Sanyo DHX4852 User Manual

OUTDOOR MODEL No. PRODUCT CODE No. APPLICABLE INDOOR MODEL No. V/ø/Hz
CHDX09053 85403301 AHX,UHX,KHX 0752
CHDX14053 85403302 AHX,KHX 0952 OUTDOOR
XHX,AHX,UHX,THX,KHX 1252 208-230/3ø/60
XHX,UHX,THX,KHX 1852
XHX,UHX,THX,KHX 2452 INDOOR
XHX,UHX,DHX 3652 208-230/1ø/60
DHX 4852
85464869238002
REFERENCE NO.
i
Check of Density Limit
NO TE
Outdoor unit
Refrigerant tubing
Indoor unit
e.g., charged amount (353 oz)
Outdoor unit
Indoor unit
Room A Room B Room C Room D Room E Room F
e.g., charged amount (529 oz)
Refrigerant tubing
Outdoor unit
Very small room
Indoor unit
Small room
Medium room
Large room
Mechanical ventilation device – Gas leak detector
0 0
57
114
170
227
284
341
398
454
0
500
1000
1500
2000
2500
3000
3500
4000
400200 600 800 1000 1200
Total amount of refrigerant
Min. indoor volume
Min. indoor floor area
(when the ceilin
g
is 8.8 ft. hi
g
h)
ft.
3
ft.
2
oz
Range above the density limit of
0.3 oz/ft.
3
(countermeasures needed)
Range below the density limit of
0.3 oz/ft.
3
(countermeasures not needed)
The room in which the air conditioner is to be installed requires a design that in the event of refrig­erant gas leaking out, its density will not exceed a set limit.
The refrigerant (R410A), which is used in the air con­ditioner, is safe, without the toxicity or combustibility of ammonia, and is not restricted by laws imposed to protect the ozone layer. However, since it contains more than air, it poses the risk of suffocation if its density should rise excessively. Suffocation from leakage of refrigerant is almost non-existent. With the recent increase in the num­ber of high density buildings, however, the installation of multi air conditioner systems is on the increase because of the need for effective use of floor space, individual control, energy conservation by curtailing heat and carrying power, etc. Most importantly, the multi air conditioner system is able to replenish a large amount of refrigerant compared to conventional individual air conditioners. If a single unit of the multi air conditioner system is to be installed in a small room, select a suitable model and installation pro­cedure so that if the refrigerant accidentally leaks out, its density does not reach the limit (and in the event of an emergency, measures can be made before injury can occur). In a room where the density may exceed the limit, create an opening with adjacent rooms, or install mechanical ventilation combined with a gas leak detection device. The density is as given below.
2. The standards for minimum room volume are as fol­lows.
(1) No partition (shaded portion)
(2) When there is an effective opening with the adjacent
room for ventilation of leaking refrigerant gas (open­ing without a door, or an opening 0.15% or larger than the respective floor spaces at the top or bottom of the door).
(3) If an indoor unit is installed in each partitioned room
and the refrigerant tubing is interconnected, the smallest room of course becomes the object. But when mechanical ventilation is installed interlocked with a gas leakage detector in the smallest room where the density limit is exceeded, the volume of the next smallest room becomes the object.
Total amount of refrigerant (lbs)
Min. volume of the indoor unit installed room (ft.3)
<
Density limit (oz/ft.3)
The density limit of refrigerant which is used in multi air conditioners is 0.3 oz/ft.3 (ISO 5149).
1.If there are 2 or more refrigerating systems in a single refrigerating device, the amount of refrigerant should be as charged in each independent device.
For the amount of charge in this example:
The possible amount of leaked refrigerant gas in rooms A, B and C is 353 oz. The possible amount of leaked refrigerant gas in rooms D, E and F is 529 oz.
3. The minimum indoor floor space compared with the amount of refrigerant is roughly as follows: (When the ceiling is 8.8 ft. high)
ii

Contents

Section 1: OUTLINE OF W-2WAY ECO-i SYSTEM ................................................................1-1
1. Line-up .............................................................................................................1-2
2. Features of W-2WAY ECO-i SYSTEM .............................................................1-4
Section 2: DESIGN OF W-2WAY ECO-i SYSTEM ..................................................................2-1
1. Model Selecting and Capacity Calculator ........................................................2-2
2. System Design ...............................................................................................2-17
3. Electrical Wiring .............................................................................................2-23
4. Installation Instructions ..................................................................................2-27
Section 3: Control of W-2WAY ECO-i SYSTEM .....................................................................3-1
1. Main Operating Functions ................................................................................3-3
2. Wireless Remote Controller .............................................................................3-5
3. Timer Remote Controller................................................................................3-22
4. System Controller ..........................................................................................3-38
5. Simplified Remote Controller .........................................................................3-56
6. Remote Sensor ..............................................................................................3-64
Section 4: W-2WAY ECO-i SYSTEM UNIT SPECIFICATIONS ..............................................4-1
1. Outdoor Unit ....................................................................................................4-2
2. 4-Way Air Discharge Semi-concealed Type (X Type) .....................................4-12
3. 1-Way Air Discharge Semi-concealed Type (A Type) .....................................4-24
4. Concealed Duct Type (U Type) .......................................................................4-33
5. Concealed Duct High-Static Pressure Type (D Type) .....................................4-50
6. Ceiling-Mounted Type (T Type) ......................................................................4-57
7. Wall-Mounted Type (K Type) ..........................................................................4-66
Section 5: TEST RUN ..............................................................................................................5-1
1. Preparing for Test Run .....................................................................................5-2
2. Test Run Procedure .........................................................................................5-3
3. Main Outdoor Unit PCB Setting .......................................................................5-4
4. Auto Address Setting .......................................................................................5-6
5. Remote Controller Test Run Settings .............................................................5-12
6. Caution for Pump Down .................................................................................5-13
7. Meaning of Alarm Messages .........................................................................5-14
Section 6: ELECTRICAL DATA ...............................................................................................6-1
1. Outdoor Unit ....................................................................................................6-2
2. Indoor Unit .......................................................................................................6-6
Section 7: PCB AND FUNCTIONS .........................................................................................7-1
1. Outdoor Unit Control PCB ...............................................................................7-2
2. Indoor Unit Control PCB Switches and Functions ...........................................7-6
iii
Outline of W-2Way ECO-i SYSTEM
1
2
3
4
5
6
7
8
Contents

1. OUTLINE OF W-2Way ECO-i MULTI SYSTEM

1. Line-up .................................................................................................................................1-2
2. Features of W-2WAY ECO-i SYSTEM .................................................................................1-4
1-1
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8

