Sanyo C1852, XS1852, CL1852 User Manual 2

Page 1
TECHNICAL DATA
&
SERVICE MANUAL
XS1852 / C1852, CL1852
SPLIT SYSTEM AIR CONDITIONER
INDOOR MODEL No. PRODUCT CODE No. OUTDOOR MODEL No. PRODUCT CODE No.
XS1852 854 016 13
Indoor Unit Outdoor Unit
CL1852 852 068 36
FILE NO.
XS1852 C1852
CL1852
85464849179000 REFERENCE NO. SM830079
Page 2
Important
Please Read Before Starting
This air conditioning system meets strict safety and operating standards. As the installer or service person, it is an important part of your job to install or service the system so it operates safely and efficiently.
For safe installation and trouble-free operation, you must :
Carefully read this instruction booklet before beginning.Follow each installation or repair step exactly as shown.Observe all local, state, and national electrical codes.Pay close attention to all warning and caution notices
given in this manual.
This symbol refers to a hazard or unsafe practice which can result in severe personal injury or death.
This symbol refers to a hazard or
CAUTION
unsafe practice which can result in personal injury or product or property damage.
If Necessary, Get Help
These instructions are all you need for most installation sites and maintenance conditions. If you require help for a special problem, contact our sales/service outlet or your certified dealer for additional instructions.
In Case of Improper Installation
The manufacturer shall in no way be responsible for improper installation or maintenance service, including failure to follow the instructions in this document.
SPECIAL PRECAUTIONS
When Wiring
……………………………………………………………………
ELECTRICAL SHOCK CAN CAUSE SEVERE PERSONAL INJURY OR DEATH. ONLY A QUALIFIED, EXPERIENCED ELECTRICIAN SHOULD ATTEMPT TO WIRE THIS SYSTEM.
• Do not supply power to the unit until all wiring and tubing are completed or reconnected and checked.
• Highly dangerous electrical voltages are used in this system. Carefully refer to the wiring diagram and these instructions when wiring. Improper connections and inadequate ground­ing can cause accidental injury or death.
Ground the unit following local electrical codes.
• Connect all wiring tightly. Loose wiring may cause overheat­ing at connection points and a possible fire hazard.
When Transporting
…………………………………………………………………… Be careful when picking up and moving the indoor and outdoor
units. Get a partner to help, and bend your knees when lifting to reduce strain on your back. Sharp edges or thin aluminum fins on the air conditioner can cut your fingers.
When Installing
……………………………………………………………………
…In a Room
Properly insulate any tubing run inside a room to prevent “sweating” that can cause dripping and water damage to walls and floors.
…In Moist or Uneven Locations
Use a raised concrete pad or concrete blocks to provide a solid, level foundation for the outdoor unit. This prevents water damage and abnormal vibration.
…In an area with High Winds
Securely anchor the outdoor unit down with bolts and a metal frame. Provide a suitable air baffle.
…In a Snowy Area (for Heat Pump-type Sys-tems)
Install the outdoor unit on a raised platform that is higher than drifting snow. Provide snow vents.
When Connecting Refrigerant Tubing
……………………………………………………………………
• Ventilate the room well, in the event that refrigerant gas leaks during the installation. Be careful not to allow contact of the refrigerant gas with a flame as this will cause the generation of poisonous gas.
• Keep all tubing runs as short as possible.
• Use the flare method for connecting tubing.
• Apply refrigerant lubricant to the matching surfaces of the flare and union tubes before connecting them, then tighten the nut with a torque wrench for a leak-free connection.
• Check carefully for leaks before starting the test run.
NOTE
Depending on the system type, liquid and gas lines may be either narrow or wide. Therefore, to avoid confusion the refrigerant tubing for your particular model is specified as either “narrow” or “wide” rather than as “liquid” or “gas”.
When Servicing
……………………………………………………………………
• Turn the power OFF at the main power box (mains) before opening the unit to check or repair electrical parts and wiring.
• Keep your fingers and clothing away from any moving parts.
• Clean up the site when installation is finished. Check that no metal scraps or bits of wiring have been left inside the unit.
CAUTION
• Ventilate any enclosed areas when installing or testing the refrigeration system. Contact of refrigerant gas with fire or heat can produce poisonous gas.
• Confirm after installation that no refrigerant gas is leaking. If the gas comes in contact with a burning stove, gas water heater, electric room heater or other heat source, it can cause the generation of poisonous gas.
– 2 –
SM830079
Page 3
Table of Contents
1. OPERATING RANGE ....................................................................................... 5
2. SPECIFICATIONS ............................................................................................ 6
(1) Unit Specifications ...................................................................................... 6
(2) Major Component Specifications ................................................................ 8
(A) Indoor Unit ............................................................................................ 8
(B) Outdoor Unit.......................................................................................... 9
(3) Other Component Specifications .............................................................. 10
(A) Indoor Unit .......................................................................................... 10
(B) Outdoor Unit........................................................................................ 11
3. DIMENSIONAL DATA..................................................................................... 12
(1) Indoor Unit ................................................................................................ 12
(2) Outdoor Unit.............................................................................................. 13
4. PERFORMANCE CHARTS ............................................................................ 14
(1) Operating Current ..................................................................................... 14
5. AIR THROW DISTANCE CHART...................................................................15
6. REFRIGERANT FLOW DIAGRAM ................................................................. 16
7. INSTALLATION INSTRUCTIONS .................................................................. 17
8. ELECTRICAL DATA ....................................................................................... 22
9. ELECTRICAL WIRING DIAGRAMS ............................................................... 23
(1) Indoor Unit ................................................................................................ 23
(2) Outdoor Unit.............................................................................................. 25
10. PROCESSES AND FUNCTIONS .................................................................. 27
(1) Room Temperature Control ...................................................................... 27
(2) Freeze Prevention..................................................................................... 28
(3) Drain Pump Control .................................................................................. 28
(4) Outdoor Fan Speed Control...................................................................... 29
11. SERVICE PROCEDURES.............................................................................. 30
(1) Troubleshooting ........................................................................................ 30
(2) A Sensor is Defective................................................................................ 40
(3) Operation of Major Electrical Parts ........................................................... 40
(4) Checking the Electrical Components ........................................................ 41
– 3 –
SM830079
Page 4
Introduction:
This manual will help you understand and service the air conditioner. To help you find the information you need, we have divided it into 5 main sections. Each section is divided into chapters with charts, tables and explana­tions to help you find and repair problems.
Section 1: Specifications, tells you about the physical and electrical make up of the unit, as well
as its heating and cooling capacities. Look in this section to find the correct values for components and functions.
Section 2: Processes and Functions, explains each different part of the cooling and heating
cycle, and how each control function reacts to changing conditions to keep the room at the set temperature range.
Section 3: Electrical Data, which has fold-out schematic and wiring diagrams so you can find
the parts you need to check when something is wrong, and see how they should be connected.
Section 4: Service Procedures, has two main parts, a
specific component to replace or adjust, and a chapter with specific procedures and values to guide you in checking the electrical components in the unit.
Read Me First!
diagnostic
chapter to help you find the
HOW TO USE THIS MANUAL
You can use this manual both as a construction of this unit, and as a source of information to help you set up and maintain the unit. When this unit is not working properly, and the cause is not known, you can use the procedures in Section 3: Servicing Procedures to find the problem, fix it, and restore the unit to its proper functioning.
This air conditioner has many helpful self diagnostic features to help you identify problem areas quickly.
