Sanyo COOL, DRY, CM1972A, CM2472A, CM3172A Installation Instructions Manual

...
Page 1
APPENDIX A
INSTALLATION INSTRUCTIONS
CM1972A CM2472A CM3172A
(II-852-6-4190-509-00-0)
A-1
Page 2
CAUTION
For Outdoor Unit
NOTE
INSTALLATION INSTRUCTIONS
– Inverter Multi Split System Air Conditioner –
This air conditioner uses the new refrigerant R410A.
Refrigerant service valve size = 5/16"
Contents
IMPORTANT!
Please Read Before Starting .................................. 2
1. GENERAL .......................................................... 3
1-1. Tools Required for Installation (not supplied) 1-2. Accessories Supplied with Unit 1-3. Optional Copper Tubing Kit 1-4. Type of Copper Tube and Insulation Material 1-5. Additional Materials Required for Installation
2. INSTALLATION SITE SELECTION ................... 4
2-1. Indoor Unit 2-2. Connecting Indoor Units 2-3. Outdoor Unit 2-4 Baffle Plate for the Outdoor Unit 2-5. Outer Dimensions of Outdoor Unit 2-6. Diagram of Outdoor Unit Installation
3. INSTALLATION PROCESS .............................. 15
3-1. Embedding the Tubing and Wiring 3-2. Use of the Flaring Method 3-3. Flaring Procedure with a Flare Tool 3-4. Caution before Connecting Tubes Tightly 3-5. Tubing Connections 3-6. Insulation of Refrigerant Tubing 3-7. Taping the Tubes 3-8. Finishing the Installation
4. AIR PURGING................................................... 18
I Air Purging with a Vacuum Pump (for Test Run) I Pump Down
COOL/ DRY Model
Model Combinations
Combine indoor and outdoor units only as listed below.
Indoor Unit Outdoor Unit
KMS0772 CM1972A KMS0972 CM2472A KMS1272 CM3172A KMS1872 KMS2472 XMS0972 XMS1272 XS1872
Power Source: 60 Hz, single-phase, 230 / 208 VAC
Be sure to connect indoor and outdoor units only in combinations that are listed in the combination table(s) included in the outdoor unit package. Connecting any other model may result in operation failure and malfunction.
Combination example
Indoor unit B
Indoor unit A
Indoor unit C
5. WIRING INSTRUCTIONS ................................. 21
5-1. General Precautions on Wiring 5-2. Recommended Wire Length and Diameter 5-3. Wiring System Diagram 5-4. How to Connect Wiring to the Terminal 5-5. Wiring Instructions for the Outdoor Unit
6. TEST RUN......................................................... 25
7. CONNECTING A HOME AUTOMATION
DEVICE ............................................................. 26
8. INSTALLATION CHECK SHEET ...................... 26
Be sure to read the yellow instruction sheet attached to the outdoor unit for models using the new refrigerant R410A.
85264190509000 © SANYO 2010
Outdoor unit
Indoor unit D
NOTE
The illustrations are based on the typical appearance of a standard model. Consequently, the shape may differ from that of the air conditioner that you are installing.
SANYO North America Corporation In Canada Commercial Solutions Division SANYO Canada Inc. 2055 Sanyo Ave., San Diego 201 Creditview Road, Woodbridge CA 92154, U.S.A. Ontario, L4L 9T1, Canada
Page 3
IMPORTANT!
CAUTION
WARNING
WARNING
CAUTION
Please Read Before Starting
When Installing…
This air conditioning system meets strict safety and operating standards. As the installer or service person, it is an important part of your job to install or service the system so it operates safely and efficiently.
For safe installation and trouble-free operation, you must:
G
Carefully read this instruction booklet before beginning.
G
Follow each installation or repair step exactly as shown.
G
Observe all local, state, and national electrical codes.
G
Pay close attention to all warning and caution notices given in this manual.
This symbol refers to a hazard or unsafe practice which can result in severe personal injury or death.
This symbol refers to a hazard or unsafe practice which can result in personal injury or prod­uct or property damage.
If Necessary, Get Help
These instructions are all you need for most installation sites and maintenance conditions. If you require help for a special problem, contact our sales/service outlet or your certified dealer for additional instructions.
In Case of Improper Installation
The manufacturer shall in no way be responsible for improp­er installation or maintenance service, including failure to follow the instructions in this document.
SPECIAL PRECAUTIONS
When Wiring
ELECTRICAL SHOCK CAN CAUSE SEVERE PERSONAL INJURY OR DEATH. ONLY A QUALIFIED, EXPERIENCED ELECTRICIAN SHOULD ATTEMPT TO WIRE THIS SYSTEM.
• Do not supply power to the unit until all wiring and tubing are completed or reconnected and checked.
• Highly dangerous electrical voltages are used in this system. Carefully refer to the wiring diagram and these instructions when wiring. Improper connections and inadequate grounding can cause accidental injury or
death.
• Ground the unit following local electrical codes.
• Connect all wiring tightly. Loose wiring may cause over­heating at connection points and a possible fire hazard.
When Transporting
Be careful when picking up and moving the indoor and out­door units. Get a partner to help, and bend your knees when lifting to reduce strain on your back. Sharp edges or thin alu­minum fins on the air conditioner can cut your fingers.
…In a Ceiling or Wall
Make sure the ceiling/wall is strong enough to hold the unit’s weight. It may be necessary to construct a strong wood or metal frame to provide added support.
…In a Room
Properly insulate any tubing run inside a room to prevent “sweating” that can cause dripping and water damage to walls and floors.
…In Moist or Uneven Locations
Use a raised concrete pad or concrete blocks to provide a solid, level foundation for the outdoor unit. This prevents water damage and abnormal vibration.
…In an Area with High Winds
Securely anchor the outdoor unit down with bolts and a metal frame. Provide a suitable air baffle.
…In a Snowy Area
Install the outdoor unit on a raised platform that is higher than drifting snow. Provide snow vents.
When Connecting Refrigerant Tubing
• Use the flare method for connecting tubing.
• Apply refrigerant lubricant to the matching surfaces of the flare and union tubes before connecting them, then tighten the nut with a torque wrench for a leak-free connection.
• Check carefully for leaks before starting the test run.
When Servicing
• Turn the power OFF at the main power box (mains) before opening the unit to check or repair electrical parts and wiring.
• Keep your fingers and clothing away from any moving parts.
• Clean up the site after you finish, remembering to check that no metal scraps or bits of wiring have been left inside the unit being serviced.
Others
• Ventilate any enclosed areas when installing or testing the refrigeration system. Escaped refrigerant gas, on contact with fire or heat, can produce dangerously toxic gas.
• Confirm upon completing installation that no refrigerant gas is leaking. If escaped gas comes in contact with a stove, gas water heater, electric room heater or other heat source, it can produce dangerously toxic gas.
• Do not install only a single indoor unit.
2
Page 4
CAUTION
1. General
This booklet briefly outlines where and how to install the air conditioning system. Please read over the entire set of instruc­tions for the indoor and outdoor units and make sure all accessory parts listed are with the system before beginning. If the electric wiring diagram does not appear in this manual, please check for the diagram on the indoor unit.
