Contents
Page
IMPORTANT!
Please Read Before Starting .................................. 2
1. GENERAL .......................................................... 3
1-1. Tools Required for Installation (not supplied) 1-2. Accessories Supplied with Unit 1-3. Optional Copper Tubing Kit 1-4. Type of Copper Tube and Insulation Material 1-5. Additional Materials Required for Installation
2. INSTALLATION SITE SELECTION ................... 4
2-1. Indoor Unit 2-2. Outdoor Unit 2-3. Baffle Plate for the Outdoor Unit
3. HOW TO INSTALL THE INDOOR UNIT ............. 6
3-1. Remove the Rear Panel from the Unit 3-2. Make a Hole 3-3. Install the Rear Panel on the Wall 3-4. Remove the Grille to Install the Indoor Unit 3-5. Shape the Indoor Side Tubing 3-6. Wiring Instructions 3-7. Recommended Wire Length and Diameter 3-8. Wiring Instructions for Inter-unit Connections 3-9. Mounting 3-10. Drain Hose
4. HOW TO INSTALL THE OUTDOOR UNIT ....... 16
4-1. Wiring Instructions for the Outdoor Unit
5. REFRIGERANT TUBING.................................. 17
5-1. Use of the Flaring Method 5-2. Flaring Procedure with a Flare Tool 5-3. Caution before Connecting Tubes Tightly 5-4. Connecting Tubing between Indoor and
Outdoor Units 5-5. Insulation of Refrigerant Tubing 5-6. Taping the Tubes 5-7. Finishing the Installation
6. AIR PURGING................................................... 19
I Air Purging with a Vacuum Pump (for Test Run) I Basic Functions of the Service Valves I Pump Down
INSTALLATION INSTRUCTIONS
Model Combinations
Combine indoor and outdoor units only as listed below.
Indoor Unit Outdoor Unit
KS0971 C0971
CL0971
KS1271 C1271
CL1271
Power Source: 60 Hz, single-phase, 115 V
– Inverter Split System Air Conditioner –
COOL/ DRY Model
This air conditioner uses the new refrigerant R410A.
Be sure to read the yellow instruction sheet attached to the outdoor unit for models using the new refrigerant R410A.
The illustrations are based on the typical appearance of a standard model. Consequently, the shape may differ from that of the air conditioner that you are installing.
NOTE
7. REMOTE CONTROL UNIT INSTALLATION
POSITION ......................................................... 23
7-1. Mounting on a Wall
8. ADDRESS SWITCH.......................................... 24
8-1. Address Setting of the Remote
Control Unit
05-424 KS0971-1271 12/13/05 1:27 PM Page a
Page 2
2
IMPORTANT! Please Read Before Starting
This air conditioning system meets strict safety and operating standards. As the installer or service person, it is an important part of your job to install or service the system so it operates safely and efficiently.
For safe installation and trouble-free operation, you must:
G
Carefully read this instruction booklet before beginning.
G
Follow each installation or repair step exactly as shown.
G
Observe all local, state, and national electrical codes.
G
Pay close attention to all warning and caution notices given in this manual.
This symbol refers to a hazard or unsafe practice which can result in severe personal injury or death.
This symbol refers to a hazard or unsafe practice which can result in personal injury or prod­uct or property damage.
If Necessary, Get Help
These instructions are all you need for most installation sites and maintenance conditions. If you require help for a special problem, contact our sales/service outlet or your certified dealer for additional instructions.
In Case of Improper Installation
The manufacturer shall in no way be responsible for improp­er installation or maintenance service, including failure to follow the instructions in this document.
SPECIAL PRECAUTIONS
When Wiring
ELECTRICAL SHOCK CAN CAUSE SEVERE PERSONAL INJURY OR DEATH. ONLY A QUALIFIED, EXPERIENCED ELECTRICIAN SHOULD ATTEMPT TO WIRE THIS SYSTEM.
• Do not supply power to the unit until all wiring and tubing are completed or reconnected and checked.
• Highly dangerous electrical voltages are used in this system. Carefully refer to the wiring diagram and these instructions when wiring. Improper connections and inadequate grounding can cause accidental injury or
death.
• Ground the unit following local electrical codes.
• Connect all wiring tightly. Loose wiring may cause over­heating at connection points and a possible fire hazard.
When Transporting
Be careful when picking up and moving the indoor and out­door units. Get a partner to help, and bend your knees when lifting to reduce strain on your back. Sharp edges or thin alu­minum fins on the air conditioner can cut your fingers.
When Installing…
…In a Ceiling or Wall
Make sure the ceiling/wall is strong enough to hold the unit’s weight. It may be necessary to construct a strong wood or metal frame to provide added support.
…In a Room
Properly insulate any tubing run inside a room to prevent “sweating” that can cause dripping and water damage to walls and floors.
…In Moist or Uneven Locations
Use a raised concrete pad or concrete blocks to provide a solid, level foundation for the outdoor unit. This prevents water damage and abnormal vibration.
…In an Area with High Winds
Securely anchor the outdoor unit down with bolts and a metal frame. Provide a suitable air baffle.
…In a Snowy Area (for Heat Pump-type Systems)
Install the outdoor unit on a raised platform that is higher than drifting snow. Provide snow vents.
When Connecting Refrigerant Tubing
• Use the flare method for connecting tubing.
• Apply refrigerant lubricant to the matching surfaces of the flare and union tubes before connecting them, then tighten the nut with a torque wrench for a leak-free connection.
• Check carefully for leaks before starting the test run.
When Servicing
• Turn the power OFF at the main power box (mains) before opening the unit to check or repair electrical parts and wiring.
• Keep your fingers and clothing away from any moving parts.
• Clean up the site after you finish, remembering to check that no metal scraps or bits of wiring have been left inside the unit being serviced.
Others
• Ventilate any enclosed areas when installing or testing the refrigeration system. Escaped refrigerant gas, on contact with fire or heat, can produce dangerously toxic gas.
