Sanyo C3682, KS3682, C3082, KS3082 User Manual

Contents
Page
IMPORTANT!
Please Read Before Starting .................................. 2
1. GENERAL .......................................................... 3
1-1. Tools Required for Installation (not supplied) 1-2. Accessories Supplied with Unit 1-3. Optional Copper Tubing Kit 1-4. Type of Copper Tube and Insulation Material 1-5. Additional Materials Required for Installation
2. INSTALLATION SITE SELECTION ................... 4
2-1. Indoor Unit 2-2. Outdoor Unit
3. HOW TO INSTALL THE INDOOR UNIT ............ 12
3-1. Remove the Rear Panel from the Unit 3-2. Make a Hole 3-3. Install the Rear Panel on the Wall 3-4. Removing and Installing the Grille 3-5. Shape the Indoor Side Tubing 3-6. Wiring Instructions 3-7. Wire Size and Length 3-8. Wiring Instructions for Inter-unit Connections 3-9. Mounting 3-10. Frame Fastening Method 3-11. Drain Hose
4. HOW TO INSTALL THE OUTDOOR UNIT ........ 22
4-1. Wiring Instructions for the Outdoor Unit 4-2. Routing the Tubing and Wiring
5. REFRIGERANT TUBING .................................. 23
5-1. Use of the Flaring Method 5-2. Flaring Procedure with a Flare Tool 5-3. Caution before Connecting Tubes Tightly 5-4. Connecting Tubing between Indoor and
Outdoor Units 5-5. Insulation of Refrigerant Tubing 5-6. Taping the Tubes 5-7. Finishing the Installation
6. AIR PURGING................................................... 25
Air Purging with a Vacuum Pump (for Test Run)
Basic Functions of the Service Valves
Pump Down
Service Valve Connections
This air conditioner uses the new refrigerant R410A.
Refrigerant service valve size = 5/16"
85264190499000 © SANYO 2010
INSTALLATION INSTRUCTIONS
Model Combinations
Combine indoor and outdoor units only as listed below.
Indoor Unit Outdoor Unit
KS3082 C3082
KS3682 C3682
Power Source: 60 Hz, single-phase, 230/208 V
– Inverter Split System Air Conditioner –
COOL/ DRY Model
Be sure to read the yellow instruction sheet attached to the outdoor unit for models using the new refrigerant R410A.
The illustrations are based on the typical appearance of a standard model. Consequently, the shape may differ from that of the air conditioner that you are installing.
7. REMOTE CONTROL UNIT INSTALLATION
POSITION ......................................................... 29
7-1. Mounting on a Wall
8. ADDRESS SWITCH .......................................... 30
8-1. Address Setting of the Remote
Control Unit
SANYO North America Corporation In Canada Commercial Solutions Division SANYO Canada Inc. 2055 Sanyo Ave., San Diego 201 Creditview Road, Woodbridge CA 92154, U.S.A. Ontario, L4L 9T1, Canada
W
10-018 C3082-3682 2/15/10 11:50 AM Page a
NOTE
NOTE
2
IMPORTANT! Please Read Before Starting
This air conditioning system meets strict safety and operating standards. As the installer or service person, it is an important part of your job to install or service the system so it operates safely and efficiently.
For safe installation and trouble-free operation, you must:
Carefully read this instruction booklet before beginning.
Follow each installation or repair step exactly as shown.
Observe all local, state, and national electrical codes.
Pay close attention to all warning and caution notices given in this manual.
This symbol refers to a hazard or unsafe practice which can result in severe personal injury or death.
This symbol refers to a hazard or unsafe practice which can result in personal injury or prod­uct or property damage.
If Necessary, Get Help
These instructions are all you need for most installation sites and maintenance conditions. If you require help for a special problem, contact our sales/service outlet or your certified dealer for additional instructions.
In Case of Improper Installation
The manufacturer shall in no way be responsible for improp­er installation or maintenance service, including failure to follow the instructions in this document.