So you will be ready when a problem happens, we suggest you look this manual over and become familiar with it by following these steps:
1. Look at the TABLE OF CONTENTS to get an idea of what is in this manual and where to find it.
2. Look at the chapter about TROUBLE SHOOTING, so you are familiar with the way the flow
charts work. They are designed to guide you quickly through the possible causes for each kind of problem that is likely to happen to the Unit. Particularly read the introduction to this section, and the parts about the self-diagnosis and error codes which show on the display.
3. Look at the chapter about CHECKING ELECTRICAL COMPONENTS. You already know
about most of these procedures. This chapter gives you the specific values and methods for these components. If you don’t know some of these procedures, you can easily learn them here.
4. Read the Instruction Manual! The Instruction Manual is included here because it helps you help
the user to set the temperature controls properly and know how to take care of any simple problems that may happen, as well as know when to call for service. The Instruction Manual also has illustrations, care, and installation information not found in the rest of the service manual. It is short, and if you read it carefully, you will be able to answer the customers questions easily, and also know the most efficient ways for setting times and temperatures.
reference
to find specific information about the capacity, functions and
Please use this manual to make your work easier, keep the air conditioner functioning well, and keep your customers satisfied.
– 4 –
SM830079
Page 5
1. OPERATING RANGE
XS1852 / C1852
Temperature Indoor Air Intake Temp. Outdoor Air Intake Temp.
Maximum 95 °F DB / 71 °F WB 115 °F DB
Minimum 67 °F DB / 57 °F WB 67 °F DB
XS1852 / CL1852
Temperature Indoor Air Intake Temp. Outdoor Air Intake Temp.
Maximum 95 °F DB / 71 °F WB 115 °F DB
Minimum 67 °F DB / 57 °F WB 0 °F DB
– 5 –
SM830079
Page 6
2. SPECIFICATIONS
(1) Unit Specifications
MODEL No. Indoor Unit XS1852
Outdoor Unit C1852 , CL1852 POWER SOURCE 230 - 208 V / 1 Phase / 60 Hz PERFORMANCE Cooling
Capacity BTU / h 18,000 17,500
kW 5.27 5.13 Air circulation (Hi) Moisture removal (High) Pints / h 5.5 5.4
ELECTRICAL RATINGS
Voltage rating VAC 230 208 Available voltage range VAC 187 - 253 Running amperes* A 8.2 8.77 Max. running amperes** A 9.7 10.6 Power input W 1,780 1,740 Power factor % 97 98 S.E.E.R Max. starting amperes A 44.7 44.6 Maximum fuse size A 20
FEATURES
Controls Microprocessor Low ambient control Built-in 0 °F (Only for CL1852) Timer ON / OFF 24-hours & Program Fan speed Indoor / Outdoor 3 and Automatic control / 1 (3 : CL1852) Air deflection Horizontal / Vertical – / Automatic Air filter Washable, easy access Remote controller (Accessory) RCS - 5PS4U Refrigerant control Capillary tube Refrigerant tubing connections Flare type Drain pump (drain connection) Max. head 9-27/32 in. above drain connection Compressor Rotary Operation sound
REFRIGERANT TUBING
Limit of tubing length ft. (m) 65 (20) Limit of tubing length at shipment ft. (m) 33 (10) Limit of elevation difference ft. (m) Outdoor unit is higher than indoor unit: 23 (7)
between the two units Outdoor unit is lower than indoor unit: 23 (7) Refrigerant tube Narrow tube in. (mm) 1 / 4 (6.35)
outer diameter Wide tube in. (mm) 5 / 8 (15.88) Refrigerant amount at shipment lbs. (kg) R22 : 4.45 (2.02)
Indoor - Hi / Me / Lo Outdoor - Hi dB - A 52
cu.ft. / min.
BTU / Wh
dB - A 37 / 35 / 31
540 510
10.6 10.6
– 6 –
SM830079
Page 7
2. SPECIFICATIONS
(1) Unit Specifications
DIMENSIONS & WEIGHT Indoor unit Outdoor unit
Unit dimensions Height in. (mm) 9-27/32 (250) 24-19/32 (625)
Width in. (mm) 29-29/32 (760) 32-21/32 (880) Depth in. (mm) 29-29/32 (760) 12-19/32 (320)
Net weight lbs. (kg) 49 (22) 104 (47)
Indoor grille dimensions Height in. (mm) 3-1/16 (78)
Width in. (mm) 33-27/32 (860) Depth in. (mm) 33-27/32 (860)
Net weight lbs. (kg) 11 (5)
Indoor Unit Height in. (mm) 11-6/32 (284) 27-30/32 (710)
Package dimensions Width in. (mm) 32-14/32 (824) 40-18/32 (1,030)
Depth in. (mm) 32-25/32 (833) 16-6/32 (411) Shipping weight lbs. (kg) 57 (26) 112 (51) Shipping volume cu. ft. (m3) 6.9 (0.195) 10.3 (0.301)
Indoor grille Height in. (mm) 4-3/32 (104)
Package dimensions Width in. (mm) 38-2/32 (967)
Depth in. (mm) 39-11/32 (999) Shipping weight lbs. (kg) 18 (8) Shipping volume cu. ft. (m3) 3.5 (0.100)
Cooling :
Rating conditions (*) : Indoor air temperature 80 °F DB / 67 °F WB, Outdoor air temperature 95 °F DB / 75 °F WB Full load conditions (**) : Indoor air temperature 80 °F DB / 67 °F WB, Outdoor air temperature 115 °F DB
DATA SUBJECT TO CHANGE WITHOUT NOTICE
– 7 –
SM830079
Page 8
2. SPECIFICATIONS
(2) Major Component Specifications
(A) Indoor Unit
MODEL No. XS1852 Source 230 - 208 V / 1 phase / 60 Hz Remote controller (Accessory) RCS - 5PS4U Controller P. C. B Ass'y CR - TS2432 Control circuit fuse 250 V, 3 A Switch Ass'y SW - X363GS Fan (Number … diameter) in. (mm) Turbo (1…19-9/32 (490)) Fan motor
Model SFG6X - 41A5P Source 230 - 208 V / 1 phase / 60 Hz No. of pole … r.p.m. (230 V, High) rpm 6 … 451 Nominal output W 40 Coil resistance BRW - WHT : 114.0 , ORG - YEL : 66.4 (Ambient temperature 68 °F) WHT - VLT : 23.9 , WHT - PNK : 77.4
VLT - ORG : 12.4 , YEL - BLK : 82.1
Safety device
Operating temperature Open °F266± 14.4
Close °F 174.2 ± 27
Run capacitor VAC, µF 440 V , 3.5 µF
Heat exchanger
Coil Aluminum plate fin / Copper tube Rows … Fins per inch 2 … 14.9 Face area ft.
