Sanyo C2432, CL2432 User Manual

INSTALLATION INSTRUCTIONS
W
– Split System Air Conditioner – COOL/DRY Model
ATTENTION
Use this manual when installing combined models of indoor unit KS2432A and outdoor unit C2432 or CL2432 only. On items not included in this manual, see the Installation Instructions (No. 85464179694003) packed in the outdoor unit model C2432 or CL2432.
Contents
Model Combinations
Combine indoor and outdoor units only as listed below.
Indoor Unit Outdoor Units
KS2432A C2432
CL2432
Power supply: 60Hz, single-phase, 208/230V
Units should be installed by a licensed contractor according to local code requirements.
Page
IMPORTANT!
Please Read Before Starting.................................. 1
1. GENERAL.......................................................... 2
1-1. Tools Required for Installation (not supplied) 1-2. Accessories Supplied with Indoor Unit 1-3. Optional Copper Tubing Kit 1-4. Type of Copper Tube and Insulation Material 1-5. Field Wiring 1-6. Additional Materials Required for Installation
2. INSTALLATION SITE SELECTION................... 3
2-1. Indoor Unit 2-2. Outdoor Unit
3. HOW TO INSTALL THE INDOOR UNIT ........... 5
3-1. Remove the Rear Panel from the Unit 3-2. Make a Hole 3-3. Install the Rear Panel on the Wall 3-4. Remove the Grille to Install the Indoor Unit 3-5. Shape the Indoor Side Tubing 3-6. Wiring Instructions 3-7. Recommended Wire Length and Diameter 3-8. Wiring Instructions for Inter-unit Connections 3-9. Mounting 3-10. Drain Hose
4. REFRIGERANT TUBING .................................. 13
4-1. Indoor Unit Tubing 4-2. Outdoor Unit Tubing 4-3. Connecting Tubing between Indoor and
Outdoor Units 4-4. Insulation of Refrigerant Tubing 4-5. Taping the Tubes 4-6. Finishing the Installation
5. REMOTE CONTROL UNIT INSTALLATION
POSITION ......................................................... 16
5-1. Mounting on a Wall
In Canada
SANYO FISHER COMPANY SANYO Canada Inc.
A DIVISION OF SANYO NORTH AMERICA CORPORATION 300 Applewood Crescent 21605 Plummer Street Concord, Ontario
85264189704003 © SANYO 2003 Chatsworth, CA 91311 U.S.A. L4K 5C7, Canada
IMPORTANT!
WARNING
WARNING
CAUTION
CAUTION
Please Read Before Starting
This air conditioning system meets strict safety and operat­ing standards. As the installer or service person, it is an important part of your job to install or service the system so it operates safely and efficiently.
For safe installation and trouble-free operation, you must:
Carefully read this instruction booklet before beginning.
Follow each installation or repair step exactly as shown.
Observe all local, state, and national electrical codes.
Pay close attention to all warning and caution notices given in this manual.
This symbol refers to a hazard or unsafe practice which can result in severe personal injury or death.
This symbol refers to a hazard or unsafe practice which can result in personal injury or prod­uct or property damage.
If Necessary, Get Help
These instructions are all you need for most installation sites and maintenance conditions. If you require help for a special problem, contact our sales/service outlet or your certified dealer for additional instructions.
In Case of Improper Installation
The manufacturer shall in no way be responsible for improper installation or maintenance service, including failure to follow the instructions in this document.
When Installing…
…In a Ceiling, Wall or Floor
Make sure the ceiling/wall/floor is strong enough to hold the unit’s weight. It may be necessary to construct a strong wood or metal frame to provide added support.
…In a Room
Properly insulate any tubing run inside a room to prevent “sweating” that can cause dripping and water damage to walls and floors.
…In Moist or Uneven Locations
Use a raised concrete pad or concrete blocks to provide a solid, level foundation for the outdoor unit. This prevents water damage and abnormal vibration.
…In an Area with High Winds
Securely anchor the outdoor unit down with bolts and a metal frame. Provide a suitable air baffle.
…In a Snowy Area (for Heat Pump-type Systems)
Install the outdoor unit on a raised platform that is higher than drifting snow. Provide snow vents.
When Connecting Refrigerant Tubing
• Use the flare method for connecting tubing.
• Apply refrigerant lubricant to the matching surfaces of the flare and union tubes before connecting them, then tighten the nut with a torque wrench for a leak-free con­nection.