SPECIAL PRECAUTIONS
When Wiring
ELECTRICAL SHOCK CAN CAUSE SEVERE PERSONAL INJURY OR DEATH. ONLY A QUALIFIED, EXPERIENCED ELECTRICIAN SHOULD ATTEMPT TO WIRE THIS SYSTEM.
• Do not supply power to the unit until all wiring and tubing are completed or reconnected and checked.
• Highly dangerous electrical voltages are used in this system. Carefully refer to the wiring diagram and these instructions when wiring. Improper connections and inadequate grounding can cause accidental injury or
death.
• Ground the unit following local electrical codes.
• Connect all wiring tightly. Loose wiring may cause over­heating at connection points and a possible fire hazard.
When Transporting
Be careful when picking up and moving the indoor and out­door units. Get a partner to help, and bend your knees when lifting to reduce strain on your back. Sharp edges or thin alu­minum fins on the air conditioner can cut your fingers.
When Installing…
…In a Ceiling or Wall
Make sure the ceiling/wall is strong enough to hold the unit’s weight. It may be necessary to construct a strong wood or metal frame to provide added support.
…In a Room
Properly insulate any tubing run inside a room to prevent “sweating” that can cause dripping and water damage to walls and floors.
…In Moist or Uneven Locations
Use a raised concrete pad or concrete blocks to provide a solid, level foundation for the outdoor unit. This prevents water damage and abnormal vibration.
…In an Area with High Winds
Securely anchor the outdoor unit down with bolts and a metal frame. Provide a suitable air baffle.
…In a Snowy Area
Install the outdoor unit on a raised platform that is higher than drifting snow. Provide snow vents.
When Connecting Refrigerant Tubing
• Use the flare method for connecting tubing.
• Apply refrigerant lubricant to the matching surfaces of the flare and union tubes before connecting them, then tighten the nut with a torque wrench for a leak-free connection.
• Check carefully for leaks before starting the test run.
When Servicing
• Turn the power OFF at the main power box (mains) before opening the unit to check or repair electrical parts and wiring.
• Keep your fingers and clothing away from any moving parts.
• Clean up the site after you finish, remembering to check that no metal scraps or bits of wiring have been left inside the unit being serviced.
Others
• Ventilate any enclosed areas when installing or testing the refrigeration system. Escaped refrigerant gas, on contact with fire or heat, can produce dangerously toxic gas.
• Confirm upon completing installation that no refrigerant gas is leaking. If escaped gas comes in contact with a stove, gas water heater, electric room heater or other heat source, it can produce dangerously toxic gas.
WARNING
WARNING
CAUTION
CAUTION
10-018 C3082-3682 2/15/10 11:50 AM Page 2
3
1. General
This booklet briefly outlines where and how to install the air conditioning system. Please read over the entire set of instructions for the indoor and outdoor units and make sure all accessory parts listed are with the system before beginning.
1-1. Tools Required for Installation (not supplied)
1. Standard screwdriver
2. Phillips head screwdriver
3. Knife or wire stripper
4. Tape measure
5. Carpenter’s level
6. Sabre saw or key hole saw
7. Hacksaw
8. Core bits
9. Hammer
10. Drill
11. Tube cutter
12. Tube flaring tool
13. Torque wrench
14. Adjustable wrench
15. Reamer (for deburring)
1-2. Accessories Supplied with Unit
Table 1
1-3. Optional Copper Tubing Kit
Copper tubing for connecting the outdoor unit to the indoor unit is available in kits which contain the narrow and wide tubing, fittings and insulation. Consult your nearest sales outlet or air conditioning workshop.
1-4. Type of Copper Tube and Insulation Material
If you wish to purchase these materials separately from a local source, you will need:
1. Deoxidized annealed copper tube for refrigerant tub­ing as detailed in Table 2.
Cut each tube to the appropriate lengths 1' to 1'4" (30 cm to 40 cm) to dampen vibration between units.
Table 2
2. Foamed polyethylene insulation for the specified copper tubes as required to precise length of tubing. Wall thickness of the insulation should be not less than 5/16" (8 mm).
3. Use insulated copper wire for field wiring. Wire size varies with the total length of wiring. Refer to 3-6. Wiring Instructions for details.
