SUBMITTAL SHEET
SYSTEM INDOOR/OUTDOOR
36THS32 THS3632/CH3632
CEILING SUSPENDED HEAT PUMP
POWER V/PH/HZ 230/208/1/60
Circuit Ampacity, Min. (A) 50
Fuse size, Max. (A) 50
COMPRESSOR Scroll
No. used 1
R.L. Amps - L.R. Amps (A) 15.2 -107.0
Crankcase Heater 30W
OUTDOOR FAN - TYPE Propeller
Dia. (in.) - No. used 18-3/32 - 2
Type Drive - No. speeds Direct ñ 2 (AUTO)
No. Poles - RPM (High) 6 - 879
No. Motors - WATTS 2-110
CFM (High) 3,670
F.L. Amps. (A) 1.8
OUTDOOR COIL - TYPE Aluminum Fin & Copper Pipe
Fin Type - Pipe Type Slit Plate - Inner Riffled
Rows - F.P.I. 2 - 14.1
Face Area (sq.ft.) 11.63
Tube Size (in.) 3/8
INDOOR FAN - TYPE Centrifugal
Dia. (in.) - No. used 5-29/32 - 4
No. speeds 3 & Auto
No. Poles -RPM (High) 4 - 1,200
No. Motors - HP 1 - 3/25
CFM (HI/MED/LOW) 950/830/715
F.L. Amps (A) 0.9
INDOOR COIL - TYPE Aluminum Fin & Copper Pipe
Fin Type - Pipe type Slit Plate - Inner Riffled
Rows - F.P.I. 3 - 12.7
Face Area (sq. ft.) 3.66
Tube Size (in.) 3/8
Drain Connection Size (in.) 1-1/4
REFRIGERANT R22
Lbs. - R22 (O.D. Unit) 8.82
Control Electronic Expansion Valve
Connection Flare
Line Length, Max (ft.) 165
Lift difference, Max (ft.) 100
Line Size - in. O.D. Discharge 3/8
Line Size - in. O.D. Suction 3/4
DIMENSIONS (in.) H x W x D
Indoor Unit -Uncrated 9-27/32x 61-13/16 x 26-3/8
Outdoor Unit -Uncrated 48-5/8 x 37 x 13-3/8
GENERAL DATA(AT 230V)
-Crated 13-7/32 x 65- 3/4 x 30-25/32
-Crated 52 -7/32 x 40 x 16-12/32
AIRCONDITIONING PRODUCTS
SS36THS32-1
PERFORMANCE DATA @ ARI STANDARD CONDITIONS (230/208V)
COOLING
Total Capacity (BTU/H) 36,000/35,000
Sensible Capacity (BTU/H) 23,530/22,630
Latent Capacity (BTU/H) 12,470/12,370
SEER 10.0/10.2
Dehumidification (Pints/H) 10.4/10.2
Amps (A) 17.5/18.3
Power Inputs (W) 3,650/3,550
HEATING
Total Capacity (BTU/H) 37,000/36,000
HSPF 7.2/7.2
Amps (A) 16.7/16.6
Power Inputs (W) 3,450/3,300
Back-up Strip Heater (KW) 3.00/2.45
Outdoor Sound Rating (bels) 8.0
FEATURE
Controls Microprocessor
Remote Controller LCD Wireless type
Temperature Control IC Thermostat
Timer ON/OFF, 24 hours
Night Setback Built-IN
Air Louver (Horizontal) Manual
Power Failure Automatic Restart Built-In
Self Diagnosis Built-In
Heating/Cooling Automatic Changeover Built-In
OPTION
Refrigerant Line Set AP3210BH (30 ft)
Low Ambient Control N/A
Fresh Air Intake Available
Central Remote ON-OFF Control Available
Airduct Extension N/A
Indoor Frame Extension N/A
Condensate Drain Pump Available
Non-Removable Remo-con Bracket Available
OPERATING RANGE
Cooling Indoor Air Outdoor Air
Heating Maximum 80 F DB/67 F WB 75 F DB / 65 F WB
CERTIFICATION
(Vertical) Automatic
AP3215BH (50 ft)
Intake Temp. Intake Temp.
Maximum 95 F DB/71 F WB 115 F DB
Minimum 67 F DB/57 F WB 67 F DB
Minimum - F DB/ - F WB 17 F DB/ 15 F WB
WEIGHT INDOOR OUTDOOR
Net (lbs.) 98.0 198.0
Shipping (lbs.) 123.0 223.0
Shipping Volume (cu.ft.) 15.5 19.8
36THS32

DIMENSIONAL DATA
Indoor Unit: THS3632
Drain connection
Drain connection for left side
Refrigerant liquid line (3/8") Flare connection
Refrigerant gas line (3/4") Flare connection
Hole for rear side refrigerant tubing
Hole for through-the-wall refrigerant tubing (ø3-15/16" hole)
Hole for fresh air intake (Knockout hole)
Hole for right side refrigerant tubing (Knockout hole)
Hole for left side drain connection (Knockout hole)
Hole for power supply (Conduit size 1/2")
Infrared rays receiver for wireless remote controller
Cutting position for fresh air intake
Dimension : inch
Air intake
Air outlet
2 ft. or more
Hole for wall-through piping (View from front)
2-13/32 23/32
9-7/8
6-25/32
9-7/16
8-7/16
62
26-3/8
11-1/32
12-7/32
61-7/32
7-3/4
12-19/32 6-5/16
5-15/16
• Remote controller (Accessory)
5-1/2
7-3/4
6-11/16
4-1/2
7-1/4
7-3/4
1-3/326-5/16
3-5/324-3/4
5-3/4
7-7/32
4-1/16
9-7/8
5-9/16
1-3/859-1/4 (Suspension bolt hole pitch)
3-1/2
5-25/32
2-25/325-3/16
11-1/32
3-15/16 1-31/32
3-3/8
6-3/32 7-31/32
Front
(Service space)(Service space)
Holes in the rear side (View from front)
(Suspension bolt hole pitch)
10
or more
10
or more
Outdoor Unit: CH3632
48-5/8
22-27/32
23-29/32
37
Dimension : inch
Hole for anchor bolt (4-ø13)
Refrigerant tube joint (narrow tube)
Flare connection 3/8 in (9.52 mm)
Refrigerant tube joint (wide tube)
Flare connection 3/4 in (19.05 mm)
Refrigerant tubing inlet
Power supply inlet
15-3/4
14-31/32 13/32
1-3/16
1-31/32 1-31/32
13-3/8
4-21/64266-11/16
WARRANTY
SANYO products are warranted against defects in materials and workmanship for the
period below;
LABOR PARTS
Compressor 30 Days 5 Years
Other Components N/A 1 Year
Because of a policy of continuous product improvements, SANYO reserves the right
to change specifications and design without notice.
Full specific warranty rights, conditions, exclusions and obli gations are specified in the
warranty packed with each products.
SANYO FISHER COMPANY
A Division of SANYO North America Corporation
21605 Plummer St. Chatsworth, CA 91311
Phone : (818) 998- 7322