• Confirm upon completing installation that no refrigerant gas is leaking. If escaped gas comes in contact with a stove, gas water heater, electric room heater or other heat source, it can produce dangerously toxic gas.
05-424 KS0971-1271 12/13/05 1:27 PM Page 2
WARNING
CAUTION
WARNING
CAUTION
Page 3
3
1. General
This booklet briefly outlines where and how to install the air conditioning system. Please read over the entire set of instructions for the indoor and outdoor units and make sure all accessory parts listed are with the system before beginning.
1-1. Tools Required for Installation (not supplied)
1. Standard screwdriver
2. Phillips head screwdriver
3. Knife or wire stripper
4. Tape measure
5. Carpenter’s level
6. Sabre saw or key hole saw
7. Hacksaw
8. Core bits
9. Hammer
10. Drill
11. Tube cutter
12. Tube flaring tool
13. Torque wrench
14. Adjustable wrench
15. Reamer (for deburring)
1-2. Accessories Supplied with Unit
Table 1
1-3. Optional Copper Tubing Kit
Copper tubing for connecting the outdoor unit to the indoor unit is available in kits which contain the narrow and wide tubing, fittings and insulation. Consult your nearest sales outlet or A/C workshop.
1-4. Type of Copper Tube and Insulation Material
If you wish to purchase these materials separately from a local source, you will need:
1. Deoxidized annealed copper tube for refrigerant tub­ing as detailed in Table 2.
Cut each tube to the appropriate lengths 1' to 1'4" (30 cm to 40 cm) to dampen vibration between units.
Table 2
2. Foamed polyethylene insulation for the specified copper tubes as required to precise length of tubing. Wall thickness of the insulation should be not less than 5/16" (8 mm).
3. Use insulated copper wire for field wiring. Wire size varies with the total length of wiring. Refer to 3-6. Wiring Instructions for details.
Check local electrical codes and regulations before obtaining wire. Also, check any specified instructions or limitations.
Model
Narrow Tube Wide Tube
Outer Dia. Thickness Outer Dia. Thickness
KS0971/1271 1/4" (6.35 mm) 0.0314" (0.8 mm) 3/8" (9.52 mm) 0.0314" (0.8 mm)
05-424 KS0971-1271 12/13/05 1:27 PM Page 3
Parts Figure Q’ty Parts Figure Q’ty
Remote control unit
1
Tapping screw
Remote control unit holder
1
Rawl plug
AAA alkaline battery
Air clean filter
2
2
Drain hose
adapter
Cushion rubber*
Tr uss-head Phillips
5
/32 ¥5/8" (4¥16 mm)
10
Hex wrench*
8
1
4
Parts Figure Q’ty
Clamp
*Packed in the outdoor unit.
1
1
CAUTION
Page 4
4
1-5. Additional Materials Required for Installation
1. Refrigeration (armored) tape
2. Insulated staples or clamps for connecting wire (See local codes)
3. Putty
4. Refrigeration lubricant
5. Clamps or saddles to secure refrigerant tubing
2. Installation Site Selection
2-1. Indoor Unit
AVOID:
G direct sunlight.
G nearby heat sources that may affect performance of the unit.
G areas where leakage of flammable gas may be expected.
G places where large amounts of oil mist exist.
DO:
G select an appropriate position from which every corner of
the room can be uniformly cooled. (High on a wall is best.)
G select a location that will hold the weight of the unit.
G select a location where tubing and drain hose have the
shortest run to the outside. (Fig. 1)
G allow room for operation and maintenance as well as unre-
stricted air flow around the unit. (Fig. 2)
G install the unit within the maximum elevation difference (H)
above or below the outdoor unit and within a total tubing length (L) from the outdoor unit as detailed in Table 3 and Fig. 3a.
G Install the indoor unit more than 3.3' (1 m) away from any
antenna or power lines or connecting wires used for television, radio, telephone, security system, or intercom. Electrical noise from any of these sources may affect operation.
Fig. 1
Fig. 2
Fig. 3a
To prevent abnormal heat genera­tion and the possibility of fire, do not place obstacles, enclosures and grilles in front of or surround­ing the air conditioner in a way that may block air flow.
* If total tubing length becomes 25 ft. (max.), charge additional refrigerant (R410A) by 0.16 oz./ft.
No additional charge of compressor oil is necessary.
Fig. 3b
For stable operation of the air conditioner, do not install wall-mounted type indoor units less than 5' (1.5 m) from floor level.
Max. Allowable Tubing Limit of Tubing Limit of Elevation Required Amount of
Model Length at Shipment Length (L) Difference (H) Additional Refrigerant
(ft.) (ft.) (ft.) (oz./ft.)*
KS0971 25 50 23 0.16
KS1271 25 65 23 0.16
Table 3
05-424 KS0971-1271 12/13/05 1:27 PM Page 4
Indoor unit
WARNING
2" (5 cm)
min.
Elevation difference (H)
Outside drainage
INDOOR UNIT
6" (15 cm) min.
Front View
Tubing length (L)
Drain hose
2" (5 cm)
min.
OUTDOOR UNIT
CAUTION
Indoor unit
Minimum height from floor level
5' (1.5 m)
Floor level
Wall
Page 5
5
2-2. Outdoor Unit
AVOID:
G heat sources, exhaust fans, etc. (Fig. 4) G damp, humid or uneven locations.
DO:
G choose a place as cool as possible. G choose a place that is well ventilated. G allow enough room around the unit for air intake/
exhaust and possible maintenance. (Fig. 5a)
G provide a solid base (level concrete pad, concrete
block, 4" ¥ 1'4" (10 ¥ 40 cm) beams or equal), a mini­mum of 4" (10 cm) above ground level to reduce humidity and protect the unit against possible water damage and decreased service life. (Fig. 5b)
G Install cushion rubber under unit’s feet to reduce
vibration and noise. (Fig. 5c)
G use lug bolts or equal to bolt down unit, reducing
vibration and noise.