1. Line-up

Capacity: BTU/h (kW)
Cooling
/
Heating
Type
97 12 18 24 36 48
XHX1252 XHX1852 XHX2452 XHX3652
KHX0952 KHX1252 KHX2452KHX1852
AHX0952 AHX1252
THX1852THX1252 THX2452
UHX0752 UHX1252 UHX1852 UHX2452
DHX4852
Wall-Mounted Type (K Type)
Concealed Duct Type (U Type)
7,500 (2.2)
8,500 (2.5)
/
9,600 (2.8)
11,000 (3.2)
/
12,000 (3.6)
14,000 (4.2)
/
36,000 (10.6)
39,000(11.4)
/
47,800 (14.0)
54,600(16.0)
/
25,000 (7.3)
27,000(8.0)
/
19,000 (5.6)
21,000(6.3)
/
KHX0752
AHX0752
4-Way Air Discharge Semi­Concealed Type (X Type)
Ceiling-Mounted Type
(T Type)
1-Way Air Discharge Semi­Concealed Type
(A Type)
Concealed Duct High-Static Pressure Type(D Type)
DHX3652
UHX3652
Indoor units
Outline of W-2Way ECO-i SYSTEM
1-2
1
2
3
4
5
6
7
8
1-3
Outline of W-2Way ECO-i SYSTEM
1
2
3
4
5
6
7
8
1. Line-up
Type
Type
90
Capacity: BTU/h (kW)
95,500 (28.0)
Cooling / Heating / 107,500 (31.5)
Outdoor Unit
Capacity: BTU/h (kW) Cooling / Heating
Outdoor Unit
CHDX14053
CHDX09053
153,600 (45.0)
140
/ 170,600 (50.0)
Air direction
Air direction
2-11/64
8-47/64
13-5/16
18-5/8
4-39/64
2-59/64
6-15/16
31-19/64
65-25/32
(8-1/2)
74-19/64
2-11/64
8-47/64
13-5/16
18-5/8
4-39/64
2-59/64
6-15/16
31-19/64
65-25/32
(8-1/2)
74-19/64
Outdoor units
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
ADDITION
CONCENTRATION
If indoor/outdoor units need servicing, a ball valve (field supply) cuts off non-operational units to let other units stay running.
* The capacity after the setting
must not exceed 32 PS.
Since all tubings are concentrated into one pipe shaft, you can minimize piping space and construc­tion labor
Maximum number of combined outdoor units
Maximum horsepower of combined outdoor units
Maximum number of connectable indoor units
Indoor/outdoor unit capacity ratio
Maximum actual tubing length
Maximum level difference (when outdoor unit is lower)
Maximum total tubing length
2
32 HP
40
50~130%
492 ft
164 (131) ft
984 ft
System limitations
CONNECTION
If your indoor capacity load changes in the future, it’s easy to add on both indoor and outdoor units using the same tubing.
*If addi tional i nst allat ion of outd oor and ind oor u nit s is
exp ect ed, the sizeof refr igera nt tube sho uld be d ecided accordin g to the to tal c apa city aft er the a ddi tion.
Combination of outdoor units
The DC inverter unit can be used independently or in combination.
CAUTION
R407C models and R22 models must not be used in combination with each other.
1
1
2
10 16
10
16
20 26 32
Total horse
power
Inverter unit
Combination of outdoor units
1
2
1

2. Features of W-2WAY ECO-i SYSTEM

2-1. Outline of W-2WAY ECO-i SYSTEM
System example
Outline of W-2Way ECO-i SYSTEM
1-4
2. Features of W-2WAY ECO-i SYSTEM
Dimensions
10HP CHDX09053 16HP CHDX14053
Air direction
(Ceiling panel dimensions)
10,16 HP
Air direction
Air direction
31-7/64
(Installation hole pitch)
35-3/64
Top view
Outline of W-2Way ECO-i SYSTEM
Air direction
(Maximum dimensions)
(Installation hole pitch)
(Ceiling panel dimensions)
36-7/32
37-13/32
35-3/64
Unit: in.
Dimensions of unit combinations
20,26,32 HP
74-1/64 (Ceiling panel dimensions)
35-3/64 (Ceiling panel dimensions) 35-3/64 (Ceiling panel dimensions)
35-3/64 (Ceiling panel dimensions)
31-7/64 (Installation hole pitch)
70-5/64 (Installation hole pitch)
31-7/64 (Installation hole pitch)
Top view
36-7/32 (Installation hole pitch)
37-13/32 (Maximum dimensions)
Unit: in.
1
2
3
4
5
1-5
6
7
8
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
In case of 32 HP system
Capacity
32
28
24
20
16
12
8
4
DC1
DC2
AC11
AC21
AC12
AC22
DC1
DC1
DC2
AC11
DC1
DC2
AC11
AC21
DC1
DC2
AC11
AC21
AC12
DC2
DC1
DC2
LOAD --->
Example of 2 unit connection
DC1
AC11
AC12
Unit 1
DC2
AC21
AC22
Unit 2
DC3
AC31
AC32
Unit 3
Outline of W-2Way ECO-i SYSTEM
2. Features of W-2WAY ECO-i SYSTEM
Capacity control
The compressor combination (DC inverter compressor + constant-speed compressor) allows smooth capacity control from 0.8 HP to 32 HP.
Realization of smooth capacity control from 0.8HP to 32HP
Capacity control is possible smoothly with a DC inverter compressor.The right graph shows the image of the operating combination of compres­sors in case of 32HP system.In actual operation, the combination will be changed by operationg condition, operating time amount, priority of com­pressor and so on.
Comp. HP Unit1(main) Unit2(sub1)
DC comp. 4.0 4.0
AC1 comp. 6.0 6.0
AC2 comp. 6.0 6.0
*32HP = CHDX14053 Type x2
1-6
Design of W-2WAY ECO-i SYSTEM Unit Specifications
1
2
3
4
5
6
7
8
Contents

2. DESIGN OF W-2WAY ECO-i SYSTEM

1. Model Selecting and Capacity Calculator ........................................................................2-2
2. System Design ..................................................................................................................2-17
3. Electrical Wiring ................................................................................................................2-23
4. Installation Instructions ...................................................................................................2-27
2-1
Design of W-2WAY ECO-i SYSTEM Unit Specifications
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
50
14
23
32
41
50
59
68
77
86
95
104
113
Indoor air intake temp.
°
F (WB)
Outdoor air intake temp.
°
F (DB)
59
57
109
68 77 86
Operating range
50
5
-4
14
23
32
41
50
59
68
77
Indoor air intake temp.
°
F (DB)
Outdoor air intake temp. °F (WB)
59 68 77 86 95
Operating range
Cooling
Heating

