Sanyo 36KHS72R User Manual

Split System Submittal Data
Print Form
System: 36KHS72R Indoor/Outdoor: KHS3672R/CH3672R Wall Mounted Heat Pump
Job Name: Location: Engineer: Submitted to: Submitted by: Reference:
General Data (at 230V)
Power V/PH/Hz 230/208/1/60
Circuit Ampacity Fuse Size, Max.
Compressor
No. used R.L. Amps - L.R. Crankcase Heater
Outdoor Unit
Fan type Dia. (in.) - No. Speeds Type Drive - No. Speeds No. Poles No. Motors CFM F.L. Amps
(A) 15-35 Indoor-Outdoor
(A) 15-35 Indoor-Outdoor
DC Rotary Inverter
1
(A) 16.4-17.5
(W) -
Propeller
18-7/64-1
DC Motor
(RPM) 8 - 830
(W) 1 - 90
(High) 1942
(A) 17.3
Approval: Date: Construction: Unit #: Drawing #:
Refrigerant
Lbs. - R410a (outdoor unit) Control Connection Line Length, Max (ft.) Lift Difference, Max (ft.) Line Size Line Size
Dimensions
Indoor Unit
Outdoor Unit
R410A
6.17
Electric Expansion Valve
Flare
165
50 (outdoor lower), 100 (outdoor higher)
(in. O.D. Discharge) 3/8”
(in. O.D. Suction) 5/8”
(in.) H x W x D
(Uncrated) 14-9/16 x 59-1/16 x 9-7/16
(Crated) 18-7/16 x 62-9/16 x 12-9/16
(Uncrated) 30-23/32 x 37 x 13-3/8
(Crated) 34-31/32 x 39-31/32 x 16-3/32
Coil Type Fin Type - Pipe Type Rows - F.P.I. Face Area Tube Size
Indoor Unit
Fan type Dia. & Length (in.) - No. Speeds No. Speeds No. Poles No. Motors CFM Indoor Sound Rating F.L. Amps
Coil Type Fin Type - Pipe Type Rows - F.P.I. Face Area Tube Size Drain Connection Size
(sq.ft.) 7.26
(in.) 3/8”
(RPM, High) 4 - 1273
(W) 1 - 50
(HI/Med/Lo) 830/710/590
(Hi) (dB-A) 48
(A) 0.5
(sq.ft.) 3.23
(in.) 3/8”
Aluminum Fin & Copper Pipe
Slit Plate - Inner Riffeled
2 - 14.1
Cross Flow
4-13/18 L46 - 1
3 & Auto
Aluminum Plate Fin & Copper Tube
Slit Plate - Inner Riffeled
3 - 12.7
(in.) 1-1/4”
Weight
Net Shipping
Shipping Volume
Performance Data @ ARI Standard Conditions (230/208V)
Cooling
Total Capacity Sensible Capacity Latent Capacity SEER Dehumidification Amps Power Inputs Outdoor Sound Rating
Heating
Total Capacity HSPF
(lbs.) 72.8 143 (lbs.) 90.4 161
(cu.ft.) 8.4 13.0
(Pints/H) 10.0
(A) 17.9/19.8
(dB-A) 52
Indoor Outdoor
Indoor Outdoor
(BTU/H) 31,400 (9,500-31,400) (BTU/H) 18,760 (BTU/H) 12,640
(W) 3,750/3,750
(BTU/H) 36,400 (8,000-36,400)
15.9
9
Dimensions
Dimensional Data for 36T72R
Indoor unit : TH3672R
Dimensional Data for 36T72R
Indoor unit : TH3672R
Amps Max. Amps Power Inputs Back-up Strip Heater Outdoor Sounds Rating
(A) 15.9/17.6
(A) 15.9/17.6
(W) 3,320/3,320
(KW) 0.00/0.00
(dB-A) 52
Feature
Controls Remote Controller Temperature Control
LCD Wired Type, Temp. Sensor Built In
Timer Night Setback Air Louver
(Horizontal) Manual
(Vertical) Automatic Power Failure Automatic Restart Heating/Cooling Automatic Changeover Self-Diagnosis Air Filter
Microprocessor
IC Thermostat
72 Hour ON/OFF
Built-In
Built-In Built-In Built-In
Washable, Anti-Mold
Option
Refrigerant Line Set Fresh Air Intake Airduct Extension Indoor Frame Extension Condensate Drain Pump Non-Removeable Remo-con Bracket
Available
Knock out
N/A
N/A Available Available
Operating Range
Indoor Air Intake Temp. Outdoor Air Intake Temp.
Cooling
Indoor Air Intake Temp. Outdoor Air Intake Temp.
Heating
Maximum 95F DB/71F WB 115F DB Minimum 67F DB/57F WB 0F DB
Maximum 80F DB/67F WB 75F DB/65F WB Minimum -DB/-WB 5F DB
Sanyo Commercial Solutions
A Division of SANYO North America
1300 Michael Drive
Wood Dale, IL 60191 USA
www.sanyohvac.com
Loading...