1-1. Tools Required for Installation (not supplied)
1. Standard screwdriver
2. Phillips head screwdriver
3. Knife or wire stripper
4. Tape measure
5. Carpenter’s level
6. Sabre saw or key hole saw
1-2. Accessories Supplied with Unit
Table 1
Parts Figure Q’ty Parts Figure Q’ty Parts Figure Q’ty
Hex wrench Cushion rubber 4
Labels for inter-unit cable and tube
ABCD
7. Hacksaw
8. Core bits
9. Hammer
10. Drill
11. Tube cutter
12. Tube flaring tool
1
4 each
Reducer (3/8" 1/2")
CM1972A
13. Torque wrench
14. Adjustable wrench
15. Reamer (for deburring)
16. Vacuum pump (For R410A)
17. Manifold valve
Reducer (1/2" 3/8")
1
CM2472A
CM3172A
Packed in the outdoor unit.
1
2
1-3. Optional Copper Tubing Kit
Copper tubing for connecting the outdoor unit to the indoor unit is available in kits which contain the narrow and wide tubing, fittings and insulation. Consult your nearest sales outlet or air conditioning workshop.
2. Foamed polyethylene insulation for the specified copper tubes as required to precise length of tubing. Wall thickness of the insulation should be not less than 5/16" (8 mm).
3. Use insulated copper wire for field wiring. Wire size varies with the total length of wiring.
1-4. Type of Copper Tube and Insulation Material
Refer to 5. Wiring Instructions for details.
If you wish to purchase these materials separately from a local source, you will need:
1. Deoxidized annealed copper tube for refrigerant tub­ing as detailed in Table 2.
Cut each tube to the appropriate lengths 1' to 1'4"
Check local electrical codes and regulations before obtaining wire. Also, check any specified instructions or limitations.
(30 cm to 40 cm) to dampen vibration between units.
Table 2
Model
KMS0772 / 0972 / 1272 1/4" (6.35 mm) 0.0314" (0.8 mm) 3/8" (9.52 mm) 0.0314" (0.8 mm)
KMS1872 1/4" (6.35 mm) 0.0314" (0.8 mm) 1/2" (12.70 mm) 0.0314" (0.8 mm)
KMS2472 1/4" (6.35 mm) 0.0314" (0.8 mm) 5/8" (15.88 mm) 0.0393" (1.0 mm)
XMS0972 / 1272 1/4" (6.35 mm) 0.0314" (0.8 mm) 3/8" (9.52 mm) 0.0314" (0.8 mm)
XS1872 1/4" (6.35 mm) 0.0314" (0.8 mm) 1/2" (12.70 mm) 0.0314" (0.8 mm)
Outer Dia. Thickness Outer Dia. Thickness
Narrow Tube Wide Tube
1-5. Additional Materials Required for Installation
1. Refrigeration (armored) tape
2. Insulated staples or clamps for connecting wire (See local codes.)
3. Putty
4. Refrigeration lubricant
5. Clamps or saddles to secure refrigerant tubing
3
Page 5
2. Installation Site Selection
Drain hose
Indoor unit
Outside drainage
INDOOR UNIT (1)
INDOOR UNIT (4)
INDOOR UNIT (3)
INDOOR UNIT (2)
Tubing length (L1)
L2
L3
L4
H2
H3
H4
OUTDOOR UNIT
Elevation difference (H1)
WARNING
CAUTION
3.3 ft.
(1m)
(1m)
(1m)
3.3 ft.
(1m)
3.3 ft.
3.3 ft.
3.3 ft.
(1m)
2-1. Indoor Unit
To prevent abnormal heat generation and the possibility of fire, do not place obstacles, enclosures and grilles in front of or surrounding the air conditioner in a way that may block air flow.
AVOID:
G direct sunlight.
G nearby heat sources that may affect performance of the
unit.
G areas where leakage of flammable gas may be expected.
Fig. 1
For wall-mounted units
G placing or allowing any obstructions near the air conditioner
inlet or outlet.
G installing in rooms that contain instant-on (rapid-start)
fluorescent lamps. (These may prevent the air conditioner from receiving signals.)
G places where large amounts of oil mist exist.
G installing in locations where there are devices that
generate high-frequency emissions.
DO:
G select an appropriate position from which every corner of
the room can be uniformly cooled. (High on a wall is best for wall-mounted types.)
G select a location that will hold the weight of the unit.
G select a location where tubing and drain hose have the
shortest run to the outside. (Fig. 1)
G allow room for operation and maintenance as well as
unrestricted air flow around the unit. (Fig. 2a or 2b)
G install the unit within the maximum elevation difference
(H1, H2, H3, H4) above or below the outdoor unit and within a total tubing length (L1+L2+L3, L1+L2+L3+L4) from the outdoor unit as detailed in Table 3 and Fig. 3a.
Fig. 3a
2" (5 cm)
min.
For ceiling-mounted cassette units
• Air delivery from a ceiling­mounted cassette unit will be degraded if the distance from the floor to the ceiling is greater than 10 ft. (3 m).
• For stable operation of the air conditioner, do not install wall-mounted units less than 5' (1.5 m) from floor level. (Fig. 3b)
4
6" (15 cm) min.
Front View
Fig. 2a
Fig. 2b
Minimum height from floor level
Fig. 3b
2" (5 cm)
Indoor unit
5' (1.5 m)
Floor level
min.
Wall
Page 6
G install the indoor unit more than 3.3' (1 m) away from any
antenna or power lines or connecting wires used for tele­vision, radio, telephone, security system, or intercom. Electrical noise from any of these sources may affect operation.
G install in a sturdy manner to avoid increased operating
noise.
Table 3
Max. Max. Allowable Total Limit of Limit of Elevation Required Amount
Model Tubing Length at shipment (L1+L2+L3) or (H1, H2, H3, H4) Refrigerant
CM1972A 82 150 (L1+L2+L3) 150 (L1+L2+L3) 50
CM2472A 82 150 (L1+L2+L3+L4) 200 (L1+L2+L3+L4) 50 0.22
CM3172A 100 150 (L1+L2+L3+L4) 230 (L1+L2+L3+L4) 50 0.22
* If total tubing length becomes 150 to 200 ft. (Max.) or 150 to 230 ft. (Max.), charge additional refrigerant (R410A) by 0.22 oz./ft.
No additional charge of compressor oil is necessary. For more detailed charging information, refer to the Technical & Service Manual.
Allowable Tubing Length Total Tubing Length Difference of Additional
per unit (L1+L2+L3) or (L1+L2+L3+L4) (ft.) (oz./ft.)*
(ft.) (L1+L2+L3+L4) (ft.)
(ft.)