Panel
Model No. PNR - XS2432 Indicator Lamp Ass'y IND - XS2432 Auto louver motor MT8 - 3C Auto louver motor … Rated V, W, rpm 240 VAC , 3 W , 3 rpm Coil resistance (Ambient temperature 77 °F) 16,430 ± 8 %
2
(m2) 3.2 (0.297)
DATA SUBJECT TO CHANGE WITHOUT NOTICE
– 8 –
SM830079
Page 9
2. SPECIFICATIONS
(2) Major Component Specifications
(B) Outdoor Unit
MODEL No. C1852 CL1852 Source 230 - 208 V / 1 phase / 60 Hz Controller P.C.B. Ass'y POW - CL125
Control circuit fuse 250 VAC, 5 A
Compressor Rotary (Hermetic)
Model C - R132H6D Source 230 - 208 V / 1 phase / 60 Hz Nominal output W 1,300 Compressor oil cc 500 Coil resistance (Ambient temperature 77 °F) C – R : 1.442 , C – S : 2.567
Safety device Internal type
Overload relay models — Operating temperature Open °F 311 ± 9
Close °F 188 ± 20
Operating ampere (at 77 °F) A — Run capacitor VAC, µF 400 V, 35 µF Crank case heater VAC, W 230 V, 20 W
Refrigerant amount charged at shipment lbs. (kg) R22 : 3.59 (1.63) Fan Propeller
Number...diameter in. (mm) 1 ... 16 - 17/32 (ø420)
Fan motor
Model KFG6 - 51E6P ... 1 KFG6T - 51B6P ... 1 Source 230 - 208 V / 1 phase / 60 Hz
No. of pole ..... rpm (230 V, High) C type : 6 ... 830 , CL type : 6 ... 813
Nominal output W 50 Coil resistance BRN – WHT : 102 , WHT – PNK: 199
(Ambient temperature 68 °F) Safety device Internal type
Operating temperature Open °F 266 ± 14
Close °F 174 ± 27
Run capacitor VAC, µF 440 V, 2 µF
Heat exchange
Coil Aluminum plate fin / Copper tube
Rows ..... Fins per inch 2 ... 1/16 (1.6)
Face area ft.
2
(m2) 4.0 (0.372)
DATA SUBJECT TO CHANGE WITHOUT NOTICE
– 9 –
SM830079
Page 10
2. SPECIFICATIONS
(3) Other Component Specifications
(A) Indoor Unit
MODEL No. XS1852 Power Transformer ATR – I104A
Rated Primary AC 220 V, 60 Hz
Secondary 10.6 V, 0.93 A Capacity 9.85 VAC
Coil resistance (Ambient temprature 77 °F)
Thermistor cut off temperature °F266
Thermistor (Coil sensor) PBC - 41E - S26
Coil resistance k 14 °F : 23.7 , 41 °F : 12.1
Thermistor (Room or coil sensor) KTEC - 35 - S6
Coil resistance k 32 °F : 16.5 , 104 °F : 2.7
Reray G7L - 2A - TUB
Coil rated V AC 220 - 240 V Contact rating V, A 277 VAC, 25A
Drain pump WP20SL - 21
Rated AC 200 V, 14.7 W
Float switch FS - 0218 - 102
MAX Rated (Contact rated) AC 200 V, 50 W
Switch Ass'y SW - X363GS Indicator Lamp Ass'y IND - XS2432
Synchronized Motor MT8 - 3C
WHT - WHT : 101 , BRN - BRN : 0.42
23 °F : 18.8 , 50 °F : 9.7 32 °F : 15.0 , 59 °F : 8.0
41 °F : 12.8 , 113 °F : 2.2 50 °F : 10.0 , 122 °F : 1.8 68 °F : 6.3 , 131 °F : 1.5 86 °F : 4.0 ,
DATA SUBJECT TO CHANGE WITHOUT NOTICE
– 10 –
SM830079
Page 11
2. SPECIFICATIONS
(3) Other Component Specifications
(B) Outdoor Unit
MODEL No. CL1852 Compressor Motor Magnetic Contactor
Coil rated – Coil resistance (at 77 °F) k – Contact rated (Main) – Contact rated (Auxiliary)
Power Transformer ATR - T5
Rated
Primary VAC 220 VAC, 60 Hz
Secondary 19 V, 15 A
Capacity 10 VA
Coil resistance (at 77 °F) Primary (WHT - WHT) : 385 ± 10 %
Secondary (BRN - BRN) : 3.3 ± 10 %
Thermal cut off temperature °F 276 ˚F, 1A 250 VAC
Thermistor (Outdoor Temp. sensor)
Coil resistance k 14 °F : 23.7 , 50 °F : 9.7
23 °F : 18.8 , 68 °F : 6.5 32 °F : 15.0 , 86 °F : 4.4 41 °F : 12.1 , 104 °F : 3.1
Reray (1X) HH62S
Coil rated DC 12 V Coil resistance (at 77 °F) 650 ± 15 % Contact rated V, A AC 240 V, 5A
DTNTKS132B
DATA SUBJECT TO CHANGE WITHOUT NOTICE
113 °F : 2.6
– 11 –
SM830079
Page 12
3. DIMENSIONAL DATA
(1) Indoor Unit: XS1852
4-29/32
4-29/32
32-9/32 (Ceiling opening)
23-7/32 (Suspention bolt pitch)
14
X-view
14
13-3/8
10-1/32
11-23/32 1-3/16
8-21/32
8-1/16
5-29/32 7-7/8
8-1/16
6-1/2
1-7/8
3-15/16
19/32
• Remote controller (Accessory)
6-25/32
2-13/32 23/32
33-27/32 19-11/16
1/2
12
X
Grille center
Min. 2-3/8
3-1/32
13-2/4 1-3/8
3-15/16
29-29/32
32-9/32 (Ceiling opening)
28-3/4(Suspention bolt pitch)
4-29/32
1/2
1/2
33-27/32
19-11/16
Dimension : inch
Air intake Air outlet
29-29/32
Narrow tube (1/4") Wide tube (5/8") Drain connection Power line (conduit size : 1/2") For discharge duct
1/2
Suspention bolt mounting
– 12 –
1331_X_S
SM830079
Page 13
3. DIMENSIONAL DATA
(2) Outdoor Unit: C1852, CL1852
4-ø15/32"
Air intake
Air discharge
34-21/32"
23-15/16"
15/32"
5-11/32"
12-7/32"
13-5/32"
12-19/32"
3-7/16" 2-5/32"
5/8"
21-19/32"
Narrow tube service valve ø1/4 (6.35)
Wide tube service valve ø5/8 (15.88)
Unit: inch (mm)
– 13 –
1880_C_I
SM830079
Page 14
4. PERFORMANCE CHARTS
(1) Operating Current
11
1 Indoor Unit: XS1852 Outdoor Unit: C1852, CL1852
11
Operating current characteristics versus outdoor ambient temperature and indoor temperature. (Indoor relative humidity: 50%, Indoor fan speed: High)
230V
230V / 208V
12 11 10
9 8 7
Operating current (A)
6 5
60
(21.1)80(26.7)90(32.2)
(15.6)
Outdoor inlet air D.B. temp. °F (°C)
(10.5)
150
(9.8)
140
Indoor inlet air
D.B. temp. °F (°C)
70
(37.8)
Indoor inlet air
D.B. temp. °F (°C)
100
110
(43.3)
120
(48.9)
95 80
67
(35.0) (26.7)
(19.4)
1881_M_I
(9.1)
130
G)
2
Low pressure psig (kg/cm
(8.4)
120
(7.7)
110
(7.0)
100
(6.3)
90
(5.6)
80
at wide tube service valve
(4.9)
70
(4.2)
60
(3.5)
50
70
60
(21.1)80(26.7)90(32.2)
(15.6)
Outdoor inlet air D.B. temp. °F (°C)
– 14 –
100
(37.8)
110
(43.3)
95 80 67
120
(48.9)
(35.0) (26.7) (19.4)
1882_M_I
SM830079
Page 15
5. AIR THROW DISTANCE CHART
MODEL: XS1852
HORIZONTAL DISTANCE (ft.)
0 3 7 10131720
0
3
7
10
VERTICAL DISTANCE (ft.)
AXIS AIR VELOCITY (ft./sec.)
13
FAN SPEED ROOM AIR TEMP.
