INDOOR MODEL No.PRODUCT CODE No.OUTDOOR MODEL No.PRODUCT CODE No.
XS4232854 016 10
TS4232854 016 09
Indoor UnitOutdoor Unit
C4232854 016 12
CL4232854 016 11
C4232854 016 12
CL4232854 016 11
FILE NO.
XS4232C4232
CL4232
TS4232
85464869178000REFERENCE NO. SM830078
Important
Please Read Before Starting
This air conditioning system meets strict safety and operating
standards. As the installer or service person, it is an important
part of your job to install or service the system so it operates
safely and efficiently.
For safe installation and trouble-free operation, you must :
ⓦ Carefully read this instruction booklet before beginning.
ⓦ Follow each installation or repair step exactly as shown.
ⓦ Observe all local, state, and national electrical codes.
ⓦ Pay close attention to all warning and caution notices
given in this manual.
This symbol refers to a hazard or
unsafe practice which can result in
severe personal injury or death.
This symbol refers to a hazard or
CAUTION
unsafe practice which can result in
personal injury or product or
property damage.
If Necessary, Get Help
These instructions are all you need for most installation sites
and maintenance conditions. If you require help for a special
problem, contact our sales/service outlet or your certified dealer
for additional instructions.
In Case of Improper Installation
The manufacturer shall in no way be responsible for improper
installation or maintenance service, including failure to follow
the instructions in this document.
SPECIAL PRECAUTIONS
When Wiring
……………………………………………………………………
ELECTRICAL SHOCK CAN CAUSE SEVERE
PERSONAL INJURY OR DEATH. ONLY A
QUALIFIED, EXPERIENCED ELECTRICIAN
SHOULD ATTEMPT TO WIRE THIS SYSTEM.
• Do not supply power to the unit until all wiring and tubing are
completed or reconnected and checked.
• Highly dangerous electrical voltages are used in this system.
Carefully refer to the wiring diagram and these instructions
when wiring. Improper connections and inadequate grounding can cause accidental injury or death.
• Ground the unit following local electrical codes.
• Connect all wiring tightly. Loose wiring may cause overheating at connection points and a possible fire hazard.
When Transporting
……………………………………………………………………
Be careful when picking up and moving the indoor and outdoor
units. Get a partner to help, and bend your knees when lifting to
reduce strain on your back. Sharp edges or thin aluminum fins
on the air conditioner can cut your fingers.
When Installing
……………………………………………………………………
…In a Room
Properly insulate any tubing run inside a room to prevent
“sweating” that can cause dripping and water damage to walls
and floors.
…In Moist or Uneven Locations
Use a raised concrete pad or concrete blocks to provide a
solid, level foundation for the outdoor unit. This prevents water
damage and abnormal vibration.
…In an area with High Winds
Securely anchor the outdoor unit down with bolts and a metal
frame. Provide a suitable air baffle.
…In a Snowy Area (for Heat Pump-type Sys-tems)
Install the outdoor unit on a raised platform that is higher than
drifting snow. Provide snow vents.
When Connecting Refrigerant Tubing
……………………………………………………………………
• Ventilate the room well, in the event that refrigerant gas
leaks during the installation. Be careful not to allow contact
of the refrigerant gas with a flame as this will cause the
generation of poisonous gas.
• Keep all tubing runs as short as possible.
• Use the flare method for connecting tubing.
• Apply refrigerant lubricant to the matching surfaces of the
flare and union tubes before connecting them, then tighten
the nut with a torque wrench for a leak-free connection.
• Check carefully for leaks before starting the test run.
NOTE
Depending on the system type, liquid and gas lines may be
either narrow or wide. Therefore, to avoid confusion the
refrigerant tubing for your particular model is specified as either
“narrow” or “wide” rather than as “liquid” or “gas”.
When Servicing
……………………………………………………………………
• Turn the power OFF at the main power box (mains) before
opening the unit to check or repair electrical parts and
wiring.
• Keep your fingers and clothing away from any moving parts.
• Clean up the site when installation is finished. Check that no
metal scraps or bits of wiring have been left inside the unit.
CAUTION
• Ventilate any enclosed areas when installing or testing the
refrigeration system. Contact of refrigerant gas with fire or
heat can produce poisonous gas.
• Confirm after installation that no refrigerant gas is leaking. If
the gas comes in contact with a burning stove, gas water
heater, electric room heater or other heat source, it can
cause the generation of poisonous gas.
