ø12.7)
153,600
(45.0)
16
ø1-1/8"
(ø28.58)
ø5/8"
(ø15.88)
10
10
16
10
16
16
191,100
(56.0)
20
ø3/4"
(ø19.05)
ø1-3/8"
(ø34.92)
ø3/8"
(ø9.52)
307,100
(90.0)
16 10
BTU/h
(kW)
Total system horsepower
Combined outdoor units
Gas tubing
Liquid tubing
ø3/4"
(ø19.05)
ø1-3/8"
(ø34.93)
ø5/8"
(ø15.88)
ø1-1/8"
(ø28.58)
ø1/2"
(ø12.7)
ø1-1/8"
(ø28.58)
ø3/8"
(ø9.52)
ø3/4"
(ø19.05)
ø3/8"
(ø9.52)
ø5/8"
(ø15.88)
ø3/8"
(ø9.52)
ø1/2"
(ø12.7)
Gas tubing
Liquid tubing
–
238,900
(25 hp)
178,800
(19 hp)
ø1/2"
(ø12.7)
ø1-1/8"
(ø28.58)
178,800
(19 hp)
143,300
(15 hp)
24,200
(2.5 hp)
24,200
(2.5 hp)
–
54,600
(6 hp)
54,600
(6 hp)
238,900
(25 hp)
76,800
(8.1 hp)
ø3/8"
(ø9.52)
ø7/8"
(ø22.22)
76,800
(8.1 hp)
102,400
(11 hp)
102,400
(11 hp)
Below BTU/h
Over BTU/h
143,300
(15 hp)
hp = horsepower
Tubing size
Total capacity
after distribution
Design of W-2WAY ECO-i SYSTEM Unit Specifications
1. Model Selecting and Capacity Calculator
1-4 Tubing Size
Table 2-5 Main Tubing Size (LA)
*1: If future extension is planned, select the tubing diameter based on the total horsepower after extension.
However extension is not possible if the resulting tubing size is two ranks higher.
*2: The balance tube (outdoor unit tube) diameter is ø1/4".
*3: Type 1 tubing should be used for the refrigerant tubes.
*4: If the length of the longest tube (L1) exceeds 295 ft. (equivalent length), increase the main tube (LM) size by 1 rank for the gas
and liquid tubes. (Use field-supply reducers.) (Select from Table 2-5 and Table 2-10.)
*5: If the longest main tube length (LM) exceeds 164 ft., increase the main tube size at the portion before 164 ft. by 1 rank for the
gas tubes.
(For the portion that exceeds 164 ft., set based on the main tube sizes (LA) listed in the table above.)
Unit: in. (mm)
Size of tubing (lB) between outdoor units
Select the size of tubing between outdoor units based on the main tubing size (LA) as given in the table above.
Table 2-6 Main Tubing Size After Distribution (LB, LC...)
Note: In case the total capacity of connected indoor units exceeds the total capacity of the outdoor units, select the main tubing
size for the total capacity of the outdoor units. (Especially the main tubing segments of LA, LB and LF.)
Unit: in. (mm)
2-6
1
2
3
4
5
6
7
8
2-7
Design of W-2WAY ECO-i SYSTEM Unit Specifications
1
2
3
4
5
6
7
8
ø7/8"
(ø22.22)
ø3/8" (ø9.52)
ø1/4" (ø6.35)
95,500
(28.0)
153,600
(45.0)
ø1-1/8"
(ø28.58)
Flare connection
Brazing connection
ø1/2" (ø12.7)
Flare connection
( A – B)
Balance tubing
Liquid tubing
Gas tubing
BTU/h
(kW)
Balance tube
Liquid tube
Gas tube
ø5/8" (ø15.88)
ø3/8" (ø9.52) ø1/4" (ø6.35)
ø1/2" (ø12.7)
Gas tubing
Liquid tubing
Indoor unit type 7 9 12 18
24
36 48
1. Model Selecting and Capacity Calculator
Table 2-7 Amount of Refrigerant Charge
Liquid tubing size Amount of refrigerant
(in. (mm)) charge (oz/ft.)
ø1/4" (ø6.35) 0.279
ø3/8" (ø9.52) 0.602
ø1/2" (ø12.7) 1.38
ø5/8" (ø15.88) 1.99
ø3/4" (ø19.05) 2.78
ø7/8" (ø22.22) 3.93
Table 2-8 Outdoor Unit Tubing Connection Size
Unit: in. (mm)
Table 2-9 Indoor Unit Tubing Connection Size
Note: Use C1220T-1/2H material for tubing over ø3/4" (ø22.22).