• Check carefully for leaks before starting the test run.
When Servicing
SPECIAL PRECAUTIONS
When Wiring
ELECTRICAL SHOCK CAN CAUSE SEVERE PER­SONAL INJURY OR DEATH. ONLY A QUALIFIED, EXPERIENCED ELECTRICIAN SHOULD ATTEMPT TO WIRE THIS SYSTEM.
Do not supply power to the unit until all wiring and tubing are completed or reconnected and checked.
• Highly dangerous electrical voltages are used in this system. Carefully refer to the wiring diagram and these instructions when wiring. Improper connections and inadequate grounding can cause accidental injury or
death.
• Ground the unit following local electrical codes.
• Connect all wiring tightly. Loose wiring may cause over­heating at connection points and a possible fire hazard.
When Transporting
Be careful when picking up and moving the indoor and out­door units. Get a partner to help, and bend your knees when lifting to reduce strain on your back. Sharp edges or thin alu­minum fins on the air conditioner can cut your fingers.
• Turn the power OFF at the main power box (mains) before opening the unit to check or repair electrical parts and wiring.
• Keep your fingers and clothing away from any moving parts.
• Clean up the site after you finish, remembering to check that no metal scraps or bits of wiring have been left inside the unit being serviced.
Others
• Ventilate any enclosed areas when installing or testing the refrigeration system. Escaped refrigerant gas, on contact with fire or heat, can produce dangerously toxic gas.
• Confirm upon completing installation that no refrigerant gas is leaking. If escaped gas comes in contact with a stove, gas water heater, electric room heater or other heat source, it can produce dangerously toxic gas.
1
1. General
CAUTION
Parts Figure Qty Parts Figure Qty
12
1
1
1
1
1
Remote control unit
Insulation
Parts Figure Qty
12
Tapping screw
Truss-head Phillips 5/32×5/8" (4
×
16 mm)
2
2
1
1
AAA alkaline battery
Joint drain
Tube Assy Packing A
Packing B
Clamp
Rawl plug
25/32"×1-3/8"×3/16"
1-3/16"
×
2-3/8"×3/16"
Remote control holder
NOTE
This booklet briefly outlines where and how to install the air conditioning system. Please read over the entire set of instructions for the indoor and outdoor units and make sure all accessory parts listed are with the system before beginning.
1-1. Tools Required for Installation (not supplied)
1. Standard screwdriver
2. Phillips head screwdriver
3. Knife or wire stripper
4. Tape measure
5. Carpenter’s level
1-2. Accessories Supplied with Indoor Unit Table 1
6. Sabre saw or key hole saw
7. Hacksaw
8. Core bits
9. Hammer
10. Drill
11. Tube cutter
12. Tube flaring tool
13. Torque wrench
14. Adjustable wrench
15. Reamer (for deburring)
16. Pipe bending tool (spring bender)
1-3. Optional Copper Tubing Kit
Copper tubing for connecting the outdoor unit to the indoor unit is available in kits which contain the narrow and wide tubing, fittings and insulation. Consult your nearest sales outlet or A/C workshop.
For rear-left tubing, optional tube connection (C) (APR- EN46U1B) is necessary. See page 13. Also consult your nearest sales outlet or A/C workshop.
1-4. Type of Copper Tube and Insulation Material
If you wish to purchase these materials separately from a local source, you will need:
1. Deoxidized annealed copper tube for refrigerant tub­ing as detailed in Table 2.
When cutting tubing, add approximately 1' to 1'4" to each tube length to reduce vibration between the air conditioning units.
2
Table 2
Model
KS2432A
Narrow Tube
Outer Diameter
3/8"
Wide Tube
3/4"
2. Foamed polyethylene insulation for the specified copper tubes as required to precise length of tubing. Wall thickness of the insulation should be not less than 5/16".
1-5. Field Wiring
Use insulated copper wire for field wiring. Wire size varies with the total length of wiring. Refer to 3-6. Wiring Instructions for details.
Check local electrical codes and regulations before obtain­ing wire. Also, check any spec­ified instructions or limitations.
1-6. Additional Materials Required for Installation
6 inches
min.
6 inches
min.
6 inches min.
Front View
INDOOR UNIT
Tubing length (L)
OUTDOOR UNIT
Elevation difference (H)
Indoor unit
Floor level
Wall
Minimum height from floor level
5 ft.