LOUVER ANGLE
AXIS AIR VELOCITY
COOLING
HIGH
80˚F
30˚
1052_X_S
– 15 –
SM830079
Page 16
6. REFRIGERANT FLOW DIAGRAM
Indoor Unit: XS1852 Outdoor Unit: C1852, CL1852
Outdoor UnitIndoor Unit
Wide tube
Wide tube
O. D. 5/8" (15.88 mm)
Evaporator
service valve
Accumulator
Compressor
Narrow tube
O. D. 1/4" (6.35 mm)
Narrow tube
service valve
Capillary
tube
Insulation of Refrigerant Tubing
IMPORTANT
To prevent heat loss and wet floors due to dripping of condensation, both the wide and narrow tubes
must be well insulated with a proper insulation material. The thickness of the insulation should be
a min. 5/16 in.
After a tube has been
CAUTION
insulated, never try to bend it into a narrow curve because it can casue the tube to break or crack.
Thickness: Min. 5/16 in.
Wide tube
Condenser
1898_C_I
Insulation
Thickness: Min. 5/16 in.
Narrow tube
0999_C_I
– 16 –
SM830079
Page 17
7. INSTALLATION INSTRUCTIONS
1) Tubing Length
• Refrigerant tubing between the indoor and outdoor units should be kept as short as possible.
• Select and decide the installation location
Elevation difference (H)
so that the length of the refrigerant tubing will be within the limits given in Table 1.
Table 1
Models C1852
Tubing Data
Tubing size outer dia.
Narrow tube in. (mm) 1/4 (6.35): Thickness 0.0314" (0.8 mm) Wide tube in. (mm) 5/8 (15.88): Thickness 0.0394" (1.0 mm)
Limit of tubing length (ft.) 65
Limit of elevation difference between the 2 units than indoor unit
Outdoor unit is higher than indoor unit (ft.)
Outdoor unit is lower
(ft.) Max. allowable tubing length at shipment (ft.) 33 Required additional refrigerant *
1
(oz./ft.) 0.27
CL1852
INDOOR UNIT
23
23
Tubing length (L)
OUTDOOR UNIT
0711_M_I
Fig. 1
No additional charge of compressor oil is necessary. *1If total tubing length becomes 33 to 65 ft., charge additional refrigerant (R22) by 0.27 oz./ft..
– 17 –
SM830079
Page 18
7. INSTALLATION INSTRUCTIONS
2) Selecting the Installation Site
Indoor Unit
AVOID:
ã areas where leakage of flammable gas may
be expected.
ã places where large amount of oil mist exist. ã direct sunlight. ã locations near heat sources which may
affect performance of the unit.
ã locations where external air may enter the
room directly. This may cause “sweating” on the air discharge ports, causing them to spray or drip.
ã locations where the remote control unit will
be splashed with water or affected by dampness or humidity.
ã installing the remote control unit behind
curtains or furniture.
ã locations where the receiver in the indoor
unit is exposed to the inverter lamp light. Faulty operation of the unit occurs.
DO:
ã select an appropriate position from which
every corner of the room can be uniformly cooled.
ã select a location where the ceiling is strong
enough to support the weight of the unit.
ã
select a location where tubing and drain pipe have the shortest run to the outdoor unit.
ã allow room for operation and maintenance
as well as unrestricted air flow around the unit. (Fig. 2)
ã
install the unit within the maximum elevation difference above or below the outdoor unit and within a total tubing length from the outdoor unit as detailed in Table 1.
ã allow room for mounting the remote control
unit about 3 ft. off the floor, in an area that is not in direct sunlight nor in the flow of cool air from the indoor unit.
3 ft.
3 ft.
3 ft.
3 ft.
3 ft.
1330_X_S
Fig. 2
NOTE
Air delivery will be degraded if the distance from the floor to the ceiling is greater than 10 ft..
– 18 –
SM830079
Page 19
7. INSTALLATION INSTRUCTIONS
Outdoor Unit
AVOID:
ã heat sources, exhaust fans, etc. (Fig. 3) ã damp, humid or uneven locations.
DO:
ã choose a place as cool as possible. ã choose a place that is well ventilated.
ã
allow enough room around the unit for air intake/ exhaust and possible maintenance. (Fig. 4)
ã
Install the outdoor unit
CAUTION
above snowfall line.
ã
Do not place objects on or sit on the out­door unit. Also, never block the air intake/out­let or exhaust. Distor­tion of the outdoor unit or incomplete combus­tion may result.
ã Do not introduce for-
eign matter into the air intake/outlet or ex­haust. Do not poke them with such ob­jects as a stick.
ã
provide a solid base (level concrete pad, concrete block, 4 in. × 16 in. (10 × 40 cm) beams or equal), a minimum of 4 in. (10 cm) above ground level to reduce humidity and protect the unit against possible water damage and decreased service life (Fig. 5).
ã use lug bolts or equal to bolt down unit,
reducing vibration and noise.
Air intake
Min. 6" (15 cm)
Air intake
Concrete or equal
NO
Hot air
Out­door unit
Min. 6" (15 cm)
Air discharge
About 16" (40 cm)
Exhaust fan
Fig. 3
Valve side Min. 10" (25 cm)
Min. 12" (30 cm)
Fig. 4
Heat source
1817_C_I
1818_M_I
About 4" (10 cm)
Obstacle above
Min.
7 ft.
(2 m)
Air discharge
Ground
Min. 6 in. (15 cm) Air intake
Anchor bolts (4 pcs)
Min.
7 ft.
(2 m)
1819_M_I
Min. 4" (10 cm)
Obstacle
3) Baffle Plates for the Outdoor Unit
(CL×× models only)
NOTE
It is recommended to use baffle plates for model CL1852. The baffle plates are not normally required for the other models.
When the outdoor unit is installed in a position exposed to strong wind (like seasonal winds with low air temperature in winter), baffle plates must be installed on the outdoor unit. (Fig. 6)
This unit is designed so that the fan of the outdoor unit runs at low speed when the air conditioner is operated at low outdoor air temperatures. When the outdoor unit is exposed to strong wind, the system pressure drops because of the freeze protector.
– 19 –
6" min
Air discharge
Baffle plate
Fig. 5
Fig. 6
Air discharge
6" min
SM830079
1820_M_I
Baffle plate
1821_M_I
Page 20
7. INSTALLATION INSTRUCTIONS
4) Electrical Wiring
General Precautions on Wiring
(1) Before wiring, confirm the rated voltage
of the unit as shown on its nameplate, then carry out the wiring closely following the wiring diagram.
(2) Provide a power outlet to be used exclu-
sively for each unit, and a power supply disconnect and circuit breaker for overcurrent protection should be pro­vided in the exclusive line.
(3) To prevent possible hazards from insula-
tion failure, the unit must be grounded.
(4) Each wiring connection must be done in
accordance with the wiring system dia­gram. Wrong wiring may cause the unit to misoperate or become damaged.
(5) Do not allow wiring to touch the refriger-
ant tubing, compressor, or any moving parts of the fan.
(6) Unauthorized changes in the internal
wiring can be very dangerous. The manufacturer will accept no responsibility for any damage or misoperation that occurs as a result of such unauthorized changes.
(7) Regulations on wire diameters differ from
locality to locality. For field wiring rules, please refer to your LOCAL ELECTRI­CAL CODES (ex. National Electric Code: ANSI/NFPA70) before beginning. You must ensure that installation complies with all relevant rules and regulations.
(8) To prevent malfunction of the air condi-
tioner caused by electrical noise, care must be taken when wiring as follows:
ã The inter-unit control wiring and the remote
control wiring (option) should be wired apart from the inter-unit power wiring.