– 2 –
SM830078
Table of Contents
1.OPERATING RANGE ....................................................................................... 5
(2) A Sensor is Defective................................................................................ 61
(3) Operation of Major Electrical Parts ........................................................... 61
(4) Checking the Electrical Components ........................................................ 62
– 3 –
SM830078
Introduction:
This manual will help you understand and service the air conditioner. To help you find the information you need,
we have divided it into 5 main sections. Each section is divided into chapters with charts, tables and explanations to help you find and repair problems.
❑Section 1: Specifications, tells you about the physical and electrical make up of the unit, as well
as its heating and cooling capacities. Look in this section to find the correct values for
components and functions.
❑Section 2: Processes and Functions, explains each different part of the cooling and heating
cycle, and how each control function reacts to changing conditions to keep the room at the set
temperature range.
❑Section 3: Electrical Data, which has fold-out schematic and wiring diagrams so you can find
the parts you need to check when something is wrong, and see how they should be connected.
❑Section 4: Service Procedures, has two main parts, a
specific component to replace or adjust, and a chapter with specific procedures and values to
guide you in checking the electrical components in the unit.
Read Me First!
diagnostic
chapter to help you find the
HOW TO USE THIS MANUAL
You can use this manual both as a
construction of this unit, and as a source of information to help you set up and maintain the unit.
When this unit is not working properly, and the cause is not known, you can use the procedures in
Section 3: Servicing Procedures to find the problem, fix it, and restore the unit to its proper functioning.
This air conditioner has many helpful self diagnostic features to help you identify problem areas quickly.
So you will be ready when a problem happens, we suggest you look this manual over and become familiar with it
by following these steps:
1.Look at the TABLE OF CONTENTS to get an idea of what is in this manual and where to find it.
2.Look at the chapter about TROUBLE SHOOTING, so you are familiar with the way the flow
charts work. They are designed to guide you quickly through the possible causes for each kind of
problem that is likely to happen to the Unit. Particularly read the introduction to this section, and
the parts about the self-diagnosis and error codes which show on the display.
3.Look at the chapter about CHECKING ELECTRICAL COMPONENTS. You already know
about most of these procedures. This chapter gives you the specific values and methods for
these components. If you don’t know some of these procedures, you can easily learn them here.
4.Read the Instruction Manual! The Instruction Manual is included here because it helps you help
the user to set the temperature controls properly and know how to take care of any simple
problems that may happen, as well as know when to call for service. The Instruction Manual also
has illustrations, care, and installation information not found in the rest of the service manual. It is
short, and if you read it carefully, you will be able to answer the customers questions easily, and
also know the most efficient ways for setting times and temperatures.
reference
to find specific information about the capacity, functions and
Please use this manual to make your work easier, keep the air conditioner functioning well, and keep your
customers satisfied.
– 4 –
SM830078
1. OPERATING RANGE
XS4232, TS4232 / C4232
TemperatureIndoor Air Intake Temp.Outdoor Air Intake Temp.
Maximum95 °F DB / 71 °F WB115 °F DB
Minimum67 °F DB / 57 °F WB 67 °F DB
XS4232, TS4232 / CL4232
TemperatureIndoor Air Intake Temp.Outdoor Air Intake Temp.
