Sanyo 36THS32, THS3632, CH3632 Submittal Sheet

Page 1
SUBMITTAL SHEET
SYSTEM INDOOR/OUTDOOR
36THS32 THS3632/CH3632
CEILING SUSPENDED HEAT PUMP
POWER V/PH/HZ 230/208/1/60 Circuit Ampacity, Min. (A) 50 Fuse size, Max. (A) 50
COMPRESSOR Scroll No. used 1 R.L. Amps - L.R. Amps (A) 15.2 -107.0 Crankcase Heater 30W
OUTDOOR FAN - TYPE Propeller Dia. (in.) - No. used 18-3/32 - 2 Type Drive - No. speeds Direct ñ 2 (AUTO) No. Poles - RPM (High) 6 - 879 No. Motors - WATTS 2-110 CFM (High) 3,670 F.L. Amps. (A) 1.8
OUTDOOR COIL - TYPE Aluminum Fin & Copper Pipe Fin Type - Pipe Type Slit Plate - Inner Riffled Rows - F.P.I. 2 - 14.1 Face Area (sq.ft.) 11.63 Tube Size (in.) 3/8
INDOOR FAN - TYPE Centrifugal Dia. (in.) - No. used 5-29/32 - 4 No. speeds 3 & Auto No. Poles -RPM (High) 4 - 1,200 No. Motors - HP 1 - 3/25 CFM (HI/MED/LOW) 950/830/715 F.L. Amps (A) 0.9
INDOOR COIL - TYPE Aluminum Fin & Copper Pipe Fin Type - Pipe type Slit Plate - Inner Riffled Rows - F.P.I. 3 - 12.7 Face Area (sq. ft.) 3.66 Tube Size (in.) 3/8 Drain Connection Size (in.) 1-1/4
REFRIGERANT R22 Lbs. - R22 (O.D. Unit) 8.82 Control Electronic Expansion Valve Connection Flare Line Length, Max (ft.) 165 Lift difference, Max (ft.) 100 Line Size - in. O.D. Discharge 3/8 Line Size - in. O.D. Suction 3/4
DIMENSIONS (in.) H x W x D Indoor Unit -Uncrated 9-27/32x 61-13/16 x 26-3/8
Outdoor Unit -Uncrated 48-5/8 x 37 x 13-3/8
GENERAL DATA(AT 230V)
-Crated 13-7/32 x 65- 3/4 x 30-25/32
-Crated 52 -7/32 x 40 x 16-12/32
AIRCONDITIONING PRODUCTS
SS36THS32-1
PERFORMANCE DATA @ ARI STANDARD CONDITIONS (230/208V)
COOLING Total Capacity (BTU/H) 36,000/35,000 Sensible Capacity (BTU/H) 23,530/22,630 Latent Capacity (BTU/H) 12,470/12,370 SEER 10.0/10.2 Dehumidification (Pints/H) 10.4/10.2 Amps (A) 17.5/18.3 Power Inputs (W) 3,650/3,550
HEATING Total Capacity (BTU/H) 37,000/36,000 HSPF 7.2/7.2 Amps (A) 16.7/16.6 Power Inputs (W) 3,450/3,300 Back-up Strip Heater (KW) 3.00/2.45 Outdoor Sound Rating (bels) 8.0
FEATURE
Controls Microprocessor Remote Controller LCD Wireless type Temperature Control IC Thermostat Timer ON/OFF, 24 hours Night Setback Built-IN Air Louver (Horizontal) Manual
Power Failure Automatic Restart Built-In Self Diagnosis Built-In Heating/Cooling Automatic Changeover Built-In
OPTION
Refrigerant Line Set AP3210BH (30 ft)
Low Ambient Control N/A Fresh Air Intake Available Central Remote ON-OFF Control Available Airduct Extension N/A Indoor Frame Extension N/A Condensate Drain Pump Available Non-Removable Remo-con Bracket Available
OPERATING RANGE
Cooling Indoor Air Outdoor Air
Heating Maximum 80 F DB/67 F WB 75 F DB / 65 F WB
CERTIFICATION
(Vertical) Automatic
AP3215BH (50 ft)
Intake Temp. Intake Temp. Maximum 95 F DB/71 F WB 115 F DB Minimum 67 F DB/57 F WB 67 F DB
Minimum - F DB/ - F WB 17 F DB/ 15 F WB
WEIGHT INDOOR OUTDOOR Net (lbs.) 98.0 198.0 Shipping (lbs.) 123.0 223.0
Shipping Volume (cu.ft.) 15.5 19.8
36THS32
Page 2
DIMENSIONAL DATA
Indoor Unit: THS3632
Drain connection Drain connection for left side Refrigerant liquid line (3/8") Flare connection Refrigerant gas line (3/4") Flare connection Hole for rear side refrigerant tubing Hole for through-the-wall refrigerant tubing (ø3-15/16" hole) Hole for fresh air intake (Knockout hole) Hole for right side refrigerant tubing (Knockout hole) Hole for left side drain connection (Knockout hole) Hole for power supply (Conduit size 1/2") Infrared rays receiver for wireless remote controller Cutting position for fresh air intake
Dimension : inch
Air intake
Air outlet
2 ft. or more
Hole for wall-through piping (View from front)
2-13/32 23/32
9-7/8
6-25/32
9-7/16
8-7/16
62
26-3/8
11-1/32
12-7/32
61-7/32
7-3/4
12-19/32 6-5/16
5-15/16
• Remote controller (Accessory)
5-1/2
7-3/4
6-11/16
4-1/2
7-1/4
7-3/4
1-3/326-5/16
3-5/324-3/4
5-3/4
7-7/32
4-1/16
9-7/8
5-9/16
1-3/859-1/4 (Suspension bolt hole pitch)
3-1/2
5-25/32
2-25/325-3/16
11-1/32
3-15/16 1-31/32
3-3/8
6-3/32 7-31/32
Front
(Service space)(Service space)
Holes in the rear side (View from front)
(Suspension bolt hole pitch)
10
or more
10
or more
Outdoor Unit: CH3632
48-5/8
22-27/32
23-29/32
37
Dimension : inch
Hole for anchor bolt (4-ø13) Refrigerant tube joint (narrow tube) Flare connection 3/8 in (9.52 mm) Refrigerant tube joint (wide tube) Flare connection 3/4 in (19.05 mm) Refrigerant tubing inlet Power supply inlet
15-3/4
14-31/32 13/32
1-3/16
1-31/32 1-31/32
13-3/8
4-21/64266-11/16
WARRANTY
SANYO products are warranted against defects in materials and workmanship for the period below;
LABOR PARTS Compressor 30 Days 5 Years Other Components N/A 1 Year
Because of a policy of continuous product improvements, SANYO reserves the right to change specifications and design without notice.
Full specific warranty rights, conditions, exclusions and obli gations are specified in the warranty packed with each products.
SANYO FISHER COMPANY
A Division of SANYO North America Corporation
21605 Plummer St. Chatsworth, CA 91311 Phone : (818) 998- 7322 Fax : (818) 701- 4160 Website: http://www.sanyohvac.com