Table 2-10 Refrigerant tubing (Existing tubing can be used.)
Y-branch distribution joint Equivalent length conversion not needed.
Ball valve for service Equivalent length conversion not needed.
1. Model Selecting and Capacity Calculator
Straight equivalent length of joints
Design the tubing system by referring to the following table for the straight equivalent length of joints.
Table 2-11 Straight Equivalent Length of Joints
Capacity loss caused by differences in tubing diameters
* Capacity loss will occur if a tubing system that matches the horsepower is not selected (for example, if a tubing system was
determined and installed with no plan for extension and extension occurs later). The loss rate can be found from the graph
below.
Unit: ft.
(Reading the graph)
<Example 1>
Currently a 16 HP system and ø1-1/8" Gas tubings are used. Subsequently the system is expanded, with 16 HP added to the
same tubing system.
Horsepower after extension: 16 + 16 = 32 HP
From the graph above: Cooling: Capacity ratio is 90.8%. Actual capacity = 32 × 0.908 = 29.1 HP
Heating: Capacity ratio is 96.0%. Actual capacity = 32 × 0.960 = 30.7 HP
2-8
1
2
3
4
5
6
7
8
2-9
Design of W-2WAY ECO-i SYSTEM Unit Specifications
1
2
3
4
5
6
7
8
WARNING
CAUTION
WARNING
00
57
114
170
227
284
341
398
454
511
568
625
682
738
795
852
909
966
1022
1079
1136
0
500
1000
1500
2000
2500
3000
3500
4000
4500
5000
5500
6000
6500
7000
7500
8000
8500
9000
9500
10000
10005001500 2000 2500 3000
Total amount of refrigerant
Min. indoor volume
Min. indoor floor area
(when the ceilin
g
is 8.8 ft. hi
g
h)
ft.
3
ft.
2
oz
Range above
the density limit of
0.3 oz/ft.
3
(countermeasures
needed)
Range below
the density limit of
0.3 oz/ft.
3
(countermeasures
not needed)
1. Model Selecting and Capacity Calculator
Additional refrigerant charge amount
Additional refrigerant charge amount is calculated from the liquid tubing total length as follows.
Table 2-12 Amount of Refrigerant Charge Per Meter, According to Liquid Tubing Size
Liquid tubing size Amount of refrigerant
(in. (mm)) charge (oz/ft.)
ø1/4" (ø6.35) 0.279
ø3/8" (ø9.52) 0.602
ø1/2" (ø12.7) 1.38
ø5/8" (ø15.88) 1.99
ø3/4" (ø19.05) 2.78
ø7/8" (ø22.22) 3.93
Check of limit density
Required amount of charge = (Amount of refrigerant charge per
meter of each size of liquid tube × its tube length) + (...) + (...)
* Always charge accurately using a scale for weighing.
1-5. Check of Limit Density
When installing an air conditioner in a room, it is necessary to
ensure that even if the refrigerant gas accidentally leaks out, its
density does not exceed the limit level for that room.
If the density could exceed the limit level, it is necessary to provide
an opening between the unit and the adjacent room, or to install
mechanical ventilation which is interlocked with a leak detector.
(Total refrigerant charged amount: oz)
(Min. indoor volume where the indoor unit is installed: ft.3)
<
The limit density of refrigerant R410A which is used in this unit is
0.3 oz/ft.3 (ISO 5149).
The shipped outdoor unit comes charged with the amount of refrigerant fixed for each type, so add it to the amount that is charged in
the field. (For the refrigerant charge amount at shipment, refer to the
unit’s nameplate.)
Always check the gas density
limit for the room in which the
unit is installed.
Limit density 0.3 (oz/ft.3)
Pay special attention to any location,
such as a basement, etc., where leaking
refrigerant can accumulate, since
refrigerant gas is heavier than air.
Minimum indoor volume & floor area as against the amount
of refrigerant is roughly as given in the following table.
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
Capacity distribution ratio for each indoor unit (3) = Correction coefficient for that indoor unit / Correction coefficient for the outdoor uni
t
However, the corrected cooling capacity of each indoor unit is found as shown below.
