SUBMITTAL SHEET
SYSTEM INDOOR/OUTDOOR
24THS32 THS2432/CH2432
CEILING SUSPENDED HEAT PUMP
GENERAL DATA (AT 230V)
POWER V/PH/HZ 230/208/1/60
Circuit Ampacity, Min. (A) 30
Fuse size, Max (A) 30
COMPRESSOR Rotary-Hermetic
No. used 1
R.L. Amps - L.R. Amps (A) 9.4 - 66.0
Crankcase Heater 30W
OUTDOOR FAN - TYPE Propeller
Dia. (in.) - No. used 18-3/32- 1
Type Drive - No. speeds Direct ñ 2 (AUTO)
No. Poles - RPM (High) 6 - 879
No. Motors ñ HP 1 - 1/7
CFM (High) 1,840
F.L. Amps. (A) 0.9
OUTDOOR COIL ñ TYPE Aluminum Fin & Copper Pipe
Fin Type - Pipe Type Slit Plate - Inner Riffled
Rows - F.P.I. 2- 14.1
Face Area (sq.ft.) 6.78
Tube Size (in.) 3/8
INDOOR FAN ñ TYPE Centrifugal
Dia. & Length (in.) - No. used 5-1/8 & 4
No. speeds 3 & Auto
No. Poles -RPM (High) 4-1,187
No. Motors - HP 1 - 1/24
CFM (HI/MED/LOW) 540/490/425
F.L. Amps (A) 0.4
INDOOR COIL - TYPE Aluminum Fin & Copper Pipe
Fin Type - Pipe type Slit Plate - Inner Riffled
Rows - F.P.I. 3 - 14.9
Face Area (sq. ft.) 1.81
Tube Size (in.) 3/8
Drain Connection Size (in.) 1-1/4
REFRIGERANT R22
Lbs. - R22 (O.D. Unit) 6.17
Control Capillary Tube
Connection Electronic Refrigerant Control Valve
Line Length, Max (ft.) 165
Lift difference, Max (ft.) 100
Line Size - in. O.D. Discharge 1/4
Line Size - in. O.D. Suction 3/4
DIMENSIONS (in.) H x W x D
Indoor Unit -Uncrated 7- 15/32 x 51- 6/32 x 26-3/8
-Crated 9- 14/32 x 54- 19/32 x 29-31/32
Outdoor Unit-Uncrated 28-15/16 x 37 x 13-3/8
-Crated 32-17/32 x 40 x 16-12/32
AIRCONDITIONING PRODUCTS
SS24THS32-1
PERFORMANCE DATA @ ARI STANDARD CONDITIONS (230/208V)
COOLING
Total Capacity (BTU/H) 22,400/21,600
Sensible Capacity (BTU/H) 13,640/12,970
Latent Capacity (BTU/H) 8,760/8,630
SEER 10.0/10.0
Dehumidification (Pints/H) 6.3/6.2
Amps (A) 10.7/11.3
Power Inputs (W) 2,290/2,250
HEATING
Total Capacity (BTU/H) 25,400/25,000
HSPF 7.0/7.0
Amps (A) 11.7/12.9
Power Inputs (W) 2,350/2,280
Back-up Strip Heater (KW) 1.80/1.47
Outdoor Sound Rating(bels) 7.6
FEATURE
Controls Microprocessor
Remote Controller LCD Wireless type
Temperature Control IC Thermostat
Timer ON/OFF, 24 hours
Night Setback Built-In
Air Louver (Horizontal) Manual
Power Failure Automatic Restart Built-In
Self Diagnosis N/A
OPTION
Refrigerant Line Set AP2710BH (30 ft)
Low Ambient Control Built-In
Fresh Air Intake N/A
Central Remote ON-OFF Control Available
Airduct Extension N/A
Indoor Frame Extension N/A
Condensate Drain Pump Available
Non-Removable Remo-con Bracket RCS5PS4B
OPERATING RANGE
Cooling Indoor Air Outdoor Air
Heating Maximum 80F DB/67F WB 75F DB/67F WB
CERTIFICATION
(Vertical) Automatic
AP2715BH (50 ft)
Intake Temp. Intake Temp.
Maximum 95F DB/71F WB 115F DB
Minimum 67F DB/57F WB 23F DB
Minimum -F DB/ - F WB 17F DB/15F WB
WEIGHT INDOOR OUTDOOR
Net (lbs.) 60.0 157.0
Shipping(lbs.) 77.0 170.0
Shipping Volume (cu.ft.) 8.9 12.3
24THS32
Dimensional Data
6-3/32 3-15/16
12-7/32
Indoor Unit: THS2432
Dimension : inch
Drain connection
Drain connection for left side
Refrigerant liquid line (1/4") Flare connection
Refrigerant gas line (3/4") Flare connection
Hole for rear side refrigerant tubing
Hole for through-the-wall refrigerant tubing (ø3-15/16" hole)
Hole for fresh air intake (Knockout hole)
Hole for right side refrigerant tubing (Knockout hole)
Hole for left side drain connection (Knockout hole)
Hole for power supply (Conduit size 1/2")
Infrared rays receiver for wireless remote controller
Cutting position for fresh air intake
1919_THS_I
9-7/8
Air intake
Air outlet
2 ft. or more
5-25/32
3-3/8
12-19/32 6-5/16
10
or more
3-3/32
11-1/32
Holes in the rear side (View from front)
(Suspension bolt hole pitch)
3-15/16 1-3/8
50-13/32
51-3/16
Front
11-1/32
(Service space)(Service space)
5-9/32
2-17/32
5-25/32
5-3/4
3-9/324-9/16
Hole for wall-through piping (View from front)
1-3/326-5/16
2-25/325-3/16
1-3/848-7/16 (Suspension bolt hole pitch)
10
or more
5-9/16
26-3/8
8-7/16
9-7/8
4-23/32
7-15/32
3-3/4
5-25/32
Outdoor Unit: CH2432
1-31/32
13-3/8
37
1-31/32
4-21/64266-11/16
3-1/2
4-1/16
5-25/32
7-7/32
1-3/16
15-3/4
14-31/32 13/32
Dimension : inch
28-15/16
11
WARRANTY
SANYO products are warranted against defects in materials and workmanship for the
period below;
Compressor 30 Days 5 Years
Other Components N/A 1 Year
Because of a policy of continuous product improvements, SANYO reserves the right
to change specifications and design without notice.
LABOR PARTS
Hole for anchor bolt (4-ø1/2)
Refrigerant tube joint (narrow tube)
Flare connection 1/4 in (6.35 mm)
Refrigerant tube joint (wide tube)
Flare connection 3/4 in (19.05 mm)
Refrigerant tubing inlet
12-1/16
Full specific warranty rights, conditions, exclusions and obligations are specified in the
warranty packed with each products.
Power supply inlet
1131_THS_I
SANYO FISHER COMPANY
A Division of SANYO North America Corporation
21605 Plummer St. Chatsworth, CA 91311
Phone : (818) 998- 7322
Fax : (818) 701- 4160
Website: http://www.sanyohvac.com