CAUTION
Check local electrical codes and regulations before obtaining wire. Also, check any specified instructions or limitations.
Model
Narrow Tube Wide Tube
Outer Dia. Thickness Outer Dia. Thickness
KS3082 3/8" (9.52 mm) 0.0314" (0.8 mm) 5/8" (15.88 mm) 0.0393" (1.0 mm)
KS3682 3/8" (9.52 mm) 0.0314" (0.8 mm) 5/8" (15.88 mm) 0.0393" (1.0 mm)
10-018 C3082-3682 2/15/10 11:50 AM Page 3
Parts Figure Q’ty Parts Figure Q’ty
Remote control unit
1
Air clean filter
Remote control unit holder
1
Tapping screw
AAA alkaline battery
Tapping screw
2
Truss-head Phillips
5
/32 × 5/8" (4×16 mm)
Truss-head Phillips
5
/32 × 13/32" (4×10 mm)
2
10
2
Parts Figure Q’ty
Rawl plug
Drain hose
adapter
Flare insulation
8
1
1
4
1-5. Additional Materials Required for Installation
1. Refrigeration (armored) tape
2. Insulated staples or clamps for connecting wire (See local codes.)
3. Putty
4. Refrigeration lubricant
5. Clamps or saddles to secure refrigerant tubing
2. Installation Site Selection
2-1. Indoor Unit
AVOID:
direct sunlight.
nearby heat sources that may affect performance of the unit.
areas where leakage of flammable gas may be expected.
places where large amounts of oil mist exist.
DO:
select an appropriate position from which every corner of
the room can be uniformly cooled. (High on a wall is best.)
select a location that will hold the weight of the unit.
select a location where tubing and drain hose have the
shortest run to the outside. (Fig. 1)
allow room for operation and maintenance as well as unre-
stricted air flow around the unit. (Fig. 2)
install the unit within the maximum elevation difference (H)
above or below the outdoor unit and within the maximum tub­ing length (L) from the outdoor unit as detailed in Table 3 and Fig. 3a.
install the indoor unit more than 3.3' (1 m) away from any
antenna or power lines or connecting wires used for television, radio, telephone, security system, or intercom. Electrical noise from any of these sources may affect operation.
Drain hose
Indoor unit
Outside drainage
Fig. 1
Fig. 2
INDOOR UNIT
Tubing length (L)
OUTDOOR UNIT
Elevation difference (H)
Fig. 3a
WARNING
To prevent abnormal heat genera­tion and the possibility of fire, do not place obstacles, enclosures and grilles in front of or surround­ing the air conditioner in a way that may block air flow.
Fig. 3b
For stable operation of the air conditioner, do not install wall-mounted type indoor units less than 5' (1.5 m) from floor level.
CAUTION
Table 3
10-018 C3082-3682 2/15/10 11:50 AM Page 4
2" (5 cm)
min.
3" (7.5 cm) min.
2" (5 cm)
min.
Front View
Indoor unit
Minimum height from floor level
5' (1.5 m)
Wall
Model
KS3082 KS3682
* If total tubing length becomes 100 to 165 ft. (Max.), charge additional refrigerant (R410A) by 0.43 oz./ft.
No additional charge of compressor oil is necessary. For more detailed charging information, refer to the Technical & Service Manual.
Charge-less Tubing
Length (Actual Length)
(ft.)
Maximum Tubing
Maximum Elevation Difference (H)
Length (L)
(ft.)
16510 to 100 0.43
If the outdoor unit is higher
If the outdoor unit is lower
(ft.)
100
50
Required Amount
of Additional Refrigerant
Floor level
(oz./ft.)*
Concerning air-intake side distance “A” (Fig. 5a)
The minimum for distance “A” is 6" if there are no obstructions on the air-discharge side (wall *1 side) and *2 or *4 is not present. In all other cases, the min­imum for distance “A” is 8".
If wall *1 is on the air-discharge side (Fig. 5a), or if
obstructions are present on all 3 sides *2, *3, and *4 (Fig. 5a), then the minimum distance for “B” and “C” is 39-3/8". Even if there is no wall on the air-discharge side, a minimum of 39-3/8" is required.