If (2) < 100% and (2)
×
(3) > 100%: Corrected cooling capacity for that indoor unit [5] = Rated cooling capacity for that indoor unit
If (2) ≥ 100%: Corrected cooling capacity for that indoor unit (5) = Rated cooling capacity for that indoor unit
1-6. Calculation of Actual Capacity of Indoor Unit
Calculating the actual capacity of each indoor unit
Because the capacity of a multi air-conditioner changes according to the temperature conditions, tubing length, elevation difference and other factors, select the correct model after taking into account the various correction values. When selecting The
model, calculate the corrected capacities of the outdoor unit and each indoor unit. Use the corrected outdoor unit capacity and
the total corrected capacity of all the indoor units to calculate the actual final capacity of each indoor unit.
1. Outdoor unit capacity correction coefficient
Find the outdoor unit capacity correction coefficient for the following items.
(1) Capacity correction for the outdoor unit model
The capacity correction coefficient is 1.00.
(2) Capacity correction for the outdoor unit temperature conditions
From the graph of capacity characteristics on page 2-12, use the outdoor temperature to find the capacity correction coefficient.
(3) Capacity correction for the outdoor unit tubing length and elevation difference
From the graph of capacity change characteristics on page 2-13, use the tubing length and elevation difference to find the
capacity correction coefficient.
The outdoor unit correction coefficient is the value which corresponds to the most demanding indoor unit.
(4) Capacity correction for outdoor unit frosting/defrosting during heating
From the table on page 2-12, find the capacity correction coefficient.
2. Indoor unit capacity correction coefficients
Find the indoor unit capacity correction coefficient for the following items.
(2) Capacity correction for the indoor unit temperature conditions
From the graph of capacity characteristics on page 2-13, use the indoor temperature to find the capacity correction coefficient.
(3) Capacity distribution ratio based on the indoor unit tubing length and elevation difference
First, in the same way as for the outdoor unit, use the tubing length and elevation difference for each indoor unit to find the
correction coefficient from the graph of capacity change characteristics on page 2-13. Then divide the result by the outdoor
unit correction coefficient to find the capacity distribution ratio for each indoor unit.
3. Calculating the corrected capacities for the outdoor unit and each indoor unit
The corrected capacities for the outdoor unit and each indoor unit are calculated form the formula below.
<Cooling>
Outdoor unit corrected cooling capacity (5) = Outdoor unit rated cooling capacity × Correction coefficient for model ((1)
Page 2-12) × Correction coefficient for outdoor temperature conditions ((2)
Page 2-12) × Correction coefficient for tubing length and elevation difference
((3) Page 2-13)
* However, if the outdoor unit corrected cooling capacity [5] is greater than 100%, then the outdoor unit corrected cooling
capacity [5] is considered to be 100%.
Corrected cooling capacity of each indoor unit (5) = Rated cooling capacity for that indoor unit × Correction coefficient for
indoor temperature conditions at that indoor unit ((2) Page 2-13) × Distribution ratio based on tubing length and elevation difference at that indoor unit ((3) Page 2-13)
2-10
1
2
3
4
5
6
7
8
2-11
Design of W-2WAY ECO-i SYSTEM Unit Specifications
1
2
3
4
5
6
7
8
However, the corrected heating capacity of each indoor unit is found as shown below.
If (2) < 100% and (2) ×(3) > 100%: Corrected heating capacity for that indoor unit (5) = Rated heating capacity for that indoor unit
If (2) ≥ 100%: Corrected heating capacity for that indoor unit (5) = Rated heating capacity for that indoor unit ×(2)
1. Model Selecting and Capacity Calculator
<Heating>
Outdoor unit corrected heating capacity (5) = Outdoor unit rated heating capacity × Correction coefficient for model ((1)
Page 2-12) × Correction coefficient for outdoor temperature conditions ((2)
Page 2-12) × Correction coefficient for tubing length and elevation difference
((3) Page 2-13) × Correction coefficient for frosting/defrosting ((4) Page
* However, if the outdoor unit corrected heating capacity [5] is greater than 100%, then the outdoor unit corrected heating
capacity is considered to be 100%.
Corrected heating capacity of each indoor unit (5) = Rated heating capacity for that indoor unit × Correction coefficient for
indoor temperature conditions at that indoor unit ((2) Page 2-13) × Distribution ratio based on tubing length and elevation
difference at that indoor unit.
* Characteristic graphs are shown on the pages listed above next to each correction item. Find each correction coefficient
from the appropriate conditions.