1. Model Selecting and Capacity Calculator

1-1. Operating Range
2-2
1
2
3
4
5
6
7
8
2-3
Design of W-2WAY ECO-i SYSTEM Unit Specifications
1
2
3
4
5
6
7
8
Select the model and calculate the capacity for each refrigerant system according to the procedure shown below.
Calculation of the indoor air-conditioning load
Calculate the maximum air-conditioning load for each room or zone.
Selection of an air conditioning system
Select the ideal air conditioning system for air conditioning of each room or zone.
Design of the control system
Design a suitable control system for the selected air conditioning system.
Preliminary selection of indoor and outdoor units
Make preliminary selections that are within the allowable range for the system.
........
2-4 ~ 2-10
Check of the tubing length and elevation difference
Check that the length of refrigerant tubing and the elevation difference are within the allowable
ranges.......................................................................................................................................
2-4
Calculation of the corrected outdoor unit capacity
Capacity correction coefficient for model.................................................................... 2-11, 13, 14
Capacity correction coefficient for outdoor temperature conditions ..................................2-11, 13
Capacity correction coefficient for tubing length and elevation difference ........................ 2-11, 14
Heating capacity correction coefficient for frosting/defrosting .......................................... 2-11, 13
Calculation of the corrected capacity for each indoor unit
Capacity correction coefficient for indoor temperature conditions .................................... 2-11, 14
Capacity distribution ratio based on the tubing length and elevation difference .............. 2-11, 14
Calculation of the actual capacity for each indoor unit
Calculate the corrected indoor/outdoor capacity ratio, based on the corrected outdoor unit capacity and the total corrected capacity of all indoor units in the same system. Use the result to
calculate the capacity correction coefficient for the indoor units.................................
2-11 ~ 2-14
Multiply the corrected capacity of each indoor unit by the capacity correction coefficient to calcu-
late the actual capacity for each indoor unit. .......................................................................... 2-12
Recheck of the actual capacity for each indoor unit
If the capacity is inadequate, reexamine the unit combinations.
Example 1: Increasing the outdoor unit capacity.................................................................... 2-18
Example 2: Increasing the indoor unit capacity ...................................................................... 2-19
Increasing the tubing size ...................................................................................................... 2-20
Design of tubing
Create a tubing design which minimizes the amount of additional refrigerant charge as much as
possible. .......................................................................................................................... 2-4 ~ 2-6
If tubing extension for additional unit is expected in the future, create the tubing design with adequate consideration for this extension.
Select the tubing size for the main tube (LA) up to the No. 1 distribution joint based on the rated cooling capacity of the outdoor unit. Select tubing sizes after the distribution point based on the total rated cooling capacity of the connected indoor units.
Increasing the tubing size of the wide tubes can reduce the loss of capacity caused by longer tubing lengths. (Only the main wide tube with the largest tube diameter (main tube LA and main tubes after the distribution point that are the same size as LA) can be changed.) In this case, it is
necessary to recalculate the actual indoor unit capacities. ....................................................
2-20
Calculation of additional refrigerant charge amount
Calculate the additional refrigerant charge from the diameters and lengths of the refrigerant tub­ing. Even if the wide tubing diameter was increased, determine the additional refrigerant charge
based only on the narrow tubing size.....................................................................................
2-21
Check the minimum indoor capacity (limit density) with respect to the amount of refrigerant. If the limit density is exceeded, be sure to install ventilation equipment or take other corrective steps. 2-22
Design of electrical wiring capacity
Select a wiring capacity according to the method of power supply. ...................................... 2-24
1. Model Selecting and Capacity Calculator
1-2. Procedure for Selecting Models and Calculating Capacity
Model Selection Procedure
Design of W-2WAY ECO-i SYSTEM Unit Specifications
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
R410A distribution joint APR-CHP680BA (for outdoor unit) APR-CHP680BA (for outdoor unit) APR-CHP680BA (for outdoor unit) APR-CHP680BA (for outdoor unit) APR-P1350BA (for indoor unit)
Explanation of symbols
Distribution joint (APR: purchased separately)
Solidly welded shut (pinch weld)
Balance tubing ( 1/4")
Main distribution tubes LC – LG are selected according to the capacity after the distribution joint.
Sizes of indoor unit connection tubing 1 – 40 are determined by the connection tubing sizes on the indoor units.
Main tubing length LM = LA + LB … 262 ft
1.
2.
3. The outdoor connection main tubing ( B portion) is determined by the total capacity of the outdoor units that are connected to the tube ends.
4.
Ball valve (field supply)
T-joint (field supply)
Note: Do not use commercially available T-joints for the liquid tubing and parts. * Be sure to use special R410A distribution joints (APR: purchased separately) for outdoor unit connections and tubing branches.
Table 2-1 Ranges that Apply to Refrigerant Tubing Lengths and to Differences in Installation Heights
Select the installation location so that the length and size of refrigerant tubing are within the allowable range shown in the figure below.
Item Mark Contents Length (ft.)
L1 Max. tubing length
Actual length 492
Equivalent length 574
L (L2 – L4)
Difference between max. length and min. length from the No.1 distribution joint
131
LM Max. length of main tubing (at max. diameter) 262
1, 2... 40
Max. length of each distribution tube 98
L1+ 1+ 2... 39+ A+LE+LF+LG
Total max. tubing length including length of each distribution tube (only liquid tubing)
984
L5
L3
Distance between outdoor units
32
H1
When outdoor unit is installed higher than indoor unit 164 When outdoor unit is installed lower than indoor unit 131
H2
Max. difference between indoor units 49
H3 Max. difference between outdoor units
13
L = Length, H=Height
Allowable tubing length
Allowable elevation difference
*3
6.6
Allowable length of joint tubing
T-joint tubing (field-supply); Max. tubing length between the first T-joint and solidly welded-shut end point
1: The outdoor connection main tubing ( B portion) is determined by the total capacity of the outdoor units that are connected to the tube ends.