Maximum95 °F DB / 71 °F WB115 °F DB
Minimum67 °F DB / 57 °F WB 0 °F DB
– 5 –
SM830078
2. SPECIFICATIONS
(1)Unit Specifications
MODEL No.Indoor UnitXS4232
POWER SOURCE230 - 208 V / 1 Phase / 60 Hz
PERFORMANCECooling
CapacityBTU / h42,00040,500
Air circulation (Hi)
Moisture removal (High)Pints / h14.614.8
ELECTRICAL RATINGS
Voltage ratingVAC230208
Available voltage rangeVAC187 - 253
Running amperes*A20.821.1
Max. running amperes**A24.125.3
Power inputW4,2304,120
Power factor%8894
S.E.E.R
Max. starting amperesA134134
Maximum fuse sizeA50
FEATURES
ControlsMicroprocessor
TimerON / OFF 24-hours & Program
Fan speed Indoor / Outdoor3 and Automatic control / 2 (Auto)
Air deflectionHorizontal / Vertical– / Automatic
Air filterWashable, easy access, long life (2,500 hr)
Remote controller (Accessory)RCS - 5PS4U
Refrigerant controlCapillary tube
Refrigerant tubing connectionsFlare type
Drain pump / Drain pipe trade sizeMax. head 9-27/32 in. above drain connection / 3/4 in. (26.7 mm)
CompressorScroll
Operation sound
REFRIGERANT TUBING
Limit of tubing lengthft. (m)165 (50)
Limit of tubing length at shipmentft. (m)50 (15)
Limit of elevation differenceft. (m)Outdoor unit is higher than indoor unit: 165 (50)
between the two unitsOutdoor unit is lower than indoor unit: 100 (30)
Refrigerant tubeNarrow tubein. (mm)3 / 8 (9.52)
Rating conditions (*): Indoor air temperature 80 °F DB / 67 °F WB, Outdoor air temperature 95 °F DB / 75 °F WB
Full load conditions (**): Indoor air temperature 80 °F DB / 67 °F WB, Outdoor air temperature 115 °F DB
– 6 –
SM830078
2. SPECIFICATIONS
(1)Unit Specifications
MODEL No.Indoor UnitXS4232
POWER SOURCE230 - 208 V / 1 Phase / 60 Hz
PERFORMANCECooling
CapacityBTU / h42,00040,500
Air circulation (Hi)
Moisture removal (High)Pints / h14.614.8
ELECTRICAL RATINGS
Voltage ratingVAC230208
Available voltage rangeVAC187 - 253
Running amperes*A20.821.1
Max. running amperes**A24.125.3
Power inputW4,2304,120
Power factor%8894
S.E.E.R
Max. starting amperesA134134
Maximum fuse sizeA50
FEATURES
ControlsMicroprocessor
Low ambient controlBuilt-in 0 °F
TimerON / OFF 24-hours & Program
Fan speed Indoor / Outdoor3 and Automatic control / 3 (Auto)
Air deflectionHorizontal / Vertical– / Automatic
Air filterWashable, easy access, long life (2,500 hr)
Remote controller (Accessory)RCS - 5PS4U
Refrigerant controlCapillary tube
Refrigerant tubing connectionsFlare type
Drain pump / Drain pipe trade sizeMax. head 9-27/32 in. above drain connection / 3/4 in. (26.7 mm)
CompressorScroll
Operation sound
REFRIGERANT TUBING
Limit of tubing lengthft. (m)165 (50)
Limit of tubing length at shipmentft. (m)50 (15)
Limit of elevation differenceft. (m)Outdoor unit is higher than indoor unit: 165 (50)
between the two unitsOutdoor unit is lower than indoor unit: 100 (30)
Refrigerant tubeNarrow tubein. (mm)3 / 8 (9.52)
Rating conditions (*): Indoor air temperature 80 °F DB / 67 °F WB, Outdoor air temperature 95 °F DB / 75 °F WB
Full load conditions (**): Indoor air temperature 80 °F DB / 67 °F WB, Outdoor air temperature 115 °F DB
– 7 –
SM830078
2. SPECIFICATIONS
(1)Unit Specifications
MODEL No.Indoor UnitTS4232
Outdoor UnitC4232
POWER SOURCE230 - 208 V / 1 Phase / 60 Hz
PERFORMANCECooling
CapacityBTU / h42,00040,500
kW12.3211.88
Air circulation (Hi)
Moisture removal (High)Pints / h14.814.6
ELECTRICAL RATINGS
Voltage ratingVAC230208
Available voltage rangeVAC187 - 253
Running amperes*A20.621.0
Max. running amperes**A21.422.7
Power inputW4,1904,100
Power factor%8894
S.E.E.R
Max. starting amperesA134134
Maximum fuse sizeA50
FEATURES
ControlsMicroprocessor
TimerON / OFF 24-hours & Program
Fan speed Indoor / Outdoor3 and Automatic control / 2 (Auto)
Air deflectionHorizontal / VerticalManual / Automatic
Air filterWashable, easy access, long life (2,500 hr)
Remote controller (Accessory)RCS - 5PS4U
Refrigerant controlCapillary tube
Refrigerant tubing connectionsFlare type
Drain pipe trade size3 / 4 in. (26.7 mm)
CompressorScroll
Operation soundIndoor - Hi / Me / LodB - A42 / 40 / 35
REFRIGERANT TUBING
Limit of tubing lengthft.(m)165 (50)
Limit of tubing length at shipmentft.(m)50 (15)
Limit of elevation differenceft.(m)Outdoor unit is higher than indoor unit: 165 (50)
between the two unitsOutdoor unit is lower than indoor unit: 100 (30)
Refrigerant tubeNarrow tubein. (mm)3 / 8 (9.52)
Rating conditions (*): Indoor air temperature 80 °F DB / 67 °F WB, Outdoor air temperature 95 °F DB / 75 °F WB
Full load conditions (**) : Indoor air temperature 80 °F DB / 67 °F WB, Outdoor air temperature 115 °F DB
cu.ft. / min.