G Install in a location where no antenna of a television
or radio exists within 10' (3 m).
2-3. Baffle Plate for the Outdoor Unit
(CLxx models only)
It is recommended to use baffle plates for models CL0971 and CL1271. The baffle plates are not normally required for the other models.
When the outdoor unit is installed in a position exposed to strong wind (like seasonal winds with low air tempera­ture in winter), baffle plates must be installed in front of the outdoor unit. (Fig. 5d)
This unit is designed so that the fan of the outdoor unit runs at low speed when the air conditioner is operated at low outdoor air temperatures. When the outdoor unit is exposed to strong wind, the system pressure drops because of the freeze protector.
NOTE
Fig. 4
Fig. 5a
Fig. 5b
Fig. 5c
Fig. 5d
05-424 KS0971-1271 12/13/05 1:27 PM Page 5
NO
Hot air
Outdoor unit
Air intake Min. 2" (5 cm)
Min.
2" (5 cm)
Air intake
Concrete or equal
Air discharge
Valve side Min. 10" (25 cm)
Min. 8" (20 cm)
Exhaust fan
Heat source
Ground
Obstacle above
Min.
7' (2 m)
Air discharge
Min. 2" (5 cm)
Air intake
Anchor bolts (4 pcs.)
Min. 4" (10 cm)
Min.
7' (2 m)
Obstacle
Baffle plate
6" min
6" min
Air discharge
Air discharge
Baffle plate
About 16" (40 cm)
4" (10 cm)
About
Cushion rubber
Page 6
6
Fig. 6
Fig. 7
Fig. 8
3. How to Install the Indoor Unit
3-1. Remove the Rear Panel from the Unit
(1) Remove and discard the set screw on the rear
panel. (Fig. 6)
(2) Press the 2 LL marks on the frame cover and disen-
gage the stationary tabs from the frame. (Fig. 7)
(3) Remove the rear panel.
Tubing can be extended in 5 directions as shown in Fig.
8. Select the direction you need providing the shortest
run to the outside unit.
G When left tubing is to be done, switch the drain hose
and drain cap. (For details, refer to “Switching drain hose and drain cap” on page 14.)
3-2. Make a Hole
(1) Place the rear panel from the indoor unit on the wall
at the location selected. Make sure the panel is hori­zontal, using a carpenter’s level or tape measure to measure down from the ceiling. Wait until after cut­ting the hole before attaching the rear panel to the wall.
(2) Determine which side of the unit you should make
the hole for tubing and wiring. (Fig. 9)
In the case of left-rear tubing, use the measurement points 2-3/4" (70 mm) from the edge of the rear panel for precise placement of the hose outlet. (Fig. 9)
(3) Before making the hole, check carefully that no
studs or pipes are directly run behind the spot to be cut.
The above precautions are also applicable if tubing goes through the wall in any other location.
NOTE
NOTE
Fig. 9
Also avoid areas where elec­trical wiring or conduits are located.
05-424 KS0971-1271 12/13/05 1:27 PM Page 6
Left tubing
Set screw only for transportation
Rear panel
Left-rear tubing
marks
Right-rear tubing (recommended)
Right tubing
Downward tubing
CAUTION
2-3/4" (70 mm)
Page 7
7
Indoor side
Outdoor side
Hole should be made at a slight downward slant to the outdoor side.
NOTE
Fig. 10
Fig. 12
g
Fig. 11
(4) Using a sabre saw, key hole saw or hole-cutting drill
attachment, cut a hole in the wall. See Table 4 and Fig. 10.
Table 4
(5) Measure the thickness of the wall from the inside
edge to the outside edge and cut PVC pipe at a slight angle 1/4" (6 mm) shorter than the thickness of the wall. (Fig. 11)
(6) Place the plastic cover over the end of the pipe (for
indoor side only) and insert the pipe in the wall. (Fig.
12)
3-3. Install the Rear Panel on the Wall
Be sure to confirm that the wall is strong enough to sus­pend the unit.
See either Item a) or b) below depending on the wall type.
a) If Wooden Wall
(1) Attach the rear panel to the wall with the 8 screws
provided. (Fig. 13)
If you are not able to line up the holes in the rear panel with the beam locations marked on the wall, use rawl plugs or toggle bolts to go through the holes on the panel or drill 3/16" (5 mm) dia. holes in the panel over the stud locations and then mount the rear panel.
(2) Double check with a carpenter’s level or tape mea-
sure that the panel is level. This is important to install the unit properly. (Fig. 14)
(3) Make sure the panel is flush against the wall. Any
space between the wall and unit will cause noise and vibration.
b) If Block, Brick, Concrete or Similar Type Wall
Make 3/16" (4.8 mm) dia. holes in the wall. Insert rawl plugs for appropriate mounting screws. (Fig. 15)
Hole Dia.
2-9/16" (65 mm)
Fig. 13
Fig. 14
Fig. 15
05-424 KS0971-1271 12/13/05 1:27 PM Page 7
PVC pipe (Locally purchased)
INSIDE OUTSIDE
Plastic cover
(Locally purchased)
Cut at sli
Wall
ht angle
PVC pipe
Slight angle
3/16" (4.8 mm) dia. hole
Rawl plug
Page 8
8
3-4. Remove the Grille to Install the Indoor Unit
Basically, these models can be installed and wired without removing the grille. If access to any internal part is need­ed, follow the steps as given below.
How to remove the grille
(1) Grasp both ends of the air intake grille, and remove it
by opening towards the front and pulling towards you. (Fig. 16a)
(2) Remove the 2 screws. (Fig. 16b) (3) Remove the screw on the right side cover plate and
open the cover. (Fig. 17a)
(4) Take out the thermistor from the grille. (Fig. 17b) (5) Pull the lower part of the grille toward you to remove.
(Fig. 18a)
(6) Use a standard screwdriver to push on the tabs to
remove the grille.
How to replace the grille
(1) Reinstall the grille into the lower part while aligning
its tabs on the upper part. (Fig. 18b) Insert the tabs in the slots and push the lower part of the grille back into position.