CAUTION
Drain hose
Indoor unit
Outside drainage
1. Refrigeration (armored) tape
2. Insulated staples or clamps for connecting wire (See local codes)
3. Putty
4. Refrigeration lubricant
5. Clamps or saddles to secure refrigerant tubing
2. Installation Site Selection
2-1. Indoor Unit
WARNING
AVOID:
direct sunlight.
nearby heat sources that may affect performance of
the unit.
areas where leakage of flammable gas may be
expected.
places where large amount of oil mist exist.
DO:
select an appropriate position from which every corner
of the room can be uniformly cooled. (High on a wall is best.)
select a location that will hold the weight of the unit.
select a location where tubing and drain hose have
the shortest run to the outside. (Fig. 1)
allow room for operation and maintenance as well as
unrestricted air flow around the unit. (Fig. 2)
install the unit within the maximum elevation differ-
ence (H) above or below the outdoor unit and within a total tubing length (L) from the outdoor unit as detailed in Table 3 and Fig. 3a.
To prevent abnormal heat gen­eration and the possibility of fire, do not place obstacles, enclosures and grilles in front of or surrounding the air condi­tioner in a way that may block air flow.
Fig. 1
Fig. 2
Fig. 3a
For stable operation of the air conditioner, do not install wall-mounted type indoor units less than 5 ft. from floor level.
Fig. 3b
Table 3
Model Length at Shipment Length (L) Difference (H) Additional Refrigerant
C2432, CL2432 25 132 50 0.27
* If total tubing length becomes 25 to 132 ft. (max.), additional refrigerant (R22) charge of 0.27 oz./ft. is required.
No additional charge of compressor oil is necessary.
Max. Allowable Tubing Limit of Tubing Limit of Elevation Required Amount of
(ft.) (ft.) (ft.) (oz./ft.)*
3
2-2. Outdoor Unit
Outdoor unit
Hot air
Heat source
Exhaust fan
Min. 1 inch
Min. 1 inch
Min. 2 ft.
Min. 4 inches
Min. 7 ft.
Obstacle above
Ground
Air dis­charge
Air in
Air in
Air discharge
Concrete block 4 inch × 1 ft. 4 inch beams or equal
Anchor bolts (4 pieces)
Min. 6 inch
AVOID:
heat sources, exhaust fans, etc. (Fig. 4a)
damp, humid or uneven locations.
DO:
choose a place as cool as possible.
choose a place that is well ventilated.
allow enough room around the unit for air intake/
exhaust and possible maintenance. (Fig. 4b)
provide a solid base a minimum of 6 inches above
ground level to reduce humidity and protect the unit against possible water damage and decreased service life. (Fig. 5)
use lug bolts or equal to bolt down unit, to reduce
vibration and noise.
Fig. 4a
Fig. 4b
Fig. 5
4
Indoor side
Outdoor side
Set screws for transportation only
Right-rear tubing (recommended)
Right tubing
Left-rear tubling
Center of left-rear tubing hole
Center of right-rear tubing hole
NOTE
3. How to Install the Indoor Unit
NOTE
CAUTION
PVC pipe (locally purchased)
Cut at slight angle
3-1. Remove the Rear Panel from the Unit
Remove and discard the set screws and take off the rear panel. (Fig. 6)
Tubing can be extended in 3 directions as shown in Fig. 7a. Select the direction you need providing the shortest run to the outside unit.
3-2. Make a Hole
(1) Remove the rear panel from the indoor unit and
place it on the wall at the location selected. Make sure the unit is horizontal, using a carpenters level or tape measure to measure down from the ceiling.
(2) Determine which side of the unit you should make
the hole. (Fig. 7b)
(3) Before making a hole, check carefully that no studs
or pipes are directly run behind the spot to be cut.
Fig. 6
Fig. 7a
In case of left-rear or right-rear tubing
Also avoid areas where electri­cal wiring or conduits are located.
The above precautions are also applicable if tubing goes through the wall in any other location.
(4) Using a sabre saw, key hole saw or hole-cutting drill
attachment, cut a hole in the wall. See Table 4 and Fig. 8.
Table 4
Hole Dia. (inch)
3-3/16"
(5) Measure the thickness of the wall from the inside
edge to the outside edge and cut PVC pipe at a slight angle 1/4" shorter than the thickness of the wall. (Fig. 9)
(6) Place the plastic cover over the end of the pipe (for
indoor side only) and insert in the wall. (Fig. 10)
Fig. 7b
Hole should be made at a slight downward slant to the outdoor side.