BTU / Wh
900800
10.210.3
DATA SUBJECT TO CHANGE WITHOUT NOTICE
– 8 –
SM830078
2. SPECIFICATIONS
(1)Unit Specifications
MODEL No.Indoor UnitTS4232
Outdoor UnitCL4232
POWER SOURCE230 - 208 V / 1 Phase / 60 Hz
PERFORMANCECooling
CapacityBTU / h42,00040,500
kW12.3211.88
Air circulation (Hi)
Moisture removal (High)Pints / h14.814.6
ELECTRICAL RATINGS
Voltage ratingVAC230208
Available voltage rangeVAC187 - 253
Running amperes*A20.621.0
Max. running amperes**A21.422.7
Power inputW4,1904,100
Power factor%8894
S.E.E.R
Max. starting amperesA134134
Maximum fuse sizeA50
FEATURES
ControlsMicroprocessor
Low ambient controlBuilt-in 0 °F
TimerON / OFF 24-hours & Program
Fan speed Indoor / Outdoor3 and Automatic control / 3 (Auto)
Air deflectionHorizontal / VerticalManual / Automatic
Air filterWashable, easy access, long life (2,500 hr)
Remote controller (Accessory)RCS - 5PS4U
Refrigerant controlCapillary tube
Refrigerant tubing connectionsFlare type
Drain pipe trade size3 / 4 in. (26.7 mm)
CompressorScroll
Operation soundIndoor - Hi / Me / LodB - A42 / 40 / 35
Outdoor - HidB - A56
REFRIGERANT TUBING
Limit of tubing lengthft.(m)165 (50)
Limit of tubing length at shipmentft.(m)50 (15)
Limit of elevation differenceft.(m)Outdoor unit is higher than indoor unit: 165 (50)
between the two unitsOutdoor unit is lower than indoor unit: 100 (30)
Refrigerant tubeNarrow tubein. (mm)3 / 8 (9.52)
Rating conditions (*): Indoor air temperature 80 °F DB / 67 °F WB, Outdoor air temperature 95 °F DB / 75 °F WB
Full load conditions (**) : Indoor air temperature 80 °F DB / 67 °F WB, Outdoor air temperature 115 °F DB
cu.ft. / min.
BTU / Wh
900800
10.210.3
DATA SUBJECT TO CHANGE WITHOUT NOTICE
– 9 –
SM830078
2. SPECIFICATIONS
(2)Major Component Specifications
(A)Indoor Unit
MODEL No.XS4232
Source230 - 208 V / 1 phase / 60 Hz
Remote controller (Accessory)RCS - 5PS4U
Controller P. C. B Ass'yCR - TS2432
Control circuit fuse250 V, 3 A
Switch Ass'ySW - X363GS
Fan (Number … diameter)in.(mm)Turbo (1…19-9/32 (490))
Fan motor
ModelSFG6X - 61A3P
Source230 - 208 V / 1 phase / 60 Hz
No. of pole … r.p.m. (230 V, High)rpm6 … 560
Nominal outputW60
Coil resistanceΩBRW - WHT:71.1,ORG - YEL:22.7
(Ambient temperature 68 °F)WHT - VLT:8.7,VLT - PNK:43.2
VLT - ORG :13.3,YEL - BLK: 54.32
Safety device
Operating temperatureOpen°F266± 14.4
Close°F174.2 ± 27
Run capacitorVAC,µF440 V , 6 µF
Heat exchanger
CoilAluminum plate fin / Copper tube
Rows … Fins per inch2 … 14.9
Face areaft.