5
Page 7
Union 1/2"(12.70mm)
1/2"(12.70
mm
)
Flare 3/8"(9.52
mm
)
A joint for connecting tubes of different sizes (3/8"(9.52mm) 1/2"(12.70mm)) Supplied Reducer
1/4"(6.35mm)
1/4"(6.35
mm
)
1/4"(6.35
mm
)
C
B
A
Outdoor unit Indoor unit
(KMS0772,KMS0972,KMS1272) (XMS0972,XMS1272)
(KMS0772,KMS0972,KMS1272) (XMS0972,XMS1272)
(KMS1872) (XS1872)
3/8"(9.52mm)
3/8"(9.52mm)
3/8"(9.52
mm
)
3/8"(9.52
mm
)
3/8"(9.52
mm
)
C
B
A
(KMS0772,KMS0972,KMS1272) (XMS0972,XMS1272)
(KMS0772,KMS0972,KMS1272) (XMS0972,XMS1272)
D
Outdoor unit Indoor unit
3/8"(9.52
mm
)
3/8"(9.52mm)
3/8"(9.52
mm
)
3/8"(9.52mm)
(KMS0772,KMS0972,KMS1272) (XMS0972,XMS1272)
3/8"(9.52
mm
)
3/8"(9.52
mm
)
1/4"(6.35
mm
)
1/4"(6.35
mm
)
1/4"(6.35
mm
)
Union 3/8"(9.52mm)Flare 1/2"(12.70mm)
(KMS0772,KMS0972,KMS1272) (XMS0972,XMS1272)
1/2"(12.70mm)
3/8"(9.52
mm
)
1/4"(6.35
mm
)
(1/2"(12.70
mm
) 3/8"(9.52mm)) Supplied Reducer
3/8"(9.52mm)
3/8"(9.52mm)
1/4"(6.35mm)
1/4"(6.35
mm
)
1/4"(6.35
mm
)
3/8"(9.52
mm
)
3/8"(9.52
mm
)
3/8"(9.52
mm
)
3/8"(9.52
mm
)
C
B
A
Outdoor unit Indoor unit
(KMS0772,KMS0972,KMS1272) (XMS0972,XMS1272)
(KMS0772,KMS0972,KMS1272) (XMS0972,XMS1272)
(KMS0772,KMS0972,KMS1272) (XMS0972,XMS1272)
2-2. Connecting Indoor Units
Figures (4a) – (4k) show the different types of indoor unit connections, including the use of a reducer. To select the required indoor unit to be connected, refer to the Combination Table that was included in the outdoor unit package.
(1) Connecting indoor unit for CM1972A
(A)
Fig. 4a
(B)
(2) Connecting indoor unit for CM2472A
(A)
Fig. 4b
Fig. 4c
6
Page 8
(B)
C
B
A
(KMS0772,KMS0972,KMS1272) (XMS0972,XMS1272)
(KMS0772,KMS0972,KMS1272) (XMS0972,XMS1272)
D
Outdoor unit Indoor unit
(KMS1872) (XS1872)
1/2"(12.70
mm
)
1/2"(12.70
mm
)
3/8"(9.52mm)
3/8"(9.52
mm
)
3/8"(9.52
mm
)
3/8"(9.52
mm
)
(KMS0772,KMS0972,KMS1272) (XMS0972,XMS1272)
3/8"(9.52
mm
)
3/8"(9.52
mm
)
1/4"(6.35
mm
)
1/4"(6.35
mm
)
1/4"(6.35
mm
)
1/4"(6.35
mm
)
Locally purchased
C
B
(KMS1872) (XS1872)
D
Outdoor unit Indoor unit
Union 1/2"(12.70
mm
)Flare 3/8"(9.52mm)
(3/8"(9.52
mm
) 1/2"(12.70mm))
1/2"(12.70mm)
3/8"(9.52
mm
)
(KMS0772,KMS0972,KMS1272) (XMS0972,XMS1272)
3/8"(9.52
mm
)
3/8"(9.52
mm
)
1/4"(6.35mm)
1/4"(6.35
mm
)
A
(KMS0772,KMS0972,KMS1272) (XMS0972,XMS1272)
3/8"(9.52mm)
3/8"(9.52
mm
)
1/4"(6.35
mm
)
(KMS1872) (XS1872)
1/2"(12.70
mm
)
1/2"(12.70
mm
)
1/4"(6.35
mm
)
Union 5/8"(15.88mm)Flare 1/2"(12.70mm)
(1/2"(12.70
mm
) 5/8"(15.88mm)) Locally purchased
C
B
(KMS0772,KMS0972,KMS1272) (XMS0972,XMS1272)
(KMS0772,KMS0972,KMS1272) (XMS0972,XMS1272)
D
Outdoor unit Indoor unit
(KMS2472)
1/2"(12.70mm)
3/8"(9.52
mm
)
3/8"(9.52mm)
5/8"(15.88
mm
)
3/8"(9.52
mm
)
3/8"(9.52mm)
A
(KMS0772,KMS0972,KMS1272) (XMS0972,XMS1272)
3/8"(9.52
mm
)
3/8"(9.52
mm
)
1/4"(6.35
mm
)
1/4"(6.35
mm
)
1/4"(6.35
mm
)
1/4"(6.35
mm
)
(C)
Fig. 4d
(D)
Fig. 4e
Fig. 4f
7
Page 9
(3) Connecting indoor unit for CM3172A
Union 3/8"(9.52mm)Flare 1/2"(12.70mm)
(1/2"(12.70
mm
) 3/8"(9.52mm)) Supplied Reducer
D
C
(KMS0772,KMS0972,KMS1272) (XMS0972,XMS1272)
Outdoor unit Indoor unit
(KMS0772,KMS0972,KMS1272) (XMS0972,XMS1272)
1/2"(12.70mm)
1/2"(12.70
mm
)
3/8"(9.52
mm
)
3/8"(9.52
mm
)
A
(KMS0772,KMS0972,KMS1272) (XMS0972,XMS1272)
B
(KMS0772,KMS0972,KMS1272) (XMS0972,XMS1272)
3/8"(9.52
mm
)
3/8"(9.52
mm
)
3/8"(9.52mm)
3/8"(9.52
mm
)
1/4"(6.35
mm
)
1/4"(6.35mm)
1/4"(6.35
mm
)
1/4"(6.35
mm
)
Union 3/8"(9.52mm)Flare 1/2"(12.70mm)
(1/2"(12.70
mm
3/8"(9.52mm)) Supplied Reducer
A
Outdoor unit Indoor unit
(KMS0772,KMS0972,KMS1272) (XMS0972,XMS1272)
3/8"(9.52mm)
3/8"(9.52
mm
)
1/4"(6.35
mm
)
B
(KMS0772,KMS0972,KMS1272) (XMS0972,XMS1272)
3/8"(9.52
mm
)
3/8"(9.52
mm
)
1/4"(6.35mm)
C
(KMS0772,KMS0972,KMS1272) (XMS0972,XMS1272)
1/2"(12.70
mm
)
3/8"(9.52
mm
)
1/4"(6.35
mm
)
D
(KMS1872) (XS1872)
1/2"(12.70
mm
)
1/2"(12.70
mm
)
1/4"(6.35
mm
)
A
(KMS0772,KMS0972,KMS1272) (XMS0972,XMS1272)
B
Outdoor unit Indoor unit
(KMS0772,KMS0972,KMS1272) (XMS0972,XMS1272)
3/8"(9.52
mm
)
3/8"(9.52
mm
)
3/8"(9.52
mm
)
3/8"(9.52mm)
1/4"(6.35
mm
)
1/4"(6.35mm)
D
C
(KMS1872) (XS1872)
(KMS1872) (XS1872)
1/2"(12.70
mm
)
1/2"(12.70
mm
)
1/2"(12.70
mm
)
1/2"(12.70mm)
1/4"(6.35
mm
)
1/4"(6.35
mm
)
(A)
(B)
Fig. 4g
(C)
Fig. 4h
Fig. 4i
8
Page 10
(D)
Union 5/8"(15.88mm)Flare 1/2"(12.70mm)
(1/2"(12.70
mm
) 5/8"(15.88mm))Locally purchased
C
D
(KMS0772,KMS0972,KMS1272) (XMS0972,XMS1272)
Outdoor unit Indoor unit
(KMS2472)
Union 3/8"(9.52mm)Flare 1/2"(12.70mm)
(1/2"(12.70
mm
) 3/8"(9.52mm))Supplied Reducer
1/2"(12.70mm)
1/2"(12.70
mm
)
5/8"(15.88
mm
)
3/8"(9.52
mm
)
A
(KMS0772,KMS0972,KMS1272) (XMS0972,XMS1272)
3/8"(9.52
mm
)
3/8"(9.52
mm
)
1/4"(6.35
mm
)
B
(KMS0772,KMS0972,KMS1272) (XMS0972,XMS1272)
3/8"(9.52
mm
)
3/8"(9.52
mm
)
1/4"(6.35mm)
1/4"(6.35
mm
)
1/4"(6.35
mm
)
Union 5/8"(15.88mm)Flare 1/2"(12.70mm)
(1/2"(12.70
mm
) 5/8"(15.88mm)) Locally purchased
B
(KMS0772,KMS0972,KMS1272) (XMS0972,XMS1272)
A
Outdoor unit Indoor unit
(KMS0772,KMS0972,KMS1272) (XMS0972,XMS1272)
3/8"(9.52mm)
3/8"(9.52
mm
)
3/8"(9.52
mm
)
3/8"(9.52
mm
)
1/4"(6.35
mm
)
1/4"(6.35
mm
)
C
(KMS1872) (XS1872)
1/2"(12.70
mm
)
1/2"(12.70
mm
)
1/4"(6.35mm)
D
(KMS2472)
1/2"(12.70
mm
)
5/8"(15.88
mm
)
1/4"(6.35
mm
)
(E)
Fig. 4j
Fig. 4k
9
Page 11
2-3. Outdoor Unit
NOTE
Outdoor unit
Hot air
Heat source
Exhaust fan
NO
Min.