(2) Make sure that the grille and frame are firmly fitted
together by engaging the tabs. (3) Attach the thermistor on the grille. (Fig. 17a) (4) Close the cover and replace the screw. (Fig. 17a) (5) Affix the grille with the 2 previously removed
screws. (Fig. 16b) (6) Install the air intake grille. (a) Allow the edge of the air intake grille to slide into
the top of the indoor unit, and then insert it all the
way inside. (Fig. 19a) (b) Press the bottom right and left corners of the air
intake grille to attach it to the indoor unit. (Fig. 19b)
Attach so that the round pins at the top right and left cor­ners of the air intake grille are inserted into the grooves at the top right and left of the indoor unit.
NOTE
Fig. 16a
Fig. 16b
Fig. 17a
Fig. 17b
Fig. 18a
Fig. 18b
Fig. 19b
Fig. 19a
Pin
Groove
Be sure to wear work gloves during installation to avoid being cut by the sharp aluminum fins of the heat exchanger.
05-424 KS0971-1271 12/13/05 1:27 PM Page 8
CAUTION
Screw cover
Thermistor
Air intake grille
Cover
Grille
Thermistor
Ta b
*
*
*
Grille
Frame
Ta b
*
Page 9
9
3-5. Shape the Indoor Side Tubing
(1) Arrangement of tubing by direction
a) Right or left tubing
Cut out the corner of the right/left frame with a hacksaw or the like. (Figs. 20 and 21)
b) Right-rear or left-rear tubing
In this case, the corner of the frame need not be cut.
(2) To mount the indoor unit on the rear panel:
Hang the 2 mounting slots of the unit on the upper tabs of the rear panel. (Fig. 22)
3-6. Wiring Instructions
General precautions on wiring
(1) Before wiring, confirm the rated voltage of the unit as
shown on its nameplate, then carry out the wiring closely following the wiring diagram.
(2) Provide a power outlet to be used exclusively for
each unit, with a power supply disconnect and cir­cuit breaker for overcurrent protection provided in the exclusive line.
(3) To prevent possible hazards due to insulation failure,
the unit must be grounded.
(4) Each wiring connection must be done tightly and in
accordance with the wiring system diagram. Wrong wiring may cause the unit to misoperate or become damaged.
(5) Do not allow wiring to touch the refrigerant tubing,
compressor, or any moving parts of the fan.
(6) Unauthorized changes in the internal wiring can be
very dangerous. The manufacturer will accept no responsibility for any damage or misoperation that occurs as a result of such unauthorized changes.
Fig. 21
Fig. 22
Fig. 20
05-424 KS0971-1271 12/13/05 1:27 PM Page 9
Frame
Left tubing outlet
Frame
Right tubing outlet
Page 10
10
3-7. Recommended Wire Length and Diameter
Regulations on wiring diameter differ from locality to locality. For field wiring requirements, please refer to your local electrical codes. Carefully observe these regulations when carrying out the installation. Table 5 lists recommended wire lengths and diameters for power supply systems.
Refer to the wiring system diagram (Fig. 23) for the meaning of (A), (B), and (C) in Table 5.
Refer to your local codes or in the absence of local codes see the National Elec­tric Code: ANSI/NFPA70.
NOTE
Fig. 23
WIRING SYSTEM DIAGRAM
G Be sure to comply with local codes on running the wire
from the indoor unit to the outdoor unit (size of wire and wiring method, etc.).
G Each wire must be firmly connected. G No wire should be allowed to touch refrigerant tubing, the
compressor, or any moving part.
G Be sure to connect the power supply line to the outdoor unit as shown in the wiring diagram.
The indoor unit draws its power from the outdoor unit.
G Do not run wiring for antenna, signal, or power lines of television, radio, stereo, telephone,
security system, or intercom any closer than 3'4" (1 m) from the power cable and wires between the indoor and outdoor units. Electrical noise may affect the operation.
G To avoid the risk of electric shock, each air conditioner
unit must be grounded.
G For the installation of a grounding device, please
observe local electrical codes.
G Grounding is necessary, especially for units using
inverter circuits, in order to release charged electricity
and electrical noise caused by high tension.
Otherwise, electrical shock may occur.
G Place a dedicated ground more than 7' (2 m) away from
other grounds and do not have it shared with other elec-
tric appliances.
(A)+(B) (A) Power Supply Wiring Length (ft) (C) Control
Fuse or Circuit AWG
(B) Power Line Length (ft) Line Length (ft)
Model (#14) (#12) (#14)
Breaker Capacity
C0971, CL0971, C1271, CL1271
131 (Max.) 230 (Max.) 65 (Max.) 20A
# ... AWG (American Wire Gauge)
Table 5
05-424 KS0971-1271 12/13/05 1:27 PM Page 10
WARNING
WARNING
INDOOR
UNIT
Te r mi nal Terminal
1 2
3
Disconnect switch
Field supply
115V
115V
115V
(C)
Grounding line
(B)
(B)
OUTDOOR
UNIT
1 2
3
4
5 6
Powe r supply
(A)
L
N
Grounding line
Single phase 115V 60HZ
CAUTION
Page 11
11
3-8. Wiring Instructions for Inter-unit Connections
(1) Insert the inter-unit wiring (according to local codes)
into the through-the-wall PVC pipe. Run the wiring toward the indoor side allowing approx. 10" (25 cm) to extend from the wall face. (Fig. 24)
(2) Grasp both ends of the air intake grille, and remove
it by opening towards the front and pulling towards you.
(3) Remove the screw on the right side cover plate and
open the cover. (Fig. 25)
(4) Route the inter-unit wiring from the back of the
indoor unit and pull it toward the front for connec­tion. (Fig. 26a, 26b)
(5) Connect the inter-unit wiring to the corresponding
terminals on the terminal plate (Fig. 26a, 26b) while referring to the wiring diagram.