Fig. 8
Fig. 9
INSIDE
Wall
Plastic cover
(Field Supply)
OUTSIDE
PVC pipe
Slight angle
Fig. 10
5
3-3. Install the Rear Panel on the Wall
3/16 inch dia. hole
1-3/16 inches or more
Rawl plug (Field supply)
Air intake grille
Grille
Air intake grille
Be sure to confirm that the wall is strong enough to sus­pend the unit.
See either Item a) or b) below depending on the wall type.
a) If Wooden Wall
(1) Attach the rear panel to the wall with the 10 screws
provided. (Fig. 11) If you are not able to line up the holes in the rear panel with the beam locations marked on the wall, use toggle bolts to go through the holes on the panel or drill 3/16 inch dia. holes in the panel over the stud locations and then mount the rear panel.
(2) Double check with a ruler or carpenters level that
the panel is level. This is important to install the unit properly. (Fig. 12)
(3) Make sure the panel is flush against the wall. Any
space between the wall and unit will cause noise and vibration.
Fig. 11
Fig. 12
b) If Block, Brick, Concrete or Similar Type Wall
Make 3/16 inch dia. holes in the wall. Insert rawl plugs for appropriate mounting screws. (Fig. 13)
3-4. Remove the Grille to Install the Indoor Unit
Basically, these models can be installed and wired with­out removing the grille. If access to any internal part is
needed, follow the steps as given below: How to remove the grille
(1) Set the 2 flaps in the horizontal position. (2) Unscrew the 3 screws. (Fig. 14a) (3) Remove the grille.
(a) Hold both corners of the air intake grille, then pull
out and up to open. (Fig. 14b)
(b) Use a standard screwdriver to push up the 3 tabs
to remove the grille. (Fig. 14b)
(c) Pull the lower part of the grille toward you to
remove. (Fig. 14a)
Fig. 13
Fig. 14a
Fig. 14b
6
How to replace the grille
Frame
Right tubing outlet
Tab
Mounting slot
(1) Close the flaps. (2) Reinstall the grille into the lower part while aligning
its tabs on the upper part. (Fig. 15a) Insert the tabs in the slots and push the lower part of the grille back into position.
(3) Press at each of the 5 tabs to completely close the
grille. Make sure that the grille and frame are firmly fitted together. (Fig. 15b)
3-5. Shape the Indoor Side Tubing
1) Arrangement of tubing by directions
a) Right tubing
Fig. 15a
The corner of right frame needs to be cut by a hacksaw or the like. (Fig. 16)
b) Right-rear or left-rear tubing
In this case, the corner of the frame need not be cut.
2) To mount the indoor unit on the rear panel:
Hang the 3 mounting slots of the unit on the upper tabs of the rear panel. (Fig. 17)
3-6. Wiring Instructions General precautions on wiring
1) Before wiring, confirm the rated voltage of the unit as shown on its nameplate, then carry out the wiring closely following the wiring diagram.
2) Provide a power outlet to be used exclusively for each unit, with a power supply disconnect and circuit breaker for overcurrent protection provided in the exclusive line.
3) To prevent possible hazard due to insulation failure, the unit must be grounded.
Fig. 15b
Fig. 16
Fig. 17
4) Each wiring connection must be done tightly and in accordance with the wiring system diagram. Wrong wiring may cause the unit to misoperate or become damaged.
5) Do not allow wiring to touch the refrigerant tubing, compressor, or any moving parts of the fan.
6) Unauthorized changes in the internal wiring can be very dangerous. The manufacturer will accept no responsibility for any damage or misoperation that occurs as a result of such unauthorized changes.
7
3-7. Recommended Wire Length and Diameter
2
4
2
4
11
INDOOR
UNIT
Terminal
OUTDOOR
UNIT
(B)
Terminal
(A)
L2
L1
G
G
G
230V/208V
230V/208V
230V/208V
(Inter-unit) power line
Grounding line
Grounding line
Power supply
Single phase 230V/208V 60HZ
Disconnect switch
Field supply
WARNING
CAUTION
Regulations on wiring diameter differ from locality to locality. For field wiring requirements, please refer to your local electrical codes. Carefully observe these regu­lations when carrying out the installation. Table 5 lists recommended wire lengths and diameters for power supply systems. Refer to the wiring system diagram (Fig. 18) for the meaning of “A” and “B” in Table 5.