7' (2 m)
Min.
7' (2 m)
Ground
Obstacle
Obstacle above
Air discharge
Min. 8" (20 cm)
Air intake
CAUTION
AVOID:
G heat sources, exhaust fans, etc. (Fig. 5a)
G damp, humid or uneven locations.
DO:
G choose a place as cool as possible.
G choose a place that is well ventilated.
G install in a location where at least two sides are unob-
structed, so that the flow of air at the intake port or exhaust port is not blocked, and so that sufficient space is ensured for maintenance to be carried out without trouble. In general the top also must be unob­structed. (Fig. 5b)
G provide a solid base (level concrete pad, concrete block,
6" × 1'4" (15 × 40 cm) beams or equal), a minimum of 6" (15 cm) above ground level to reduce humidity and protect the unit against possible water damage and decreased service life. (Figs. 5c and 5d)
Fig. 5a
Air intake Min. 8" (20 cm)
Min.
4" (10 cm)
Air discharge
Valve side Min. 10" (25 cm)
Min. 1’8" (50 cm)
Fig. 5b
Drain holes
A solid base must not cover the hole of the bottom plate.
G install cushion rubber under unit’s feet to reduce vibration
and noise. (Fig. 5e)
G use lug bolts or equal to bolt down unit, reducing vibration
and noise.
G install in a location where no antenna of a television or
radio exists within 10' (3 m).
2-4. Baffle Plate for the Outdoor Unit
It is recommended to use baffle plates.
When the outdoor unit is installed in a position exposed to strong wind (such as seasonal winds with low air tempera­ture in winter), baffle plates must be installed on the outdoor unit. (Fig. 5f)
This unit is designed so that the fan of the outdoor unit runs at low speed when the air conditioner is operated at low outdoor air temperatures. When the outdoor unit is exposed to strong wind, the system pressure drops because of the freeze protector.
Install a pair of windbaffle plates at the front and back of the outdoor unit if it will be subject to strong wind during the winter. (Figs. 5f, 5g, 5h, 5i, and 5j)
Air intake
Concrete or equal
About 16" (40 c
Wind
Back
Fig. 5c
m)
Fig. 5d
Fig. 5e
Air intake baffle
Anchor bolts (4 pcs.)
Min. 6" (15 cm)
About 6" (15 cm)
Cushion rubber
Front
Wind
10
Air discharge baffle
No air intake baffle required on this side.
Fig. 5f
Page 12
(1) Recommended dimensions of the baffle plates
D
F
E
C
J
H
L
I
B
K
Q
R
A
G
O
(3- 6.5 mm)
3- 1/4"
(2- 6 mm)
2- 15/64"
A
B
H
C
E
F
K
I
J
G
G
D
(4- 6.5 mm)
4- 1/4"
Air Intake Baffle
Air Discharge Baffle
Fig. 5g
Fig. 5h
For Air Intake
Model
CM1972A CM2472A
CM3172A
Dimensions
(inch)
(mm) 640 20 50 635 270 270 10 20 15 657 7.5 10 150 20 20
(inch)
(mm) 640 20 35 785 350 350 10 20 15 807 7.5 10 150 20 20
ABCDE FGH I JKLOQR
25-3/16 25/32 1-31/32 25 10-5/8 10-5/8 25/64 25/32 19/32 25-7/8 19/64 25/64 5-29/32 25/32 25/32
25-3/16 25/32 1-3/8
30-29/32 13-25/32 13-25/32
25/64 25/32 19/32
31-25/32
19/64 25/64 5-29/32 25/32 25/32
For Air Discharge
Dimensions
Model
CM1972A, 2472A, 3172A
Material to be used: Metal plate with corrosion protection treatment Plate thickness: 0.0394 to 0.0472" (1.0 to 1.2 mm)
(inch)
(mm) 560 585 350 150 490 35 55 465 60 85 25
(2) Parts required (field supply except for screws)
Air Intake Baffle
Baffle plate 1
Screw 5/32 × 15/32" (4 × 12 mm) tapping 2 Attached to outdoor unit
Bolt 15/64 × 19/32 – 25/32" (M6 × 15 – 20 mm) 3
Nut 15/64" (M6) 3
Washer 3
Spring washer 3
Item Q’ty Remarks
ABCDE FGH I JK
22-1/16 23-1/32 13-25/32 5-29/32 19-9/32 1-3/8 2-5/32 18-5/16 2-3/8 3-11/32 31/32
Air Discharge Baffle
Baffle plate 1
Bolt 15/64 × 13/32 – 19/32" (M6 × 10 – 15 mm) 4
Nut 15/64" (M6) 4
Washer 4
Spring washer 4
Item Q’ty Remarks
11
Page 13
(3) Installation procedure
Panel top
Panel front
Panel side R
Panel side L
Panel side R
Panel top
Panel front
Panel side L
1. Air Intake Baffle
(1) Left side
1. Remove the top panel from the unit.
2. Remove the panel side L, and drill 3 holes of ø1/4 inch (6.5 mm) at the prescribed position.
3. Install the windbaffle on the unit using field supply bolts and nuts.
4. Recommended bolts to be used are 15/64" (M6 ISO standard), and the recommended length of the bolts is between 19/32 – 25/32 inch (15 – 20 mm).
5. Use washers and spring washers to tightly fasten the windbaffle to the unit.
(2) Right side
1. Remove the top panel from the unit.
2. Use 2 preholes on the panel side R to install the baffle plate.
3. Remove the panel side R from the unit by removing the screws. These screws are used in step 4 below.
4. Put (sandwich) the windbaffle between the unit and the panel side R, then install the windbaffle on the unit using the above screws. Be careful not to damage the screw holes.