– 20 –
SM830079
Page 21
7. INSTALLATION INSTRUCTIONS
Recommended Wire Length and Wire Diameter for Power Supply System
Power Supply Terminal Base (Outdoor Unit)
Capacity
Models
(A)*1 Power Supply
(B)*1 Inter-unit
AWG #12 AWG #12
Wiring
Time Delay Fuse or Circuit Capacity
C1852, CL1852 75 ft. 65 ft. 15 A 20 A AWG #12
*1 Refer to the Wiring System Diagrams (See below diagram) for the meaning of “A”, “B”.
AWG = American Wire Gauge
NOTE
To access the electrical component box, open the air intake grille and remove the electrical component box cover.
Wiring System Diagram
Single-phase 60 Hz, 230 / 208 V
ã Conduit's trade size for this unit is 1/2".
The conduit can be purchased at a hard­ware store.
ã The fuse located in the outdoor unit pro-
vides power supply protection and may blow when power is applied if the system has been incorrectly wired.
(1) Ground the unit in accordance with local
codes.
INDOOR
INDOOR UNIT
1 2 3
Disconnect switch (Field supply)
(Inter-unit) Power lines
230/208 V 230/208 V 230/208 V
OUTDOOR UNIT
B
(2) Be sure to size each wire allowing sev-
eral inches longer than the required length for wiring.
(3) Use lock nuts to secure the conduit
G
Grounding line
Fig. 7
tubes.
Max. Wire Diameter
1
Fuse
2 3 4 5 6
G
A
L1 L2
Power supply line
Single-phase, 230/208 V
1823_M_I
ã Be sure to comply with
local codes while run­ning the wire from the indoor unit to the out­door unit (size of wire and wiring method, etc.).
ã Every wire must be
connected firmly.
ã No wire should be
allowed to touch refrig­erant tubing, the com­pressor or any moving part.
– 21 –
CAUTION
ã To avoid the risk of
electric shock, each air conditioner unit must be grounded.
ã Be sure to connect the
power supply line to the outdoor unit as shown in the wiring diagram. The indoor unit draws its power from the outdoor unit.
SM830079
Page 22
8. ELECTRICAL DATA
Electrical characteristics
Indoor model: XS1852 / Outdoor model: C1852, CL1852
Indoor Unit Outdoor Unit
Fan Motor Fan Motor Compressor
Performance at 230 - 208 V / 1 phase / 60 Hz 230 - 208 V / 1 phase / 60 Hz
A 0.60 - 0.60 0.5 - 0.5 7.1 - 7.7 8.2 - 8.77
Rating conditions
kW 0.12 - 0.11 0.11 - 0.10 1.56 - 1.53 1.79 - 1.74
A 0.60 - 0.60 0.5 - 0.5 8.4 - 9.5 9.7 - 10.57
Full load conditions
kW 0.12 - 0.11 0.11 - 0.10 1.93 - 1.96 2.16 - 2.17
Starting amperes A 1 - 1 0.7 - 0.6 43 - 43 44.7 - 44.6
Complete Unit
Rating Conditions : Indoor Air Temperature 80 °F DB / 67 °F WB
Outdoor Air Temperature 95 °F DB
Full Load Conditions : Indoor Air Temperature 80 °F DB / 67 °F WB
Outdoor Air Temperature 115 °F DB
– 22 –
SM830079
Page 23
9. ELECTRICAL WIRING DIAGRAMS
(1) Indoor Unit
11
1 XS1852
11
• Electric Wiring Diagram
E
GRN/YEL
Earth Terminal
TH1 (Coil)
BLK
BLK
21
2P(RED)
TH1
5P(WHT)
WHT
BLK
23
1
Terminal Plate(4P)
To Outdoor Unit
TH2 (Room)
2P(YEL)
TH2
SUP
BRN
BLK
G
BLK
BLK
21
1PR64
08 2
WHT
Switch Assy
213
BRN
213
3P(WHT)
SW ASSY
Controller (CR-TS2432)
RED
RED
PRY
2P(WHT)
21
WHT
WHT
GRN/YEL
SEC
2P(WHT)DP3P(BLU)FS3P(RED)
P
S
TR1
RED
BRN
ORG
21
BRN
BRN
PS
22 11
Connector
2P(YEL)
Earth Terminal
BRN
IND Lamp Assy
7P(WHT)
31
BLK
BLK
DP
GRN/YEL
W/LESS
71
71
31
BLK
SP123
3P(GRN)
FM
COM
RC1
BLK
P
123456789 1
S
FS
GRN/YEL
Earth Terminal
LM
GRN/YEL
GRY
BLK
123
Connector 3P(WHT)
GRN/YEL
Earth
GRY
BLK
Terminal
31
LM
7P(WHT)
MHL
3175315
ORG
VLT
PNK
BRN
3456789
2
YEL
ORG
PNK
BRN
BLK
FMI
3P(WHT)
49FMI
31
GRY
WHT
VLT
WHT
BRN
GRY
BRN
GRY
Connector
9P(WHT)
– 23 –
W 854-2-5268-872-00-0 (XS1852)
SM830079
Page 24
9. ELECTRICAL WIRING DIAGRAMS
(1) Indoor Unit
11
1 XS1852
11
4P-1
4P-3
4P-2
• Schematic Diagram
3
F1
(3A)
PRPR
RY5
RY3
5
1
RY4
1
1
1
DP
LMPR
2
3
3
RY1
RY2
HLM
RY2
735
456
FMI
12
RC1
8
49FI
9
1
1
3
49FMI
PRY
2
122
1
TR1
RY1
RY2
RY3
RY4
RY5
1
CR-TS2432
Controller
SEC
LM
DP
W/ LESS
SW ASSY
TH1
TH2
1
IND
717
1
1
2
2
SW
3
3
FS
1
FS
3
TH1
1 2
Coil
TH2
1 2
Room
Symbols Description
FMI 49FI RC1 F1 DP LM TR1 PR RY1-RY5
Indoor Fan Motor Indoor Motor Thermal Protector Running Capacitor Fuse Drain Pump Auto Louver Motor Power Transformer Power Relay Auxiliary Relay
Symbols Description
FS TH1 TH2 CR-TS2432 IND SW
Float Switch Thermistor (Indoor Coil) Room Thermistor Indoor Controller Indicator Lamp Assy Switch Assy Terminal Plate Connector Terminal
S 854-2-5268-872-00-0 (XS1852)
– 24 –
SM830079
Page 25
9. ELECTRICAL WIRING DIAGRAMS
(2) Outdoor Unit
11
1 C1852
11
• Electric Wiring Diagram
Terminal Plate (6P)
1
BLK
2
To Indoor Unit
L1 L2
Power Supply
3 4
G
5
WHT
6
G
BLK
GND
Fuse
WHT
BLK
Capacitor (FM)
PNK (RED)
BRN
FM
Fan Motor
Overload Relay
RED
Capacitor (CM)
GRY
BLK
WHT
R
CM
Compressor Motor
RED
CS
– 25 –
SM830079
Page 26
9. ELECTRICAL WIRING DIAGRAMS
(2) Outdoor Unit
11
1 CL1852
11
• Electric Wiring Diagram
To Indoor Unit
G
L1 L2
Power
Supply
Heater Relay
WHT (09)
Crankcase Heater
Terminal
Plate (6P)
1 2 3 4 5 6
G
GND
6
4
WHT (10)
WHT (03)
BLK (04)
RED (05)
2
WHT (23)
BLK (12)
BLK (01)
WHT (06)
WHT (24)
BLK (08)
7
8153
BLK (11)
Fuse
BLK (02)
RED (07)
S
11 33
R1 R2
Controller
Supply
1357 1357
PNK (RED)
BRN
Capacitor (FM)
( 21 )
( 22 )
GRY
FM
Fan Motor
FM
WHT
VLT
YEL
TH2
BLK
TH1
BLU
PRY1
PRY2
SEC2
SEC1
BRN
BRN
WHT
WHT
( 18 )
1234 12
34
Connector
BRN
BRN
WHT
WHT
( 17 )
Power Transformer
SP
1
(19)
212
Connector
P S
SP
BLK BLK
(Outdoor Air) Thermistor
(20)
(13)
Capacitor (CM)
WHT
Compressor Motor
(14) BLK
R
CM
RED (16)
Overload Relay
(15) RED
CS
– 26 –
SM830079
Page 27
10. PROCESSES AND FUNCTIONS
(1) Room Temperature Control
The Unit adjusts room temperature by turning the outdoor unit’s compressor ON and OFF. This process is controlled by the thermostat located in the remote control unit. The figures on this and the next pages show how each part of the system performs when the room temperature changes and the thermostat activates the compressor to start (thermo ON) or stop (thermo OFF). Fig. 8 shows about the cooling cycle.
