Sanyo C2462R, CL2462R User Manual

TECHNICAL DATA
SERVICE MANUAL
KS2462R / C2462R, CL2462R
SPLIT SYSTEM AIR CONDITIONER
INDOOR MODEL No. PRODUCT CODE No. OUTDOOR MODEL No. PRODUCT CODE No.
KS2462R 854 019 00
Indoor Unit Outdoor Unit
C2462R 854 019 01
CL2462R 854 019 02
FILE NO.
854648419200
KS2462R C2462R
CL2462R
REFERENCE NO. SM830092
– 1 –
SM830092
Important
Please Read Before Starting
This air conditioning system meets strict safety and operating standards. As the installer or service person, it is an important part of your job to install or service the system so it operates safely and efficiently.
For safe installation and trouble-free operation, you must :
Carefully read this instruction booklet before beginning. Follow each installation or repair step exactly as shown. Observe all local, state, and national electrical codes. Pay close attention to all warning and caution notices
given in this manual.
This symbol refers to a hazard or unsafe practice which can result in severe personal injury or death.
This symbol refers to a hazard or
CAUTION
unsafe practice which can result in personal injury or product or property damage.
If Necessary, Get Help
These instructions are all you need for most installation sites and maintenance conditions. If you require help for a special problem, contact our sales/service outlet or your certified dealer for additional instructions.
In Case of Improper Installation
The manufacturer shall in no way be responsible for improper installation or maintenance service, including failure to follow the instructions in this document.
SPECIAL PRECAUTIONS
When Wiring
……………………………………………………………………
ELECTRICAL SHOCK CAN CAUSE SEVERE PERSONAL INJURY OR DEATH. ONLY A QUALIFIED, EXPERIENCED ELECTRICIAN SHOULD ATTEMPT TO WIRE THIS SYSTEM.
• Do not supply power to the unit until all wiring and tubing are completed or reconnected and checked.
• Highly dangerous electrical voltages are used in this system. Carefully refer to the wiring diagram and these instructions when wiring. Improper connections and inadequate ground­ing can cause accidental injury or death.
Ground the unit following local electrical codes.
• Connect all wiring tightly. Loose wiring may cause overheat­ing at connection points and a possible fire hazard.
When Transporting
…………………………………………………………………… Be careful when picking up and moving the indoor and outdoor
units. Get a partner to help, and bend your knees when lifting to reduce strain on your back. Sharp edges or thin aluminum fins on the air conditioner can cut your fingers.
When Installing
……………………………………………………………………
…In a Room
Properly insulate any tubing run inside a room to prevent “sweating” that can cause dripping and water damage to walls and floors.
…In Moist or Uneven Locations
Use a raised concrete pad or concrete blocks to provide a solid, level foundation for the outdoor unit. This prevents water damage and abnormal vibration.
…In an area with High Winds
Securely anchor the outdoor unit down with bolts and a metal frame. Provide a suitable air baffle.
…In a Snowy Area (for Heat Pump-type Sys-tems)
Install the outdoor unit on a raised platform that is higher than drifting snow. Provide snow vents.
When Connecting Refrigerant Tubing
……………………………………………………………………
• Ventilate the room well, in the event that refrigerant gas leaks during the installation. Be careful not to allow contact of the refrigerant gas with a flame as this will cause the generation of poisonous gas.
• Keep all tubing runs as short as possible.
• Use the flare method for connecting tubing.
• Apply refrigerant lubricant to the matching surfaces of the flare and union tubes before connecting them, then tighten the nut with a torque wrench for a leak-free connection.
• Check carefully for leaks before starting the test run.
NOTE
Depending on the system type, liquid and gas lines may be either narrow or wide. Therefore, to avoid confusion the refrigerant tubing for your particular model is specified as either “narrow” or “wide” rather than as “liquid” or “gas”.
When Servicing
……………………………………………………………………
• Turn the power OFF at the main power box (mains) before opening the unit to check or repair electrical parts and wiring.
• Keep your fingers and clothing away from any moving parts.
• Clean up the site when installation is finished. Check that no metal scraps or bits of wiring have been left inside the unit.
CAUTION
• Ventilate any enclosed areas when installing or testing the refrigeration system. Contact of refrigerant gas with fire or heat can produce poisonous gas.
• Confirm after installation that no refrigerant gas is leaking. If the gas comes in contact with a burning stove, gas water heater, electric room heater or other heat source, it can cause the generation of poisonous gas.
– 2 –
SM830092
Table of Contents
1. OPERATING RANGE ....................................................................................... 4
2. SPECIFICATIONS............................................................................................ 5
(1) Unit Specifications ...................................................................................... 5
(2) Major Component Specifications ................................................................ 7
(A) Indoor Unit ............................................................................................ 7
(B) Outdoor Unit.......................................................................................... 8
(3) Other Component Specifications .............................................................. 10
(A) Indoor Unit .......................................................................................... 10
(B) Outdoor Unit........................................................................................ 12
3. DIMENSIONAL DATA..................................................................................... 13
(1) Indoor Unit ................................................................................................ 13
(2) Outdoor Unit.............................................................................................. 14
4. COOLING CAPACITY..................................................................................... 15
5. PERFORMANCE CHARTS ............................................................................ 17
(1) Operating Current ..................................................................................... 17
(2) High and Low Pressure............................................................................. 19
6. AIR THROW DISTANCE CHART................................................................... 21
7. REFRIGERANT FLOW DIAGRAM ................................................................. 22
8. INSTALLATION INSTRUCTIONS .................................................................. 23
9. ELECTRICAL DATA ....................................................................................... 29
10. ELECTRICAL WIRING DIAGRAMS ............................................................... 30
(1) Indoor Unit ................................................................................................ 30
(2) Outdoor Unit.............................................................................................. 31
11. PROCESSES AND FUNCTIONS.................................................................. 35
(1) Room Temperature Control ...................................................................... 35
(2) Dry Operation............................................................................................ 36
(3) Freeze Prevention..................................................................................... 37
(4) Outdoor Fan Speed Control......................................................................38
12. SERVICE PROCEDURES.............................................................................. 39
(1) Troubleshooting ........................................................................................ 39
(2) A Sensor is Defective................................................................................ 50
(3) Checking the Electrical Components ........................................................ 51
– 3 –
SM830092
1. OPERATING RANGE
KS2462R / C2462R
Temperature Indoor Air Intake Temp. Outdoor Air Intake Temp.
Maximum 95 °F DB / 71 °F WB 115 °F DB
Minimum 67 °F DB / 57 °F WB 67 °F DB
KS2462R / CL2462R
Temperature Indoor Air Intake Temp. Outdoor Air Intake Temp.
Maximum 95 °F DB / 71 °F WB 115 °F DB
Minimum 67 °F DB / 57 °F WB 0 °F DB
– 4 –
SM830092
2. SPECIFICATIONS
1-1 Unit Specifications
MODEL No. Indoor Unit
Outdoor Unit C2462R
POWER SOURCE 230 - 208 V / 1 Phase / 60 Hz PERFORMANCE Cooling
Capacity
Air circulation (Hi) Moisture removal (High) Pints / h 6.5
ELECTRICAL RATINGS
Voltage rating VAC Available voltage range 187 – 253 Running amperes* A 10.2 Max. running amperes** A 12.5 Power input W 2,240 Power factor % 95.5 S.E.E.R 13.0 Max. starting amperes A 61
FEATURES
Controls Microprocessor Timer ON/OFF 24-hours & Program Fan speed Indoor / Outdoor 3 and Automatic control / 2 (Auto) Air deflection Horizontal / Vertical – / Automatic Air filter Washable, easy access Remote controller (Accessory) RCS - 1PS4U - G Refrigerant control Capillary tube Refrigerant tubing connections Flare type Compressor Scroll Operation sound
REFRIGERANT TUBING
Limit of tubing length ft. (m) Limit of tubing length at shipment 23 ( 7 ) Limit of elevation difference between the two units Refrigerant tube Narrow tube 3 / 8 (9.52) outer diameter Wide tube 3 / 4 (19.05) Refrigerant amount at shipment lbs. (kg) R410A - 6.6 (3)
DIMENSIONS & WEIGHT Indoor unit Outdoor unit
Unit dimensions Height in. (mm)
Package dimensions Height
Net weight lbs. (kg) Shipping weight Shipping volume
Cooling:
Rating conditions (*) : Indoor air temperature 80 °F DB / 67 °F WB, Outdoor air temperature 95 °F DB / 75°F WB Full load conditions (**):Indoor air temperature 80 °F DB / 67 °F WB, Outdoor air temperature 115°F DB
Indoor - Hi/Me/Lo Outdoor - Hi
Width Depth
Width Depth 15-31/32 (406)
BTU / h
kW
Cu.ft. / min.
