Sanyo 26THW72R User Manual

Split System Submittal Data
Print Form
System: 26THW72R Indoor/Outdoor: THW2672R/CH2672R Ceiling Suspended Heat Pump
Job Name: Location: Engineer: Submitted to: Submitted by: Reference:
General Data (at 230V)
Power V/PH/Hz 230/208/1/60
Circuit Ampacity Fuse Size, Max.
Compressor
No. used R.L. Amps - L.R.
Fan type Dia. (in.) - No. Speeds Type Drive - No. Speeds No. Poles No. Motors CFM F.L. Amps
(A) 15-30 Indoor-Outdoor
(A) 15-30 Indoor-Outdoor
DC Rotary Inverter
1
(A) 12.9-17.5
Propeller
18-7/64-1 DC Motor
(RPM) 8 - 800
(W) 1 - 90
(High) 1765
(A) 13.8
Approval: Date: Construction: Unit #: Drawing #:
Refrigerant
Lbs. - R410a (outdoor unit) Control Connection Line Length, Max (ft.) Lift Difference, Max (ft.) Line Size Line Size
Dimensions
Indoor Unit
Outdoor Unit
(Uncrated) 7-17/16 x 51-3/16 x 26-3/8
R410A
4.19
Electric Expansion Valve
Flare
165
50 (outdoor lower), 100 (outdoor higher)
(in. O.D. Discharge) 3/8”
(in. O.D. Suction) 5/8”
(in.) H x W x D
(Crated) 9-7/16 x 54-19/32 x 31-1/16
(Uncrated) 30-23/32 x 37 x 13-3/8
(Crated) 34-31/32 x 39-31/32 x 16-3/32
Coil Type Fin Type - Pipe Type Rows - F.P.I. Face Area Tube Size
Indoor Unit
Fan type Dia. & Length (in.) - No. Speeds No. Speeds No. Poles No. Motors CFM Indoor Sound Rating F.L. Amps
Coil Type Fin Type - Pipe Type Rows - F.P.I. Face Area Tube Size Drain Connection Size
(sq.ft.) 7.26
(in.) 3/8”
(RPM, High) 4 - 1179
(W) 1 - 31
(HI/Med/Lo) 550/490/460
(Hi) (dB-A) 39
(A) 0.5
(sq.ft.) 1.81
(in.) 9/32”
Aluminum Fin & Copper Pipe
Slit Plate - Inner Riffeled
1-15.9
Centrifugal
5-1/8 - 4
3 & Auto
Aluminum Plate Fin & Copper Tube
Slit Plate - Inner Riffeled
3 - 14.9
(in.) 1-1/4”
Weight
Net Shipping
Shipping Volume
Performance Data @ ARI Standard Conditions (230/208V)
Cooling
Total Capacity Sensible Capacity Latent Capacity SEER Dehumidification Amps Power Inputs Outdoor Sound Rating
Heating
Total Capacity HSPF
(cu.ft.) 8.9 13.0
(Pints/H) 7.7
(A) 15.6/17.3
Indoor Outdoor (lbs.) 64 128 (lbs.) 75 148
Indoor Outdoor
(BTU/H) 24,400 (9,500-24,400) (BTU/H) 14,330 (BTU/H) 10,070
(W) 2,880/2,880
(dB-A) 49
(BTU/H) 30,800 (8,000-30,800)
14.5
10.3
Dimensions
Dimensional Data for 26TH72R
Indoor unit : TH2672R
Heating
Amps Max. Amps Power Inputs Back-up Strip Heater Outdoor Sounds Rating
(A) 16.4/18.1
(A) 16.4/18.1
(W) 3,000/3,000
(KW) 0.00/0.00
(dB-A) 49
Features
Controls Remote Controller
LCD Wired Type, Temp. Sensor Built In Temperature Control Timer Night Setback Air Louver
(Horizontal) Manual
(Vertical) Automatic Power Failure Automatic Restart Heating/Cooling Automatic Changeover Self-Diagnosis Air Filter
Microprocessor
IC Thermostat
72 Hr. ON/OFF
Built-In
Built-In
Built-In Built-In
Washable, Anti-Mold
Options
Refrigerant Line Set Fresh Air Intake Airduct Extension Indoor Frame Extension Condensate Drain Pump Non-Removeable Remo-con Bracket
Operating Range
Indoor Air Intake Temp. Outdoor Air Intake Temp.
Cooling
Maximum 95F DB/71F WB 115F DB
Indoor Air Intake Temp. Outdoor Air Intake Temp.
-
Minimum 67F DB/57F WB 0F DB
Heating
Maximum 80F DB/67F WB 75F DB/65F WB Minimum -DB/-WB 5F DB
Available
Knock-out
N/A
N/A Available Available
Sanyo Commercial Solutions
A Division of SANYO North America
1300 Michael Drive
Wood Dale, IL 60191 USA
www.sanyohvac.com
Loading...