ROOM TEMPERATURE
S. T.+ 1°F SET TEMP. T°F (S.T.)
WITHIN 3 MINUTE
THERMO OFF 3 MINUTES
THERMO ON
MORE THAN 5 MINUTES
MORE THAN 3 MINUTES
THERMO ON
THERMO OFF
COMPRESSOR
ON
INDOOR FAN
ON ON
OUTDOOR FAN
OFF
SET SPEED (MANUAL)
OFF OFF
ON ON
OFF
Fig. 8
Chart Summary and Explanations
Once the compressor starts, it keeps running for 5 minutes. Once the compressor stops, it will not start running again for 3 minutes. If you change the operation mode during the cooling cycle, the control circuit stops the
compressor for 3 minutes.
For 5 minutes after the compressor is first turned on, and for 3 minutes after it is turned off,
the compressor is not controlled by the room sensor.
Thermo ON: When room temperature rises 1 °F above the set temperature T˚, (T ˚+1 °F):
Compressor ON
Thermo OFF: When the room temperature is equal to or below the set temperature T˚:
Compressor OFF
ON
1028_X_S
– 27 –
SM830079
Page 28
10. PROCESSES AND FUNCTIONS
(2) Freeze Prevention
Freeze Prevention keeps the indoor heat exchange coil from freezing. Freezing reduces the efficiency of the unit, and frost buildup on the coil blocks cool air circulation from the indoor unit’s fan.
INDOOR COIL TEMPERATURE
MORE THAN 10 MINUTES
FREEZE PREVENTION
6 MINUTES 10 MINUTES
FREEZE PREVENTION
6 MINUTES
30°F
COMPRESSOR
OUTDOOR FAN
INDOOR FAN
ON
ON
(THERMO OFF)
OFF
OFF OFF
SET SPEED
ON
ON
(THERMO ON)
OFF
ON
ON
1029_X_S
Fig. 9
(3) Drain Pump Control
Drain pump operates when compressor starts to operate or when Float Switch turns off.
FLOAT SWITCH
ON: low water level OFF: high water level
COMPRESSOR
DRAIN PUMP
OUTDOOR FAN
INDOOR FAN
ON
ON
ON
ON
OFF
OFF
OFF
ON
ON
SET SPEED
– 28 –
OFF
20 MINUTES
OFF
ON
OFF
ON
ON
ON
0609_X_S
Fig. 10
SM830079
Page 29
10. PROCESSES AND FUNCTIONS
(4) Outdoor Fan Speed Control (CL1852)
Low ambient fan speed control
This function protects the compressor from being damaged due to flowback of the liquid refrigerant to the compressor when the outdoor temperature is very low.
When the air temp. thermistor (TH) on the outdoor units detects a change in tem­perature, the controller on the electrical component box activates to control the fanspeed automatically.
If the outdoor temperature falls below 57°F, the fan speed switches to MED.
If the outdoor temperature falls below 30°F, the fan speed switches to LOW.
Outdoor
temperature
57°F
30°F
Fan speed
HIGH
MEDIUM
LOW
1
*
Fan motor output
3 – 1 (BLU–GRY) or (WHT–GRY)
5 – 1 (VLT–GRY)
7 – 1 (YEL–GRY)
(Line voltage 115V or 230V)
2
*
1893_M_I
Fig. 11
*1Regardless of outdoor temperature, outdoor fan motor operates at first at HIGH
speed for 23 ± 5 seconds to give the motor an initial boost.
*2When the fan speed switches, the controller terminal’s location where line voltage
comes out (j–j) shifts accordingly.
– 29 –
SM830079
Page 30
11. SERVICE PROCEDURES
(1) Troubleshooting
1) Check before and after Troubleshooting
Many problems may happen because of wiring or power supply problems, so you should check these areas first. Problems here can cause false results in some of the other tests, and so should be corrected first.
11
1 Check power supply wiring
11
(a) Single-phase
Check that power supply wires are correctly connected to terminal No. 1
through No. 4 on the 4P terminal plate in the indoor unit and No. 5 and No. 6 on the 6P terminal in the outdoor unit.
22
2 Check inter-unit wiring
22
Check that inter-unit control wiring (AC 230 - 208 V Line voltage) is cor-
rectly connected between the indoor unit and outdoor unit.
Single-phase outdoor unit
INDOOR
INDOOR UNIT
1 2 3
Disconnect switch (Field supply)
14 AWG (Inter-unit) Power lines
230/208 V 230/208 V 230/208 V
OUTDOOR UNIT
B
1 2 3 4 5 6
Fuse
A
L1 L2
Power supply line
Single-phase, 230/208 V
14 AWG
G
Grounding line
G
1306_M_I
Fig. 12
33
3 Check power supply
33
Check that voltage is within the specified range (±10 % of the rating). Check that power is being supplied.
If the following troubleshooting must be done with power being supplied, be careful not to touch any uninsulated live part that can cause ELECTRIC SHOCK.
44
4 Check the lead wires and connectors in indoor and outdoor units.
44
Check that the sheath of lead wires is not damaged. Check that the lead wires are firmly connected at the terminal plate. Check that the wiring is correct.
55
5 Reference
55
Condition of general cooling operation (Thermo. ON)
SWEEP .................. ON
Indoor fan speed .... HIGH
– 30 –
SM830079
Page 31
11. SERVICE PROCEDURES
2) Air Conditioner does not Operate
11
1 Circuit breaker trips (or fuse blows).
11
(a) When the circuit breaker is set to ON, it is tripped soon.
• There is a possibility of ground fault.
• Check insulation resistance. If resistance value is 1 M or less, it is a defect of insulation.
(Example)
1 3
Outdoor
unit
6
Circuit breaker
*Set the circuit breaker to OFF.
Power supply cords
+ +
Ground
5
1 2 3
G
2
4
+ +
+
Inter-unit power line
Indoor
1
+
2
+
3
+
G
unit
1
Remove power supply cords from the terminal plate in the outdoor unit.
• Check insulation resistance of power supply cords.
OK
Remove inter-unit power line
2
from the terminal plate in the outdoor unit.
• Check insulation resistance of outdoor unit.
OK
3
Remove inter-unit power line from the terminal plate in the indoor unit.
• Check insulation resistance of indoor unit.
NO
NO Insulation of
NO
Execute rewiring.
outdoor unit is defective.
Insulation of indoor unit is defective.
• Check insulation resistance of electrical parts in the outdoor unit.