VAC
BTU / Wh
dB - A 48 / 42 / 38 dB - A 55
ft. (m) ft. (m)
in. (mm) in. (mm)
in. (mm) in. (mm) in. (mm) in. (mm) in. (mm)
lbs. (kg)
cu. ft.(m )
3
27,000
7.912 559
230
13 (330) 44-7/8 (1,140) 8-31/32 (228) 12-25/32 (325) 48-15/32 (406)
40 (18) 44 (20)
5.7 (0.162)
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
KS2462R
26,000
7.619 519
6.4
208
10.9
13.5
2,200
97.0
13.0 61
132 ( 40 )
50 ( 15 )
36-5/8 (930) 37 (940) 13-3/8 (340) 39-3/4 (1,010) 39-3/8 (1,000) 15-3/4 (400) 150 (68) 190 (86.5)
14.1 (0.40)
– 5 –
SM830092
2. SPECIFICATIONS
1-1 Unit Specifications
MODEL No. Indoor Unit
Outdoor Unit CL2462R
POWER SOURCE 230 - 208 V / 1 Phase / 60 Hz PERFORMANCE Cooling
Capacity
Air circulation (Hi) Moisture removal (High) Pints / h 6.5
ELECTRICAL RATINGS
Voltage rating VAC Available voltage range 187 – 253 Running amperes* A 10.2 Max. running amperes** A 12.5 Power input W 2,240 Power factor % 95.5 S.E.E.R 13.0 Max. starting amperes A 61
FEATURES
Controls Microprocessor Timer 1-hour OFF, ON/OFF 12-hours & Program Fan speed Indoor / Outdoor 3 and Automatic control / 3 (Auto) Air deflection Horizontal / Vertical – / Automatic Air filter Washable, easy access Remote controller (Accessory) RCS - 1PS4U - G Refrigerant control Capillary tube Refrigerant tubing connections Flare type Compressor Scroll Operation sound
REFRIGERANT TUBING
Limit of tubing length ft. (m) Limit of tubing length at shipment 23 ( 7 ) Limit of elevation difference between the two units Refrigerant tube Narrow tube 3 / 8 (9.52) outer diameter Wide tube 3 / 4 (19.05) Refrigerant amount at shipment lbs. (kg) R410A - 6.6 (3)
DIMENSIONS & WEIGHT Indoor unit Outdoor unit
Unit dimensions Height in. (mm)
Package dimensions Height
Net weight lbs. (kg) Shipping weight Shipping volume
Cooling:
Rating conditions (*) : Indoor air temperature 80 °F DB / 67 °F WB, Outdoor air temperature 95 °F DB / 75°F WB Full load conditions (**):Indoor air temperature 80 °F DB / 67 °F WB, Outdoor air temperature 115°F DB
Indoor - Hi/Me/Lo Outdoor - Hi
Width Depth
Width Depth
BTU / h
kW
Cu.ft. / min.
VAC
BTU / Wh
dB - A 48 / 42 / 38 dB - A 55
ft. (m) ft. (m)
in. (mm) in. (mm)
in. (mm) in. (mm) in. (mm) in. (mm) in. (mm)
lbs. (kg)
cu. ft.(m )
3
27,000
7.912 559
230
13 (330) 44-7/8 (1,140) 8-31/32 (228) 12-25/32 (325) 48-15/32 (406) 15-31/32 (406) 40 (18) 44 (20)
5.7 (0.162)
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
KS2462R
26,000
7.619 519
6.4
208
10.9
13.5
2,200
97.0
13.0 61
132 ( 40 )
50 ( 15 )
36-5/8 (930) 37 (940) 13-3/8 (340) 39-3/4 (1,010) 39-3/8 (1,000) 15-3/4 (400) 150 (68) 190 (86.5)
14.1 (0.40)
– 6 –
SM830092
2. SPECIFICATIONS
(2) Major Component Specifications
(A) Indoor Unit
MODEL No. KS2462R Source 230 - 208 V / 1 phase / 60 Hz Remote controller (Accessory) RCS - 1PS4U - G Controller P. C. B Ass'y CR - KS2462R
Control circuit fuse 250 V, 3 A
Fan Type Cross-flow Number ... Dia. and length in. (mm) 1 ... O.D. 4 (100), L33-3/8 (847) Fan motor
Model KFG4X - 31B6P-S Source 230 - 208 V / 1 phase / 60 Hz No. of pole … r.p.m. (230 V, High) rpm 4 … 1,365 Nominal output W 30 Coil resistance BRW - WHT : 161.2 , ORG - YEL : 26.9 (Ambient temperature 68 °F) WHT - VLT : 11.6 , YEL - BLK : 22.8
VLT - ORG : 68.7 , BLK - PNK : 115.2
Safety device Internal
Operating temperature Open °F 266 ± 9
Close °F 181 ± 27
Run capacitor VAC, µF 440 V , 1.5 µF
Heat exchanger
Coil Aluminum plate fin / Copper tube Rows … Fins per inch 2 … 19.5 Face area ft.
Flap Motor
Type Stepping motor Model ... Q’ty MP24GA2 ... 2 Step angle 5.625 deg / step Rating V DC 12 V Coil resistance (Ambient temperature 77 °F) 400 ± 7 %
2
(m2) 2.30 (0.214)
DATA SUBJECT TO CHANGE WITHOUT NOTICE
– 7 –
SM830092
2. SPECIFICATIONS
(2) Major Component Specifications
(B) Outdoor Unit
MODEL No. C2462R Source 230 - 208 V / 1 phase / 60 Hz Compressor Scroll (Hermetic)
Model ZP23K3E Source 230 - 208 V / 1 phase / 60 Hz Nominal output W 2,400 Compressor oil cc 1,120 Coil resistance (Ambient temperature 77 °F) C - R : 2.28 , C - S : 1.01 Safety device Internal type
Overload relay models — Operating temperature Open °F 284 ± 9
Close °F
Operating ampere (at 77 °F) A
Run capacitor VAC, µF 400 V, 40 µF
Refrigerant amount charged at shipment lbs. (kg) R410A : 6.6 (3) High pressure switch ACB - 1UB24W
Set pressure OFF MPa 4.15
ON MPa 3.15 ± 0.3
Fan Propeller
Number...diameter in. (mm) 1 … 18-3/32 (460)
Fan speeds 2 (AUTO) Fan motor
Model KFC6T - 91D6P Source 230 - 208 V / 1 phase / 60 Hz No. of pole … rpm (230 V, High) rpm 6 … 879 Nominal output W 110 Coil resistance BRW – WHT : 67.14 , VLT – YEL : 11.42
(Ambient temperature 68 °F) Safety device
Operating temperature Open °F 248 ± 9
Close °F 171 ± 27
Run capacitor VAC, µF 440 V, 4 µF
Heat exchanger
Coil Aluminum plate fin / Copper tube Rows … Fins per inch 2 … 14.1 Face area ft.
2
(m2) 8.72 (0.81)
WHT – VLT : 64.85 , YEL – PNK : 10.60
DATA SUBJECT TO CHANGE WITHOUT NOTICE
156 189
+ 0 – 0.15
Internal
– 8 –
SM830092
2. SPECIFICATIONS
(2) Major Component Specifications
(B) Outdoor Unit
MODEL No. CL2462R Source 230 - 208 V / 1 phase / 60 Hz Controller P.C.B. Ass'y CR - CL2432 (Microprocessor)
Control circuit fuse 250 V, 3 A
Compressor Scroll (Hermetic)
Model ZP23K3E Source 230 - 208 V / 1 phase / 60 Hz Nominal output W 2,400 Compressor oil cc 1,120 Coil resistance (Ambient temperature 77 °F) C – R : 0.885 , C – S : 1.773
Safety device Internal type
Overload relay models — Operating temperature Open °F 284 ± 9
Close °F 156 189
Operating ampere (at 77 °F) A — Run capacitor VAC, µF 400 V, 40 µF Crank case heater V, W 230 V, 30 W
Refrigerant amount charged at shipment lbs. (kg) R410A : 6.6 (3) High pressure switch ACB-1UB24W
Set pressure OFF MPa 4.15
ON MPa 3.15 ± 0.3
Fan Propeller
Number...diameter in. (mm) 1 ... 18 - 3/32 (460)
Fan speeds 3 (AUTO) Fan motor
Model KFC6T - 91D6P Source 230 - 208 V / 1 phase / 60 Hz
No. of pole ..... rpm (230 V, High) 6 ... 879
Nominal output W 110 Coil resistance BRN – WHT : 67.14 , VLT – YEL : 11.42
(Ambient temperature 68 °F) WHT – VLT : 64.85 , YEL – PNK : 10.60 Safety device Internal
Operating temperature Open °F 248 ± 9
Close °F 171 ± 27
Run capacitor VAC, µF 440 V, 4 µF
Heat exchange
Coil Aluminum plate fin / Copper tube
Rows ..... Fins per inch 2 ... 14.1
2
Face area ft.