2. Air Discharge Baffle
1. Remove the panels front, top, side L and R from the unit and drill 4 holes of ø1/4 inch (6.5 mm) at the prescribed positions.
2. Install the windbaffle on the unit using field supply bolts and nuts.
3. Recommended bolts to be used are 15/64" (M6 ISO standard), and the recommended length of the bolts is between 13/32 – 19/32 inch (10 – 15 mm).
4. Use washers and spring washers to tightly fasten the windbaffle to the unit.
Fig. 5i Fig. 5j
NOTE
G In order to prevent contact of the bolts and heat exchanger and other parts inside the unit, install the windbaffle using
bolts from inside the unit and fasten the bolts with nuts from outside the unit.
G When the windbaffle is installed on the unit, the unit has higher wind resistance. In order to prevent the unit from
falling over, anchor the legs of the unit using anchor bolts (or similar method).
(4) Precautions for installation
1. Be sure not to damage painted surfaces.
2. Finish the edges of the windbaffle to avoid cuts or injury.
3. Drilling of holes must be carefully done so that no damage is caused to external or internal parts of the unit. Particular care must be taken that drill chips do not drop into the unit.
12
Page 14
2-5. Outer Dimensions of Outdoor Unit
(1) CM1972A
(2) CM2472A
23-15/16
23-15/16
5-11/32
15/32
A
5-11/32
15/32
A
13-19/32
12-19/32
12-19/32
13-19/32
14-17/32
14-17/32
A
35-7/16 (900)
Fig. 6a
A
35-7/16 (900)
2-29/32
2-29/32
23/32
1-13/16
2-1/16
29-1/8 (740)
29-1/8 (740)
2-27/32
2-3/4
5-29/32
2-3/4
2-1/32
Service valve on narrow tube side (Outer diameter 1/4"(
Service valve on wide tube side
(Outer diameter 3/8"(
2-3/4
2-15/16
4-1/2
4-7/16
Service valve on wide tube side (Outer diameter 1/2"(12.70))
Service valve on narrow tube side (Outer diameter 1/4"(6.35))
2-3/4
6.35
9.52
))
))
(3) CM3172A
23-15/16
5-11/32
15/32
A
12-19/32
13-19/32
14-17/32
Fig. 6b
A
35-7/16 (900)
2-29/32
23/32
1-13/16
2-1/16
2-13/32
23/32
1-13/16
2-1/16
2-13/32
2-27/32
5-29/32
2-3/4
35-1/32 (890)
2-27/32
5-29/32
2-1/32
2-1/32
4-1/2
4-1/2
2-15/16
4-7/16
Service valve on wide tube side (Outer diameter 3/8"(9.52))
Service valve on narrow tube side (Outer diameter 1/4"(6.35))
Service valve on wide tube side (Outer diameter 1/2"(12.70))
2-3/4
2-15/16
4-7/16
Service valve on wide tube side (Outer diameter 3/8"(9.52))
Fig. 6c
13
unit: inch (mm)
Page 15
2-6. Diagram of Outdoor Unit Installation
(
Never install only a single indoor unit.
Over 4"(10cm)
Be sure to connect indoor and outdoor units only in combinations that are listed in the catalog or in the combination table that was provided with the outdoor unit. (Use caution. Connecting any other model may result in operation failure and malfunction.)
The dimensions indicated by in the figure below are spaces that are required in order to maintain performance. Install in a location where the dimensions indicated by are ensured, and where 2 or more faces of the unit are unobstructed. In principle, the top direction should be unobstructed.
Over 8"(20cm)
Power breaker
Wall-mounted types
Indoor unit D
Indoor unit C
Indoor unit B
Indoor unit A
Service space
Ceiling-mounted
cassette types
Indoor unit D
Indoor unit C
Indoor unit B
Indoor unit A
Ensure 6"(15cm) of space if a drain hose is to be used.
(50cm)
Over 1'8"
Base (not provided) (concrete or similar material)
D C B A
Fasten with anchor bolts (not provided)
3/8" or M10, 4 locations)
Over 10
"(25cm)
Access panel C
Ground wire (not provided)
Fig. 7
14
Page 16
3. Installation Process
3-1. Embedding the Tubing and Wiring
G Do not connect tubes to locations that are embedded.
G Be sure to bind refrigerant tubing and inter-unit cables
together with vinyl tape.
G The power cable must be obtained on-site.
(#12: Less than 85 ft.) # ... AWG (American Wire Gauge)
G Be sure to apply the provided labels to both ends of
the inter-unit cables to prevent miswiring.
G Securely seal the end of embedded tubing with vinyl
tape in order to prevent dirt or moisture entry.
G In order to prevent insulation breakdown and ground
faults, do not allow the wire ends to come in contact with rainwater, or be subject to dew condensation.
3-2. Use of the Flaring Method
Many of the conventional split system air conditioners employ the flaring method to connect refrigerant tubes which run between indoor and outdoor units. In this method, the copper tubes are flared at each end and connected with flare nuts.
Before
Deburring
After
3-3. Flaring Procedure with a Flare Tool
(1) Cut the copper tube to the required length with a
tube cutter. It is recommended to cut approx. 12" to 20" (30 to 50 cm) longer than the tubing length you estimate.
(2) Remove burrs at the end of the copper tube with a
tube reamer or file. This process is important and should be done carefully to make a good flare. (Fig. 8)
Fig. 8
15
Page 17
NOTE
Flare nut
Union
Apply the provided labels to the indoor and outdoor unit tubing connectors to prevent errors in connections.
Service valve on narrow tube side
Service valve on wide tube side
A
B
C
D
When reaming, hold the tube end downward and be sure that no copper scraps fall into the tube. (Fig. 9)
Copper tubing
(3) Remove the flare nut from the unit and be sure to mount
it on the copper tube.
(4) Make a flare at the end of copper tube with a flare tool.*
(Figs. 10 and 11)
(*Use “RIDGID” or equivalent.)
NOTE
A good flare should have the following characteristics:
G inside surface is glossy and smooth.
G edge is smooth.
G tapered sides are of uniform length.
3-4. Caution before Connecting Tubes Tightly
a) Be sure to apply a sealing cap or water-proof tape to
prevent dust or water from getting into the tubes before they are used.
b) Be sure to apply refrigerant lubricant to the matching
surfaces of the flare and union before connecting them together. This is effective for reducing gas leaks. (Fig. 12)
If the special R410A flare tool is used:
0 to 0.0196" (0 to 0.5 mm)
Reamer
Fig. 9
If the previous flare tool (clutch-type) is used:
0.0472" (1.2 mm)
Adjust so that the amount of tube protrusion is as shown in the figure.
Fig. 10
Flare nut
Copper tubing
Flare tool
Fig. 11
c) For proper connection, align the union tube and flare
tube straight with each other, then screw in the flare nut lightly at first to obtain a smooth match. (Fig. 13)
3-5. Tubing Connections
a) Temporary connection:
Screw in 3 – 5 turns by hand. (Fig.14)
b) To fasten the flare nuts, apply specified torque as:
Table 4
Tube Dia. Tightening Torque
1/4" (6.35 mm) Approx. 120 – 160 lbs·in (140 – 180 kgf· cm)
3/8" (9.52 mm) Approx. 300 – 360 lbs·in (340 – 420 kgf· cm)
1/2" (12.70 mm) Approx. 430 – 540 lbs·in (490 – 610 kgf·cm)
5/8" (15.88 mm) Approx. 590 – 710 lbs·in (680 – 820 kgf·cm)
16
Fig. 14
Apply refrigerant lubricant here and here
Fig. 12
Fig. 13
Page 18
IMPORTANT
Indoor unit
Outdoor unit
Spanner
Torque wrench
Insulation
CAUTION
Be sure to match refrigerant
Insulation tape (supplied)
Flare insulation (3/16"(T5, supplied) )
Flare insulation (1/8"(T3, supplied) )
Tube insulation
(not supplied)
Vinyl tie (supplied)
Flare nut
tubing and electric wiring between indoor and outdoor units.