2-12)
4. Calculating the actual indoor unit capacity based on the indoor/outdoor corrected capacity ratio
Calculate the actual capacity of each indoor unit from the values (found in (3)) for the corrected outdoor unit capacity and the
corrected capacity of each indoor unit.
<Cooling capacity>
Corrected indoor/outdoor capacity ratio during cooling (Ruc) = Total corrected cooling capacity of all indoor units in that system /
Corrected outdoor unit cooling capacity
If the corrected outdoor unit cooling capacity is greater than or equal to the total corrected unit cooling capacity of all indoor units
in that system (Ruc 1), then:
Actual cooling capacity of each indoor unit (7) = Corrected cooling capacity of each indoor unit (5) (In other words, the correction coefficient (6), based on the corrected indoor/outdoor capacity ratios for each indoor unit, is 1.)
If the corrected outdoor unit cooling capacity is less than the total corrected unit cooling capacity of all indoor units in that system (Ruc > 1), then:
(Actual cooling capacity of each indoor unit (7)) = (Corrected cooling capacity of each indoor unit (5)) × (0.25 × Ruc + 0.75)
/ Ruc
(In other words, the correction coefficient (6), based on the corrected indoor/outdoor capacity ratios for each indoor unit, is
the underlined part in the formula above.)
<Heating capacity>
Corrected indoor/outdoor capacity ratio during heating (Ruh) = Total corrected heating capacity of all indoor units in that system
/ Corrected outdoor unit heating capacity
If the corrected outdoor unit heating capacity is greater than or equal to the total corrected unit heating capacity of all indoor
units in that system (Ruh 1), then:
Actual heating capacity of each indoor unit (7) = Corrected heating capacity of each indoor unit (5)
(In other words, the correction coefficient (6), based on the corrected indoor/outdoor capacity ratios for each indoor unit, is 1.)
If the corrected outdoor unit heating capacity is less than the total corrected unit heating capacity of all indoor units in that system (Ruh > 1), then:
(Actual heating capacity of each indoor unit (7)) = (Corrected heating capacity of each indoor unit (5)) × (0.1 × Ruh + 0.9) /
Ruh
(In other words, the correction coefficient (6), based on the corrected indoor/outdoor capacity ratios for each indoor unit, is
the underlined part in the formula above.)
Design of W-2WAY ECO-i SYSTEM Unit Specifications
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
Indoor unit capacity correction coefficient for Ruc (cooling)
Indoor unit capacity correction coefficient for Ruh (heating)
Graph of indoor unit capacity characteristics (2 – (2))
Graph of capacity change characteristics resulting from tubing length and elevation difference (1 / 2 – (3))
The positive side for the elevation difference indicates that the outdoor unit is installed at a higher position than the indoor units.
The negative side indicates the opposite.
The capacity loss that is caused by the tubing length can be reduced by increasing the sizes of the discharge tubes and suc-
tion tubes. Refer to Table 2-13 and make the appropriate changes. However be sure that the total length does not exceed the
maximum.
* The only sizes which can be increased are the LM (main tube with the largest diameter) gas tubes, and the changes are
limited to those shown in Table 2-13.
In addition, note that the additional refrigerant charge is determined only by the narrow-tube size.
Table 2-13 Equivalent Length Correction Coefficient when the Size of the Discharge Tubes and Suction Tubes (LM)
is Increased
Standard tubing diameter
(gas tube, in.(mm))
Tubing diameter after change
(gas tube,in.(mm))
Equivalent length correction
coefficient
* If the size of the discharge tubes and suction tubes (LM) have been increased, apply the correction coefficient from Table
2-13 and calculate the equivalent length of the LM section.
Equivalent length of tubing after size increase
= Standard tubing equivalent length × Equivalent length correction coefficient
ø1/2"
(ø12.7)
ø5/8"ø3/4"ø7/8"ø1-1/8"ø1-3/8"
(ø15.88)(ø19.05)(ø22.22)(ø28.58)(ø34.93)
ø5/8"
(ø15.88)(ø19.05)(ø22.22)(ø28.58)
0.40.50.6
ø3/4"ø7/8"ø1-1/8"
Design of W-2WAY ECO-i SYSTEM Unit Specifications
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
<Cooling>
<Heating>
16HP
10HP
Indoor air intake temp. (°F DB)
59
68
77
59
68
77
Capacity ratio (%)
Input ratio (%)
130
120
110
100
90
80
70
60
50
40
130
120
110
100
90
80
70
60
50
– 4 5 14 23 32 41 50 59
Outdoor air intake temp. (°F WB)
Indoor air intake temp. (°F DB)
59
68
77
59
68
77
Capacity ratio (%)
Input ratio (%)
130
120
110
100
90
80
70
60
50
40
130
120
110
100
90
80
70
60
50
– 4 5 14 23 32 41 50 59
Outdoor air intake temp. (°F WB)
* Broken line indicates 16 HP DC inverter unit
Outdoor air intake temp. ( °F DB)
130
120
110
100
90
80
120
110
100
90
80
70
60
50
40
30
20
10
)
%
(
o
i
t
ar
y
t
i
cap
a
C
)
%( oitar tu
pn
I
14 23 32 41 50 59 68 77 86 95 104 113
WB = 66
°
F
Indoor air intake temp. (WB) = 71°F
WB = 60°F
Indoor air intak
e tem
p
.