(m2) 8.72 (0.81)
DATA SUBJECT TO CHANGE WITHOUT NOTICE
+ 0 – 0.15
– 9 –
SM830092
2. SPECIFICATIONS
(3) Other Component Specifications
(A) Indoor Unit
MODEL No. KS2462R Power Transformer ATR – T5
Rated Primary AC 230 V, 60 Hz
Secondary AC19 V, 0.5 A Capacity 9.5 VA
Coil resistance (Ambient temprature 77 °F) Secondary (BRN - BRN) : 3.9
Thermistor cut off temperature 277 °F
Thermistor (Coil sensor) DTN - TKS131B
Coil resistance k 32 °F : 15.0 ± 2 %
Thermistor (Room sensor) DTN - TKS128B
Coil resistance k 77 °F : 5.0 ± 3 %
Lamp Ass'y IND - K301AH Flap Motor MP24GA2
Primary (WHT - WHT) : 457.5
– 10 –
SM830092
2. SPECIFICATIONS
(3) Other Component Specifications
(A) Outdoor Unit
MODEL No. C2462R
Compressor Motor Magnetic Contactor FC - 1SUL
Coil rated AC 240 V, 60 Hz Coil resistance (at 68 °F) 587 ± 5 % Contact rated (Main) AC 240 V, 26 A Contact rated (Auxiliary) AC 240 V, 3 A
Power Relay HH62S
Coil rated AC 240 V, 60 Hz Coil resistance (at 68 °F) k 17.2 Contact rated AC 220 V, 5 A
Thermostat (Coil sensor) YTB - 4U305F
Operating Temperature °F 79 ± 3 OFF
75 ON
Contact rated 200 to 240 V, 1 A
+ 3 – 1
– 11 –
SM830092
2. SPECIFICATIONS
(3) Other Component Specifications
(B) Outdoor Unit
MODEL No. CL2462R Compressor Motor Magnetic Contactor FC - 1SUL
Coil rated AC 240 V, 60 Hz Coil resistance (at 77 °F) 587 ± 5 % Contact rated (Main) AC 240 V, 26 A Contact rated (Auxiliary) AC 240 V, 3 A
Power Relay HH62S
Coil rated AC 240 V, 60 Hz Coil resistance (at 77 °F) k 17.2 Contact rated AC 220 V, 5 A
Power Transformer ATR - I35B
Rated
Primary AC 220 V, 60 Hz
Secondary 14 V, 0.2 A Capacity 2.8 VAC Coil resistance (at 78 °F ) WHT – WHT : 482.5 , BRN – BRN : 3.95 Thermal cut off temperature °F 266
Thermistor (Outdoor Temp. sensor)
Coil resistance k 14 °F : 23.7 , 50 °F : 9.7
23 °F : 18.8 , 68 °F : 6.5 32 °F : 15.0 , 86 °F : 4.4 41 °F : 12.1 , 104 °F : 3.1
Solenoid control valve or coil
Solenoid control valve VPV - 202DQ50 Solenoid coil VPV - MOAQ517B1
PBC - 41E - S4
113 °F : 2.6
– 12 –
SM830092
3. DIMENSIONAL DATA
(1) Indoor Unit: KS2462R
44-7/8
13
1-7/8
6-27/32
Center of tubing hole (2 places)
Narrow tube 3/8"(ø9.52)
Drain hose O.D. 23/32"(ø18)
5-5/16
Wide tube 3/4"(ø19.05)
8-31/32
Remote control unit
6-7/32
1-7/8
2-13/32
Dimension : inch
25/32
2199_M_S
– 13 –
SM830092
3. DIMENSIONAL DATA
(2) Outdoor Unit: C2462R, CL2462R
13-3/8
36-5/8
6-23/32
1/2
25-31/32
37
1/21/2
1/2
4-3/8
25/323/4
15-15/16
14-31/32
18-1/16
16-7/8
5
4
Dimension : inch
Hole for anchor bolt (4-R1/4) Refrigerant tube joint (narrow tube) Flare connection 3/8 in (9.52 mm) Refrigerant tube joint (wide tube) Flare connection 3/4 in (19.05 mm) Refrigerant tubing inlet Power supply inlet
5
4
– 14 –
SM830092
4. COOLING CAPACITY
Indoor Unit: KS2462R Outdoor Unit: C2462R
1
• 230V / 1 phase / 60Hz
RATING CAPACITY : 27,000 BTU / h AIR FLOW RATE : 559 Cu.ft / min EVAPORATOR CONDENSER
ENT. TEMP. °F (°C) AMBIENT TEMP. °F (°C)
WB DB 75 85 95 105 115
TC
CI 1.66
72(22.2) SHC 18,460
59
(15.0)
63
(17.2)
67
(19.4)
71
(21.7)
75
(23.9)
76(24.4) SHC 20,150 80(26.7) SHC 21,930 84(28.9) SHC 23,620 88(31.1)
72(22.2) 76(24.4) 80(26.7) 84(28.9) 88(31.1)
72(22.2) 76(24.4) 80(26.7) 84(28.9) 88(31.1)
72(22.2) 76(24.4) 80(26.7) 84(28.9) 88(31.1)
76(24.4) 80(26.7) 84(28.9) 88(31.1)
SHC 25,320
TC
CI SHC SHC SHC SHC SHC
TC
CI SHC SHC SHC SHC SHC
TC
CI SHC SHC SHC SHC SHC
TC
CI SHC SHC SHC SHC
(23.9) (29.4) (35.0) (40.6) (46.1)
27,350
28,380
1.67 16,130 17,820
19,590 21,290 22,990 29,460
1.69 13,770 15,470
17,240 18,940 20,630 31,020
1.7 11,500 13,190
14,960 16,660 18,360 31,640
1.74 10,560 12,330
14,020
15,720
26,030
1.81 17,640 19,340 21,110 22,810 24,500 27,110
1.83 15,400 17,100 18,870 20,570 22,260 28,300
1.85 13,170 14,870 16,640 18,330 20,030 29,940
1.87 10,990 12,680 14,450 16,150 17,850 30,620
1.9 10,120 11,900 13,590 15,290
24,520
1.97 16,740 18,430 20,210 21,900 23,600 25,760
2 14,660 16,360 18,130 19,820 21,520
# 27,000
2.02 12,510 14,210 15,980 17,680 19,370 28,780
2.05 10,450 12,140 13,920 15,610 17,310 29,540
2.08
9,680 11,450 13,150 14,840
22,820
2.23 15,760 17,450
19,220 20,920 22,620 24,220
2.26 13,840 15,530
17,310 19,000 20,700 25,570
2.29 11,810 13,510
15,280 16,970 18,670 27,510
2.32
9,870
11,570
13,340 15,040 16,730 28,300
2.35
9,170 10,950 12,640 14,340
20,930
2.49 14,710 16,400 18,170 19,870 20,930 22,550
2.52 12,970 14,670 16,440 18,140 19,830 24,000
2.55 11,060 12,760 14,530 16,230 17,920 26,110
2.59
9,260 10,950 12,730 14,420 16,120 26,970
2.63
8,650 10,420 12,110 13,810
TC : Total Cooling Capacity (BTU / h) SHC : Sensible Heat Capacity (BTU / h) CI : Compressor Input (kW)
Rating conditions are
: Outdoor Ambient Temp. 95 °F DB : Indoor Unit Entering Air Temp. 80 °F DB / 67 °F WB
SM830092
– 15 –
4. COOLING CAPACITY
Indoor Unit: KS2462R Outdoor Unit: C2462R
1
• 208V / 1 phase / 60Hz
RATING CAPACITY : 26,000 BTU / h AIR FLOW RATE : 519 Cu.ft / min EVAPORATOR CONDENSER
ENT. TEMP. °F (°C) AMBIENT TEMP. °F (°C)
WB DB 75 85 95 105 115
TC
CI 1.64
72(22.2) SHC 17,760
59
(15.0)
63
(17.2)
67
(19.4)
71
(21.7)
75
(23.9)
76(24.4) SHC 19,360 80(26.7) SHC 21,030 84(28.9) SHC 22,630 88(31.1)
72(22.2) 76(24.4) 80(26.7) 84(28.9) 88(31.1)
72(22.2) 76(24.4) 80(26.7) 84(28.9) 88(31.1)
72(22.2) 76(24.4) 80(26.7) 84(28.9) 88(31.1)
76(24.4) 80(26.7) 84(28.9) 88(31.1)
SHC 24,230
TC
CI SHC SHC SHC SHC SHC
TC
CI SHC SHC SHC SHC SHC
TC
CI SHC SHC SHC SHC SHC
TC
CI SHC SHC SHC SHC
(23.9) (29.4) (35.0) (40.6) (46.1)
26,340
27,330
1.66 15,540 17,140 18,810 20,410 22,010 28,370
1.67 13,310 14,910 16,580 18,180 19,770 29,870
1.69 11,150 12,750 14,420 16,020 17,620 30,470
1.72 10,240 11,910 13,510 15,110
25,060
1.79 16,960 18,560 20,230 21,830 23,430 26,100
1.82 14,840 16,430 18,110 19,700 21,300 27,250
1.83 12,720 14,320 15,990 17,590 19,190 28,830
1.85 10,650 12,250 13,920 15,520 17,120 29,480
1.88
9,810 11,480 13,080 14,680
23,610
1.95 16,080 17,680 19,350 20,950 22,550 24,800
1.98 14,110 15,710 17,380 18,980 20,580
# 26,000
2 12,080 13,680 15,350 16,950 18,550 27,720
2.03 10,130 11,730 13,400 15,000 16,600 28,440
2.06
9,380 11,050 12,650 14,250
21,970
2.23 15,120 16,720 18,390 19,990 21,590 23,320
2.27 13,310 14,910 16,580 18,180 19,780 24,620
2.29 11,390 12,990 14,660 16,260 17,860 26,490
2.32
9,570 11,170 12,840 14,440 16,040 27,250
2.36
8,890 10,560 12,160 13,760
20,150
2.52 14,100 15,700 17,370 18,970 20,150 21,710
2.55 12,470 14,070 15,740 17,340 18,940 23,110
2.58 10,670 12,260 13,940 15,540 17,130 25,140
2.62
8,970 10,570 12,240 13,840 15,440 25,970
2.66
8,380 10,050 11,650 13,250
TC : Total Cooling Capacity (BTU / h) SHC : Sensible Heat Capacity (BTU / h) CI : Compressor Input (kW)
Rating conditions are
: Outdoor Ambient Temp. 95 °F DB : Indoor Unit Entering Air Temp. 80 °F DB / 67 °F WB
SM830092
– 16 –
5. PERFORMANCE CHARTS
(1) Operating Current
Indoor Unit: KS2462R Outdoor Unit: C2462R
1
Operating current characteristics versus outdoor ambient temperature and indoor temperature. (Indoor relative humidity: 50%, Indoor fan speed: High)
230V
208V
Outdoor fan speed
Low
14 13 12 11 10
9 8
Operating current (A)
7
59 68 77 86 95 104
(15) (20) (25) (30) (35) (40)
Outdoor ambient temp. °F (°C)