Fig. 15
3-6. Insulation of Refrigerant Tubing
To prevent heat loss and wet floors due to dripping of con­densation, both tubes must be well insulated with a
proper insulation material.
The thickness of the insulation should be a minimum 5/16" (8 mm). (Fig. 16)
I For wall-mounted units
After connecting the refrigerant tubing to the outdoor unit and performing a leak test on the connecting part, insulate it with the tubing insulation. (Fig 17a)
I For ceiling-mounted cassette units
Wind the insulation tape around the flare nuts at the tube connections. Secondly cover up the tubing connections with the flare insulation (1/8" (T3, supplied)). Then wind the other flare insulation (3/16" (T5, supplied)). Finally, fasten the insulation at both ends with the supplied vinyl ties. (Fig. 17b)
Min. 5/16" (8 mm)
Insulation
Thickness: min. 5/16" (8 mm)
Fig. 16
Fig. 17a
Insulation material
The material used for insulation must have good insulation characteristics, be easy to use, be age resistant, and must not easily absorb moisture.
Fig. 17b
Drain hose insulation and vinyl tie (supplied)
Drain hose and hose band (supplied)
Drain pipe and insulation (not supplied)
Vinyl tie (supplied)
Flare insulation
The procedure used for installing the insulation for both wide and
narrow tubes are the same.
Refrigerant tubing and insulation (not supplied)
Insulation tape
Fig. 17c
Never grasp the drain or refrigerant connecting out­lets when moving the unit.
17
Page 19
CAUTION
3-7. Taping the Tubes
NOTE
Clamp
Insulated tubes
Apply putty here
Tubing
CAUTION
After a tube has been insulated, never try to bend it into a narrow curve, as this may cause the tube to break or crack.
(1) At this time, the 2 refrigerant tubes (and electrical wire
if local codes permit) should be taped together with armoring tape. The drain hose may also be included and taped together as 1 bundle with the tubing.
(2) Wrap the armoring tape from the bottom of the outdoor
unit to the top of the tubing where it enters the wall. As you wrap the tubing, overlap half of each previous tape turn. (Fig. 18)
(3) Clamp the tubing bundle to wall, using 1 clamp approx.
every 47" (120 cm).
Do not wind the armoring tape too tightly, since this will decrease the heat insulation effect. Also, be sure the con­densation drain hose splits away from the bundle and drips clear of the unit and the tubing.
Fig. 18
Fig. 19
3-8. Finishing the Installation
After finishing insulating and taping over the tubing, use sealing putty to seal off the hole in the wall to prevent rain and draft from entering. (Fig. 19)
4. Air Purging
Air and moisture remaining in the refrigerant system have undesirable effects as indicated below. Therefore, they must be purged completely.
G pressure in the system rises
G operating current rises
G cooling efficiency drops
G moisture in the air may freeze and block capillary tubing
G water may lead to corrosion of parts in the refrigerant
system
Air Purging with a Vacuum Pump
I
(for Test Run)
G In order to protect the earth’s environment, be sure to use
a vacuum pump to perform the air purge. (Never perform an air purge by using the refrigerant gas cylinder or other external gas, or by using the gas inside the outdoor unit.)
Service valve on narrow tube side
Service valve on wide tube side
With push-pin
D C
B A
Hex wrench
Manifold gauge (special for R410A)
Low-pressure valve
Leave the valve open.
Open
Charging hose (special for R410A)
High-pressure valve
Vacuum pump adapter
HiLo
(for preventing reverse flow) (special for R410A)
Vacuum pump
Fig. 20
In order to prevent charging errors with the air conditioner that uses R410A, the screw diameter at the service valve charging port has been changed. When recharging or performing other servicing, use the special charging hose and manifold gauge.
18
Page 20
Cap tightening torque: 170 – 215 lbs·in (200 – 250 kgf·cm) (Tighten by hand, then use a wrench to turn approximately 45°.)
Stopper
Spindle
Service port Screw diameter: 1/2 UNF 20 threads
Valve core
Cap nut tightening torque: 60 – 95 lbs·in (70 – 110 kgf·cm) (Tighten by hand, then use a wrench to turn approximately 30 .)
<Structure of service valve on wide tube side>
NOTE
CAUTION
CAUTION
Perform the air purge for tubes A, B, C, and D. Use the same
CAUTION
CAUTION
procedures for all tubes.
(1) Check that each tube (both narrow and wide tubes)
between the indoor and outdoor units have been proper­ly connected and all wiring for the test run has been completed. Note that both narrow and wide tube service valves on the outdoor unit are kept closed at this stage.
(2) Using an adjustable wrench or box wrench, remove the
valve caps from the service valve on both narrow and wide tubes.
(3) Connect a vacuum pump and a manifold valve (with
pressure gauges) to the service port on the wide tube service valve. (Fig. 20).
Before using the vacuum pump adapter, read the vacuum pump adapter manual, and use the adapter correctly.
External diameter of service port R410A: 5/16"
Fig. 21
Be sure to use a manifold valve for air purging. If it is not available, use a stop valve for this purpose. The “Hi” knob of the manifold valve must always be kept closed.
G When using a hex wrench to open the spindle, an
extremely small amount of refrigerant may leak. This does not indicate a problem.
G Use a hex wrench of a type to which force can be
easily applied.
(4) With the “Lo” knob of the manifold valve open and high-pressure valve (“Hi”) closed completely, run the vacuum pump.
Run the pump until the pressure is –101 kPa (–76 cmHg). The operation time for the vacuum pump varies with tubing length and the capacity of the pump. The following table shows the amount of time required for evacuation:
Table 5
Required time for evacuation when capacity
of 100 liter/h vacuum pump is used
20 min. or more
NOTE
The required time in Table 5 is calculated based on the assumption that the ideal (or target) vacuum condition is around 10 mmHg abs.
(5) With the vacuum pump still running, close the “Lo” knob of the manifold valve. Then stop the vacuum pump. Fully
close the low-pressure valve and stop the vacuum pump. (Wait 1 – 2 minutes and check that the manifold gauge pointer does not return. If it does return, find and repair the leak, then apply the vacuum again.)
(6) With a hex wrench, turn the valve stem on the narrow tube service valve counter-clockwise by 90 degrees (1/4 turn)
for 10 seconds, and then turn the stem clockwise to close it again.
Be sure to completely insert the hex wrench before attempting to turn the valve.
(7) With a standard screwdriver, turn the wide tube service valve stem counterclockwise to fully open the valve. (8) Turn the narrow tube service valve stem counter-clockwise to fully open the valve. (9) Loosen the vacuum hose connected to the wide tube service port slightly to release the pressure. Then, remove
(10) Leak test all joints at the tubing (both indoor and outdoors) with liquid soap. Bubbles indicate a leak. Be sure to wipe
the hose.
off the soap with a clean cloth.