Table 5
AWG
Model
C2432, CL2432 69 (Max.) 164 (Max.) 25A
(A) Power Supply
Wiring Length (ft.)
(#12)
(B) Inter-Unit
Power Line
(#14)
# …AWG (American Wire Gauge)
Fuse or Circuit
Capacity
WARNING
Be sure to comply with local
codes on running the wire from the indoor unit to the outdoor unit (size of wire and wiring method, etc.).
Each wire must be firmly
connected.
No wire should be allowed to
touch refrigerant tubing, the compressor, or any moving part.
To avoid the risk of electric shock, each air conditioner unit must be grounded.
Be sure to connect the power supply line to the outdoor unit as shown in the wiring dia­gram. The indoor unit draws its power from the outdoor unit.
WIRING SYSTEM DIAGRAM
Fig. 18
8
3-8. Wiring Instructions for Inter-unit Connections
Rear panel
Wiring
Wall
10 in.
Plastic cover
Terminal plate
Cover plate
Lock nut
Top of conduit connector
Inter-unit control line
wiring Earth plate
(1) Insert the inter-unit wiring (according to local codes)
into the through-the-wall PVC pipe. Run the wiring toward the indoor side allowing approx. 10 inch to extend from the wall face. (Fig. 19)
(2) Route the inter-unit wiring from the back of the
indoor unit and pull it toward the front for connection. (Fig. 20a, 20b)
(3) Connect the inter-unit wiring to the corresponding
terminals on the terminal plate (Fig. 20a, 20b) while referring to the wiring diagram.
(4) Be sure to secure the wiring with the provided
clamp.
How to remove the cover plate
To access the terminal plate inside the indoor unit, follow these steps.
(1) Using a Phillips screwdriver, take out the screw on
the cover plate. (Fig. 20a, 20b)
(2) Remove the cover plate.
Fig. 19
Fig. 20a
Fig. 20b
9
NOTE
Solid wire
Loop
Insulation
Strip 1 inch
Stranded wire
Ring connector
Strip 3/8 inch
Screw with special washer
Ring connector
Terminal plate
Wire
Screw with special washer
Ring connector
Wire
WARNING
Loose wiring may cause the
Twist wire ends
terminal to overheat or result in unit malfunction. A fire haz­ard may also exist. Therefore, be sure all wiring is tightly connected.
When connecting each power wire to the corresponding terminal, follow the instructions How to connect wiring to the terminal and fasten the wire securely tight with the fixing screw of the terminal plate.
How to connect wiring to the terminal
For solid core wiring (or F-cable)
Fig. 21a
(1) Cut the wire end with a cutting pliers, then strip the
insulation to expose the solid wire about 1 inch. (Fig. 21a)
(2) Using a screwdriver, remove the terminal screw(s)
on the terminal plate.
(3) Using the pliers, bend the solid wire to form a loop
suitable for the terminal screw.
(4) Shape the loop wire properly, place it on the termi-
nal plate and fix it securely with the removed termi­nal screw using a screwdriver.
For stranded wiring
(1) Cut the wire end with a cutting pliers, then strip the
insulation to expose the stranded wiring about 3/8 inch and tightly twist the wire ends. (Figs. 21b and 21c)
(2) Using a screwdriver, remove the terminal screw(s)
on the terminal plate.
(3) Using a ring connector fastener or pliers, securely
clamp each stripped wire end with a ring connector. (Fig. 21b)
(4) Place the ring connector wire, and replace and tight-
en the removed terminal screw using a screwdriver. (Fig. 22)
Fig. 21b
Fig. 21c
Fig. 22
Being careful not to cut the wire, strip off the plastic insu­lation using a wire cutter or pliers. (Fig. 23)
Fig. 23
10
3-9. Mounting
Cover
Refrigerant tubing
Drain hose
Inter-unit wiring
Pipe bending tool
a
b
b / a = 0.7 or more
Insulation (Field supply)
Refrigerant tubing
Drain hose
Conduit
Inter-unit wiring
CAUTION
CAUTION
Right-side tubing
(1) Shape the refrigerant tubing so that it can easily go
into the wall hole. (Fig. 24)
If using a stepladder, be careful to keep your balance and not fall off. To prevent the unit from damage and avoid per­sonal injury, ask for someone’s help when feeding the tubing through the hole because the unit is heavy and difficult to hold in place.