Outdoor fan speed
Low
14 13 12 11 10
9 8
Operating current (A)
7
High
High
Indoor temp. °F (°C)
85 (30) 80 (27) 75 (24) 70 (21)
1061_X_S
Indoor temp. °F (°C)
85 (30) 80 (27) 75 (24) 70 (21)
59 68 77 86 95 104
(15) (20) (25) (30) (35) (40)
Outdoor ambient temp. °F (°C)
– 17 –
1062_X_S
SM830092
5. PERFORMANCE CHARTS
(1) Operating Current
Indoor Unit: KS2462R Outdoor Unit: CL2462R
2
Operating current characteristics versus outdoor ambient temperature and indoor temperature. (Indoor relative humidity: 50%, Indoor fan speed: High)
230V
Operating current (A)
208V
Operating current (A)
Outdoor fan speed
Low High
14 13 12 11 10
9 8
7
23 32 41 50
(–5) (0) (5) (10) (35) (40)
14 13 12 11 10
9 8 7
59 68 77 86 95 104
(15) (20) (25) (30)
Outdoor ambient temp. °F (°C)
Outdoor fan speed
Low High
Med
Med
Indoor temp. °F (°C)
85 (30) 80 (27) 75 (24) 70 (21)
1063_X_S
Indoor temp. °F (°C)
85 (30) 80 (27) 75 (24) 70 (21)
23 32 41 50
(–5) (0) (5) (10) (35) (40)
59 68 77 86 95 104
(15) (20) (25) (30)
Outdoor ambient temp. °F (°C)
– 18 –
1064_X_S
SM830092
5. PERFORMANCE CHARTS
(2) High and Low Pressure
Indoor Unit: KS2462R Outdoor Unit: C2462R
1
• High Pressure
High pressure characteristics versus outdoor ambient temperature and indoor temperature. (Indoor relative humidity: 50%, Indoor fan speed: High)
230V / 208 V
480 460 440 420 400 380 360 340
Discharge pressure (psig)
320 300
59 68 77 86 95 104
(15) (20) (25) (30) (35) (40)
• Low Pressure
Outdoor fan speed
Low
Outdoor ambient temp. °F (°C)
High
Indoor temp. °F (°C)
85 (30) 80 (27) 75 (24) 70 (21)
1065_X_S
Low pressure characteristics versus outdoor ambient temperature and indoor temperature. (Indoor relative humidity: 50%, Indoor fan speed: High)
230V / 208 V
170 160 150 140 130 120
Suction pressure (psig)
110
59 68 77 86 95 104
(15) (20) (25) (30) (35) (40)
Outdoor fan speed
Low
Outdoor ambient temp. °F (°C)
High
– 19 –
Indoor temp. °F (°C)
85 (30) 80 (27) 75 (24) 70 (21)
1066_X_S
SM830092
5. PERFORMANCE CHARTS
(2) High and Low Pressure
Indoor Unit: KS2462R Outdoor Unit: CL2462R
2
• High Pressure
High pressure characteristics versus outdoor ambient temperature and indoor temperature. (Indoor relative humidity: 50%, Indoor fan speed: High)
230 / 208V
500 480 460 420 400 380 360 340
Discharge pressure (psig)
320 300
23 32 41 50
(–5) (0) (5) (10) (35) (40)
Low High
Outdoor ambient temp. °F (°C)
Outdoor fan speed
Med
59 68 77 86 95 104
(15) (20) (25) (30)
• Low Pressure
Low pressure characteristics versus outdoor ambient temperature and indoor temperature. (Indoor relative humidity: 50%, Indoor fan speed: High)
Indoor temp. °F (°C)
85 (30) 80 (27) 75 (24) 70 (21)
1067_X_S
230 / 208V
170 160 150 140 130 120
Suction pressure (psig)
110
23 32 41 50
(–5) (0) (5) (10) (35) (40)
Outdoor fan speed
Low High
59 68 77 86 95 104
(15) (20) (25) (30)
Outdoor ambient temp. °F (°C)
Med
– 20 –
Indoor temp. °F (°C)
85 (30) 80 (27) 75 (24) 70 (21)
1068_X_S
SM830092
6. AIR THROW DISTANCE CHART
Indoor Unit: KS2462R
Room air temp. : 80°F (26.7°C) Fan speed : High
Horizontal distance (ft.)
0
5
10
Axis air velocity (ft./sec.)
Vertical distance (ft.)
15
5 1015202530
: Flap angle 0° , : Axis air velocity 0 ° : Flap angle 30°, : Axis air velocity 30 °
2200_M_S
– 21 –
SM830092
7. REFRIGERANT FLOW DIAGRAM
Indoor Unit: KS2462R Outdoor Unit: C2462R
Indoor Unit Outdoor Unit
Wide tube
O. D. 3/4" (19.05mm)
Evaporator
O. D. 3/4" (19.05mm)
Wide tube service valve
Accumulator
High pressure switch
LP
Compressor
HP
Narrow tube
O. D. 3/8" (9.52 mm)
Narrow tube service valve
O. D. 3/8" (9.52 mm)
Capillary
tube
Strainer
Indoor Unit: KS2462R Outdoor Unit: CL2462R
Indoor Unit Outdoor Unit
O. D. 3/4" (19.05mm)
Evaporator
Wide tube
O. D. 3/4" (19.05mm)
Wide tube service valve
Accumulator
Capillary
Sub-condenser
High pressure switch
HP
S
HGBV
Condenser
2201_M_S
LP
Compressor
Narrow tube
O. D. 3/8" (9.52 mm)
O. D. 3/8" (9.52 mm)
Narrow tube service valve
– 22 –
Capillary
tube
Condenser
Strainer
Sub-condenser
2202_M_S
SM830092
8. INSTALLATION INSTRUCTIONS
1) Tubing Length
• Refrigerant tubing between the indoor and outdoor units should be kept as short as
INDOOR UNIT
Tubing length (L)
possible.
• Select and decide the installation location so that the length of the refrigerant tubing
Elevation difference (H)
OUTDOOR UNIT
will be within the limits given in Table 1.
Fig. 1
Table 3
Model Length at Shipment Length (L) Difference (H) Additional Refrigerant
C2462R, CL2462R 23 132 50 0.43
*
If total tubing length becomes 23 to 132 ft. (max.), additional refrigerant (R410A) charge of 0.43 oz./ft. is required. No additional charge of compressor oil is necessary.
Max. Allowable Tubing Limit of Tubing Limit of Elevation Required Amount of
(ft.) (ft.) (ft.) (oz./ft.)
0711_M_I
*
– 23 –
SM830092
8. INSTALLATION INSTRUCTIONS
2) Selecting the Installation Site
Indoor Unit
AVOID:
areas where leakage of flammable gas may be expected. places where large amounts of oil mist exist. (Fig. 2) direct sunlight. locations near heat sources which may affect performance of the unit. locations where external air may enter the room directly. This may cause “sweating” on the air discharge ports, causing them to spray or drip. (Fig. 3) locations where the remote control unit will be splashed with water or affected by dampness or humidity.
Indoor unit
Outside drainage
Drain hose
2203_M_S
Fig. 2
DO:
select an appropriate position from which every corner of the room can be uniformly air-conditioned. select a location that will hold weight of the unit. select a location where the tubing and drain pipe have the shortest run to the outside. (Fig. 2) allow room for operation and maintenance as well as unrestricted air flow around the unit. (Fig. 3a and 3b) Install the unit within the maximum elevation difference above or below the outdoor unit and within a total tubing length from the outdoor unit as detailed in Table 1 and Fig. 1 on the previous page.
6 inches
min.
INDOOR UNIT
CAUTION
6 inches min.
Front View
Fig. 3a
For stable operation of the air conditioner, do not install wall-mounted type indoor units less than 5 ft. from floor level.
Fig. 3b
6 inches
min.
2204_M_S
Indoor Unit
Wall
Minimum height from floor level 5 ft.
Floor level
2205_M_S
– 24 –
SM830092
8. INSTALLATION INSTRUCTIONS
Outdoor Unit
AVOID:
heat sources, exhaust fans, etc. Fig. 4 damp, humid or uneven locations.
DO:
choose a place as cool as possible. choose a place that is well ventilated and outside air temperature does not exceed maximum 115 °F constantly. allow enough room around unit for air intake/ exhaust and possible maintenance. Fig. 5 provide a solid base; about 6 inch above grond level to reduce humidity and possible water damage in the unit and decrease service life. Fig. 6 use lug bolts or equivalent to bolt down unit, reducing vibration and noise.
CAUTION
Min. 1 inch
Hot air
4 in.
Air in
Out­door unit
Min. 2 ft.
Min. 1 inch
0931_C_I
Exhaust fan
Heat source
Fig. 4
Obstacle above
Air dis­charge
Ground
Fig. 5
Air in
0591_C_I
Min. 7 ft.
0932_C_I
If more than 2 outdoor units are installed in the same location, keep at least 3 meters away from the neighboring unit to avoid influence of air discharge.