If a CFC gas detector is used, use a
special detector for HFC refrigerant (such as R410A and R134a).
19
Page 21
(11) Replace the flare nut on the wide tube service port and fasten the flare nut securely with an adjustable wrench or
box wrench. Next, mount the valve cap and tighten it with a torque wrench (the cap needs to be tightened with the torque of 180 lbs·in (200 kgf·cm)). This process is very important to prevent gas from leaking from the system.
(12) Test run the air conditioner. (See page 25.)
(13) While the air conditioner is running, apply liquid soap to check for any gas leaks around the service valves or caps.
(14) If there is no leakage, stop the air conditioner.
(15) Wipe off the soap on the tubing.
This completes air purging with a vacuum pump and the air conditioner is ready for actual operation.
I Pump Down
In order to protect the earth’s environment, be sure to perform pump-down to recover refrigerant
gas without releasing it into the atmosphere.
G When relocating or disposing of the air conditioner, request this
service from the dealer where the unit was purchased, or from an appropriate agent. Perform pump-down as described below.
What is pump-down?
G Pump-down refers to recovering the refrigerant gas from the refrig-
erant cycle at the outdoor unit. This work must be performed dur­ing cooling operation. The refrigerant gas cannot be recovered during heating operation.
G During winter, or if the temperature sensor prevents cooling opera-
tion, perform “forced cooling operation.”
Pump-down procedure
(1) Fully close the spindles at the valves on the narrow tube side of
tubes A, B, C and D. (Refer to Fig. 22.)
(2) Connect the manifold gauge to the charging port at the valve on
the wide tube side of tube D. Purge the air from the charging hose. (Refer to Fig. 23.)
(3) Perform cooling operation or forced cooling operation.
When the pressure at the low-pressure side is 0.05 – 0.1 MPaG (0.5 – 1 kg/cm
2
G), fully close the spindles at the valves on the wide tube side of tubes A, B, C, and D, and immediately stop operation. (Refer to Fig. 23.) In the winter, the outdoor unit may stop after 5 - 10 minutes of operation. This is in order to protect the indoor unit heat exchanger from freezing and does not indicate a problem.
Narrow tube side
Charging port
Wide tube side
Charging hose
Cap
Close
D
Close
C
Close
B
Close
A
Fig. 22
D
C
B
A
Manifold gauge
Fig. 23
(4) Disconnect the manifold gauge and the inter-unit tubes, and
attach the caps and flare nuts. At this point, pump-down is com­pleted. (If the caps and flare nuts are not reattached, there is the danger of gas leakage.) (Refer to Fig. 24.)
If pump-down is not possible
If the air conditioner cannot be operated because of a malfunction or other cause, use a refrigerant recovery device to recover the refrigerant.
20
Cap
Cap
Cap
After disconnecting the inter-unit tubes, attach the flare nuts with flare bonnets.
Fig. 24
Page 22
5. Wiring Instructions
5-1. General Precautions on Wiring
(1) Before wiring, confirm the rated voltage of the unit as
shown on its nameplate, then carry out the wiring closely following the wiring diagram.
(2) Provide a power outlet to be used exclusively for each
unit, with a power supply disconnect and circuit break­er for overcurrent protection provided in the exclusive line.
(3) To prevent possible hazard due to insulation failure,
the unit must be grounded.
(4) Each wiring connection must be done tightly and in
accordance with the wiring system diagram. Wrong wiring may cause the unit to misoperate or become damaged.
(5) Do not allow wiring to touch the refrigerant tubing,
compressor, or any moving parts of the fan.
(6) Unauthorized changes in the internal wiring can be
very dangerous. The manufacturer will accept no responsibility for any damage or misoperation that occurs as a result of such unauthorized changes.
5-2. Recommended Wire Length and Diameter
Regulations on wiring diameter differ from locality to locality. For field wiring requirements, please refer to your local elec­trical codes. Carefully observe these regulations when car­rying out the installation. Table 6 shows maximum wire lengths for control line and power line and fuse or circuit capacity.
NOTE
Refer to the wiring system diagram (Fig. 25a or 25b) for the meaning of (A), (B), and (C) in Table 6.
Refer to your local codes or in the absence of local codes see the National Electric Code: ANSI/NFPA70.
Table 6
AWG
Model
CM1972A 85 (Max.) 82 (Max.) 20 A
CM2472A 85 (Max.) 82 (Max.) 20 A
CM3172A 85 (Max.) 100 (Max.) 20 A
Max. Power Line Length (ft.)
(A)
(#12) (#14)
Max. Control Line Length (ft.)
(B) (C)
Fuse
or
Circuit Capacity
# ... AWG (American Wire Gauge)
21
Page 23
WARNING
G Be sure to comply with local codes on running the
CAUTION
WARNING
CAUTION
wire from the indoor unit to the outdoor unit (size of wire and wiring method, etc.).
G Each wire must be firmly connected. G No wire should be allowed to touch refrigerant
tubing, the compressor, or any moving part.
G Be sure to connect power wires correctly match-
ing up numbers on terminals of the outdoor unit and respective indoor units A – D.
G Be sure to connect the power supply line to the
outdoor unit as shown in the wiring diagram. The indoor unit draws its power from the outdoor unit.
G Do not run wiring for antenna, signal, or power
lines of television, radio, stereo, telephone, secu­rity system, or intercom any closer than 3'4" (1 m) from the power cable and wires between the indoor and outdoor units. Electrical noise may affect the operation.
5-3. Wiring System Diagram
G To avoid the risk of electric shock, each air
conditioner unit must be grounded.
G For the installation of a grounding device, please
observe local electrical codes.
G Grounding is necessary, especially for units using
inverter circuits, in order to release charged electricity and electrical noise caused by high tension. Otherwise, electrical shock may occur.
G Place a dedicated ground more than 7' (2 m) away
from other grounds and do not have it shared with other electric appliances.
NOTE
*
Disconnect switch may be required by national or local codes.
Always comply with national and local code requirements.
(A)
INDOOR UNIT
*
(B)
INDOOR UNIT
*
(C)
INDOOR UNIT
3 indoor units with CM1972A
Disconnect
*
switch Field supply
230/208V
(C)
Grounding line
230/208V
230/208V
230/208V
(C)
Grounding line
230/208V
230/208V
(C)
Grounding
(B)
230/208V
(B)
(B)
(B)
line
230/208V
230/208V
1
2
3
Terminal
Disconnect switch
1
2
3
TerminalTerminal
Disconnect switch
1
2
3
Field supply
Field supply
Fig. 25a
OUTDOOR UNIT
Te r mi n a l(9P
(B)
(B)
1
2
3
4
5
6
7
8
9
Terminal
(2P)
)
UNIT A
UNIT B
UNIT C
1
2
(A)
Power supply
Single-phase 230/208VAC 60HZ
L1
L2
Grounding line
(A)
INDOOR UNIT
(B)
INDOOR UNIT
(C)
INDOOR UNIT
(D)
INDOOR UNIT
4 indoor units with CM2472A, CM3172A
Disconnect
*
switch
Field supply
1
2
3
Terminal
1
2
3
Terminal
1
2
3
Terminal
Disconnect switch
*
Field supply
1
2
3
Terminal
(C)
Grounding line
Disconnect
*
switch Field supply
(C)
Grounding line
Disconnect switch
*
(Inter-unit) power line
230/208V
230/208V
(C)
230/208V
Grounding line
230/208V
230/208V
(C)
Grounding line
230/208V
230/208V
230/208V
230/208V
230/208V
230/208V
Field supply
230/208V
OUTDOOR UNIT
Terminal(12P
(B)
(B)
(B)
(B)
(B)
(B)
(B)
(B)
1
2
3
4
5
6
7
8
9
10
11
12
)
2P
(
Terminal
)
UNIT A
UNIT B
UNIT C
UNIT D
1
2
(A)
Power supply
Single-phase 230/208VAC 60HZ
L1
L2
Grounding line
Fig. 25b
22
Page 24
Screw and special washer
Ring connector
Wire
WARNING
5-4. How to Connect Wiring to the Terminal
Loose wiring may cause the terminal to overheat or result in unit malfunction. A fire hazard may also exist. There­fore, be sure all wiring is tightly connected.