(2) Push the wiring, refrigerant tubing, and drain hose
through the hole in the wall. Adjust the indoor unit so it is securely seated on the rear panel.
(3) Carefully bend the tubing (if necessary) to run along
the wall in the direction of the outdoor unit and then tape as far as the fittings.
Fig. 24
Fig. 25
The air conditioners perfor­mance will be deteriorated if a tube is crushed. To prevent crushing of the tube, avoid sharp bends. Use a pipe bend­ing tool to bend the tube. (Fig. 25)
(4) Connect the refrigerant tubing to the outdoor unit.
(After performing a leak test on the connecting part, insulate it with tubing insulation. (Fig. 26)) Also, refer to Section 4-3. Connecting Tubing between Indoor and Outdoor Units.
(5) Assemble the refrigerant tubing, drain hose, and
inter-unit wiring as shown in Fig. 27.
Fig. 26
Fig. 27
11
3-10. Drain Hose
Slant
Drain hose
Indoor unit
Condensation
Insulation material (locally purchased) must be used.
a) The drain hose should be slanted downward to the
outdoors. (Fig. 28) b) Never form a trap in the course of the hose. c) If the drain hose will run in the room, insulate the
hose with insulation* so that chilled condensation
will not damage furniture or floors. (Fig. 29)
* Foamed polyethylene or its equivalent is recom-
mended.
Fig. 28
WARNING
Do not supply power to the unit or operate it until all tub­ing and wiring to the outside unit are completed.
Risk of Electric Shock
Fig. 29
12
4. Refrigerant Tubing
B'
B
A'
2. Mount the rear panel
A
Rear View
Wide tube
Optional tube connection (C) 1/2" (Optional part)
1. Cut hole in wall
3. Cut
4. Flare
5. Connect
4-1/8"
4. Flare wide tube
3. Cut wide tube
5. Connect tube assy
Optional tube connection (C) 1/2" (Optional part)
Narrow tube 3/8"
6. Connect wide tube 3/4"
7. Connect
narrow tube 3/8"
Mounting valve
Packing B
Packing A
Clamp
Narrow tube (3/8")
Wide tube (3/4")
Wide tube valve
Narrow tube valve
Tube assy
NOTE
4-1. Indoor Unit Tubing
Rear-left tubing
For rear-left tubing, optional tube connection (C) (APR­EN46U1B) is necessary. Please consult your nearest
sales outlet or A/C workshop.
1. Make a 3-3/16" hole in the wall, centered on the crossing point between the triangle marks (A and B) on the rear panel. (Fig. 30a)
2. Set the rear panel at its original position where it was installed with screws.
3. Cut the wide tube at a point 4-1/8" from the triangle mark.
4. Remove the 1/2" flare nut from the optional tube connection (C), place it on the cut wide tube, and then flare the wide tube. (Fig. 30b)
5. Connect the optional tube connection (C) to the wide tube.
Fig. 30a
6. Connect the 3/4" tube to the connected optional tube connection.
7. Connect the 3/8" tube to the narrow tube.
8. Cover the narrow and wide tubes with insulation material.
Rear-right tubing
9. Make a 3-3/16" hole in the wall, centered on the crossing point between the triangle marks (A' and B') on the rear panel. (Fig. 30a)