(6) Be sure to secure the wiring with the provided
clamp.
When closing the air intake grille, press on both corners. (Fig. 27)
Please refer to “How to replace the grille” on page 8 for installing the air intake grille.
NOTE
Fig. 24
Fig. 25
Fig. 26a
Fig. 26b
Fig. 27
05-424 KS0971-1271 12/13/05 1:28 PM Page 11
Rear panel
Wiring
Wall
Plastic cover
10" (25 cm)
Cover
Te r mi nal plate
Inter-unit wiring
Earth plate
Lock nut
Top of conduit connector
Page 12
12
When connecting each power wire to the corresponding terminal, follow the instructions “How to connect wiring to the terminal” and fasten the wire securely tight with the fixing screw of the terminal plate.
How to connect wiring to the terminal
a) For Indoor Unit
(1) Cut the wire end with a cutting pliers, then strip the
insulation to expose the wire about 9/32" (7 mm). See the label (Fig. 28) near the terminal plate.
(2) Using a screwdriver, loosen the terminal screw on
the terminal plate.
(3) Insert the wire and tighten the terminal screw com-
pletely using a screwdriver.
b) For Outdoor Unit I For solid core wiring (or F-cable)
(1) Cut the wire end with a cutting pliers, then strip the
insulation to expose the solid wire about 15/16" (25 mm). (Fig. 29)
(2) Using a screwdriver, remove the terminal screw(s)
on the terminal plate.
(3) Using the pliers, bend the solid wire to form a loop
suitable for the terminal screw.
(4) Shape the loop wire properly, place it on the termi-
nal plate and fix it securely with the removed termi­nal screw using a screwdriver.
I For stranded wiring
(1) Cut the wire end with a cutting pliers, then strip the
insulation to expose the stranded wiring about 3/8" (10 mm) and tightly twist the wire ends. (Figs. 30 and 31)
(2) Using a screwdriver, remove the terminal screw(s)
on the terminal plate.
(3) Using a ring connector fastener or pliers, securely
clamp each stripped wire end with a ring connector. (Fig. 30)
(4) Place the ring connector wire, and replace and
tighten the removed terminal screw using a screw­driver. (Fig. 32)
Fig. 29
Fig. 28
Fig. 30
Fig. 32
Screw and special washer
Ring connector
Wire
Loose wiring may cause the terminal to overheat or result in unit malfunction. A fire hazard may also exist. There­fore, be sure all wiring is tightly connected.
Fig. 31
05-424 KS0971-1271 12/13/05 1:28 PM Page 12
WARNING
STRIP SIZE
Solid wire
9/32"
(7 mm)
(ACTUAL
SIZE)
Loop
Strip 15/16" (25 mm)
Insulation
Stranded wire
Strip 3/8" (10 mm)
Twist wire ends
Ring connector
Wire
Special washer
Screw
Ring connector
Terminal plate
Page 13
13
3-9. Mounting
(1) To install the indoor unit, mount the indoor unit onto
the 2 tabs on the upper part of the rear plate.
(2) Hold down the air discharge outlet and press the
lower part of the indoor unit until it clicks to securely fasten to the 2 tabs on the lower part of the rear plate. (Fig. 33)
For tubing, choose either the right or left tubing direction and follow the steps below. This work can be made easi­er by placing padding material (such as styrofoam) at the rear right side of the indoor unit. (Fig. 34)
I Right-side tubing
(1) Shape the refrigerant tubing so that it can easily go
into the wall hole. (Fig. 35)
(2) Push the wiring, refrigerant tubing, and drain hose
through the hole in the wall. Adjust the indoor unit so it is securely seated on the rear panel. (Fig. 36)
(3) Carefully bend the tubing (if necessary) to run along
the wall in the direction of the outdoor unit and then tape as far as the fittings. (See Caution on page
18.) The drain hose should come straight down the wall to a point where water runoff won’t stain the wall.
(4) Connect the refrigerant tubing to the outdoor unit.
(After performing a leak test on the connecting part, insulate it with the tubing insulation. (Fig. 37a)) Also, refer to Section 5-4. Connecting Tubing between Indoor and Outdoor Units.
(5) Assemble the refrigerant tubing, drain hose, and
conduit (including inter-unit wiring) as shown in Fig. 37b.
NOTE
Fig. 35
Fig. 36
Fig. 33
Fig. 34
05-424 KS0971-1271 12/13/05 1:28 PM Page 13
Push
Padding material
Rear panel
Cover
Refrigerant tubing
Refrigerant tubing
Fig. 37a
Insulation
Conduit
Fig. 37b
Drain hose
Inter-unit wiring
Inter-unit wiring
Drain hose
Page 14
14
Fig. 38
Fig. 39
I Left-side tubing
(1) Lead the tubing and drain hose through the wall,
allowing sufficient length for connection. Then bend the tubing using a tube bender to make the attach­ment. (Fig. 38)
(2) Switch the drain hose and drain cap.
Switching drain hose and drain cap
(a) Locate the drain hose and the drain cap. (Fig.
39)
(b) Remove the screws fastening the drain hose on
the right side, and pull out the drain hose to remove it. (Fig. 39)
(c) Apply moderate force to pull off the drain cap
on the left side. (If you cannot pull it off by hand, use a long-nose pliers.)
(d) Reattach the drain hose to the left side and the
drain cap to the right side. (Fig. 40a)
Drain hose
Slide the drain hose fully onto the drain pan outlet until the drain hose edge is pushed into the insula­tion. Check that the screw holes in the drain bracket and the drain pan outlet are aligned and securely in contact, then fasten them with the screw. (After attaching the drain hose, check that it is attached securely.) (Fig. 40c)
Drain cap
Use a Phillips screwdriver to push the drain cap in firmly. (If it is difficult to push in, wet the cap with water first.)
(3) Install the indoor unit on the rear panel.
(4) Connect the tubing and wiring led inside from out-
doors.