When connecting each power wire to the corresponding terminal, follow the instructions “How to connect wiring to the terminal” and fasten the wire securely tight with the fixing screw of the terminal plate.
How to connect wiring to the terminal
a) For Indoor Unit
(1) Cut the wire end with a cutting pliers, then strip the
insulation to expose the wire about 9/32" (7 mm). See the label (Fig. 26) near the terminal plate.
(2) Using a screwdriver, loosen the terminal screw on
the terminal plate.
STRIP SIZE
9/32"
(7 mm)
Fig. 26
Solid wire
(ACTUAL
SIZE)
Loop
(3) Insert the wire and tighten the terminal screw com-
pletely using a screwdriver.
b) For Outdoor Unit
I For solid core wiring (or F-cable)
(1) Cut the wire end with a cutting pliers, then strip the
insulation to expose the solid wire about 15/16" (25 mm). (Fig. 27)
(2) Using a screwdriver, remove the terminal screw(s)
on the terminal plate.
(3) Using the pliers, bend the solid wire to form a loop
suitable for the terminal screw.
(4) Shape the loop wire properly, place it on the termi-
nal plate and fix it securely with the removed termi­nal screw using a screwdriver.
I For stranded wiring
(1) Cut the wire end with a cutting pliers, then strip the
insulation to expose the stranded wiring about 3/8" (10 mm) and tightly twist the wire ends. (Figs. 28 and 29)
(2) Using a screwdriver, remove the terminal screw(s)
on the terminal plate.
(3) Using a ring connector fastener or pliers, securely
clamp each stripped wire end with a ring connector. (Fig. 28)
Wire
Special washer
Strip 15/16" (25 mm)
Insulation
Fig. 27
Stranded wire
Strip 3/8" (10 mm)
Fig. 28
Twist wire ends
Fig. 29
Screw
Ring connector
Te r mi nal plate
Ring connector
(4) Place the ring connector wire, and replace and
tighten the removed terminal screw using a screw­driver. (Fig. 30)
Fig. 30
23
Page 25
5-5. Wiring Instructions for the Outdoor Unit
CAUTION
G Be sure to correctly align inter-unit cables A, B, C and D.
Outdoor unit
Terminal board
1 2
Indoor unit A
A is the indoor unit with refrigerant tubing that is connected to service valve A (bottom) of the outdoor unit.
Terminal board
Indoor unit B
B is the indoor unit with refrigerant tubing that is connected to service valve B (second from the bottom) of the outdoor unit.
Terminal board
1 2 3 4 5 6 7 8 9 10 11 12
Power supply (conduit)
Power: Single-phase, 230/208VAC 60HZ
Power breaker (not provided)
Ground
Power cable (not provided) Inter Unit (conduit)
3
2
1
Label A
A
Inter-unit cables #14 (not provided)
3
2
1
Label B
B
Inter-unit cables #14 (not provided)
Inter-unit cables #14 (not provided)
Inter Unit (conduit)
Label D
D
Inter-unit cables #14 (not provided)
Label C
C
(#12: Less than 85 ft.)
Indoor unit D
D is the indoor unit with refrigerant tubing that is connected to service valve
3
2
1
D (top) of the outdoor unit.
Indoor unit C
C is the indoor unit with refrigerant tubing that is connected to service valve
3
2
1
C (third from the bottom) of the outdoor unit.
Terminal board
Terminal board
Be sure to perform grounding.
Attach a ground wire to either the outdoor unit or indoor unit. If there is a grounding terminal inside the room, use the grounding screw inside the indoor unit.
G Use a dedicated air conditioner circuit for power. G To make connections to the outdoor unit, remove the inspection panel and tubing panel. G Do not bring the inter-unit cables or power cable into contact with tubing or service valves. G Use outdoor unit cable fasteners and fasten the inter-unit cables at the location where the cables are double-
sheathed.
G Arrange the wiring so that the inter-unit cables are contained in the inspection panel and tubing panel, as shown in
Fig. 31.
Be sure to apply the provided labels to both ends of the inter-unit cables to prevent mis­wiring. The units will not function if the wiring connections are incorrect.
# ... AWG (American Wire Gauge)
Fig. 31
24
Page 26
Regulations on wire size differ from locality to locality. For
CAUTION
Conduit plate
Make sure there is no gap between access panel “C” and the conduit plate.
Access panel C
CAUTION
field wiring requirements, please refer to your local electri­cal codes. Make sure that the installation fully complies with all local and national regulations.
(1) Remove access panel “C”. (Fig. 32)
(2) Connect the inter-unit and power supply line accord-
ing to the drawing on the panel side.
(3) Be sure to size each wire allowing approx. 4"
(10 cm) longer than the required length for wiring. Store excess wiring inside the cabinet.
(4) When connections are completed, check that all con-
nections are correct as shown in the wiring system diagram on panel side.
(5) Be sure to ground the unit according to your local
codes.
6. Test Run
Performing a test run
G Refer to the test run procedures in the indoor unit
installation manual.
G Perform the test run separately for each connected
indoor unit. If 2 units are operated simultaneously, it is not possible to correctly check for errors in tubing and wiring.
Terminal block
Conduit plate
Plug
Lock nut
Inter unit (Conduit)
Cabinet
Access panel “C”
Power supply (Conduit)
Fig. 32
Checking tubing and wiring
Perform the test run and check that operation is normal. If there is an error in tubing or wiring, the refrigerant may flow to indoor unit B when indoor unit A is operated (for example).
G Stop operation immediately if there is an error in tubing
or wiring. Turn the power (breaker) to OFF, and check whether the inter-unit cables are connected incorrectly, or whether the narrow tubes A and B are connected in reverse. Correct the connections.
G If there is an error in tubing, pump-down must be per-
formed. Be sure to perform pump-down. After making corrections, again purge the air from the tubes.
Fig. 33
25
Page 27
7. Connecting a Home Automation device
The HA (white) 4P terminal is located on the indoor unit PCB. If a HA device will be used, connect it to this terminal.
8. Installation Check Sheet
The strength of the installation location is sufficient to support the air conditioner weight.
The indoor and outdoor units are installed level and vertically.
The power and voltage are as specified.
Inter-unit cables are securely fastened to the terminal board.
Inter-unit cables are securely fixed.
The power cable and inter-unit cables are not connected anywhere along their paths.
The ground wire is securely connected.
An air purge of the refrigerant circuit has been conducted.
A leak test of the tubing connections has been performed.
Thermal insulation has been applied to the tubing connections.
Drain connections are secure and water drains properly.
Putty has been used to close the hole in the wall.
All service valves are fully open.
Remote controller signals are being positively received.
26
Loading...