Split System Submittal Data
System: 36UW72R Indoor/Outdoor: UHW3672R/C3672R
Concealed Duct Air Conditioner
Job Name:
Location:
Engineer:
Submitted to:
Submitted by:
Reference:
General Data (at 230V)
Power V/PH/Hz 230/208/1/60
Circuit Ampacity
Fuse Size, Max.
Compressor
No. used
R.L. Amps - L.R.
Crankcase Heater
Outdoor Unit
Fan type
Dia. (in.) - No. Speeds
Type Drive - No. Speeds
No. Poles
No. Motors
CFM
F.L. Amps
(A) 15-35 Indoor-Outdoor
(A) 15-35 Indoor-Outdoor
DC Rotary Inverter
1
(A) 16.4-17.5
(W) -
Propeller
18-7/64-1
Direct Inverter
(RPM) 8 - 830
(W) 1-90
(High) 1942
(A) 17.3
Approval:
Date:
Construction:
Unit #:
Drawing #:
Refrigerant
Lbs. - R410a (outdoor unit)
Control
Connection
Line Length, Max
Lift Difference, Max
Line Size
Line Size
Dimensions
Indoor Unit
(Crated) 14-3/32 x 65-25/32 x 30-13/16
Outdoor Unit
R410A
6.17
Electric Expansion Valve
Flare
165
50 (Outdoor lower), 100 (Outdoor higher)
(in. O.D. Discharge) 3/8”
(in. O.D. Suction) 5/8”
(in.) H x W x D
(Uncrated) 12-7/32 x 58-9/32 x 24-13/16
(Uncrated) 30-23/32 x 37 x 13-3/8
(Crated) 34-31/32 x 39-31/32 x 16-3/32
Coil Type
Fin Type - Pipe Type
Rows - F.P.I.
Face Area
Tube Size
Indoor Unit
Fan type
Dia. & Length (in.) - No. Speeds
No. Speeds
No. Poles
No. Motors
CFM
Indoor Sound Rating
F.L. Amps
Coil Type
Fin Type - Pipe Type
Rows - F.P.I.
Face Area
Tube Size
Drain Connection Size
(sq.ft.) 7.26
(in.) 3/8”
(RPM, High) 4-940
(W) 1-100
(HI/Med/Lo) 1060/920/750
(Hi) (dB-A) 38
(A) 1.0
(sq.ft.) 3.32
(in.) 3/8”
Aluminum Fin & Copper Pipe
Slit Plate - Inner Rifl ed
2-14.1
Centrifugal
5-29/32-3
3 & Auto
Aluminum Plate Fin & Copper Tube
Slit Plate - Inner Rifl ed
3-12.7
1-17/64
Weight
Net
Shipping
Shipping Volume
Performance Data @ ARI Standard Conditions (230V)
Cooling
Total Capacity
Sensible Capacity
Latent Capacity
SEER
Dehumidification
Amps
Power Inputs
Outdoor Sound Rating
(cu.ft.) 16.5 13.0
(Pints/H) 10.0
(A) 18.6/20.6
(dB-A) 52
Indoor Outdoor
(lbs.) 104 143
(lbs.) 115 161
Indoor Outdoor
(BTU/H) 31,200 (9,500-31,200)
(BTU/H) 19,570
(BTU/H) 11,630
(W) 3,920/3,920
13.9

Dimensions
Dimensional Data for 36U72R
Indoor unit : UH3672R
Feature
Controls
Remote Controller
Temperature Control
Timer
Night Setback
Air Louver
Power Failure Automatic Restart
Self-Diagnosis
Air Filter
(Horizontal) Manual
(Vertical) Automatic
LCD Wired Type, Temp. Sensor Built In
Microprocessor
IC Thermostat
72HR, ON/OFF
Built-In
Built-In
Built-In
Washable, Anti-Mold
Option
Refrigerant Line Set
Fresh Air Intake
Condensate Drain Pump
Wireless Remote Controller
Non-Removeable Remo-con Bracket
Operating Range
Indoor Air Intake Temp. Outdoor Air Intake Temp.
Cooling
Maximum 95F DB/71F WB 109F DB
Minimum 67F DB/57F WB 0F DB
Available
N/A
Standard
Available
Available
Sanyo Commercial Solutions
A Division of SANYO North America
1300 Michael Drive
Wood Dale, IL 60191 USA
www.sanyohvac.com