(5) After completing a leak test, bundle the tubing
together with armoring tape and store it inside the tubing storage area at the back of the indoor unit and hold it with clamps. (Figs. 40a and 41)
Fig. 40a
Fig. 40b
Fig. 40c
Fig. 41
05-424 KS0971-1271 12/13/05 1:28 PM Page 14
Rear panel
Hole in wall
Drain hose
Bent part
Wide tube
Narrow tube
Drain cap
Drain hose
Clamp
Insulation
Drain bracket
Drain hose
Drain cap
Screw hole
Drain bracket
Screw
Conduit
Drain pan outlet
Drain hose
Refrigerant tubing
Inter-unit wiring
Page 15
15
To unmount indoor unit
Press the 2 LL marks on the lower part of the indoor unit and unlatch the tabs. Then lift the indoor unit and unmount. (Fig. 42)
3-10. Drain Hose
a) The drain hose should be slanted downward to the
outdoors. (Fig. 43)
b) Never form a trap in the course of the hose.
c) If the drain hose will run in the room, insulate the
hose with insulation* so that chilled condensation will not damage furniture or floors. (Fig. 44)
* Foamed polyethylene or its equivalent is recom-
mended.
WARNING
Risk of Electric Shock
Do not supply power to the unit or operate it until all tubing and wiring to the out­side unit are completed.
Fig. 44
Fig. 42
Fig. 43
05-424 KS0971-1271 12/13/05 1:28 PM Page 15
Indoor unit
Insulation material (Locally purchased) must be used.
Push
Slant
Drain hose
Condensation
Page 16
16
4. How to Install the Outdoor Unit
First refer to Section 2. Installation Site Selection.
4-1. Wiring Instructions for the Outdoor Unit
Regulations on wire size differ from locality to locality. For field wiring requirements, please refer to your local elec­trical codes. Make sure that the installation fully complies with all local and national regulations.
(1) Remove access panel “C”. (Fig. 46)
(2) Connect the inter-unit and power supply line accord-
ing to the drawing on the panel side.
(3) Be sure to size each wire allowing approx. 4"
(10 cm) longer than the required length for wiring. Store excess wiring inside the cabinet.
(4) When connections are completed, check that all
connections are correct as shown in the wiring sys­tem diagram on panel side.
(5) Be sure to ground the unit according to your local
codes.
Fig. 46
05-424 KS0971-1271 12/13/05 1:28 PM Page 16
Te r mi nal block
Conduit plate
Plug
Lock nut
Inter unit (Conduit)
Cabinet
Access panel “C”
Power supply (Conduit)
Page 17
17
5. Refrigerant Tubing
5-1. Use of the Flaring Method
Many of the conventional split system air conditioners employ the flaring method to connect refrigerant tubes which run between indoor and outdoor units. In this method, the copper tubes are flared at each end and connected with flare nuts.
5-2. Flaring Procedure with a Flare Tool
(1) Cut the copper tube to the required length with a
tube cutter. It is recommended to cut approx. 12" to 20" (30 to 50 cm) longer than the tubing length you estimate.
(2) Remove burrs at the end of the copper tube with a
tube reamer or file. This process is important and should be done carefully to make a good flare. (Fig. 47)
When reaming, hold the tube end downward and be sure that no copper scraps fall into the tube. (Fig. 48)
(3) Remove the flare nut from the unit and be sure to
mount it on the copper tube.
(4) Make a flare at the end of copper tube with a flare
tool.* (Figs. 49a and 49b)
(*Use “RIGID” or equivalent.)
A good flare should have the following characteristics:
G inside surface is glossy and smooth. G edge is smooth. G tapered sides are of uniform length.
5-3. Caution before Connecting Tubes Tightly
a) Be sure to apply a sealing cap or water-proof tape
to prevent dust or water from getting into the tubes before they are used.
b) Be sure to apply refrigerant lubricant to the match-
ing surfaces of the flare and union before connect­ing them together. This is effective for reducing gas leaks. (Fig. 50)
c) For proper connection, align the union tube and
flare tube straight with each other, then screw in the flare nut lightly at first to obtain a smooth match. (Fig. 51)
NOTE
NOTE
Fig. 47
Fig. 48
Fig. 49b
Fig. 49a
Fig. 50
Flare nut
Union
Fig. 51
05-424 KS0971-1271 12/13/05 1:28 PM Page 17
Deburring
Before
If the special R410A flare tool is used:
0 to 0.0196" (0 to 0.5 mm)
After
Copper tubing
Reamer
If the previous flare tool (clutch-type) is used:
0.0472" (1.2 mm)
Adjust so that the amount of tube protrusion is as shown in the figure.
Flare nut
Copper tubing
Flare tool
Apply refrigerant lubricant here and here
Page 18
18
5-4. Connecting Tubing between Indoor and
Outdoor Units
a) Tightly connect the indoor side refrigerant tubing exten-
ded from the wall with the outdoor side tubing. (Fig. 52)
b) To fasten the flare nuts, apply specified torque as:
Table 6
5-5. Insulation of Refrigerant Tubing
To prevent heat loss and wet floors due to dripping of con­densation, both tubes must be well insulated with a proper insulation material. (Fig. 53) The thickness of the insulation should be a minimum 5/16" (8 mm). (Fig. 54)
5-6. Taping the Tubes
(1) At this time, the 2 refrigerant tubes (and electrical wire
if local codes permit) should be taped together with armoring tape. The drain hose may also be included and taped together as 1 bundle with the tubing.
(2) Wrap the armoring tape from the bottom of the outdoor
unit to the top of the tubing where it enters the wall. As you wrap the tubing, overlap half of each previous tape turn. (Fig. 55)
(3) Clamp the tubing bundle to wall, using 1 clamp approx.
every 47" (120 cm).
Do not wind the armoring tape too tightly, since this will decrease the heat insulation effect. Also, be sure the con­densation drain hose splits away from the bundle and drips clear of the unit and the tubing.