(WB) = 71
°
F
WB = 66
°
F
WB = 60
°
F
1. Model Selecting and Capacity Calculator
1-7. Capacity Correction Graph According to Temperature Condition
Capacity characteristics
(The corrected capacity for specific temperature conditions can be found from the graphs below.)
Heating capacity correction coefficients for frost/defrost operation
The positive side for the elevation difference indicates that
the outdoor unit is installed at a higher position than the
indoor units. The negative side indicates the opposite.
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
Design of W-2WAY ECO-i SYSTEM Unit Specifications
1. Model Selecting and Capacity Calculator
If the maximum tubing length (L1) exceeds 295 ft (equivalent length), increase the tubing size of the main liquid, gas tubes (LM)
by one rank.
However, the upper limit for the gas tube size is ø1-5/8".
Increasing the tubing size of the gas tubes can reduce the loss of capacity caused by longer tubing lengths.
Refer to Table 2-13 to increase the tubing size. However, the maximum allowable tubing length must not be exceeded.
* The amount of additional refrigerant charge is determined from the liquid tube size only.
Table 2-13 Correction coefficient for equivalent length when the size of the gas tube (LM) is increased
Standard tube diameter
(gas tube, in.(mm))
Tube diameter after change
(gas tube, in.(mm))
Equivalent length correction
coefficient
* When increasing the size of the suction and discharge tubing (LM), multiply by the
correction coefficient from Table 2-13 and calculate the equivalent length for section LM.
Tubing equivalent length after size increase
= Standard tubing equivalent length × Equivalent length correction coefficient
ø1/2"
(ø12.7)
ø5/8"
(ø15.88)
ø5/8"
(ø15.88)
ø3/4"
(ø19.05)
0.40.50.6
ø3/4"
(ø19.05)
ø7/8"
(ø22.22)
ø7/8"
(ø22.22)
ø1-1/8"
(ø28.58)
ø1-1/8"
(ø28.58)
ø1-3/8"
(ø34.93)
2-16
1
2
3
4
5
6
7
8
Outdoor
unit 1
Indoor
unit 1
Indoor
unit 2
Indoor
unit 3
Indoor
unit 4
Outdoor
unit 2
Elevation
difference: 33 ft
164 ft
33 ft33 ft66 ft
33 ft33 ft33 ft
Design of W-2WAY ECO-i SYSTEM Unit Specifications
2. System Design
2-1. System Example
(1) Below are the tables created using the “Sanyo PAC System Diagram Software.” Details of the calculations are shown in (2).
Selection conditions
Assumes that installation is in a 60 Hz region.
Outdoor unit
Cooling
Heating
Actual tubing length291 ft197 ft230 ft263 ft296 ft
Equivalent length (with consideration
for curves, etc.)
Total corrected capacity of indoor units (cooling/heating) = 145,200/168,700
Ruc = 145,200/159,600 = 0.910 < 1 Ruh = 168,700/156,100 = 1.081 > 1
Outdoor unit changes
During heating, the corrected outdoor unit capacity is less than the total corrected capacity of all indoor units in the system. As a
result, the actual capacity of each indoor unit is less than the maximum load. Therefore the outdoor unit is increased by one rank.
