Split System Submittal Data
System: 18KS72 Indoor/Outdoor: KS1872/C1872
Wall Mounted Air Conditioner
Job Name:
Location:
Engineer:
Submitted to:
Submitted by:
Reference:
General Data (at 230V)
Power V/PH/Hz 230/208/1/60
Circuit Ampacity
Fuse Size, Max.
Compressor
No. used
R.L. Amps - L.R.
Crankcase Heater
Outdoor Unit
Fan type
Dia. (in.) - No. Speeds
Type Drive - No. Speeds
No. Poles
No. Motors
CFM
F.L. Amps
(A) 20
(A) 20
DC Rotary Inverter
1
(A) 7 - 17.5
(W) N/A
Propeller
16-17/32 - 1
DC Motor
(RPM) 8 - 820
(W) 50 - 1
(High) 524
(A) 0.5
Approval:
Date:
Construction:
Unit #:
Drawing #:
Refrigerant
Lbs. - R410a (outdoor unit)
Control
Connection
Line Length, Max
Lift Difference, Max
Line Size
Line Size
Dimensions
Indoor Unit
Outdoor Unit
R410A
2.87
Electric Expansion Valve
Flare
100
50
(in. O.D. Discharge) 1/4”
(in. O.D. Suction) 1/2”
(in.) H x W x D
(Uncrated) 11-23/32 x 41-15/16 x 8-19/32
(Crated) 11-3/8 x 44-7/8 x 14-29/32
(Uncrated) 26-3/8 x 34-21/32 x 11-7/32
(Crated) 29-1/8 x 39-27/32 x 14-31/32
Coil Type
Fin Type - Pipe Type
Rows - F.P.I.
Face Area
Tube Size
Indoor Unit
Fan type
Dia. & Length (in.) - No. Speeds
No. Speeds
No. Poles
No. Motors
CFM
Indoor Sound Rating
F.L. Amps
Coil Type
Fin Type - Pipe Type
Rows - F.P.I.
Face Area
Tube Size
Drain Connection Size
(sq.ft.) 5.49
(in.) 9/32”
(RPM, High) 8 - 1250
(W) 30 - 1
(HI/Med/Lo) 523/470/417
(Hi) (dB-A) 42
(A) 0.3
(sq.ft.) 3.07
(in.) 9/32”
Aluminum Fin & Copper Pipe
Corrugated Plate - Inner Riffl ed
2 - 21.2
Cross Flow
3-11/16 33-9/32 - 1
3 & Auto
Aluminum Plate Fin & Copper Tube
Slit Plate - Inner Riffl ed
2 - 19.5
(in.) 23/32”
Weight
Net
Shipping
Shipping Volume
Performance Data @ ARI Standard Conditions (230V)
Cooling
Total Capacity
Sensible Capacity
Latent Capacity
SEER
Dehumidification
Amps
Power Inputs
Outdoor Sound Rating
(lbs.) 26.5 90.4
(lbs.) 33.1 99.2
(cu.ft.) 4.23 9.88
(Pints/H) 4.89
(A) 7/7.7
(dB-A) 51
Indoor Outdoor
Indoor Outdoor
(BTU/H) 17,500 (4,000-17,500)
(BTU/H) 13,100
(BTU/H) 4,400
(W) 1,500/1,500 (250-1,500)
20
Dimensions
Feature
Controls
Remote Controller
Temperature Control
Timer
Night Setback
Air Louver
Power Failure Automatic Restart
Heating/Cooling Automatic Changeover
Self-Diagnosis
Quiet Operation
Air Filter
Ion Generator
Air Clean Apatite Filer
(Horizontal) Manual
(Vertical) Automatic
LCD Wireless Type, Temp. Sensor Built In
Microprocessor
IC Thermostat
24 Hr. Program, 1 Hr. Off
Built-In
Built-In
N/A
Built-In
Built-In
Washable, Anti-Mold
Equipped
Standard
Option
Refrigerant Line Set
Fresh Air Intake
Airduct Extension
Indoor Frame Extension
Condensate Drain Pump
Non-Removeable Remo-con Bracket
Operating Range
Indoor Air Intake Temp. Outdoor Air Intake Temp.
Cooling
Maximum 95F DB/71F WB 115F DB
Minimum 67F DB/57F WB 67F DB
Available
N/A
N/A
N/A
Available
Available
Sanyo Commercial Solutions
A Division of SANYO North America
1300 Michael Drive
Wood Dale, IL 60191 USA
www.sanyohvac.com