5-7. Finishing the Installation
After finishing insulating and taping over the tubing, use sealing putty to seal off the hole in the wall to prevent rain and draft from entering. (Fig. 56)
NOTE
IMPORTANT
Fig. 52
Fig. 54
Fig. 55
Clamp
Insulated tubes
Fig. 56
After a tube has been insulat­ed, never try to bend it into a narrow curve, as this may cause the tube to break or crack.
Fig. 53
Tube Dia. Tightening Torque
1/4" (6.35 mm) Approx. 120 – 160 lbs·in (140 – 180 kgf·cm)
3/8" (9.52 mm) Approx. 300 – 360 lbs·in (340 – 420 kgf·cm)
1/2" (12.70 mm) Approx. 430 – 540 lbs·in (490 – 610 kgf·cm)
5/8" (15.88 mm) Approx. 590 – 710 lbs·in (680 – 820 kgf·cm)
05-424 KS0971-1271 12/13/05 1:28 PM Page 18
Torque wrench
CAUTION
Indoor unit
Min. 5/16" (8 mm)
Spanner
Outdoor unit
Insulation
Insulation
Thickness: min. 5/16" (8 mm)
Apply putty here
Tubing
Page 19
19
6. Air Purging
Air and moisture remaining in the refrigerant system have undesirable effects as indicated below. Therefore, they must be purged completely.
G pressure in the system rises G operating current rises G cooling (or heating) efficiency drops G moisture in the air may freeze and block capillary tubing G water may lead to corrosion of parts in the refrigerant
system
I Air Purging with a Vacuum Pump (for Test Run)
(1) Check that each tube (both narrow and wide tubes)
between the indoor and outdoor units have been properly connected and all wiring for the test run has been completed. Note that both narrow and wide tube service valves on the outdoor unit are kept closed at this stage.
(2) Using an adjustable wrench or box wrench, remove
the valve caps from the service valve on both nar­row and wide tubes.
(3) Connect a vacuum pump and a manifold valve (with
pressure gauges) to the service port on the wide tube service valve. (Fig. 57)
(4) With the “Lo” knob of the manifold valve open, run
the vacuum pump. The operation time for the vacu­um pump varies with tubing length and the capacity of the pump. The following table shows the amount of time for evacuation:
Table 7
Fig. 57
Be sure to use a manifold valve for air purging. If it is not avail­able, use a stop valve (field sup­ply) for this purpose. The “Hi” knob of the manifold valve must always be kept closed.
The required time in Table 7 is calculated based on the assumption that the ideal (or target) vacuum condition is around 10 mmHg abs.
NOTE
Required time for evacuation when
100 liter/h vacuum pump is used
If tubing length is If tubing length is
less than 33 ft. (10 m) more than 33 ft. (10 m)
10 min. or more 15 min. or more
The service port on the wide tube service valve uses a Schrader core valve to access the refrigerant sys­tem. The valve core is similar to those used in automobile tires. Therefore, be sure to use a vacuum hose connector which has a push­pin inside.
To prevent other refrigerants from being mistakenly charged to units which use R410A, the size of the charge port on the service valve is different from the one for other refrigerant types. For servicing such as recharging, the specified charging hose, manifold and vacuum pump adapter (with reverse flow prevention) for R410A must be used.
NOTE
05-424 KS0971-1271 12/13/05 1:28 PM Page 19
CAUTION
Manifold valve (Exclusively for R410A)
Pressure gauge
Indoor unit
Outdoor unit
HiLo
Charging hose (Exclusively for R410A)
CAUTION
Vacuum pump adapter (Exclusively for R410A) (with reverse flow prevention)
Vacuum pump
Page 20
20
(5) With the vacuum pump still running, close the “Lo”
knob of the manifold valve. Then stop the vacuum pump.
(6) With the accessory hex wrench, turn the valve stem
on the narrow tube service valve counter-clockwise by 90 degrees (1/4 turn) for 10 seconds, and then turn the stem clockwise to close it again. (Fig. 58)
(7) Leak test all joints at the tubing (both indoor and out-
doors) with soapy water. Bubbles indicate a leak. Tight­en the joint more when leaks, then check if there is no leak. Be sure to wipe off the soap with a clean cloth.
(8) With the hex wrench, turn the wide tube service
valve stem counter-clockwise to fully open the valve.
(9) Turn the narrow tube service valve stem counter-
clockwise to fully open the valve.
(10) Loosen the vacuum hose connected to the wide
tube service port slightly to release the pressure. Then, remove the hose.
(11) Fasten the valve cap on the wide tube service port
securely with an adjustable wrench or box wrench. Next, mount the valve cap on the service valve and tighten it to 170 lbs·in (200 kgf·cm) with a torque wrench. This process is very important to prevent gas from leaking from the system.
(12) Test run the air conditioner. (See next page.)
(13) While the air conditioner is running, apply liquid
soap to check for any gas leaks around the service valves or caps.
(14) If there is no leakage, stop the air conditioner.
(15) Wipe off the soap on the tubing.
This completes air purging with a vacuum pump and the air conditioner is ready for actual operation.
Be sure to completely insert the hex wrench before attempting to turn the valve.
Fig. 58
This may cause the refriger­ant gas to leak. In order to avoid this, take off the hose quickly.
05-424 KS0971-1271 12/13/05 1:28 PM Page 20
CAUTION
90° (1/4 turn)
Valve cap
Vacuum hose to manifold valve
Narrow tube
Hex wrench
Wide tube
CAUTION
Page 21
21
How to Test Run the Air Conditioner
After turning on power to the air conditioner, use the remote controller and follow the steps below to conduct the test run.
(1) Set the remote controller in Test Run mode.
(Fig. 59a) a) Press and hold the ION button. b) Then press and hold the 1HR TIMER button.
c) At the same time, press the ACL (reset) button once.
Use a pointed object such as the tip of a pen to press the ACL button.
• After a few seconds, “ ” appears and “oP-1” blinks in the remote controller display area. (Fig. 59b)
d) Release the 1HR TIMER button. e) Release the ION button.
