SUBMITTAL SHEET
SYSTEM
42XS32A
CEILING RECESSED (4-WAY) AIR CONDITIONER
POWER V/PH/HZ 230/208/1/60
Circuit Ampacity, Min. (A) 30
Fuse size, Max. (A) 50
COMPRESSOR Scroll-Hermetic
No. used 1
R.L. Amps - L.R. Amps (A) 18.1 -131
Crankcase Heater -
OUTDOOR FAN - TYPE Propeller
Dia. (in.) - No. used 18-3/32 - 2
Type Drive - No. speeds Direct – 2 (AUTO)
No. Poles - RPM (High) 6 - 879
No. Motors - Watts 2 - 110
CFM (High) 3,450
F.L. Amps. (A) 1.8
OUTDOOR COIL - TYPE Aluminum Fin & Copper Pipe
Fin Type - Pipe Type Slit Plate - Inner Riffled
Rows - F.P.I. 2 - 12.7
Face Area (sq.ft.) 11.63
Tube Size (in.) 3/8
INDOOR FAN - TYPE Turbo
Dia. & Length (in.) - No. used 19-9/32 -1
No. speeds 3 & Auto
No. Poles -RPM (High) 6 - 560
No. Motors - Watts 1- 60
CFM (HI/MED/LOW) 980/830/650
F.L. Amps (A) 0.9
INDOOR COIL - TYPE Aluminum Fin & Copper Pipe
Fin Type - Pipe type Slit Plate - riffled
Rows - F.P.I. 2 - 14.9
Face Area (sq. ft.) 5.17
Tube Size (in.) 5/16
Drain Connection Size (in.) 3/4
REFRIGERANT R22
Lbs. - R22 (O.D. Unit) 9.7
Control Capillary Tube
Connection Flare
Line Length, Max (ft.) 165
Lift difference, Max (ft.) 100
Line Size - in. O.D. Discharge 3/8
Line Size - in. O.D. Suction 3/4
DIMENSIONS (in.) H x W x D
Indoor Unit -Uncrated 14-3/32 x 45-9/32 x 33-27/32
Outdoor unit -Uncrated 48-5/8 x 37 x 13-3/8
WEIGHT INDOOR OUTDOOR
Net (lbs.) 75 198
Shipping (lbs.) 71/29(Grille) 223
Shipping Volume (cu.ft.) 10.4/4.6(Grille) 19.8
GENERAL DATA (AT 230V)
-Crated 12-7/16 x 43- 27/32 x 32-25/32(Indoor unit)
-Crated 52 -7/32 x 40 x 16-3/8
INDOOR/OUTDOOR
XS4232/C4232A
4-3/32 x 49-1/2 x 39-11/32(Indoor Grille)
AIRCONDITIONING PRODUCTS
PERFORMANCE DATA @ ARI STANDARD CONDITIONS
COOLING
Total Capacity (BTU/H) 42,000/40,500
Sensible Capacity(BTU/H) 22,360/21,470
Latent Capacity (BTU/H) 19,640/19,030
SEER 10.2/10.3
Dehumidification (Pints/H) 14.6/14.8
Amps (A) 20.8/21.1
Power Inputs (W) 4,230/4,120
Outdoor Sound Rating (bels) 7.9
FEATURE
Controls Microprocessor
Remote Controller LCD Wireless type
Temperature Control IC Thermostat
Timer ON/OFF, 24 hours
Night Setback Built-In
Air Louver (Horizontal) -
(Vertical) Automatic
Power Failure Automatic Restart Built-In
Self Diagnosis N/A
OPTION
Refrigerant Line Set AP3210BH (30 ft)
AP3215BH (50 ft)
Low Ambient Control N/A
Fresh Air Intake CMB-GS140TAirduct Extension Available
Condensate Drain Pump Built-In
Non-Removable Remo-con Bracket RCS5PS4B
Wired Remote Control RCS-102WD/RCS-302WD
OPERATING RANGE
Cooling Indoor Air Outdoor Air
Intake Temp. Intake Temp.