Panel
Model No.PNR - XS3632
Indicator Lamp Ass'yIND - XS3632
Auto louver motorMT8 - 3C
Auto louver motor … RatedV, W, rpm240 VAC , 3 W , 3 rpm
Coil resistance (Ambient temperature 77 °F)Ω16,430 Ω± 8 %
2
(m2)5.17 (0.48)
DATA SUBJECT TO CHANGE WITHOUT NOTICE
– 10 –
SM830078
2. SPECIFICATIONS
(2)Major Component Specifications
(A)Indoor Unit
MODEL No.TS4232
Source230 - 208 V / 1 phase / 60 Hz
Remote controller (Accessory)RCS- 5PS4U
Controller P. C. B Ass'yCR - TS2432
Control circuit fuse250 V, 3 A
Switch Ass'ySW - X363GS
Fan (Number … diameter)in.(mm)Centrifugal (4 ... 5-29/32(150))
Fan motor
ModelKFG4X - 101C6P
Source230 - 208 V / 1 phase / 60 Hz
No. of pole … r.p.m. (230 V, High)rpm1,015
Nominal outputW100
Coil resistanceΩBRW - WHT:61.05,ORG - YEL:13.23
(Ambient temperature 68 °F)WHT - VLT:9.955 ,YEL - BLK:19.25
VLT - ORG :9.576 ,BLK - PNK: 10.81
Safety device
Operating temperatureOpen°F266± 14.4
Close°F174.2 ± 27
Run capacitorVAC,µF440 V , 4 µF
Heat exchanger
CoilAluminum plate fin / Copper tube
Rows … Fins per inch3 … 14.9
Face areaft.
Auto louver motor
Model No.MT8 - 3C
Auto louver motor … RatedV, W, rpm240 VAC , 3 W , 3 rpm
Coil resistance (Ambient temperature 77 °F)Ω16,430 Ω± 8 %
2
(m2)3.51 (0.326)
DATA SUBJECT TO CHANGE WITHOUT NOTICE
– 11 –
SM830078
2. SPECIFICATIONS
(2)Major Component Specifications
(B)Outdoor Unit
MODEL No.C4232
Source230 - 208 V / 1 phase / 60 Hz
CompressorScroll (Hermetic)
ModelZR47KC - PFV
Source230 - 208 V / 1 phase / 60 Hz
Nominal outputW4,270
Compressor oilcc1,240
Coil resistance (Ambient temperature 77 °F)ΩR - W : 0.475 , S - W : 1.850
Safety deviceInternal type
Air intake grille
Air outlet
Refrigerant liquid line (ø3/8")
Refrigerant gas line (ø3/4")
Drain connection
Power supply entry
For discharge duct
Humidifier (option) mounting hole
Suspension bolt mounting
– 18 –
1813_X_S
SM830078
3. DIMENSIONAL DATA
Drain connection
Drain connection for left side
Refrigerant liquid line (3/8") Flare connection
Refrigerant gas line (3/4") Flare connection
Hole for rear side refrigerant tubing
Hole for through-the-wall refrigerant tubing (ø3-15/16" hole)
Hole for fresh air intake (Knockout hole)
Hole for right side refrigerant tubing (Knockout hole)
Hole for left side drain connection (Knockout hole)
Hole for power supply (Conduit size 1/2")
Infrared rays receiver for wireless remote controller
Cutting position for fresh air intake
1341_TS_I
Dimension : inch
Air intake
Air outlet
2 ft. or more
Hole for wall-through piping (View from front)
2-13/3223/32
9-7/8
6-25/32
9-7/16
8-7/16
62
26-3/8
11-1/32
12-7/32
61-7/32
7-3/4
12-19/32 6-5/16
5-15/16
• Remote controller (Accessory)
5-1/2
7-3/4
6-11/16
4-1/2
7-1/4
7-3/4
1-3/326-5/16
3-5/324-3/4
5-3/4
7-7/32
4-1/16
9-7/8
5-9/16
1-3/859-1/4 (Suspension bolt hole pitch)
3-1/2
5-25/32
2-25/325-3/16
11-1/32
3-15/161-31/32
3-3/8
6-3/327-31/32
Front
(Service space)(Service space)
Holes in the rear side (View from front)
(Suspension bolt hole pitch)
10
or more
10
or more
(1)Indoor Unit: TS4232
– 19 –
SM830078
3. DIMENSIONAL DATA
(2)Outdoor Unit: C4232, CL4232
1-31/321-31/32
4-21/64266-11/16
1-3/16
13-3/8
48-5/8
37
15-3/4
14-31/3213/32
22-27/32
23-29/32
– 20 –
Dimension : inch
Hole for anchor bolt (4-ø13)
Refrigerant tube joint (narrow tube)
Flare connection 3/8 in (9.52 mm)
Refrigerant tube joint (wide tube)
Flare connection 3/4 in (19.05 mm)
Refrigerant tubing inlet
Power supply inlet
1342_C_S
SM830078