Air discharge chamber for top discharge
Install the air-discharge chamber in the filed when:
it is difficult to keep a space of minimum 2 ft. between the air-discharge outlet and the obstacle. the air-discharge outlet is facing the sidewalk and discharged hot air can annoy the passers-by. Refer to Fig. 6 and Fig. 7.
– 25 –
Air discharge
Concrete block 4 inch 1 ft. 4 inch beams or equal
Anchor bolts (4 pieces)
Min. 6 inch
0934_C_I
Fig. 6
Air discharge
0426_C_I
Fig. 7
SM830092
8. INSTALLATION INSTRUCTIONS
IMPORTANT
Wind shield (air discharge side)
Front
3 -
ø1-9/16"
hole
6 -
ø15/64" hole
9-27/32"21-5/8"15/16"
5-3/16"
22-7/16"1/2"
23-15/32"
21-13/16"
5-5/32"9-27/32"9-27/32"1-1/16"
21-13/16"
Wind Shield for "CL" Model
It is recommended to use wind shields for "CL" model (Fig. 5b). "CL" model is designed to use in low outdoor temperature conditions.
General
When the outdoor unit is installed in a position exposed to strong wind (like seasonal winds with low air tempera­ture in winter), a suitable wind shield must be installed on the outdoor unit.
This unit is designed so that the fan of the outdoor unit runs at low speed when the air conditioner is operated at low outdoor air temperatures. When the outdoor unit is exposed to strong wind, the system pressure drops because of the freeze protector.
Fig. 5b
Recommended outer dimensions of wind shield (field supply)
For outer dimensions of the wind shield, see Fig. 5c.
CL2462R
Fig. 5c
SM830092
– 26 –
8. INSTALLATION INSTRUCTIONS
3) Electrical Wiring General Precautions on Wiring
(1) Before wiring, confirm the rated voltage of
the unit as shown on its nameplate, then carry out the wiring closely following the wiring diagram.
Provide a power outlet to be used
(2)
exclusively for each unit, and a power supply disconnect and circuit breaker for overcurrent protection should be provided in the exclusive line.
(3) T
o prevent possible hazards from
insulation
failure, the unit must be grounded.
(4) Each wiring connection must be done in
accordance with the wiring system diagram. Wrong wiring may cause the unit to misoperate or become damaged.
(5) Do not allow wiring to touch the refrigerant
tubing, compressor, or any moving parts of the fan.
(6) Unauthorized changes in the internal
wiring can be very dangerous. The manufacturer will accept no repsonsibility for any damage or misoperation that occurs as a result of such unauthorized changes.
(7) Regulations on wire diameters differ from
locality to locality. For field wiring rules, please refer to your LOCAL ELECTRICAL CODES before beginning. You must ensure that installation complies with all relevant rules and regulations.
– 27 –
SM830092
8. INSTALLATION INSTRUCTIONS
7-2. Recommended Wire Length and Wire Diameter for Power Supply System
Time Delay Fuse or Circuit Capacity
Models
*1
Power Supply
(A)
(B)*1 Inter-unit
Wiring
AGW #14
C2462R, CL2462R 64 ft. (AWG #12) 35 A
132 ft.
*1 Refer to the Wiring System Diagrams (See below diagram) for the meaning of “A” and “B.”
AWG = American Wire Gauge
Disconnect SW
1 2
G
4
(Field supply)
Ground
(B)
1 2
G
4
NOTE
To access the electrical component box, open the air intake grille and remove the electrical component box cover.
7-3. Wiring System Diagram
Outdoor Unit: “C”, “CL” models Single-phase
Indoor Unit Outdoor Unit
60 Hz, 208/230 V
L1 L2
(A)
G
Ground
– 28 –
SM830092
9. ELECTRICAL DATA
Electrical characteristics
Indoor model: KS2462R / Outdoor model: C2462R, CL2462R
Indoor Unit Outdoor Unit
Fan Motor Fan Motor Compressor
Performance at 230 - 208 V / 1 phase / 60 Hz
A 0.38 - 0.37 0.90 - 0.90 8.8 - 9.6 10.1 - 10.9
Rating conditions
kW 0.08 - 0.07 0.18 - 0.17 2.02 - 2.00 2.25 - 2.24
A 0.38 - 0.37 0.90 - 0.90 11.1 - 12.4 12.4 - 13.7
Full load conditions
kW 0.08 - 0.07 0.18 - 0.17 2.55 - 2.58 2.81 - 2.32
Starting amperes A 1 - 1 1 - 1 61 - 55 63 - 57
Complete Unit
Rating Conditions : Indoor Air Temperature 80 °F DB / 67 °F WB
Outdoor Air Temperature 95 °F DB
Full Load Conditions : Indoor Air Temperature 80 °F DB / 67 °F WB
Outdoor Air Temperature 115 °F DB
– 29 –
SM830092
10. ELECTRICAL WIRING DIA GRAMS
(1) Indoor Unit
KS2462R
1
• Electric Wiring Diagram
FAN MOTOR
FMI
GRN / YEL
G
G
TERMINAL
PLATE
WHT
BLK
G
GRN RED
1 2 G 4
FROM
OUTDOOR UNIT
BLK
VLT
YEL
ORG
87654321 87654321
CONNECTOR
[WHT]
FLP
PNK
BRN
GRY
WHT
CONNECTOR
[WHT]
CAPACITOR
PNK BRN GRY WHT
VLT ORG YEL
BLK
[WHT] [WHT]
1
1
2
2
3
3
4
4
5
5
WHT
BLU BLU BLU BLU
FLAP MOTOR [UPPER]
CONNECTOR
[WHT] [GRN] [BLK]
FLP
*
FLAP MOTOR [LOWER]
WHT
1
1
BLU
2
2
BLU
3
3
BLU
4
4
BLU
5
5
1 2 3 4 5
1 2 3 4 5
GRN
w
G
FM
w w
HH
w
H
w
M
w
L
w
LL
1 2
FLAP1
3
5P [WHT]
4 5
1 2
FLAP2
3
5P [BLK]
4 5
135 135
SUP 5P [WHT]
PRY 3P [RED]
SEC 2P [WHT]
RECEIVER 3P [WHT]
LAMP 4P [WHT]
CONTROLLER
ROOM/COIL 4P [WHT]
WHT
1
WHT
313
121
3 2 1
1 2 3 4
BRN BRN
2 3
WHT
2
GRY
1
GRY WHT
1
GRY
2
GRY
3
GRY
4
P
S
1
1
2
2
3
3
4
4
5
5
6
6
7
7
COIL THERMISTOR (TH1)
BLK
1
1
BLK
2
2
BLK
3
3
BLK
4
4
ROOM THERMISTOR (TH2)
8512-5253-714XX-1 (KS2432A)
POWER
TRANSFORMER
IND LAMP ASSY
– 30 –
SM830092
10. ELECTRICAL WIRING DIA GRAMS
Outdoor Unit
C2462R
• Electric Wiring Diagram
7
TERMINAL PLATE (6P)
TO INDOOR UNIT
L1 L2
G
POWER SUPPLY
60Hz 1ø 208V/230V
RED
1 2
WHT
G
WHT
4
L1
RED
L2
2Y
13
8
5
6
24
RED
WHT BLK
RED
2P (WHT)
1
1
2
2
PS PS
1
1
2
2
2P (GRN)
BLK BLK
RED RED
63PH
63PL
EARTH
TERMINAL
GRN/YEL
EARTH
TERMINAL
YEL
52C
BRN
A
B
C
RED
U
RED
R
CM
WHT
BLK
BLK
BLU
S
BLU
TWSVR
RC1
WHT
13
14
RED
BRN BRN
23S
BLK
3
L
H
6
2
C
31
776
8 8
YEL
1Y
8P
(WHT)
7
5
14
8
32
RC2
PNK
BRN
GRY
GRY
WHT
VLT
P
1
32
54
6
3
1
54
2
S
PNK
BRN
GRY
GRY
WHT
VLT
FMO
49FO
– 31 –
854-2-5269-160-00-0
SM830092
10. ELECTRICAL WIRING DIA GRAMS
Outdoor Unit
C2462R
• Schematic Diagram
TERMINAL PLATE (6P)
– 1
– 2
– G
– 4
– L1
– L2
52C
2Y
2Y
2Y52C
1
63PH
2
2
63PL
1
1
49FO
2
1Y HM
65
FMO
C
23S
LH
RC1
R
S
C
1Y
12
RC2
CM
52C
854-2-5269-160-00-0
Symbols Description
CM FMO 52C 49FO 63PH 63PL Low Pressure Switch 23S RC1, 2 1Y, 2Y
Compressor Motor Outdoor Fan Motor Compressor Motor Magnetic Contactor Outdoor Fan Motor Thermal Protector High Pressure Switch
Fan Speed Control Thermostat Running Capacitor Auxiliary Relay Terminal Base Connector
– 32 –
SM830092
10. ELECTRICAL WIRING DIA GRAMS
Outdoor Unit
CL2462R
BLK
21
BLK
TEMP
2P (WHT)
BRN
21
BRN
SEC
2P (WHT)
WHT
31
WHT
PRY
3P(WHT)
RED
31
RED
HGBV
3P(YEL)
CONTROLLER (CR-CL2432)
9 7 5
HCOM M L
FMO
31
9P(WHT)
AC14V
AC208V
BRN
TH
TR
AC230V
YEL VLT WHT BLK GRY BRN PNK
HGBV
S7
P 87
8
65
65
43
43
21
21
YEL VLT WHT GRY GRY BRN PNK
854-2-5269-159-00-0
49FO
FMO
13
ST 31 R
1Y
BRN
24
13
8
BRN BLK
WHT
52C
EARTH
TERMINAL
14
UV W 32
B
RC2
ORG
RED
WHT
BLK RED
MGSW 3
ORG
E
GRN/YEL
ORG
ORG
6
5
7
3P(RED)
SUP
2
1
RED
3P(BLU)
1
GRY
• Electric Wiring Diagram
GRN/YEL
A
RED
BRN
RED
WHT
RED
WHT
WHT
8P
P 21
2P
P 21
2P
P 21
2P
(WHT)
S 21
(GRN)
S 21
(WHT)
S 21
(WHT)
RC1
RED RED
BLK BLK
WHT WHT
WHT BLK
R
63PL
63PH
CH
S
CM
C
PLATE (6P)
1
2
TERMINAL
4
G
L1
L1
L2
TO INDOOR UNIT
L2
G
60Hz 1ø 208V/230V
POWER SUPPLY
– 33 –
EARTH
TERMINAL
SM830092
10. ELECTRICAL WIRING DIA GRAMS
Outdoor Unit
CL2462R
TERMINAL PLATE (6P)
-1
-2
-G
-4
-L1
-L2
52C
C
1Y
R
CM
• Schematic Diagram
F1 (3A)
1
1 3
3
52C
52C
1
CH
63PL
1Y
RC1
S
2
F2 (3A)
3
49FO
1
63PH
2
1Y
4
2
1
3
52C
RY2
HLM
RC2