2: If the longest tubing length (L1) exceeds 295 ft. (equivalent length), increase the sizes of the main tubes (LM) by 1 rank for gas tubes and liquid tubes. (Use a field supply reducer.) (Select the tube size from the table of main tube sizes (Table 2-5) on the following page (LA table), and from the table of refrigerant tubing sizes (Table 2-10) on the second following page.)
3: If the longest main tube length (LM) exceeds 164 ft., increase the main tube size at the portion before 164 ft. by 1 rank for the gas tubes. (Use a field supply reducer.) (For the portion that exceeds 164 ft., set based on the main tube sizes (LA) listed in the table on the following page.)
4: If the size of the existing tubing is already larger than the standard tubing size, it is not necessary to further increase the size.
* If the existing tubing is used, and the amount of on-site additional refrigerant charge exceeds the value listed below, then
change the size of the tubing to reduce the amount of refrigerant.
Max. additional charge for 1 outdoor unit: 62 lbs Max. additional charge for 2 outdoor units: 111lbs
NOTE
L5
LA
LE
LM
LB LC
L2
L4
LF
LD L3
LG
H2
H3
H1
L1
2
3
1
5
4
A
B
38
39
40
For extension
For extension
Max. 1.3ft
Max. 1.3ft
1. Model Selecting and Capacity Calculator
1-3. Tubing Length
2-4
1
2
3
4
5
6
7
8
2-5
Design of W-2WAY ECO-i SYSTEM Unit Specifications
1
2
3
4
5
6
7
8
1. Model Selecting and Capacity Calculator
Table 2-2 Refrigerant Charge Amount at Shipment (for outdoor unit)
DC
(oz)
Additional refrigerant charge amount is calculated from the liquid tubing total length as follows.
Table 2-3 Amount of Refrigerant Charge Per Meter, According to Liquid Tubing Size
Liquid tubing size Amount of refrigerant
(in. (mm)) charge (oz/ft.)
ø1/4" (ø6.35) 0.279
ø3/8" (ø9.52) 0.602
ø1/2" (ø12.7) 1.38
ø5/8" (ø15.88) 1.99
ø3/4" (ø19.05) 2.78
ø7/8" (ø22.22) 3.93
CHDX09053 CHDX14053
423 458
Required amount of charge = (Amount of refrigerant charge per
meter of each size of liquid tube × its tube length) + (...) + (...)
* Always charge accurately using a scale for weighing.
* If the existing tubing is used, and the amount of on-site additional
refrigerant charge exceeds the value listed below, then change the
size of the tubing to reduce the amount of refrigerant.
Max. additional charge for 1 outdoor unit : 62 lbs
Max. additional charge for 2 outdoor units : 111 lbs
Table 2-4 System Limitations
Max. No. allowable connected outdoor units 2
Max. capacity allowable connected outdoor units 307,100 BTU/h (32 hp, 90 kW)
Max. connectable indoor units 40
Max. allowable indoor/outdoor capacity ratio 50 – 130 %
*1: Up to 2 units can be connected if the system has been extended.
*1
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
32
249,100
(73.0)
26
ø7/8"
(ø22.22)
10
95,500
(28.0)
ø1/2"
(ø12.7)
153,600
(45.0)
16
ø1-1/8"
(ø28.58)
ø5/8"
(ø15.88)
10 10
16 10
16 16
191,100
(56.0)
20
ø3/4"
(ø19.05)
ø1-3/8"
(ø34.92)
ø3/8"
(ø9.52)
307,100
(90.0)
16 10
BTU/h
(kW)
Total system horsepower
Combined outdoor units
Gas tubing
Liquid tubing
ø3/4"
(ø19.05)
ø1-3/8"
(ø34.93)
ø5/8"
(ø15.88)
ø1-1/8"
(ø28.58)
ø1/2"
(ø12.7)
ø1-1/8"
(ø28.58)
ø3/8"
(ø9.52)
ø3/4"
(ø19.05)
ø3/8"
(ø9.52)
ø5/8"
(ø15.88)
ø3/8"
(ø9.52)
ø1/2"
(ø12.7)
Gas tubing
Liquid tubing
238,900
(25 hp)
178,800
(19 hp)
ø1/2"
(ø12.7)
ø1-1/8"
(ø28.58)
178,800
(19 hp)
143,300
(15 hp)
24,200
(2.5 hp)
24,200
(2.5 hp)
54,600
(6 hp)
54,600
(6 hp)
238,900
(25 hp)
76,800
(8.1 hp)
ø3/8"
(ø9.52)
ø7/8"
(ø22.22)
76,800
(8.1 hp)
102,400
(11 hp)
102,400
(11 hp)
Below BTU/h
Over BTU/h
143,300
(15 hp)
hp = horsepower
Tubing size
Total capacity after distribution
Design of W-2WAY ECO-i SYSTEM Unit Specifications
1. Model Selecting and Capacity Calculator
1-4 Tubing Size
Table 2-5 Main Tubing Size (LA)
*1: If future extension is planned, select the tubing diameter based on the total horsepower after extension.
However extension is not possible if the resulting tubing size is two ranks higher. *2: The balance tube (outdoor unit tube) diameter is ø1/4". *3: Type 1 tubing should be used for the refrigerant tubes. *4: If the length of the longest tube (L1) exceeds 295 ft. (equivalent length), increase the main tube (LM) size by 1 rank for the gas
and liquid tubes. (Use field-supply reducers.) (Select from Table 2-5 and Table 2-10.) *5: If the longest main tube length (LM) exceeds 164 ft., increase the main tube size at the portion before 164 ft. by 1 rank for the
gas tubes.
(For the portion that exceeds 164 ft., set based on the main tube sizes (LA) listed in the table above.)
Unit: in. (mm)
Size of tubing (lB) between outdoor units
Select the size of tubing between outdoor units based on the main tubing size (LA) as given in the table above.
Table 2-6 Main Tubing Size After Distribution (LB, LC...)
Note: In case the total capacity of connected indoor units exceeds the total capacity of the outdoor units, select the main tubing
size for the total capacity of the outdoor units. (Especially the main tubing segments of LA, LB and LF.)
Unit: in. (mm)
2-6
1
2
3
4
5
6
7
8
2-7
Design of W-2WAY ECO-i SYSTEM Unit Specifications
1
2
3
4
5
6
7
8
ø7/8"
(ø22.22)
ø3/8" (ø9.52)
ø1/4" (ø6.35)
95,500
(28.0)
153,600
(45.0)
ø1-1/8"
(ø28.58)
Flare connection
Brazing connection
ø1/2" (ø12.7)
Flare connection
( A B)
Balance tubing
Liquid tubing
Gas tubing
BTU/h
(kW)
Balance tube
Liquid tube
Gas tube
ø5/8" (ø15.88)
ø3/8" (ø9.52) ø1/4" (ø6.35)
ø1/2" (ø12.7)
Gas tubing
Liquid tubing
Indoor unit type 7 9 12 18
24
36 48
1. Model Selecting and Capacity Calculator
Table 2-7 Amount of Refrigerant Charge
Liquid tubing size Amount of refrigerant
(in. (mm)) charge (oz/ft.)
ø1/4" (ø6.35) 0.279
ø3/8" (ø9.52) 0.602
ø1/2" (ø12.7) 1.38
ø5/8" (ø15.88) 1.99
ø3/4" (ø19.05) 2.78
ø7/8" (ø22.22) 3.93
Table 2-8 Outdoor Unit Tubing Connection Size
Unit: in. (mm)
Table 2-9 Indoor Unit Tubing Connection Size
Note: Use C1220T-1/2H material for tubing over ø3/4" (ø22.22).
Table 2-10 Refrigerant tubing (Existing tubing can be used.)
Material O Material 1/2H • H
ø1/4" (ø6.35) t1/32" (0.8) ø7/8" (ø22.22) t5/128" (1.0)
ø3/8" (ø9.52) t1/32" (0.8) ø1" (ø25.40) t5/128" (1.0)
ø1/2" (ø12.7) t1/32" (0.8) ø1-1/8" (ø28.58) t5/128" (1.0)
ø5/8" (ø15.88) t5/128" (1.0) ø1-1/4" (ø31.75) t3/64" (1.1)
ø3/4" (ø19.05) over t5/128" (1.0) ø1-3/8" (ø34.93) over t3/64" (1.15)
Tubing size (in. (mm))
Unit: in. (mm)
* When bending the tubes, use a bending
radius that is at least 4 times the outer
diameter of the tubes.
In addition, take sufficient care to avoid
crushing or damaging the tubes when
bending them.
Design of W-2WAY ECO-i SYSTEM Unit Specifications
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
Wide tubing size (mm) 12.7 15.88 19.05 22.22 25.4 28.58 31.8 38.1
90o elbow 0.3 0.35 0.42
0.48
0.52 0.57 0.7
0.79
45o elbow 0.23 0.26 0.32
0.36
0.39 0.43 0.53 0.59
U-shape tube bent (R60 100 mm) 0.9 1.05 1.26 1.44 1.56 1.71 2.1
2.37
Trap bend
2.3
2.8 3.2 3.8 4.3 4.7 5.0
5.8
Y-branch distribution joint Equivalent length conversion not needed.
Ball valve for service Equivalent length conversion not needed.
Cooling Heating
95
94
93
92
91
90
96
97
98
99
100
Capacity ratio based on Gas
tube diameter (%)
