Sanyo C3632 User Manual

Specifications and Main Features

  • Model Numbers:
  • Indoor Unit: K3032 KS, KS3563
  • Outdoor Unit: CL3032, C3032,CL3632
  • Power Source:

-208V-230V/- 208 V / 3 Phase / 60 Hz / 1

  • Performance:
  • Cooling Capacity:
  • KS3032: 30,000 BTU/h(8.8KW)
  • KS3632: 34,000 BTU/h(9.96KW)
  • Hi Air circulation:
  • KS3032:840cuft/min
  • KS3632:830cuft/min
  • Moisture removal (High): 11 Models ranging upto 10.2- Pints/h
  • Electrical Ratings:
  • 230V / 208V : Equip Voltage
  • Voltage available range: 253-187v
  • Running amperes:
  • KS3032: 13.0 a
  • ks3632: 14.9 a
  • Max. running amperes:
  • ks3032: 16.1 a
  • ks3632: 17.7 a
  • Power input:
  • ks3032: 2,880 W
  • ks3632: 3,300 W
  • Power usage capacity:96%
  • Max. starting amperes:
  • ks3032: 79.6 A
  • ks3632: 97.6 A
  • Maximum fuse sizes:
  • ks3032: 30A
  • ks3632: 35A
  • Features:
  • Controls: microprocessor
  • timers: on/off timers 24 hours & program
  • Fan speed: Indoor 3 automatic control tertiary and outdoor 2 auto
  • Air deflection Horizontal to vertical, automatic and manual sections.
  • Air filter: Replaceable hayfever with easy access parts
  • Remote controller (Accessories): RCS - 5PS4U
  • Refrigerant control: Capillary type
  • Refrigerant tubing connections: Flares
  • Drain pipe trade size: 3/4 in. (26.7 mm)
  • Compressor type: Rotary
  • Operation Sound Levels:
  • Indoor-Hi/Me/Lo: 46 dB(A)
  • Outdoor-Hi: 56 dB(A)
  • Refrigerant Tubing:
  • Limit of tubing length: 165 ft (50 m)
  • Refrigerant amount at shipment: R22: 8.6 lbs (3.9 kg) (KS3032) / R22: 9.48 lbs (4.3 kg) (KS3632)
  • Dimensional Data:
  • Indoor Unit Dimensions:
  • Height: 14-9/16 in (370 mm)
  • Width: 59-1/16 in (1,500 mm)
  • Depth: 9-7/16 in (240 mm)
  • Outdoor Unit Dimensions:
  • Height: 48-5/8 in (1,235 mm)
  • Width: 37 in (940 mm)
  • Depth: 13-3/8 in (340 mm)

Frequently Asked Questions

  • Q: What is the cooling capacity of the KS3032 model?

A: The cooling capacity of the KS3032 model is 30,000 BTU/h (8.8 kW).

  • Q: Is the distance between the indoor and outdoor units considerable?

A: The distance should not exceed 165 ft (50 m) for the refrigerant lines.

  • Q: What is the max fuse size that goes to the KS3632 model?

A: KS3632 max fuse size goes up to 35 A.

  • Q: How noisy is the indoor unit during operation?

A: The sound level of the indoor unit working on high speed reaches 46 dB(A).

  • Q: Cleaning the air filter shouldn’t take too long, right?

A: Indeed, the air filter can be cleaned easily since it is a washable type.

  • Q: This unit uses which type of refrigerant?

A: This unit is using R22 refrigerant.

  • Q: How much can an indoor unit and an outdoor unit differ in height?

A: Alone the outdoor unit is of the same height or slightly lower and the difference in height can be about 100ft (30m) but if the outdoor unit is high then the height difference can be maximum up to 165ft (50m).