RY1
FMO
1
75 9
65 7
RY3
1
HGBV
2
3
1
COMCOM
RY1
RY2
RY3
CR-CL2462R
CONTROLLER
TEMP
L
PRY
M
HGBV
DC12V
SEC
TH
1 2
OUTDOOR TEMPERATURE
TR
1
AC 208V
3
230V
1
AC 14V
2
854-2-5269-159-00-0
Symbols Description
CM CH FMO 52C 49FO 63PH 63PL HGBV TR TH RC1, 2 RY1~3, 1Y CR-CL2432 F1, 2
Compressor Motor Crankcase Heater Outdoor Fan Motor Compressor Motor Magnetic Contactor Outdoor Fan Motor Thermal Protector High Pressure Switch Low Pressure Switch Hot Gas Bypass Valve Power Transformer Thermistor (Outdoor Temperature) Running Capacitor Auxiliary Relay Outdoor Controller Fuse Terminal Base Connector Terminal
– 34 –
SM830092
11. PROCESSES AND FUNCTIONS
(1) Room Temperature Control
The Unit adjusts room temperature by turning the outdoor unit’s compressor ON and OFF. This process is controlled by the thermostat located in the indoor unit. The figures shows how each part of the system performs when the room temperature changes and the thermostat activates the compressor to start (thermo ON) or stop (thermo OFF). Fig. 1 shows about the cooling cycle.
Signal from remote control unit
3 minutes 3 minutes 3 minutes 3 minutes 3 minutes 3 minutes 3 minutes
T + 2 °F
T °Fset temp.
More than
5 minutes
ON OFF ON OFF ON OFFCompressor
Thermo.
OFF
Thermo. ON
Thermo. OFF
3 minutes5 minutes
Thermo. ON
Thermo. ON
Room temp.
Thermo. ON
Thermo. OFF
Outdoor fan
Indoor fan
ON OFF ON OFF ON OFF
Set speed
Chart Summary and Explanations
Once the compressor starts, it keeps running for 5 minutes. Once the compressor stops, it will not start running again for 3 minutes. If you change the operation mode during the cooling cycle, the control circuit stops the
compressor for 3 minutes. For 5 minutes after the compressor is first turned on, and for 3 minutes after it is turned off,
the compressor is not controlled by the room sensor. Thermo ON: When room temperature rises 1 °F above the set temperature T˚, (T ˚+1 °F):
Compressor ON
Thermo OFF: When the room temperature is equal to or below the set temperature T˚:
Compressor OFF
2212_M_S
Fig. 11
– 35 –
SM830092
11. PROCESSES AND FUNCTIONS
(2) Dry Operation (Dehumidification)
Dry operation uses the ability of the cooling cycle to remove moisture from the air, but by running at low level to dehumidify without greatly reducing the room temperature. The air conditioner repeats the cycle of turning ON and OFF automatically as shown in the chart below according to the room temperature.
Room temp.
Cooling operation
T + 4 °F
Set temp. T °F
T – 2 °F
Room temp. 59 °F
Dry A zone
Compressor : FMI (indoor fan) :
Dry B zone
Compressor : FMI (indoor fan) :
Monitor zone Both the indoor and outdoor units stop.
Continuous operation L (low speed) / LL (very low speed) intermittent ventilation
only while the compressor is ON.
Intermittent operation (ON for 3 minutes and OFF for 9 minutes) L (low speed) / LL (very low speed) intermittent ventilation
only while the compressor is ON.
Fig. 12
2213_M_S
NOTE
Intermittent ventilation occurs by switching the indoor fan speed between L LL. Dry operation does not occur when the room temperature is under 59°F, which is the monitor zone. When the compressor stops, the indoor fan stops as well.
– 36 –
SM830092
11. PROCESSES AND FUNCTIONS
(3) Freeze Prevention
Freeze Prevention keeps the indoor heat exchange coil from freezing. Freezing reduces the efficiency of the unit, and frost buildup on the coil blocks cool air circulation from the indoor unit’s fan.
Thermo. OFF
Room temp.
T + 4 °F
Set temp. T °F
Thermo. ON
Indoor heat exch. coil temp.
30 °F
Compressor
Indoor fan
When the compressor has been running for 6 minutes or more and the temperature of the indoor heat exchange coil falls below 30°F, the control circuit stops the compressor for at least 6 minutes. The compressor does not start again until the temperature rises above 46°F or 6 minutes has elapsed.
More than
6 minutes
More than
10 minutes
ON ON ON ON
Set speed
More than
10 minutes
6 minutes
OFFOFF
Set speed
Fig. 13
Chart Summary and Explanations
2214_M_S
– 37 –
SM830092
11. PROCESSES AND FUNCTIONS
(4) Outdoor Fan Speed Control
(1) C2462R Type
In low outdoor temperature, the outdoor fan is set automatically from HIGH to LOW to prevent the indoor heat exchanger from freezing.
When the outdoor temperature falls below 78 °F, the outdoor fan is set from HIGH to LOW automatically. When the outdoor temperature rises to 82 °F, the outdoor fan is set from LOW to HIGH automatically.
(2) CL2462R Type
In low outdoor temperature, the outdoor fan is set automatically from HIGH to MED, LOW to prevent the indoor heat exchanger from freezing.
When the outdoor temperature falls below 77 °F, the outdoor fan is set from HIGH to MED automatically. When the outdoor temperature rises to 81 °F, the outdoor fan is set from MED to HIGH automatically.
When the outdoor temperature falls below 59 °F, the outdoor fan is set from MED to LOW automatically. When the outdoor temperature rises to 63 °F, the outdoor fan is set from LOW to MED automatically.
When the outdoor temperature falls below 50 °F, the hot gas bypass valve opens and keeps the pressures up by allowing some hot gas to be bypassed to the suction of the compressor.
FAN ROTATION RPM
HGBV
(HOT GAS
BYPASS VALVE)
760
380
230
ON
M
L
OFF
47
(8.3)50(10)
OUTDOOR AIR TEMPERATURE °F DB
59
(15)63(17)
77
(25)81(27)
H
2217_X_S
– 38 –
Fig. 14
SM830092
12. SERVICE PROCEDURES
(1) Troubleshooting
1) Check before and after Troubleshooting
Many problems may happen because of wiring or power supply problems, so you should check these areas first. Problems here can cause false results in some of the other tests, and so should be corrected first.
Check power supply wiring
1
(a) Single-phase
Check that power supply wires are correctly connected to L1 and L2 on the 6P terminal in the outdoor unit.
Check inter-unit wiring
2
Check that inter-unit wiring (AC 230 - 208 V Line voltage) is correctly con­nected between the indoor unit and outdoor unit.
Single-phase outdoor unit
Indoor Unit Outdoor Unit
1 2
G
4
Disconnect switch (Field supply)
Inter-Unit Wiring (Line voltage)
230V/208V
230V/208V Grounding line 230V/208V
(B)
6P Terminal4P Terminal
1 2 G
(A)
4 L1 L2
G
Power supply Single phase 230V/208V 60Hz
Grounding line
2206_M_S
Fig. 15
Check power supply
3
Check that voltage is within the specified range (±10 % of the rating). Check that power is being supplied.
If the following troubleshooting must be done with power being supplied, be careful not to touch any uninsulated live part that can cause ELECTRIC SHOCK.
Check the lead wires and connectors in indoor and outdoor units.
4
Check that the sheath of lead wires is not damaged. Check that the lead wires are firmly connected at the terminal plate. Check that the wiring is correct.
Reference
5
Condition of general cooling operation (Thermo. ON)
SWEEP .................. ON
Indoor fan speed .... HIGH
– 39 –
SM830092
12. SERVICE PROCEDURES
2) Air Conditioner does not Operate
Circuit breaker trips (or fuse blows).
1
(a) When the circuit breaker is set to ON, it is tripped soon.
• There is a possibility of ground fault.
• Check insulation resistance. If resistance value is 2 M or less, it is a defect of insulation.