Recommended Gas tubes diameter (in)
ø3/4” ø7/8”
ø7/8” ø1-1/8”
ø1-1/8”
ø1-3/8”
ø1-3/8”
ø1”
10 12 14 16 18 20 26 30 35 40 45 46 47 48
Gas tubing size (in. (mm))
1/2"
(12.7)
5/8"
(15.88)
3/4"
(19.05)
7/8"
(22.22)
1"
(25.4)
1-1/8"
(28.58)
1-3/8"
(34.93)
90° elbow
1 1.1 1.4 1.6 1.7 1.9 2.5
45° elbow 0.8 0.9 1
1.2
1.3 1.4 1.8
U-shape tube bent (R2-3/8" – 4" (60 – 100)) 3 3.4 4.1 4.7 5.1 5.6 7.4
Trap bend
7.5 9.2 10.5 12.5 14.1 15.4 19.2
Y-branch distribution joint Equivalent length conversion not needed.
Ball valve for service Equivalent length conversion not needed.
1. Model Selecting and Capacity Calculator
Straight equivalent length of joints
Design the tubing system by referring to the following table for the straight equivalent length of joints.
Table 2-11 Straight Equivalent Length of Joints
Capacity loss caused by differences in tubing diameters
* Capacity loss will occur if a tubing system that matches the horsepower is not selected (for example, if a tubing system was
determined and installed with no plan for extension and extension occurs later). The loss rate can be found from the graph below.
Unit: ft.
(Reading the graph) <Example 1> Currently a 16 HP system and ø1-1/8" Gas tubings are used. Subsequently the system is expanded, with 16 HP added to the
same tubing system.
Horsepower after extension: 16 + 16 = 32 HP From the graph above: Cooling: Capacity ratio is 90.8%. Actual capacity = 32 × 0.908 = 29.1 HP
Heating: Capacity ratio is 96.0%. Actual capacity = 32 × 0.960 = 30.7 HP
2-8
1
2
3
4
5
6
7
8
2-9
Design of W-2WAY ECO-i SYSTEM Unit Specifications
1
2
3
4
5
6
7
8
WARNING
CAUTION
WARNING
0 0
57
114
170
227
284
341
398
454
511
568
625
682
738
795
852
909
966
1022
1079
1136
0
500
1000
1500
2000
2500
3000
3500
4000
4500
5000
5500
6000
6500
7000
7500
8000
8500
9000
9500
10000
1000500 1500 2000 2500 3000
Total amount of refrigerant
Min. indoor volume
Min. indoor floor area
(when the ceilin
g
is 8.8 ft. hi
g
h)
ft.
3
ft.
2
oz
Range above the density limit of
0.3 oz/ft.
3
(countermeasures needed)
Range below
the density limit of
0.3 oz/ft.
3
(countermeasures
not needed)
1. Model Selecting and Capacity Calculator
Additional refrigerant charge amount
Additional refrigerant charge amount is calculated from the liquid tubing total length as follows.
Table 2-12 Amount of Refrigerant Charge Per Meter, According to Liquid Tubing Size
Liquid tubing size Amount of refrigerant
(in. (mm)) charge (oz/ft.)
ø1/4" (ø6.35) 0.279
ø3/8" (ø9.52) 0.602
ø1/2" (ø12.7) 1.38
ø5/8" (ø15.88) 1.99
ø3/4" (ø19.05) 2.78
ø7/8" (ø22.22) 3.93
Check of limit density
Required amount of charge = (Amount of refrigerant charge per
meter of each size of liquid tube × its tube length) + (...) + (...)
* Always charge accurately using a scale for weighing.
1-5. Check of Limit Density
When installing an air conditioner in a room, it is necessary to ensure that even if the refrigerant gas accidentally leaks out, its density does not exceed the limit level for that room. If the density could exceed the limit level, it is necessary to provide an opening between the unit and the adjacent room, or to install mechanical ventilation which is interlocked with a leak detector.
(Total refrigerant charged amount: oz)
(Min. indoor volume where the indoor unit is installed: ft.3)
<
The limit density of refrigerant R410A which is used in this unit is
0.3 oz/ft.3 (ISO 5149).
The shipped outdoor unit comes charged with the amount of refrig­erant fixed for each type, so add it to the amount that is charged in the field. (For the refrigerant charge amount at shipment, refer to the unit’s nameplate.)
Always check the gas density limit for the room in which the unit is installed.
Limit density 0.3 (oz/ft.3)
Pay special attention to any location, such as a basement, etc., where leaking refrigerant can accumulate, since refrigerant gas is heavier than air.
Minimum indoor volume & floor area as against the amount of refrigerant is roughly as given in the following table.
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
Capacity distribution ratio for each indoor unit (3) = Correction coefficient for that indoor unit / Correction coefficient for the outdoor uni
t
However, the corrected cooling capacity of each indoor unit is found as shown below. If (2) < 100% and (2)
×
(3) > 100%: Corrected cooling capacity for that indoor unit [5] = Rated cooling capacity for that indoor unit
If (2) 100%: Corrected cooling capacity for that indoor unit (5) = Rated cooling capacity for that indoor unit
×
(2)
Capacity distribution ratio for each indoor unit (3) = Correction coefficient for that indoor unit / Correction coefficient for the outdoor uni
t
Design of W-2WAY ECO-i SYSTEM Unit Specifications
1. Model Selecting and Capacity Calculator
1-6. Calculation of Actual Capacity of Indoor Unit
Calculating the actual capacity of each indoor unit
Because the capacity of a multi air-conditioner changes according to the temperature conditions, tubing length, elevation dif­ference and other factors, select the correct model after taking into account the various correction values. When selecting The model, calculate the corrected capacities of the outdoor unit and each indoor unit. Use the corrected outdoor unit capacity and the total corrected capacity of all the indoor units to calculate the actual final capacity of each indoor unit.
1. Outdoor unit capacity correction coefficient
Find the outdoor unit capacity correction coefficient for the following items.
(1) Capacity correction for the outdoor unit model
The capacity correction coefficient is 1.00.
(2) Capacity correction for the outdoor unit temperature conditions
From the graph of capacity characteristics on page 2-12, use the outdoor temperature to find the capacity correction coef­ficient.
(3) Capacity correction for the outdoor unit tubing length and elevation difference
From the graph of capacity change characteristics on page 2-13, use the tubing length and elevation difference to find the capacity correction coefficient. The outdoor unit correction coefficient is the value which corresponds to the most demanding indoor unit.
(4) Capacity correction for outdoor unit frosting/defrosting during heating
From the table on page 2-12, find the capacity correction coefficient.
2. Indoor unit capacity correction coefficients
Find the indoor unit capacity correction coefficient for the following items.
(2) Capacity correction for the indoor unit temperature conditions
From the graph of capacity characteristics on page 2-13, use the indoor temperature to find the capacity correction coeffi­cient.
(3) Capacity distribution ratio based on the indoor unit tubing length and elevation difference
First, in the same way as for the outdoor unit, use the tubing length and elevation difference for each indoor unit to find the correction coefficient from the graph of capacity change characteristics on page 2-13. Then divide the result by the outdoor unit correction coefficient to find the capacity distribution ratio for each indoor unit.
3. Calculating the corrected capacities for the outdoor unit and each indoor unit
The corrected capacities for the outdoor unit and each indoor unit are calculated form the formula below.