Maximum 95 F DB/71 F WB 115 F DB
Minimum 67 F DB/57 F WB 67 F DB
CERTIFICATION
SS42XS32A-2
(230/208V)
42XS32A

SUBMITTAL SHEET
SYSTEM INDOOR/OUTDOOR
42XLS32A
CEILING RECESSED (4-WAY) LOW AMBIENT AIR CONDITIONER
GENERAL DATA (AT 230V)
POWER V/PH/HZ 230/208/1/60
Circuit Ampacity, Min. (A) 30
Fuse size, Max. (A) 50
COMPRESSOR Scroll-Hermetic
No. used 1
R.L. Amps - L.R. Amps (A) 18.1 -131
Crankcase Heater 30W
OUTDOOR FAN - TYPE Propeller
Dia. (in.) - No. used 8-3/32 - 2
Type Drive - No. speeds Direct – 3 (AUTO)
No. Poles - RPM (High) 6 - 879
No. Motors - Watts 2 - 110
CFM (High) 3,450
F.L. Amps. (A) 1.8
OUTDOOR COIL - TYPE Aluminum Fin & Copper Pipe
Fin Type - Pipe Type Slit Plate - Inner Riffled
Rows - F.P.I. 2 - 12.7
Face Area (sq.ft.) 11.63
Tube Size (in.) 3/8
INDOOR FAN - TYPE Turbo
Dia. & Length (in.) - No. used 19-9/32 -1
No. speeds 3 & Auto
No. Poles -RPM (High) 6 - 560
No. Motors - Watts 1- 60
CFM (HI/MED/LOW) 980/830/650
F.L. Amps (A) 0.9
INDOOR COIL - TYPE Aluminum Fin & Copper Pipe
Fin Type - Pipe type Slit Plate - riffled
Rows - F.P.I. 2 - 14.9
Face Area (sq. ft.) 5.17
Tube Size (in.) 5/16
Drain Connection Size (in.) 3/4
REFRIGERANT R22
Lbs. - R22 (O.D. Unit) 9.7
Control Capillary Tube
Connection Flare
Line Length, Max (ft.) 165
Lift difference, Max (ft.) 100
Line Size - in. O.D. Discharge 3/8
Line Size - in. O.D. Suction 3/4
XS4232/CL4232A
SS42XLS32A-2
PERFORMANCE DATA @ ARI STANDARD CONDITIONS (230/208V)
COOLING
Total Capacity (BTU/H) 42,000/40,500
Sensible Capacity (BTU/H) 22,360/21,470
Latent Capacity (BTU/H) 19,640/19,030
SEER 10.2/10.3
Dehumidification (Pints/H) 14.6/14.8
Amps (A) 20.8/21.1
Power Inputs (W) 4,230/4,120
Outdoor Sound Rating (bels) 7.9
FEATURE
Controls Microprocessor
Remote Controller LCD Wireless type
Temperature Control IC Thermostat
Timer ON/OFF, 24 hours
Night Setback Built-In
Air Louver (Horizontal) -
Power Failure Automatic Restart Built-In
Self Diagnosis N/A
OPTION
Refrigerant Line Set AP3210BH (30 ft)
Low Ambient Control N/A
Fresh Air Intake CMB-GS140TAirduct Extension Available
Condensate Drain Pump Built-In
Non-Removable Remo-con Bracket RCS5PS4B
Wired Remote Control RCS-102WD/RCS-302WD
OPERATING RANGE
Cooling Indoor Air Outdoor Air
CERTIFICATION
AIRCONDITIONING PRODUCTS
(Vertical) Automatic
AP3215BH (50 ft)
Intake Temp. Intake Temp.
Maximum 95 F DB/71 F WB 115 F DB
Minimum 67 F DB/57 F WB 0 F DB
DIMENSIONS (in.) H x W x D
Indoor Unit -Uncrated 14-3/32 x 45-9/32 x 33-27/32
-Crated 12-7/16 x 43- 27/32 x 32-25/32(Indoor unit)
4-3/32 x 49-1/2 x 39-11/32(Indoor Grille)
Outdoor unit -Uncrated 48-5/8 x 37 x 13-3/8
-Crated 52 -7/32 x 40 x 16-3/8
WEIGHT INDOOR OUTDOOR
Net (lbs.) 75 198
Shipping (lbs.) 71/29 (Grille) 223
Shipping Volume(cu.ft.) 10.4/4.6(Grille) 19.8
42XLS32A

8-19/32
Dimensional Data
Indoor Unit: XS4232
2-13/32
32-9/32 (Ceiling opening)
23-7/32 (Suspention bolt pitch)
13-15/32 19/32
X-view
19-9/32 1-9/16
5-23/321-3/8
29-29/32
2-3/4
8-9/32
6-1/2
11-7/32
12-29/32
8-19/32
4-29/32
2-3/8
1-3/16
15/32
33-27/32
19-11/16
Outdoor Unit: C4232/CL4232
1-31/32 1-31/32
13-3/8
37
4-21/64266-11/16
1-3/16
14-31/32 13/32
15-3/4
Panel center
41-11/32
43-11/16 (Ceiling opening)
40-5/32 (Suspention bolt pitch)
9
3-15/16 3-15/16
1-7/8
8-9/32
45-9/32
31-3/32
15/32
Dimension : inch
Air intake grille
Air outlet
Refrigerant liquid line (ø3/8")
Refrigerant gas line (ø3/4")
Drain connection
Power supply entry
For discharge duct
Humidifier (option) mounting hole
Suspension bolt mounting
48-5/8
23-29/32
22-27/32
WARRANTY
SANYO products are warranted against defects in materials and workmanship for the
period below;
Compressor 30 Days 5 Years
Other Components N/A 1 Year
Because of a policy of continuous product improvements, SANYO reserves the right
to change specifications and design without notice.
LABOR PARTS
Dimension : inch
Hole for anchor bolt (4-ø13)
Refrigerant tube joint (narrow tube)
Flare connection 3/8 in (9.52 mm)
Refrigerant tube joint (wide tube)
Flare connection 3/4 in (19.05 mm)
Refrigerant tubing inlet
Power supply inlet
Full specific warranty rights, conditions, exclusions and obligations are specified in the
warranty packed with each products.
1581_C_S
SANYO FISHER COMPANY
A Division of SANYO North America Corporation
21605 Plummer St. Chatsworth, CA 91311
Phone : (818) 998- 7322
Fax : (818) 701- 4160
Website: http://www.sanyohvac.com