(Example)
1 3
Outdoor
unit
L1
Circuit breaker
*Set the circuit breaker to OFF.
Power supply cords
+ +
Ground
L2
G
2
1
+
2
+
G
4
+
Inter-unit power line
Indoor
4
unit
1
+
2
+
G
4
+
1
Remove power supply cords from the terminal plate in the outdoor unit.
• Check insulation resistance of power supply cords.
OK
Remove inter-unit power line
2
from the terminal plate in the outdoor unit.
• Check insulation resistance of outdoor unit.
OK
3
Remove inter-unit power line from the terminal plate in the indoor unit.
• Check insulation resistance of indoor unit.
NO
NO Insulation of
NO
Execute rewiring.
outdoor unit is defective.
Insulation of outdoor unit is defective.
• Check insulation resistance of electrical parts in the outdoor unit.
• Check insulation resistance of electrical parts in the indoor unit.
OK
Inter-unit power lines are defective.
Execute rewiring.
1032_X_S
SM830092
– 40 –
12. SERVICE PROCEDURES
(b) Circuit breaker trips in several minutes after turning the air conditioner on.
• There is a possibility of short circuit.
• Check capacity of circuit breaker.
NO
Is capacity of circuit breaker sufficient ?
• Check resistance of outdoor fan motor winding.
• Check resistance of compressor motor winding.
• Check resistance of flap motor winding.
Neither indoor unit nor outdoor unit runs.
2
A. Power is not supplied
Replace it with a suitable one. (= larger capacity)
2218_X_S
• Check power supply. Is power being supplied
NO
to outdoor unit ?
B. Check remote control unit.
• Try to run both indoor and
outdoor units with another remote control unit.
OK
The other remote control unit is defective.
– 41 –
Circuit breaker is tripped.
Power failure.
Reset the breaker.
Wait for recovery or consult power supply company.
0615_X_S
0616_X_S
SM830092
12. SERVICE PROCEDURES
C. Check “Operation selector” switch in the indoor unit.
• Has “Operation selector” switch been set to ON
YES
position ?
NO
Set “Operation selector” switch to ON.
But neither unit runs.
Switch Ass’y or P.C.B. Ass’y in the indoor unit is defective.
D. Check compressor motor protectors. (a) High pressure switch (63PH)
• Check high pressure switch. Does high pressure switch actuate ? (63PH)
Disconnect the socket from 2P (WHT) connector. Check the continuity between No.1 and No.2 poles of the socket.
IND. LAMP Ass’y or P.C.B. Ass’y in the indoor unit is defective.
0617_X_S
YES
• Is outdoor heat exchanger coil dirty or are there obstacles near air suction inlet of outdoor unit ?
NO
• Check if outdoor fan rotates. Refer to “Only outdoor fan does not run.”
E. Transformer in indoor unit.
• Check resistance of transformer winding. (TR1)
1033_X_S
YES
Clean heat exchanger coil or remove obstacles.
0618_X_S
– 42 –
SM830092
12. SERVICE PROCEDURES
F. Check. auxiliary relay. (1Y or 2Y)
• Check coil resistance of auxiliary relay. (1Y or 2Y)
G. Check fuse on the P.C.B. Ass’y in the indoor unit.
0620_X_S
• Check fuse on the P.C.B. Ass'y in the indoor unit for continuity.
When the fuse blows.
• Check resistance of primary and secondary winding of transformer.
OK
• Check resistance of indoor fan motor winding.
OK
• Check coil of compressor motor magnetic contactor. (52C)
OK
• P.C.B. Ass'y is defective.
2219_X_S
– 43 –
SM830092
12. SERVICE PROCEDURES
3) Outdoor Unit does not Run.
A. Check COOL / FAN selector switch in the remote control unit.
• Is MODE selector button set to COOL ?
B. Check set temperature.
Try to lower set temperature by Temperature setting button “COOLER”.
YES
• Set “Operation selector” switch to TEST in the indoor unit.
Outdoor unit runs.
Is room temperature too low ?
NO
Set to COOL.
2220_X_S
NO
• Try to run both indoor and outdoor units with another remote control unit.
OK
The other remote control unit is defective.
2221_X_S
– 44 –
SM830092
12. SERVICE PROCEDURES
C. Check compressor motor magnetic contactor.
• Check coil resistance of compressor motor magnetic contactor. (52C)
D. Check indoor unit P.C.B.
• Check P.C.B. Ass’y.
• Check voltage between terminals No.2 and No.4 at terminal plate.
1035_X_S
No voltage appears.
P.C.B. Ass’y is defective.
0628_X_S
E. Check outdoor unit P.C.B. (CL2462R Type)
• Check P.C.B. Ass’y.
• Check voltage between terminals L1 and L2 at terminal plate.
No voltage appears.
P.C.B. Ass’y is defective.
1036_X_S
– 45 –
SM830092
12. SERVICE PROCEDURES
4) Indoor Unit does not Run.
(Indoor fan and flap motor do not run.)
P.C.B. Ass’y is defective.
0630_X_S
5) Some Part does not Operate.
A. Indoor fan does not run.
• Check fan rotation. Rotate the fan gently once or twice by hand.
Fan cannot be rotated.
Check fan casing for foreign matter on the inside.
Fan motor burnout or foreign matter in bearing.
Remove foreign matter or repair.
Repair or replace.
• Check resistance of fan motor winding.
OK
• Check fan motor capacitor. OK
Relay RY1 or RY2 on the P.C.B. Ass’y is defective.
B. Flap motor does not run.
• Check resistance of
flap motor winding.
OK
P.C.B. Ass’y or remote control unit is defective.
0631_X_S
2222_X_S
– 46 –
SM830092
12. SERVICE PROCEDURES
6) Outdoor Fan does not Run.
• Check fan rotation. Rotate the fan gently once or twice by hand.
• Check resistance of fan motor winding.
OK
• Check fan motor capacitor
• Check continuity between terminals on the compressor motor magnetic contactor.
Fan cannot be rotated.
• Check fan casing for foreign matter on the inside.
• Fan motor burnout or foreign matter in bearing.
Remove foreign matter or repair.
Repair or replace.
0633_X_S
7) Outdoor Fan Speed is not Switched from High to Low even when the Outdoor Temperature Falls below 78
• Check the thermostat (23S).
1037_X_S
°F. (C2462R Type)
8) Outdoor Fan Speed is not Switched from High to Med even when the Outdoor Temperature Falls below 77
°F.
Outdoor Fan Speed is not Switched from Med to Low even when the Outdoor Temperature Falls below 59
• Check outdoor unit P.C.B. Ass’y
°F. (CL2462R Type)
OK
• Check resistance of outdoor temp sensor.
0722 _X_S
SM830092
– 47 –
12. SERVICE PROCEDURES
9) Outdoor Fan does not Run for CL2462R.
• Check fuse on PCB Ass’y in outdoor unit for continuity.
If fuse blows,
• Check resistance of primary winding of transformer. (TR)
10) Compressor does not Run.
1038_X_S
• Check compressor motor capacitor (RC1).
OK
• Check PTC. OK
• Check resistance of compressor motor winding.
Wait for 30 minutes until com­ pressor has cooled.
Compressor runs.
Compressor internal thermal protector is operated.
• Check power supply voltage. Is voltage abnormally low?
NO
• Is outdoor heat exchanger coil dirty or are there obstacles near air suction inlet?
1039_X_S
– 48 –
SM830092
12. SERVICE PROCEDURES
11) Poor Cooling.
Check installation position of remote control unit.
• Does cool air from air condi­ tioner reach remote control unit directly ?
• Is wide tube between indoor unit and outdoor unit insulated ?
YES
• Measure temperatures of suction and discharge air of indoor unit.
Temperature difference between suction and discharge air is large enough (Approx. 10 deg. or more).
• Check clogging of air filter.
• Is fan speed set to LOW ?
YES
NO
Temperature difference is small.
Possibility of refrigerant shortage.
Air filter is clogged.
YES
Change installation position of remote control unit.
Insulate wide tube and then execute taping with narrow tube.
Charge refrigerant
Clean filter.
Set fan speed to either HIGH or MEDIUM.
• Review cooling load estimate, if performance of air conditioner is normal.
12) Excessive Cooling.
• The set temperature is too low.
• Is the remote control unit installed at a place where it can detect the room temperature properly ?
YES
NO
– 49 –
Reduce cooling load or replace the unit with higher cooling capacity.
1040_X_S
Set the temperature to higher value using temperature setting button of the remote control unit.
Change installation position of the remote control unit.
0637_X_S
SM830092
12. SERVICE PROCEDURES
(2) A Sensor is Defective.
Indoor (heat exchanger) coil temp. Sensor is defective.
1
(a) Open (=No continuity in sensor)
Compressor and outdoor fan repeat ON for 10 minutes and OFF for 6 minutes when sensor opens.
(b) Short
“Freeze Prevention” does not operate when dehumidified water is frozen on the indoor coil.
Room temp. Sensor (in the remote control unit) is defective.
2
(a) Open (=No continuity in sensor)
Neither outdoor fan nor compressor runs.
(b) Short
Outdoor fan and compressor do not stop. — Excessive cooling.
– 50 –
SM830092
12. SERVICE PROCEDURES
(3) Checking the Electrical Components
1) Measurement of Insulation Resistance
The electrical insulation is acceptable when the resistance exceeds 2 M.