• Check insulation resistance of electrical parts in the indoor unit.
OK
Inter-unit power lines are defective.
Execute rewiring.
1334_X_S
SM830079
– 31 –
Page 32
11. SERVICE PROCEDURES
(b)
Circuit breaker trips in several minutes after turning the air conditioner on.
• There is a possibility of short circuit.
• Check capacity of circuit breaker.
Is capacity of circuit breaker sufficient ?
• Check resistance of outdoor fan motor winding.
• Check resistance of compressor motor winding.
22
2 Neither indoor unit nor outdoor unit runs.
22
NO
A. Power is not supplied
Circuit breaker
• Check power supply. Is power being supplied to outdoor unit ?
NO
is tripped.
Power failure.
Replace it with a suitable one. (= larger capacity)
0614_X_S
Reset the breaker.
Wait for recovery or consult power supply company.
0615_X_S
B. Check remote control unit.
• Try to run both indoor and outdoor units with another remote control unit.
OK
The other remote control unit is defective.
NO
Refer to item C.
0616_X_S
SM830079
– 32 –
Page 33
11. SERVICE PROCEDURES
C. Check “Operation selector” switch in the indoor unit.
• Has “Operation selector” switch been set to ON
YES
position ?
NO
Set “Operation selector” switch to ON.
But neither unit runs.
Switch Ass’y or P.C.B. Ass’y in the indoor unit is defective.
D. Transformer in indoor unit.
• Check resistance of transformer winding. (TR1)
IND. LAMP Ass’y or P.C.B. Ass’y in the indoor unit is defective.
0617_X_S
E. Check. auxiliary relay.
• Check coil resistance of auxiliary relay. (RY1-RY5)
1033_X_S
1894_X_I
– 33 –
SM830079
Page 34
11. SERVICE PROCEDURES
F. Check indoor fan motor thermal protector (49FMI)
• Disconnect the socket from 9P (WHT) connector.
• Check the continuity between No. 8 and No.9 poles of the 9P socket.
No continuity.
The thermal protector (49FMI) is operated.
• Check fan rotation. Rotate the fan gently once or twice by hand.
OK
• Check fan motor capacitor.
G. Check fuse on the P.C.B. Ass’y in the indoor unit.
Fan cannot be rotated.
Check fan casing for foreign matter on the inside.
Fan motor burnout or foreign matter in bearing.
Remove foreign matter or repair.
Repair or replace.
0621_X_S
• Check fuse on the P.C.B. Ass'y in the indoor unit for continuity.
When the fuse blows.
• Check transformer. (TR1) OK
• Check resistance of indoor
fan motor winding. (FMI)
OK
• Check resistance of louver
motor winding. (LM)
OK
• Check resistance of drain pump winding. (DP)
OK
• Check coil of compressor motor magnetic contactor. (PR)
OK
• P.C.B. Ass'y is defective.
1895_X_S
– 34 –
SM830079
Page 35
11. SERVICE PROCEDURES
3) Outdoor Unit does not Run.
A. Check COOL / FAN selector switch in the remote control unit.
• Is COOL/FAN selector switch set to COOL ?
B. Check set temperature.
Try to lower set temperature by Temperature setting button “COOLER”.
YES
• Set “Operation selector” switch to TEST in the indoor unit.
Outdoor unit runs.
Is room temperature too low ?
NO
Set to COOL.
0623_X_S
NO
• Try to run both indoor and outdoor units with another remote control unit.
OK
The other remote control unit is defective. (Room sensor in the remote control unit is defective.)
0624_X_S
– 35 –
SM830079
Page 36
11. SERVICE PROCEDURES
C. Check compressor motor magnetic contactor.
• Check coil resistance of compressor motor magnetic contactor. (PR)
1896_X_S
D .Check indoor unit P.C.B.
• Check P.C.B. Ass’y.
• Check voltage between terminals No.1 and No.2 at terminal plate.
No voltage appears.
P.C.B. Ass’y is defective.
1897_X_S
F. Check float switch.
• Refer to “11. (3) Drain Pump Control”
E. Check outdoor unit P.C.B.
(CL1822 Type)
• Check P.C.B. Ass’y.
• Check voltage between terminals No.5 and No.6 at terminal plate.
No voltage appears.
P.C.B. Ass’y is defective.
1335_X_S
Is drainage prevented from flowing ?
YES
• Check drain hose.
NO (Wait for 20 minutes.)
• Check float switch (FS).
0629_X_S
SM830079
– 36 –
Page 37
11. SERVICE PROCEDURES
4) Indoor Unit does not Run.
(Indoor fan and louver motor do not run.)
P.C.B. Ass’y is defective.
0630_X_S
5) Some Part does not Operate.
A. Indoor fan does not run.
• Check fan rotation. Rotate the fan gently once or twice by hand.
Fan cannot be rotated.
Check fan casing for foreign matter on the inside.
Fan motor burnout or foreign matter in bearing.
Remove foreign matter or repair.
Repair or replace.
• Check resistance of fan motor winding.
OK
• Check fan motor capacitor. OK
Relay RY1 or RY2 on the P.C.B. Ass’y is defective.
B. Louver motor does not run.
• Check resistance of
louver motor winding.
OK
P.C.B. Ass’y or remote control unit is defective.
0632_X_S
0631_X_S
– 37 –
SM830079
Page 38
11. SERVICE PROCEDURES
6) Outdoor Fan does not Run.
• Check fan rotation. Rotate the fan gently once or twice by hand.
• Check resistance of fan motor winding.
OK
• Check fan motor capacitor
• Check continuity between terminals on the compressor motor magnetic contactor.
Fan cannot be rotated.
• Check fan casing for foreign matter on the inside.
• Fan motor burnout or foreign matter in bearing.
Remove foreign matter or repair.
Repair or replace.
7) Outdoor Fan does not Run for CL1852.
• Check fuse on PCB Ass’y in outdoor unit for continuity.
If fuse blows,
• Check resistance of primary winding of transformer. (TR)
1038_X_S
8) Compressor does not Run.
• Check compressor motor capacitor (RC1).
OK
• Check resistance of compressor motor winding.
0633_X_S
Wait for 30 minutes until com­ pressor has cooled.
Compressor runs.
Compressor internal thermal protector is operated.
– 38 –
• Check power supply voltage. Is voltage abnormally low?
NO
• Is outdoor heat exchanger coil dirty or are there obstacles near air suction inlet?
1336_X_S
SM830079
Page 39
11. SERVICE PROCEDURES
9) Poor Cooling
Check installation position of remote control unit.
• Does cool air from air condi­ tioner reach remote control unit directly ?
• Is wide tube between indoor unit and outdoor unit insulated ?
YES
• Measure temperatures of suction and discharge air of indoor unit.
Temperature difference between suction and discharge air is large enough (Approx. 10 deg. or more).
• Check clogging of air filter.
• Is fan speed set to LOW ?
YES
NO
Temperature difference is small.
Possibility of refrigerant shortage.
Air filter is clogged.
YES
Change installation position of remote control unit.
Insulate wide tube and then execute taping with narrow tube.
Charge refrigerant (R22).
Clean filter.
Set fan speed to either HIGH or MEDIUM.
• Review cooling load estimate, if performance of air conditioner is normal.
10) Excessive Cooling.
• The set temperature is too low.
• Is the remote control unit installed at a place where it can detect the room temperature properly ?
YES
NO
Reduce cooling load or replace the unit with higher cooling capacity.
1040_X_S
Set the temperature to higher value using temperature setting button of the remote control unit.
Change installation position of the remote control unit.