<Cooling>
Outdoor unit corrected cooling capacity (5) = Outdoor unit rated cooling capacity × Correction coefficient for model ((1)
Page 2-12) × Correction coefficient for outdoor temperature conditions ((2) Page 2-12) × Correction coefficient for tubing length and elevation difference ((3) Page 2-13)
* However, if the outdoor unit corrected cooling capacity [5] is greater than 100%, then the outdoor unit corrected cooling
capacity [5] is considered to be 100%.
Corrected cooling capacity of each indoor unit (5) = Rated cooling capacity for that indoor unit × Correction coefficient for
indoor temperature conditions at that indoor unit ((2) Page 2-13) × Distribution ratio based on tubing length and elevation dif­ference at that indoor unit ((3) Page 2-13)
2-10
1
2
3
4
5
6
7
8
2-11
Design of W-2WAY ECO-i SYSTEM Unit Specifications
1
2
3
4
5
6
7
8
However, the corrected heating capacity of each indoor unit is found as shown below. If (2) < 100% and (2) ×(3) > 100%: Corrected heating capacity for that indoor unit (5) = Rated heating capacity for that indoor unit If (2) 100%: Corrected heating capacity for that indoor unit (5) = Rated heating capacity for that indoor unit ×(2)
1. Model Selecting and Capacity Calculator
<Heating>
Outdoor unit corrected heating capacity (5) = Outdoor unit rated heating capacity × Correction coefficient for model ((1)
Page 2-12) × Correction coefficient for outdoor temperature conditions ((2) Page 2-12) × Correction coefficient for tubing length and elevation difference ((3) Page 2-13) × Correction coefficient for frosting/defrosting ((4) Page
* However, if the outdoor unit corrected heating capacity [5] is greater than 100%, then the outdoor unit corrected heating
capacity is considered to be 100%.
Corrected heating capacity of each indoor unit (5) = Rated heating capacity for that indoor unit × Correction coefficient for
indoor temperature conditions at that indoor unit ((2) Page 2-13) × Distribution ratio based on tubing length and elevation
difference at that indoor unit.
* Characteristic graphs are shown on the pages listed above next to each correction item. Find each correction coefficient
from the appropriate conditions.
2-12)
4. Calculating the actual indoor unit capacity based on the indoor/outdoor corrected capacity ratio
Calculate the actual capacity of each indoor unit from the values (found in (3)) for the corrected outdoor unit capacity and the corrected capacity of each indoor unit.
<Cooling capacity>
Corrected indoor/outdoor capacity ratio during cooling (Ruc) = Total corrected cooling capacity of all indoor units in that system / Corrected outdoor unit cooling capacity
If the corrected outdoor unit cooling capacity is greater than or equal to the total corrected unit cooling capacity of all indoor units in that system (Ruc 1), then:
Actual cooling capacity of each indoor unit (7) = Corrected cooling capacity of each indoor unit (5) (In other words, the cor­rection coefficient (6), based on the corrected indoor/outdoor capacity ratios for each indoor unit, is 1.)
If the corrected outdoor unit cooling capacity is less than the total corrected unit cooling capacity of all indoor units in that sys­tem (Ruc > 1), then:
(Actual cooling capacity of each indoor unit (7)) = (Corrected cooling capacity of each indoor unit (5)) × (0.25 × Ruc + 0.75) / Ruc (In other words, the correction coefficient (6), based on the corrected indoor/outdoor capacity ratios for each indoor unit, is the underlined part in the formula above.)
<Heating capacity>
Corrected indoor/outdoor capacity ratio during heating (Ruh) = Total corrected heating capacity of all indoor units in that system / Corrected outdoor unit heating capacity
If the corrected outdoor unit heating capacity is greater than or equal to the total corrected unit heating capacity of all indoor units in that system (Ruh 1), then:
Actual heating capacity of each indoor unit (7) = Corrected heating capacity of each indoor unit (5)
(In other words, the correction coefficient (6), based on the corrected indoor/outdoor capacity ratios for each indoor unit, is 1.)
If the corrected outdoor unit heating capacity is less than the total corrected unit heating capacity of all indoor units in that sys­tem (Ruh > 1), then:
(Actual heating capacity of each indoor unit (7)) = (Corrected heating capacity of each indoor unit (5)) × (0.1 × Ruh + 0.9) / Ruh (In other words, the correction coefficient (6), based on the corrected indoor/outdoor capacity ratios for each indoor unit, is the underlined part in the formula above.)
Design of W-2WAY ECO-i SYSTEM Unit Specifications
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
Indoor unit capacity correction coefficient for Ruc (cooling) Indoor unit capacity correction coefficient for Ruh (heating)
1.0
0.9
0.8
0.7
0.6
0.5
0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9
2.0
Indoor unit capacity correction coefficient
Corrected indoor/outdoor capacity ratio (Ruc or Ruh)
Outdoor unit cooling capacity characteristics
Outdoor unit heating capacity characteristics
Rate of cooling capacity change (%)
Rate of heating capacity change (%)
* Broken line indicates a 16 HP
DC inverter unit
Outdoor air intake temp. (°F DB)
WB = 66°F
Indoor air intake temp. (°F DB)
59
68
77
130 120
110
100
90 80 70 60 50 40
130
120
110
100
90
80
-4 5 14 23 32 41 50 5923 32 41 50 14 59 68 77 86 95 104 113
Outdoor air intake temp. (°F WB)
Indoor air intake temp. (WB) = 60°F
WB = 71°F
1. Model Selecting and Capacity Calculator
Refer to the graph below for the correction coefficients for Ruc and Ruh.
Note: When Ruc or Ruh is less than or equal to 1.0, the indoor unit capacity correction coefficient for both Ruc and Ruh is 1.0.
5. Graph of capacity correction coefficients
Graph of outdoor unit capacity characteristics (1 – (2))
Outdoor unit heating capacity correction coefficient during frosting/defrosting (1 – (4))
Outdoor intake air
(°FWB RH85%)
temp.
Correction coefficient 0.97 0.97 0.97 0.96 0.94 0.91 0.89 0.87 0.87 0.87 0.88 0.89 0.91 0.92 0.95 1.0
* To calculate the heating capacity with consideration for frosting/defrosting operation, multiply the heating capacity found
from the capacity graph by the correction coefficient from the table above.
– 4 5 14 17 21 23 24 28 30 32 33 35 37 39 41 42
2-12
1
2
3
4
5
6
7
8
2-13
Design of W-2WAY ECO-i SYSTEM Unit Specifications
1
2
3
4
5
6
7
8
Rate of cooling capacity change (%)
Indoor unit cooling capacity characteristics Indoor unit heating capacity characteristics
indicates the rating point. indicates the rating point.
Indoor air intake temp. (°F WB)
Rate of heating capacity change (%)
Indoor air intake temp. (°F DB)
120
110
100
90
80
110
105
100
95
90
57 59 60 62 64 66 68 69 71 73 75 77 59 60 62 64 66 68 69 71 73 75 77 78
80
<Cooling>
Elevation difference (ft)
Base capacity change rate
Elevation difference (ft)
*1
92 90 88 86 84 82 80 78 76
94
96
98
100 %
0 98 66 33 131 164 197 230 262 295 328 361 394 427 459 492
164
131
98
66
33
0
-33
-66
-98
-131
Equiv
0 98 66 33 131 164 197 230 262 295 328 361 394 427 459 492
alent length (ft)
Equivalent length (ft)
<Heating>
