Sanyo 36KS82, KS3682, C3682 Submittal Data

Page 1
Split System Submittal Data
System: 36KS82 Indoor/Outdoor: KS3682/C3682 Wall Mounted Air Conditioner
Job Name: Location: Engineer: Submitted to: Submitted by: Reference:
General Data (at 230V)
Power V/PH/Hz 230/208/1/60
Circuit Ampacity Fuse Size, Max.
Compressor
No. used R.L. Amps - L.R.
Fan type Dia. (in.) - No. Speeds Type Drive No. Poles No. Motors CFM F.L. Amps
(A) 20.0-21.9
(A) 45
DC Rotary Inverter
1
(A) 20.0-31.0
Propeller
19-9/32-1 DC Motor
(RPM) 8 - 750
(W) 1 - 142
(High) 2060
(A) 19.6/21.5
Approval: Date: Construction: Unit #: Drawing #:
Refrigerant
Lbs. - R410a (outdoor unit) Control Connection Line Length, Max (ft.) Lift Difference, Max (ft.) Line Size Line Size
Dimensions
Indoor Unit
Outdoor Unit
(Uncrated) 11-3/16 x 41-15/16 x 9-1/16
(Uncrated) 35-13/16 x 37-1/32 x 13-3/8
R410A
6.5
Electric Expansion Valve
Flare
165
50 (outdoor lower), 100 (outdoor higher)
(in. O.D. Discharge) 3/8”
(in. O.D. Suction) 5/8”
(in.) H x W x D
(Crated) 12-7/32 x 44-7/8 x 14-31/32
(Crated) 42-3/8 x 40 x 16-3/8
Coil Type Fin Type - Pipe Type Rows - F.P.I. Face Area Tube Size
Indoor Unit
Fan type Dia. & Length (in.) - No. Speeds No. Speeds No. Poles No. Motors CFM Indoor Sound Rating F.L. Amps
Coil Type Fin Type - Pipe Type Rows - F.P.I. Face Area Tube Size Drain Connection Size
(sq.ft.) 8.05
(in.) 3/8”
(RPM, High) 8 - 1370
(W) 47
(HI/Med/Lo) 630/530/412
(Hi) (dB-A) 49
(A) 0.4
(sq.ft.) 4.55
(in.) 3/8”
(in.) 1-1/4”
Aluminum Fin & Copper Pipe
Aluminum Plate Fin & Copper Tube
Slit Plate - Inner Rifl ed
2 - 21.2
Cross Flow
3-15/16 L32
Slit Plate - Inner Rifl ed
2 - 19.5
Weight
Net Shipping
Shipping Volume
Performance Data @ ARI Standard Conditions (230/208V)
Cooling
3
Total Capacity Sensible Capacity Latent Capacity SEER Dehumidification Amps Power Inputs Outdoor Sound Rating
(lbs.) 32.0 183.0
(lbs.) 39.7 205.0
(cu.ft.) 4.59 15.88
(Pints/H) 10.64
(A) 20-21.9
(dB-A) 55
Indoor Outdoor
Indoor Outdoor
(BTU/H) 34,000 (10,900-34,000)
(BTU/H) 20,700 (BTU/H) 13,300
(W) 4,000
16
Page 2
Dimensions
Features
Controls Remote Controller Temperature Control Timer Night Setback Air Louver
Power Failure Automatic Restart Self-Diagnosis Air Filter
(Horizontal) Manual
(Vertical) Automatic
Microprocessor
LCD Wireless Type, Temp. Sensor Built In
IC Thermostat
24 Hr. Program
Built-In
Built-In Built-In
Washable, Anti-Mold
Options
Refrigerant Line Set Fresh Air Intake Airduct Extension Indoor Frame Extension Condensate Drain Pump Non-Removeable Remo-con Bracket
Operating Range
Indoor Air Intake Temp. Outdoor Air Intake Temp.
Cooling
Maximum 95F DB/71F WB 115F DB Minimum 67F DB/57F WB 0F DB
Available
N/A N/A N/A
Available Available
Sanyo Commercial Solutions
A Division of SANYO North America
1300 Michael Drive
Wood Dale, IL 60191 USA
www.sanyohvac.com
Loading...