(2) Start Cooling mode test run by pressing the ON/OFF
operation button of the remote controller. (Fig. 59a)
• This starts the fan producing uncooled forced air with the 4 indicator lamps (OPERATION lamp, TIMER lamp, QUIET lamp, and ION lamp) on the main unit blinking. (Fig. 59c)
• After 3 minutes, the system shifts into cooling opera­tion, and cool air will start to be felt. Cool mode test run is unaffected by the room temperature.
(3) Press the ON/OFF operation button of the remote con-
troller again to stop the test run. (Fig. 59a)
(4) Finally press the ACL (reset) button of the remote con-
troller to release it from Test Run mode to return to nor­mal mode. (Fig. 59a)
• “ ” and “oP-1” will disappear from the remote con­troller display area.
After the test run is completed, be sure to press the ACL (reset) button to return to normal mode. The air conditioner will not operate correctly if this is not done.
IMPORTANT
Fig. 59a
Fig. 59b
Fig. 59c
05-424 KS0971-1271 12/13/05 1:28 PM Page 21
ION
button
ON/OFF operation
button
1HR. TIMER
button
A
ACL (Reset)
button
OPERATION lamp
TIMER lamp QUIET lamp ION lamp
Page 22
22
I Pump Down
Pump down means collecting all refrigerant gas in the system back into the outdoor unit without losing any of the gas. Pump down is used when the unit is to be moved or before servicing the refrigerant circuit.
Pump Down Procedure
Be sure to carry out pump down with the unit in cooling mode.
(1) Connect the Lo side charging hose of the manifold
valve to the service port on the wide tube service valve.
(2) Using a hex wrench, turn the narrow tube service
valve clockwise all the way to close the service valve. (Be sure to confirm that the wide tube service valve is fully open.)
(3) Press the operation button and start cooling oper-
ation.
(4) When the low pressure gauge reading falls to 14.2 to
7.1 psi (1 to 0.5 kg/cm
2
), fully close the wide tube
valve stem. Then quickly stop the unit.
(5) Disconnect all gauges and hoses, and replace the
valve caps as they were before.
I Basic Functions of the Service Valves
The basic functions of the service valves are given in Table 8 below.
Action
Narrow Tube Service
Valve (2-Way)
Wide Tube Service
Valve (3-Way)
CLOSED
Fully OPEN
Fully OPEN
Shipping
Operating and test running the air conditioner
Measuring pressure and gas charging
Air purging with a vacuum pump
CLOSED
Valve cap
Stem
O-ring
*
*
Table 8
* The service port on the wide tube ser-
vice valve uses a Schrader core valve to access the refrigerant system. Therefore, be sure to use a hose con­nector which has a push-pin inside. (Fig. 60a)
Fig. 60a
Close
Hex wrench
Open
Fig. 60b
When opening or clos­ing the service valve stem, use the accessory hex wrench. Be sure to fully seat the wrench before turning the valve.
05-424 KS0971-1271 12/13/05 1:28 PM Page 22
CAUTION
Service valve
Hose with push-pin
PUSH
Page 23
23
7. Remote Control Unit Installation Position
The remote control unit can be operated from either a non-fixed position or a wall-mounted position.
To ensure that the air conditioner operates correctly, do not install the remote control unit in the following places:
G In direct sunlight G Behind a curtain or other place where it is covered G More than 26' (8 m) away from the air conditioner G In the path of the air conditioner’s airstream G Where it may become extremely hot or cold G Where it may be subject to electrical or magnetic
interference
G Where there is an obstacle between the remote con-
trol unit and the air conditioner (since a check signal is sent from the remote control unit every 5 minutes)
7-1. Mounting on a Wall
Before mounting the remote control unit, press the ON/OFF operation button at the mounting location to make sure that the air conditioner operates from that location. The indoor unit should make a beeping sound to indicate that it has received the signal.
Fig. 61
To take out the remote control unit, pull it forward.
05-424 KS0971-1271 12/13/05 1:28 PM Page 23
Remote control unit mount
Mounting screws
5/32 × 5/8" (4 × 16 mm)
(Included)
Press
Set in place
Rear side
Hole
To prevent loss of the remote control unit, you can connect the remote control unit to the mount by passing a string through the remote control unit and attachment hole.
Page 24
24
8. Address Switch
8-1. Address Setting of the Remote Control Unit
The address can be set in order to prevent interference between remote controllers when two Sanyo indoor units are installed near each other. The address is normally set to “A.” To set a different address, it is necessary to change the address on the second remote controller.
Once changed, you cannot restore the original address setting of the air conditioner.
(1) Switch on the power source. (2) Break the address-setting tab marked “A” on the
second remote controller to change the address (Fig. 62). When the tab is removed, the address is automatically set to B (Fig. 63).
(3) Press and hold the remote controller ION button and
1 HR TIMER button. At the same time, press the ACL(reset) button. Use a thin object such as the tip of a pen to press the ACL button. When this has been done, “oP-1” (test run) appears, blinking, in the remote controller clock display area.
(4) Each time the 1 HR TIMER button is pressed, the
display changes as shown below. Press this button 2 times to change the display to “oP-7” (address setting). (Fig. 64)
(5) “oP-7” has now been selected for address setting. (6) Press the ON/OFF operation button on the remote
controller. (Fig. 64) Check that the “beep”signal­received sound is heard from the second indoor unit (approximately 5 times). The sound you hear is the signal that the remote controller address has been changed.
(7) Finally press the remote controller ACL (reset) but-
ton to cancel the blinking “oP-7” display. (Fig. 64)
Changing of the second remote controller address is now completed.
NOTE
Fig. 62
Fig. 63
Fig. 64
05-424 KS0971-1271 12/13/05 1:28 PM Page 24
Ta b
Te st run mode
Selfdiagnostic mode
Adress setting mode
ION
button
ACL button
ON/OFF operation
button
1HR. TIMER
button
A
ACL (Reset)
button