Fig. 5c
Air intake
Concrete or equal
About 6" (15 cm)
Min. 6" (15 cm)
Anchor bolts (4 pcs.)
About 1'4" (40 cm)
5
2-2. Outdoor Unit
AVOID:
heat sources, exhaust fans, etc. (Fig. 4)
damp, humid or uneven locations.
DO:
choose a place as cool as possible.
choose a place that is well ventilated.
install in a location where at least two sides are unob-
structed, so that the flow of air at the intake port or exhaust port is not blocked, and so that sufficient space is ensured for maintenance to be carried out without trouble. In general the top also must be unob­structed. (Fig. 5a)
provide a solid base (level concrete pad, concrete block,
6" x 1'4" (15 x 40 cm) beams or equal), a minimum of 6" (15 cm) above ground level to reduce humidity and pro­tect the unit against possible water damage and decreased service life. (Figs. 5b and 5c)
install cushion rubber under unit’s feet to reduce
vibration and noise. (Fig. 5d)
use lug bolts or equal to bolt down unit, reducing
vibration and noise.
install in a location where no antenna of a television
or radio exists within 10' (3 m).
Outdoor unit
Hot air
Heat source
Exhaust fan
NO
Fig. 4
Fig. 5d
Fig. 5a
Fig. 5b
CAUTION CAUTION
A solid base must not cover the hole of the bottom plate.
10-018 C3082-3682 2/15/10 11:50 AM Page 5
Obstacle above
Drain holes
*3
Air intake
*2
Min.
6" (15 cm)
A
Air discharge
Min. 10"
(25 cm)
Min. 3'3" (100 cm)
*4
*1
Ground
B
Air discharge
Min. 8" (20 cm)
Air intake
C
Obstacle
Cushion rubber
(Locally purchased)
6
10-018 C3082-3682 2/15/10 11:50 AM Page 6
2-2-1. Installing the Unit in an Area with High Winds and in a Snowy Area
In locations with high winds, a wind-proof duct
should be fitted and direct exposure to the wind should be avoided as much as possible. (Fig. 5e)
In regions with significant snowfall, the outdoor unit
should be provided with a platform and snow-proof duct. (Fig. 5f)
Countermeasures against snow and wind
In regions with snow and strong wind, the following problems may occur when the outdoor unit is not provided with a platform and ducting:
a) The outdoor fan may not run and damage to the
unit may occur.
b) There may be no air flow.
c) The tubing may freeze and burst.
d) The condenser pressure may drop because of
strong wind, and the indoor unit may freeze.
Air discharge
Outdoor unit
Air discharge
Air discharge
Air discharge
Fig. 5e
Duct
2-2-2. Precautions for Installation in a Snowy Area
(1) The platform should be higher than the maximum
snow depth. (Fig. 5g)
(2) The 2 anchoring feet of the outdoor unit should
be used for the platform, and the platform should be installed beneath the air intake side of outdoor unit.
(3) The platform foundation must be firm and the unit
must be secured with anchor bolts.
(4) In case of installation on a roof subject to strong
wind, countermeasures must be taken to prevent the unit from being blown over.