Base capacity change rate
164
131
98
66
33
0
-33
-66
-98
-131
1. Model Selecting and Capacity Calculator
Graph of indoor unit capacity characteristics (2 – (2))
Graph of capacity change characteristics resulting from tubing length and elevation difference (1 / 2 – (3))
The positive side for the elevation difference indicates that the outdoor unit is installed at a higher position than the indoor units. The negative side indicates the opposite.
The capacity loss that is caused by the tubing length can be reduced by increasing the sizes of the discharge tubes and suc-
tion tubes. Refer to Table 2-13 and make the appropriate changes. However be sure that the total length does not exceed the maximum. * The only sizes which can be increased are the LM (main tube with the largest diameter) gas tubes, and the changes are
limited to those shown in Table 2-13. In addition, note that the additional refrigerant charge is determined only by the narrow-tube size.
Table 2-13 Equivalent Length Correction Coefficient when the Size of the Discharge Tubes and Suction Tubes (LM)
is Increased
Standard tubing diameter (gas tube, in.(mm))
Tubing diameter after change (gas tube,in.(mm))
Equivalent length correction coefficient
* If the size of the discharge tubes and suction tubes (LM) have been increased, apply the correction coefficient from Table
2-13 and calculate the equivalent length of the LM section.
Equivalent length of tubing after size increase = Standard tubing equivalent length × Equivalent length correction coefficient
ø1/2"
(ø12.7)
ø5/8" ø3/4" ø7/8" ø1-1/8" ø1-3/8"
(ø15.88) (ø19.05) (ø22.22) (ø28.58) (ø34.93)
ø5/8"
(ø15.88) (ø19.05) (ø22.22) (ø28.58)
0.4 0.5 0.6
ø3/4" ø7/8" ø1-1/8"
Design of W-2WAY ECO-i SYSTEM Unit Specifications
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
<Cooling>
<Heating>
16HP
10HP
Indoor air intake temp. (°F DB)
59
68
77
59
68
77
Capacity ratio (%)
Input ratio (%)
130 120 110 100
90 80 70 60 50 40
130 120
110
100
90 80 70 60 50
– 4 5 14 23 32 41 50 59
Outdoor air intake temp. (°F WB)
Indoor air intake temp. (°F DB)
59
68
77
59
68
77
Capacity ratio (%)
Input ratio (%)
130 120 110 100
90 80 70 60 50 40
130 120
110
100
90 80 70 60 50
– 4 5 14 23 32 41 50 59
Outdoor air intake temp. (°F WB)
* Broken line indicates 16 HP DC inverter unit
Outdoor air intake temp. ( °F DB)
130
120
110
100
90
80
120
110
100
90
80
70
60
50
40
30
20
10
) %
( o
i
t ar
y
t
i cap
a C
) %( oitar tu
pn I
14 23 32 41 50 59 68 77 86 95 104 113
WB = 66
°
F
Indoor air intake temp. (WB) = 71°F
WB = 60°F
Indoor air intak
e tem
p
.
(WB) = 71
°
F
WB = 66
°
F
WB = 60
°
F
1. Model Selecting and Capacity Calculator
1-7. Capacity Correction Graph According to Temperature Condition
Capacity characteristics
(The corrected capacity for specific temperature conditions can be found from the graphs below.)
Heating capacity correction coefficients for frost/defrost operation
Outdoor intake air temp. (°F WB RH85%)
Correction coefficient 0.97 0.97 0.97 0.96 0.94 0.91 0.89 0.87 0.87 0.87 0.88 0.89 0.91 0.92 0.95 1.0
* The heating capacity when frost/defrost operation is considered is calculated by multiplying the heating capacity found
from the capacity graph by the correction coefficient from the table above.
– 4 5 14 17 21 23 24 28 30 32 33 35 37 39 41 42
2-14
1
2
3
4
5
6
7
8
2-15
Design of W-2WAY ECO-i SYSTEM Unit Specifications
1
2
3
4
5
6
7
8
<Cooling>
Elevation difference (ft)
Base capacity change rate
*1
92 90 88 86 84 82 80 78 76
94
96
98
100 %
0 33 66 98 131 164 197 230 262 295 328 361 394 427 459 4920 33 66 98 131 164 197 230 262 295 328 361 394 427 459 492
164
131
98
66
33
0
–33
–66
–98
–131
Equivalent length (ft)
*1 Sample calculations
(System: 20 HP, 164ft equivalent length, 49ft elevation difference
The cooling capacity and heating capacity for this system are found as shown below.)
Cooling operation
From the table, the correction coefficient for that horsepower level is found to be 1.00. From the graph, the base capacity change rate is found to be
92.0%.
92.0%×1.00 = 92.0%
Capacity change rate is 92.0%.
(56.0kW×92.0% = 51.5kW)
92.0% = 175,800 BTU/h
Cooling capacity is 175,800 BTU/h (51.5 kW)
Heating operation
From the table, the correction coefficient for that horsepower level is found to be 1.00. From the graph, the base capacity change rate is found to be
97.2%.
97.2%
×
1.00 = 97.2% Because the calculation result exceeds 97.2%, the capacity change rate is 97.2%.
(63.0kW
×
97.2% = 61.2kW) Heating capacity is 209,000 BTU/h (61.2 kW)
Cooling Heating
Item
Model (SPW-)
Cooling capacity (kW)
Power consumption (kW)
Heating capacity (kW)
Power consumption (kW)
<50Hz models>
22.4
28.0
33.5
40.0
45.0
5.99
7.90
9.58
11.6
13.3
25.0
31.5
37.5
45.0
50.0
6.17
7.15
9.60
11.5
13.2
Equivalent length (ft)
<Heating>
Base capacity change rate
164
131
98
66
33
0
–33
–66
–98
–131
0 33 66 98 131 164 197 230 262 295 328 361 394 427 459 492
Elevation difference (ft)
191,100 BTU/h
×
97.2% = 209,000 BTU/h215,000 BTU/h
×
1. Model Selecting and Capacity Calculator
Rated performance values
Type
1-8. Capacity Correction Graph According to Tubing Length and Elevation Difference
90 95,500(28.0) 27,000(7.90) 107,500(31.5) 26,500(7.75)
140 153,600(45.0) 45,400(13.3) 170,600(50.0) 45,000(13.2)
Item Cooling Heating
Cooling capacity
BTU/h(kW)
Capacity change characteristics
Power consumption
BTU/h(kW)
Heating capacity
BTU/h(kW)
Power consumption
BTU/h(kW)
NOTE
The positive side for the elevation difference indicates that the outdoor unit is installed at a higher position than the indoor units. The negative side indicates the opposite.
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
Design of W-2WAY ECO-i SYSTEM Unit Specifications
1. Model Selecting and Capacity Calculator
If the maximum tubing length (L1) exceeds 295 ft (equivalent length), increase the tubing size of the main liquid, gas tubes (LM)
by one rank. However, the upper limit for the gas tube size is ø1-5/8".
Increasing the tubing size of the gas tubes can reduce the loss of capacity caused by longer tubing lengths.
Refer to Table 2-13 to increase the tubing size. However, the maximum allowable tubing length must not be exceeded.
* The amount of additional refrigerant charge is determined from the liquid tube size only.
Table 2-13 Correction coefficient for equivalent length when the size of the gas tube (LM) is increased
Standard tube diameter (gas tube, in.(mm))
Tube diameter after change (gas tube, in.(mm))
Equivalent length correction coefficient
* When increasing the size of the suction and discharge tubing (LM), multiply by the
correction coefficient from Table 2-13 and calculate the equivalent length for section LM.
Tubing equivalent length after size increase = Standard tubing equivalent length × Equivalent length correction coefficient
ø1/2"
(ø12.7)
ø5/8"
(ø15.88)
ø5/8"
(ø15.88)
ø3/4"
(ø19.05)
0.4 0.5 0.6
ø3/4"
(ø19.05)
ø7/8"
(ø22.22)
ø7/8"
(ø22.22)
ø1-1/8"
(ø28.58)
ø1-1/8"
(ø28.58)
ø1-3/8"
(ø34.93)
2-16
1
2
3
4
5
6
7
8
Outdoor
unit 1
Indoor
unit 1
Indoor
unit 2
Indoor
unit 3
Indoor
unit 4
Outdoor
unit 2
Elevation difference: 33 ft
164 ft
33 ft 33 ft 66 ft
33 ft 33 ft 33 ft
Design of W-2WAY ECO-i SYSTEM Unit Specifications