10. Connect the 3/4" tube to the wide tube.
11. Connect the 3/8" tube to the narrow tube.
12. Cover the narrow and wide tubes with insulation material.
4-2. Outdoor Unit Tubing
1. Connect a wide tube (3/4") to the wide tube valve. (Fig. 31a)
2. Connect the tube assy, which was packed in the indoor unit carton, to the narrow tube valve.
3. Before attaching the tube assy to the mounting valve, wrap the supplied packing A(3/4" × 1-3/8" × T3/16") onto the 5/16" tube of the tube assy to avoid direct contact of the tube assy with the mounting valve. (Fig. 31b, 31c)
Fig. 30b
Fig. 31a
13
IMPORTANT
Indoor unit
Outdoor unit
Spanner
Torque wrench
Insulation (Field supply)
4. Similarly arrange the supplied packing B (2-3/8" ×
Tube assy
Narrow tube
Clamp B
Clamp A
Packing B
Packing A
3/16" hole
φ
Clamp B
Clamp A
Square hole
Packing B
Packing A
1-3/16" × T3/16") on the mounting valve. (Fig. 31b, 31c)
5. Insert clamp A in the extracted round hole (
φ
3/16") on the mounting valve, and bind the tube assy and packing A. (Fig. 31b)
6. Insert clamp B in the square hole of the mounting valve, and bind it so the tube assy is in contact with packing B. (Fig. 31c)
7. Connect the narrow tube (3/8") between the units. When tightening the flare nut, use the double-wrench method. (Torque: 300 to 340 lbs.·in) (Fig. 32)
8. After completing the tubing work, check that the tube assy is not in direct contact with the 3/4" tube.
4-3. Connecting Tubing between Indoor and
Outdoor Units
a) Tightly connect the indoor side refrigerant tubing
extended from the wall with the outdoor side tubing. (Fig. 33)
b) To fasten the flare nuts, apply specified torque as:
Table 6
Tube Dia. Tightening Torque
3/8inch Approx. 300 – 340 lbs..in (35 – 40 N.m) 3/4inch Approx. 870 – 1,040 lbs..in (100 – 120 N.m)
Fig. 31b
Fig. 31c
4-4. Insulation of Refrigerant Tubing
(For C2432 and CL2432)
To prevent heat loss and wet floors due to dripping of condensation, both tubes must be well insulated with a proper insulation material. The thickness of the insu­lation should be a minimum 5/16 inch. (Fig. 35)
4-5. Taping the Tubes
CAUTION
After a tube has been insulated, never try to bend it into a nar­row curve, as this may cause the tube to break or crack.
(1) At this time, the 2 refrigerant tubes (and electrical
wire if local codes permit) should be taped together with armoring tape. The drain hose may also be included and taped together as 1 bundle with the tubing.
Fig. 32
Fig. 33
Fig. 34
14
(2) Wrap the armoring tape from the bottom of the out-
NOTE
Apply putty here
Tubing
Clamp
Insulated tubes
Insulation
Min. 5/16"
Thickness: min. 5/16"
door unit to the top of the tubing where it enters the wall. As you wrap the tubing, overlap half of each previous tape turn. (Fig. 36)
(3) Clamp the tubing bundle to the wall, using 1 clamp
approx. every 4 ft.
Do not wind the armoring tape too tightly since this will decrease the heat insulation effect. Also be sure the con­densation drain hose splits away from the bundle and drips clear of the unit and the tubing.
4-6. Finishing the Installation
After finishing insulating and taping over the tubing, use sealing putty to seal off the hole in the wall to prevent rain and draft from entering. Fig. 37 shows refrigerant tubing taped separately from the drain hose.
Fig. 35
Fig. 36
Fig. 37
15
5. Remote Control Unit Installation Position
Truss-head tapping screw 5/32 × 5/8" (4 × 16mm supplied)
Remote control unit holder
Holder
Holder
Truss-head tapping screw 5/32 × 5/8" (4 × 16mm supplied)
The remote control unit can be operated from either a non-fixed position or a wall-mounted position.
To ensure that the air conditioner operates correctly, do not install the remote control unit in the following places:
In direct sunlight
Behind a curtain or other place where it is covered
More than 26 ft. (8 m) away from the air conditioner
In the path of the air conditioners airstream
Where it may become extremely hot or cold
Where it may be subject to electrical or magnetic
interference
5-1. Mounting on a Wall
1) Confirm the indoor unit beeps when the ON/OFF button is pressed at the wall location where the remote control unit is to be attached, then attach the holder to the wall. (Fig. 38)
2) When taking out the remote control unit, pull it from the holder.
When using the remote control unit
Point the transmission portion of the remote con­trol unit at the receiver area of the indoor unit when operating the remote control unit, and dur­ing operation of the air conditioner.
Do not place objects that may block the transmit­ted signals between the receiver and the remote control unit.
When mounting the remote control unit to prevent theft
1) Mount the holder to the wall with one of the screws (using only the hole in the top of the holder) (Fig. 39).
2) Remove the cover of the remote control unit and take out the batteries. Next, place the remote control unit in the holder.
3) Fasten both the remote control unit and holder to the wall with the remaining screw (using the hole in the bottom of the holder).
4) Install the batteries in the remote control unit and close the cover.
Fig. 38
Fig. 39
16
Loading...