Power Supply Wires
1
Clamp the earthed wire of the Power Supply wires with a lead clip of the insulation resistance tester and mea­sure the resistance by placing a probe on either of the power wires. (Fig. 16)
Then measure the resistance between the earthed wire and the other power wires. (Fig. 16)
Indoor Unit
2
Clamp an aluminum plate fin or copper tube with the lead clip of the insulation resistance tester and measure the resistance by placing a probe on the terminal plate (Fig. 17)
Probe
Copper tube or metallic part
Clip
Clip
Earthed wire
Insulation tester
Terminal plate
0638_X_S
Insulation tester
Probe
0639_X_S
Fig. 16
Fig. 17
Outdoor Unit
3
Measure the resistance by placing a probe on the terminal plate in the same manner as explained above 2 . (Fig. 17)
Measurement of Insulation Re-
4
sistance for Electrical parts
• Disconnect the connector of the desired electric part from terminal plate, P.C.B. Ass’y, etc. (Fig. 18)
Similarly, disconnect the lead wires from compressor, capacitor, etc. (Fig. 19)
• Measure the resistance in the same manner as illustrated on the right.
Refer to Electrical Wiring Diagram.
NOTE
If the probe does not enter the hole because the hole is too narrow, use a probe with a thinner pin.
Metallic part
– 51 –
Clip
Copper tube or metallic part
Clip
Insulation tester
From fan motor, compressor and other parts.
Probe
Insulation tester
Probe
0640_X_S
0641_X_S
Fig. 18
Fig. 19
SM830092
12. SERVICE PROCEDURES
2) Checking the Protective Devices
• Disconnect the connector, which consists of P (plug) and S (socket) when you want to check the protective device.
• Then check continuity among plug’s (and/or socket’s) terminal as in Fig. 20.
• The Protective Device is proved normal if there is a continuity between terminals.
socket
Multimeter
0642_X_S
Indoor fan motor thermal protector (49FI) . . . . . . Indoor unit
1
• Disconnect the connector which leads to the indoor fan motor (FMI).
• Check the socket’s terminals.
Compressor motor thermal protector . . . . . . Outdoor unit
2
• Disconnect the wires from terminals of compressor.
• Check the terminals of compressor.
Outdoor fan motor thermal protector (49FO) . . . . . . Outdoor unit
3
• Disconnect both the connector which leads to the outdoor fan motor (FMO).
• Check socket’s terminal.
Fig. 20
– 52 –
SM830092
12. SERVICE PROCEDURES
3) Checking the Electrical Parts
Power transformer ...........................Indoor unit *Measure the coil resistance.
1
Primary230-208 V ; Measure the resistance between two WHT lead wire terminals
of socket connected to power transformer.
Secondary 19 V ; Measure the resistance between two BRN lead wires.
Power transformer (TR) ................. Outdoor unit *Measure the coil resistance.
2
Primary 230-208 V ; Measure the resistance between two WHT lead wire terminals
of socket jointed to power transformer.
Secondary 19 V ; Measure the resistance between two BRN lead wires.
Indoor fan motor (FMI) ............... Indoor unit *Measure the coil resistance.
3
Measure the resistance between each terminal of the socket connected to the
indoor fan motor.
Outdoor fan motor (FMO) ........... Outdoor unit *Measure the coil resistance.
4
Measure the resistance in the same manner as explained above 2 .
Motor capacitor ............ Both in indoor and outdoor unit
5
Remove the lead wires from the
capacitor terminals, and then place a probe on the capacitor terminals as shown in Fig. 21. Observe the deflec­tion of the pointer, setting the resis­tance measuring range of the multim­eter to the maximum value.
The capacitor is “good” if the pointer
bounces to a great extent and then gradually returns to its original posi­tion.
NOTE
The range of deflection and the deflection time differ according to the capacity of the
capacitor.
Multimeter
– 53 –
Compressor motor capacitor
Fig. 21
Fan motor capacitor
1041_X_S
SM830092
12. SERVICE PROCEDURES
Continuity of fuse on P.C.B.
6
Ass’y
• Check for continuity using a multim­eter as shown in Fig. 22.
NOTE
Method Used to Replace Fuse on PCB Ass’y
1. Remove the PCB Ass’y from the
electrical component box.
2. Remove the fuse from PCB Ass’y
using pliers while heating the sol­dered leads on the back side of the PCB Ass’y with a soldering iron (30W or 60W). (Fig. 23)
3. For replacement, insert a fuse of the
same rating to the intended position and solder it. (Allow time to radiate heat during sol­dering so that the fuse does not melt.)
When replacing the
CAUTION
fuse, be sure not to break down the varistor.
Fuse
1042_X_S
Fig. 22
Soldering iron
PCB Ass’y
Fuse Varistor
Pliers
1043_X_S
Fig. 23
– 54 –
SM830092
12. SERVICE PROCEDURES
CAUTION
11. REFRIGERANT R410A: SPECIAL PRECAUTIONS WHEN INSTALLING UNIT
11-1. Characteristics of New Refrigerant R410A 11-1-1. What is New Refrigerant R410A?
R410A is a new refrigerant that contains two types of pseudo-non-azeotropic refrigerant mixture which do not adversely affect the earth’s ozone layer. Its refrigeration capacity and energy efficiency are about the same level as the conventional refrigerant, R22.
11-1-2. Components (mixing proportions)
HFC32 (50%) / HFC125 (50%)
11-1-3. Characteristics
Less toxic, more chemically stable refrigerant The composition of refrigerant R410A changes whether it is in a gaseous phase or liquid phase. Thus, when
there is a refrigerant leak the basic performance of the air conditioner may be degraded because of a change in composition of the remaining refrigerant. remaining refrigerant with the refrigerant recovery unit. Then, after evacuation, totally recharge the specified amount of refrigerant with the new refrigerant at its normal mixed composition state (in liquid phase).
Therefore, do not add new refrigerant.
Instead, recover the
When refrigerant R410A is used, the composition will differ depending on whether it is in gaseous or liquid phase, and the basic performance of the air conditioner will be degraded if it is charged while the refrigerant
is in gaseous state.
Thus, always charge the refrigerant while it is in liquid phase.
Ether-type oil is used for compressor oil for R410A-type units, which is different from the mineral oil used for R22. Thus more attention to moisture prevention and faster replacement work compared with conventional models are required.
11-2. Checklist Before Installation
Use a clutch-type flare tool for R410A or the conventional flare tool. Note that sizes of the resultant flares differ between these two tools. Where a conventional flare tool is used, make sure to observe A Specification
(amount of protrusion).
Diameter of tube (ø) D
ø6.35 (1/4") 0 – 0.5 mm 1.0 – 1.5 mm
ø19.05 (3/4") 0 – 0.5 mm 1.0 – 1.5 mm
Size of flare
Flare tool for R410A Conventional flare tool (for R22)
D
A Specification
D
A
Flare tool for R410A
A
Conventional flare tool (R22)
Flare nut: Because the new refrigerant R410A operates at 1.6 times higher pressure than the conventional
refrigerant R22, the flare nuts that came with the unit must be used.
– 55 –
SM830092
12. SERVICE PROCEDURES
Tubing precautions
Refrigerant R410A is more easily affected by dust or moisture compared to R22, thus be sure to temporarily cover the ends of the tubing with caps or tape prior to installation.
Never use 0.7mm-thick copper tubing or tubing which is less than 0.8mm in thickness, since air conditioners with R410A are subject to higher pressure than those using R22 and R407C.
Outer diameter: mm (inch) Tubing wall thickness: mm (inch)
Narrow tube ø6.35 (1/4") 0.8 (0.032) Wide tube ø19.05 (3/4") 1.0 (0.042)
No addition of compressor oil for R410A
No additional charge of compressor oil is required.
No use of refrigerant other than R410A
Never use a refrigerant other than R410A.
If refrigerant R410A is exposed to fire
Through welding, etc., toxic gas may be released when R410A refrigerant is exposed to fire. Therefore, be sure to provide ample ventilation during installation work.
Caution in case of R410A leak
Check for possible leak points with the special leak detector for R410A. If a leak occurs inside the room, immediately provide thorough ventilation.
– 56 –
SM830092
12. SERVICE PROCEDURES
11-3. Tools Specifically for R410A
For servicing, use the following tools for R410A
Tool Distinction Tool Name
Gauge manifold Charging hose Gas leak detector Refrigerant cylinder Charging cylinder Refrigerant recovery unit
Tools specifically for R410A
Tools which can be com­monly used for R22, R407C, and R410A
Vacuum pump with anti-reverse flow ( 1) (Solenoid valve-installed type, which prevents oil from flowing back into the
unit when the power is off, is recommended.) Vacuum pump ( 2) … can be used if the following adapter is attached. Vacuum pump adapter (reverse-flow prevention adapter) ( 3). (Solenoid valve-installed adapter attached to a conventional vacuum pump.) Electronic scale for charging refrigerant Flare tool Bender Torque wrench Cutter, reamer Welding machine, nitrogen gas cylinder
CAUTION
To prevent other refrigerants (R22, R407C) from being mistakenly charged to this unit, sizes of the service ports and flare nuts of the narrow tube service valve and wide tube service valve have been altered.
The above tools specifically for R410A must not be used for R22 and R407C. Doing so will cause malfunction of the unit.
For the above vacuum pump ( 1, 2) and vacuum pump adapter ( 3), those for R22-type units can be used for R407C-type. However, they must be used exclu­sively for R410A and never alternately with R22 and R407C.
SM830092
– 57 –
– 58 –
SM830092
Loading...