Room 1
(indoor unit 1)
Type 4852Type 4852Type 3652Type 1852
40,00040,00030,00018,000
47,800 /
54,600
47,400 /
54,600
47,400 /
54,600
Selected model
Maximum load
(cooling/heating) (BTU/h)
Rated capacity
(cooling/heating) (BTU/h)
(5) Corrected capacity (cooling/
heating) (BTU/h)
(7) Actual capacity
(cooling/heating) (BTU/h)
Outdoor unit
Type
14053+09035
249,100 /
278,100
208,100 /
201,900
Total corrected capacity of all indoor units (cooling/heating) = 145,200/163,700
Ruc = 145,200/208,100 = 0.698 < 1 Ruh = 168,700/201,900 = 0.835 < 1
Room 2
(indoor unit 2)
2-17
47,800 /
54,600
46,300 /
54,600
46,300 /
54,600
Room 3
(indoor unit 3)
36,000 /
39,000
34,000 /
38,900
34,000 /
38,900
Room 4
(indoor unit 4)
19,000 /
21,000
17,500 /
20,600
17,500 /
20,600
Design of W-2WAY ECO-i SYSTEM Unit Specifications
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
2. System Design
Indoor unit changes
The indoor unit in room 4, where the corrected indoor unit capacity is less than the maximum load, is increased by one rank.
Outdoor unit
Selected model
Maximum load
(cooling/heating) (BTU/h)
Rated capacity
(cooling/heating) (BTU/h)
(5) Corrected capacity
(cooling/heating) (BTU/h)
(7) Actual capacity
(cooling/heating) (BTU/h)
Total corrected capacity of all indoor units (cooling/heating) = 150,700/174,500
Ruc = 150,700/208,100 = 0.724 < 1 Ruh = 174,500/201,900 = 0.864 < 1
For both cooling and heating in all rooms, actual capacity is now greater than or equal to the maximum load. Selection is
completed.
*1: This varies depending on the values of (2) and (2) × (Distribution ratio in (3)).
*2: Corrected outdoor unit capacity = Rated outdoor unit capacity × (1) × (2) × (3) × (4)
The actual capacity is calculated as shown below.
Cooling: Ruc = (47,400 + 46,300 + 34,000 + 23,000) / 208,100 = 0.724 < 1
Therefore,
Actual cooling capacity of each indoor unit = Corrected cooling capacity of each indoor unit
(In other words, the correction coefficient (6) for the corrected capacity ratio is 1.)
Heating: Ruh = (54,600 + 54,600 + 38,900 + 26,400) / 201,900 = 0.864 < 1
Therefore,
Actual heating capacity of each indoor unit = Corrected heating capacity of each indoor unit × (0.1 × Ruh + 0.9) / Ruh
(In other words, the correction coefficient (6) for the corrected capacity ratio is (0.1 × Ruh + 0.9) / Ruh.)
0.819 / 0.871
Room 1
(indoor unit 1)
1.077 / 1.0521.052 / 1.035
0.99 / 1.030.97 / 1.010.95 / 1.000.92 / 0.98
Room 2
(indoor unit 2)
Room 3
(indoor unit 3)
1.00 / 1.00
Room 4
(indoor unit 4)
1.026 / 1.0171.00 / 1.00
2-18
1
2
3
4
5
6
7
8
2-19
Design of W-2WAY ECO-i SYSTEM Unit Specifications
1
2
3
4
5
6
7
8
964
0905314053
3652
4852
1852
1852
18520952
365236521852
LH
16.4ft
16.4ft
2. System Design
(3) Increasing the size of the refrigerant tubing
Increasing the tubing size of the gas tubes can reduce the loss of capacity caused by longer tubing lengths.
Refer to Table 2-13 to increase the tubing size. However, the maximum allowable tubing length must not be exceeded.
* The amount of additional refrigerant charge is determined from the liquid tube size only.
Table 2-13 Correction coefficient for equivalent length when the size of the gas tube (LM) is increased
Standard tube diameter
(gas tube, in.(mm))
Tube diameter after change
(gas tube, in.(mm))
Equivalent length correction
coefficient
* When increasing the size of the suction and discharge tubing (LM), multiply by the correction coefficient from Table 2-13 and
calculate the equivalent length for section LM.
Tubing equivalent length after size increase
= Standard tubing equivalent length × Equivalent length correction coefficient
ø1/2"
(ø12.7)
ø5/8"
(ø15.88)
ø5/8"
(ø15.88)
ø3/4"
(ø19.05)
0.40.50.6
ø3/4"
(ø19.05)
ø7/8"
(ø22.22)
ø7/8"
(ø22.22)
ø1-1/8"
(ø28.58)
ø1-1/8"
(ø28.58)
ø1-3/8"
(ø34.93)
2-2. Example of Tubing Size Selection for Extension and Additional Charge Amount