0637_X_S
– 39 –
SM830079
Page 40
11. SERVICE PROCEDURES
(2) A Sensor is Defective
11
1 Indoor (heat exchanger) coil temp. Sensor is defective.
11
(a) Open (=No continuity in sensor) Compressor and outdoor fan repeat ON for 10 minutes and OFF for 6 minutes
when sensor opens. (b) Short
“Freeze Prevention” does not operate when dehumidified water is frozen on the
indoor coil.
22
2 Room temp. Sensor (in the remote control unit) is defective.
22
(a) Open (=No continuity in sensor) Neither outdoor fan nor compressor runs.
(b) Short Outdoor fan and compressor do not stop. — Excessive cooling.
(3) Operation of Major Electrical Parts
Operation Mode
(Function)
Manual
Night
Cool
setback
-ing Timaer
(set) Freeze prevention VV V
Fan
Sweep
Flap
Stop
NOTE V* Refer to Cooling Mode.
Operation
Room
Temp. Thermo.ON VV VV V Thermo.OFF VV V Thermo.ON VV V VV V Thermo.OFF VV V ON Timer V OFF Timer VVV VV V
VV
Cool VV* V* VV* V* Fan VV Cool VV* V* VV* V* Fan VV
Indoor unit and Remote Control unit
Indicator lamps
Cool
Timer
Night setback Energy saver
Sweep
Fan
Oudoor unit
Fan Compressor
– 40 –
SM830079
Page 41
11. SERVICE PROCEDURES
(4) Checking the Electrical Components
1) Measurement of Insulation Resistance
The electrical insulation is acceptable when the resistance exceeds 1 M.
11
1 Power Supply Wires
11
Clamp the earthed wire of the Power Supply wires with a lead clip of the insulation resistance tester and mea­sure the resistance by placing a probe on either of the power wires. (Fig. 13)
Then measure the resistance between the earthed wire and the other power wires. (Fig. 13)
22
2 Indoor Unit
22
Clamp an aluminum plate fin or copper tube with the lead clip of the insulation resistance tester and measure the resistance by placing a probe on the terminal plate (Fig. 14)
Probe
Copper tube or metallic part
Clip
Clip
Earthed wire
Insulation tester
Terminal plate
0638_X_S
Insulation tester
Probe
0639_X_S
Fig. 13
Fig. 14
33
3 Outdoor Unit
33
Measure the resistance by placing a probe on the terminal plate in the same manner as explained above 2. (Fig. 14)
44
4 Measurement of Insulation Re-
44
sistance for Electrical parts
• Disconnect the connector of the
desired electric part from terminal plate, P.C.B. Ass’y, etc. (Fig. 15)
Similarly, disconnect the lead wires from compressor, capacitor, etc. (Fig. 16)
• Measure the resistance in the same
manner as illustrated on the right. Refer to Electrical Wiring Diagram.
NOTE
If the probe does not enter the hole because the hole is too narrow, use a probe with a thinner pin.
Copper tube or metallic part
Metallic part
Clip
Clip
Insulation tester
From fan motor, compressor and other parts.
Probe
Insulation tester
Probe
0640_X_S
0641_X_S
Fig. 15
Fig. 16
– 41 –
SM830079
Page 42
11. SERVICE PROCEDURES
2) Checking the Protective Devices
• Disconnect the connector, which consists of P (plug) and S (socket) when you want to check the
protective device.
• Then check continuity among plug’s (and/or socket’s) terminal as in Fig. 17.
• Normality of the protective device can be judged by the following table.
The Protective Device is proved normal if there is a continuity between terminals.
socket
Multimeter
0642_X_S
11
1 Indoor fan motor thermal protector (49FI) . . . . . . Indoor unit
11
• Disconnect the connector which leads to the indoor fan motor (FMI).
• Check the socket’s terminals.
22
2 Compressor motor thermal protector . . . . . . Outdoor unit
22
• Disconnect the wires from terminals of compressor.
• Check the terminals of compressor.
33
3 Outdoor fan motor thermal protector (49FO) . . . . . . Outdoor unit
33
• Disconnect both the connector which leads to the outdoor fan motor (FMO).
• Check socket’s terminal.
Fig. 17
– 42 –
SM830079
Page 43
11. SERVICE PROCEDURES
3) Checking the Electrical Parts
11
1 Power transformer (TR1) ................. Indoor unit *Measure the coil resistance.
11
• Primary 230-208 V ; Measure the resistance between two WHT lead wire terminals
of socket connected to power transformer.
• Secondary 10.6 V ; Measure the resistance between two BRN lead wires.
Refer to “2. (3) (A) Other component specifications”.
22
2 Power transformer (TR) ................. Outdoor unit *Measure the coil resistance.
22
• Primary 230-208 V ; Measure the resistance between two WHT lead wire terminals
of socket jointed to power transformer.
• Secondary 19 V ; Measure the resistance between two BRN lead wires.
Refer to “2. (3) (B) Other component specifications”.
33
3 Indoor fan motor (FMI) ............... Indoor unit *Measure the coil resistance.
33
• Measure the resistance between each terminal of the socket connected to the
indoor fan motor.
Refer to “2. (2) (A) Major component specifications”.
44
4 Outdoor fan motor (FMO) ........... Outdoor unit *Measure the coil resistance.
44
• Measure the resistance in the same manner as explained above 2.
Refer to “2. (2) (B) Major component specifications”.
55
5 Motor capacitor ............ Both in indoor and outdoor unit
55
Remove the lead wires from the
capacitor terminals, and then place a probe on the capacitor terminals as shown in Fig. 18. Observe the deflec­tion of the pointer, setting the resis­tance measuring range of the multim-
Multimeter
eter to the maximum value.
The capacitor is “good” if the pointer
bounces to a great extent and then gradually returns to its original posi­tion.
NOTE
The range of deflection and the deflection time differ according to the capacity of the
capacitor.
– 43 –
Compressor motor capacitor
Fig. 18
Fan motor capacitor
1041_X_S
SM830079
Page 44
11. SERVICE PROCEDURES
1042_X_S
Fuse
66
6 Continuity of fuse on P.C.B.
66
Ass’y
• Check for continuity using a multim-
eter as shown in Fig. 19.
NOTE
Method Used to Replace Fuse on PCB Ass’y
1. Remove the PCB Ass’y from the
electrical component box.
2. Remove the fuse from PCB Ass’y
using pliers while heating the sol­dered leads on the back side of the PCB Ass’y with a soldering iron (30W or 60W). (Fig. 20)
3. For replacement, insert a fuse of the
same rating to the intended position and solder it. (Allow time to radiate heat during sol­dering so that the fuse does not melt.)
When replacing the
CAUTION
fuse, be sure not to break down the varistor.
Fig. 19
Soldering iron
PCB Ass’y
Fuse Varistor
Pliers
1043_X_S
Fig. 20
4) Thermistor Characteristic Curve
1 Room temp. sensor
(KTEC-35)
10
9 8 7 6 5
Resistance (kn )
4 3 2 1
50 59 68 77 86 95 104
Temperature (°F)
1044_M_I
1 Coil sensor
(PBC-41E)
40
35
30
25
20
15
10
Resistance (kn )
5
0
– 44 –
4 5 14233241505968
Temperature (°F)
1045_M_I
SM830079
Page 45
• The specifications, designs, and information in this brochure are subject to change without notice.
SANYO FISHER Service Company CENTRAL REGION
1739 Sands Place, Suite G Marietta, GA 30067 Phone: (770) 951-8284
Fax: (770) 951-2077
Sep. / ’2000 Printed in U.S.A.
Loading...