2. System Design

2-1. System Example
(1) Below are the tables created using the “Sanyo PAC System Diagram Software.” Details of the calculations are shown in (2).
Selection conditions
Assumes that installation is in a 60 Hz region.
Outdoor unit
Cooling
Heating
Actual tubing length 291 ft 197 ft 230 ft 263 ft 296 ft
Equivalent length (with consideration for curves, etc.)
Air condition (DB/WB) 91.0 / 72.0 78.0 / 64.0 78.0 / 64.0 78.0 / 64.0 78.0 / 64.0
Max. load (BTU/h) 40,000 40,000 30,000 18,000
Air condition (DB/WB) 37.0 / 35.0 69.0 / 55.0 69.0 / 55.0 69.0 / 55.0 69.0 / 55.0
Max. load (BTU/h) 46,000 46,000 35,000 23,000
365 ft 236 ft 276 ft 316 ft 355 ft
Room 1 (indoor unit 1)
Room 2 (indoor unit 2)
Room 3 (indoor unit 3)
Room 4 (indoor unit 4)
Preliminary selection
Outdoor unit
Selected model
Load (cooling/heating) (BTU/h) 40,000 40,000 30,000 18,000
Rated capacity (cooling/heating) (BTU/h)
(5) Corrected capacity (cooling/
heating) (BTU/h)
(7) Actual capacity
(cooling/heating) (BTU/h)
Type
09053+09053
191,000 /
215,000
159,600 /
156,100
Room 1 (indoor unit 1)
Type 4852 Type 4852 Type 3652 Type 1852
47,800 /
54,600
47,400 /
54,600
47,400 /
50,900
Room 2 (indoor unit 2)
47,800 /
54,600
46,300 /
54,600
46,300 /
50,900
Room 3 (indoor unit 3)
36,000 /
39,000
34,000 /
38,900
34,000 /
36,300
Room 4 (indoor unit 4)
19,000 /
21,000
17,500 /
20,600
17,500 /
19,200
Total corrected capacity of indoor units (cooling/heating) = 145,200/168,700 Ruc = 145,200/159,600 = 0.910 < 1 Ruh = 168,700/156,100 = 1.081 > 1
Outdoor unit changes
During heating, the corrected outdoor unit capacity is less than the total corrected capacity of all indoor units in the system. As a result, the actual capacity of each indoor unit is less than the maximum load. Therefore the outdoor unit is increased by one rank.
Room 1 (indoor unit 1)
Type 4852 Type 4852 Type 3652 Type 1852
40,000 40,000 30,000 18,000
47,800 /
54,600
47,400 /
54,600
47,400 /
54,600
Selected model
Maximum load (cooling/heating) (BTU/h)
Rated capacity (cooling/heating) (BTU/h)
(5) Corrected capacity (cooling/
heating) (BTU/h)
(7) Actual capacity
(cooling/heating) (BTU/h)
Outdoor unit
Type
14053+09035
249,100 /
278,100
208,100 /
201,900
Total corrected capacity of all indoor units (cooling/heating) = 145,200/163,700 Ruc = 145,200/208,100 = 0.698 < 1 Ruh = 168,700/201,900 = 0.835 < 1
Room 2 (indoor unit 2)
2-17
47,800 /
54,600
46,300 /
54,600
46,300 /
54,600
Room 3 (indoor unit 3)
36,000 /
39,000
34,000 /
38,900
34,000 /
38,900
Room 4 (indoor unit 4)
19,000 /
21,000
17,500 /
20,600
17,500 /
20,600
Design of W-2WAY ECO-i SYSTEM Unit Specifications
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
2. System Design
Indoor unit changes
The indoor unit in room 4, where the corrected indoor unit capacity is less than the maximum load, is increased by one rank.
Outdoor unit
Selected model
Maximum load (cooling/heating) (BTU/h)
Rated capacity (cooling/heating) (BTU/h)
(5) Corrected capacity
(cooling/heating) (BTU/h)
(7) Actual capacity
(cooling/heating) (BTU/h)
Total corrected capacity of all indoor units (cooling/heating) = 150,700/174,500 Ruc = 150,700/208,100 = 0.724 < 1 Ruh = 174,500/201,900 = 0.864 < 1
For both cooling and heating in all rooms, actual capacity is now greater than or equal to the maximum load. Selection is completed.
Type 14053+09053
249,100 / 278,100 47,800 / 54,600 47,800 / 54,600 36,000 / 39,000 25,000 / 27,000
208,100 / 201,900 47,400 / 54,600 46,300 / 54,600 34,000 / 38,900 23,000 / 26,400
Room 1 (indoor unit 1)
Type 4852 Type 4852 Type 3652 Type 2452
40,000 / 46,000 40,000 / 46,000 30,000 / 35,000 18,000 / 23,000
47,400 / 54,600 46,300 / 54,600 34,000 / 38,900 23,000 / 26,400
Room 2 (indoor unit 2)
Room 3 (indoor unit 3)
Room 4 (indoor unit 4)
(2) Calculate the final selection results according to the capacity calculation procedure.
[From calculation of the correction coefficient to calculation of actual capacity] (Cooling/heating)
Outdoor unit
Rated capacity (BTU/h) 249,100 / 278,100 47,800 / 54,600 47,800 / 54,600 36,000 / 39,000 25,000 / 27,000
(1) Model 1.00 / 1.00
(2) Temp. condition 1.020 / 0.937 0.921 / 0.780 0.921 / 0.980 0.921 / 0.980 0.921 / 0.980
(3) Tubing length,
elevation difference
Correction coefficient
(4) Frosting/defrosting 0.89
Result of (2) × (3) 0.992 / 1.031 0.969 / 1.014 0.945 / 0.997 0.921 / 0.980
Correction coefficient applied to indoor unit *1
(5) Corrected capacity (BTU/h) *2 208,100 / 201,900 47,400 / 54,600 46,300 / 54,600 34,000 / 38,900 23,000 / 26,400
(6) Correction coefficient
for corrected capacity ratio
(7) Actual capacity (BTU/h) 47,400 / 54,600 46,300 / 54,600 34,000 / 38,900 23,000 / 26,400
*1: This varies depending on the values of (2) and (2) × (Distribution ratio in (3)). *2: Corrected outdoor unit capacity = Rated outdoor unit capacity × (1) × (2) × (3) × (4)
The actual capacity is calculated as shown below.
Cooling: Ruc = (47,400 + 46,300 + 34,000 + 23,000) / 208,100 = 0.724 < 1 Therefore, Actual cooling capacity of each indoor unit = Corrected cooling capacity of each indoor unit (In other words, the correction coefficient (6) for the corrected capacity ratio is 1.) Heating: Ruh = (54,600 + 54,600 + 38,900 + 26,400) / 201,900 = 0.864 < 1 Therefore, Actual heating capacity of each indoor unit = Corrected heating capacity of each indoor unit × (0.1 × Ruh + 0.9) / Ruh (In other words, the correction coefficient (6) for the corrected capacity ratio is (0.1 × Ruh + 0.9) / Ruh.)
0.819 / 0.871
Room 1 (indoor unit 1)
1.077 / 1.052 1.052 / 1.035
0.99 / 1.03 0.97 / 1.01 0.95 / 1.00 0.92 / 0.98
Room 2 (indoor unit 2)
Room 3 (indoor unit 3)
1.00 / 1.00
Room 4 (indoor unit 4)
1.026 / 1.017 1.00 / 1.00
2-18
1
2
3
4
5
6
7
8
2-19
Design of W-2WAY ECO-i SYSTEM Unit Specifications
1
2
3
4
5
6
7
8
964
09053 14053
3652
4852
1852
1852
1852 0952
3652 3652 1852
LH
16.4ft
16.4ft
2. System Design
(3) Increasing the size of the refrigerant tubing
Increasing the tubing size of the gas tubes can reduce the loss of capacity caused by longer tubing lengths.
Refer to Table 2-13 to increase the tubing size. However, the maximum allowable tubing length must not be exceeded.
* The amount of additional refrigerant charge is determined from the liquid tube size only.
Table 2-13 Correction coefficient for equivalent length when the size of the gas tube (LM) is increased
Standard tube diameter (gas tube, in.(mm))
Tube diameter after change (gas tube, in.(mm))
Equivalent length correction coefficient
* When increasing the size of the suction and discharge tubing (LM), multiply by the correction coefficient from Table 2-13 and
calculate the equivalent length for section LM.
Tubing equivalent length after size increase = Standard tubing equivalent length × Equivalent length correction coefficient
ø1/2"
(ø12.7)
ø5/8"
(ø15.88)
ø5/8"
(ø15.88)
ø3/4"
(ø19.05)
0.4 0.5 0.6
ø3/4"
(ø19.05)
ø7/8"
(ø22.22)
ø7/8"
(ø22.22)
ø1-1/8"
(ø28.58)
ø1-1/8"
(ø28.58)
ø1-3/8"
(ø34.93)
2-2. Example of Tubing Size Selection for Extension and Additional Charge Amount
Sample calculation for the system below
Design of W-2WAY ECO-i SYSTEM Unit Specifications
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
2. System Design
Additional refrigerant charge before extension
Liquid tube
diameter
La ø1/2 6.6 1.38 9.055
Lb ø3/8 65.6 0.602 39.501 LA ø3/4 26.2 2.78 72.966 LB ø1/2 19.7 1.38 27.165 LC ø1/2 19.7 1.38 27.165 LD ø1/2 19.7 1.38 27.165
LE1 ø3/8 16.4 0.602 9.875
LG ø5/8 26.2 1.99 52.231 LH ø3/8 13.1 0.602 7.900
L1 ø3/8 9.8 0.602 5.925
L2 ø1/4 9.8 0.279 2.746
L3 ø1/4 9.8 0.279 2.746
L7 ø3/8 9.8 0.602 5.925
L8 ø1/4 9.8 0.279 2.746
L9 ø1/4 13.1 0.279 3.661
Tubing length (ft)
(A)
Total (oz) 296.775 297 oz
Additional refrigerant charge
per 1 ft (oz/ft) (B)
(A) × (B) oz
Additional refrigerant charge after extension
Liquid tube
diameter
LE2 ø3/8 13.1 0.602 7.900
LF ø3/8 16.4 0.602 9.875
L4 ø3/8 13.1 0.602 7.900
L5 ø3/8 19.7 0.602 11.850
L6 ø1/4 23.0 0.279 6.407
Calculation of additional refrigerant charge for the entire 2-WAY ECO-i system
(Additional refrigerant charge for entire 2-WAY ECO-i system) = (Refrigerant charge at outdoor unit) + (Additional refrigerant charge) = 881 + 341 = 1222 oz (after extension) [Before extension: 458 + 297 = 755 oz]
Tubing length (ft)
(A)
Total (oz) 43.934 44 oz
Additional refrigerant charge
per 1 ft (oz/ft) (B)
(A) × (B) oz
2-20
Loading...
+ 213 hidden pages