Air Intake
About 1/2 of the unit height
Fig. 5f
w
sno
um
igher than the
m
H
axi
m
Air Intake
Platform (foundation)
h
dept
Without snow­proof ducting (Low platform)
Without snow­proof ducting (High platform)
Fig. 5g
7
11-13/16" 13-3/8"
25-3/16"
22-7/8"
(6-21/32")
6-5/16"
21-25/32" (12-9/16")
2-11/16"
35-13/16"
37-1/32"
Air discharge
Air discharge
Air discharge
Hole for anchor bolt (4-R1/4") / Anchor bolt : 3/8" or M101
Air discharge
Air discharge
25-31/32"6-11/16"
13-3/8"
25/32"25/32"
14-31/32" 13/32"25/32"
Air Intake
Air discharge
Unit: inch
Air
Air Intake
1
(4-11/32")
discharge
Air discharge
2-2-3. Dimensions of Wind-proof Duct
Reference diagram for C3082/3682
(9/16")
21-9/16"
(1/4")
22-1/4"
23-7/16"
(4-31/32")
4-31/32"
21-25/32"
11-13/16"
11-13/16"
1-5/16"
15/16"
18-15/16"
(1-31/32")
(1-31/32")
(1-31/32")8-21/32"1-3/16"
22-7/8"
Equivalent to the reverse side
Unit: inch
4- 1/4"
hole
Reference diagram for wind-proof duct (locally purchased): STK-DGV160E
10-018 C3082-3682 2/15/10 11:50 AM Page 7
8
8" na
h
t ero
M
More than 9-27/32" More than 9-27/32"
More than 6"
10-018 C3082-3682 2/15/10 11:50 AM Page 8
Required space around the outdoor unit
If the wind-proof duct is used, the space shown below must be secured around the outdoor unit. If the unit is used without the required space, a protective device may activate, preventing the unit from operating.
(1) Single-unit installation
or more
Min. 39-3/8"
" or more
Min. 8
Unit: inch
CAUTION
The top and both sides must remain open. If there are obstacles to the front and rear of the outdoor unit, the obstacle at either the front or rear must be no taller than the height of the outdoor unit.
(2) Multiple-unit installation
Installation in lateral rows
CAUTION
The front and top must remain open. The obstacles must be no taller than the height of the outdoor unit.
Installation in front-rear rows
intakes or outlets facing outlets
Unit: inch
Installation with intakes facing outletsInstallation with intakes facing
CAUTION
More than 11-13/16"
More than 47-1/4"
The front and both sides must remain open.
More than 78-3/4"
Unit: inch
9
25-13/32"
3/32"
13-3/8"
(11-15/16")
16-15/16"
Air Intake
Air discharge
39-1/4"
27-7/32"
7-1/32"
35-15/16"
28-15/16"
27-5/8" (11-5/8")
Air Intake
13/32"14-31/32"
25/32"
25/32"
25/32"
13-3/8"
4-11/32"
1
(8-15/16") 25-31/32"
Air discharge
1
Unit: inch
Hole for anchor bolt (4-R1/4") / Anchor bolt: 3/8" or M10
2-2-4. Dimensions of Snow-proof Duct
Reference diagram for C3082/3682
7
3
4
6
8
2
1
1
2
3
4
5
6
7
8
1
1
1
1
1
1
1
Unit: inch
Unit top, snow-proof duct
Unit right, snow-proof duct
Unit left, snow-proof duct
Unit front, snow-proof duct
Unit reverse side, snow-proof duct
Unit reverse side, snow-proof duct
Unit reverse side, reinforcement bracket for snow-proof duct
Unit left, reinforcement bracket for snow­proof duct
Fastened by screws at 14 locations
Fastened by screws at 3 locations
Fixing with
front panel
2- 9/32"
hole
2- 9/32"
hole
2- 9/32"
hole
2- 9/32"
hole
9/32"
X13/32"hole
15-11/32"
Fastened by screws
(Same on the reverse side)
Fastened by screws at 2 locations
28-13/16"
16-15/16"
9-1/8"
31/32"
2-7/32"
24-3/16" 28-3/16"
23
Fixing with rear panel
5/8"
6-1/32"
28-3/16"
1-15/16"20-13/32"
5/16"
5-13/32"
34-23/32"
11-7/8"
28-/13/16"
16-15/16"
9-1/8"
4-1/32"
Fixing with rear panel
Unit anchor holes
(Unit fixed bottom plate)
9-7/32"
13-7/8"
5-1/8
"
4-11/32"
1-9/16"
5-7/8"
25/32"
4-27/32"
20-7/8"
3-27/32"
3-15/16"
4-23/32"
25-13/32"
17-9/16"
Fastened by screws
at 2 locations (Same on the reverse side)
Fixing with top panel
1/16" 27-9/16"
5
1
Reference diagram for snow-proof duct (locally purchased): STK-BDV80E
10-018 C3082-3682 2/15/10 11:50 AM Page 9
Loading...
+ 21 hidden pages