Santon PES170D, PES210D, PES260D, PES300D, PES190I Installation And Servicing Instructions

...
1
36 00 5945 Issue 04
UNVENTED MAINS PRESSURE SOLAR WATER HEATER
170, 190, 210, 250, 260 AND 300 LITRE
DIRECT AND INDIRECT MODELS
INSTALLATION AND SERVICING INSTRUCTIONS
PACK CONTENTS
2
SANTON PREMIER PLUS SOLAR INSTALLATION AND SERVICING
INSTRUCTIONS.
PLEASE LEAVE THIS MANUAL WITH THE UNIT FOR FUTURE
REFERENCE.
CONTENTS
SECTION CONTENT PAGE
1 INTRODUCTION .................................................................................4
2 GENERAL REQUIREMENTS ............................................................ 5
3 INSTALLATION - GENERAL ................................................................ 6
4 INSTALLATION - SOLAR PRIMARY ...............................................11
5 INSTALLATION - DIRECT UNITS .......................................................11
6 INSTALLATION – AUXILLARY HEATING COIL ............................ 12
7 COMMISSIONING ..................................................................................14
8 MAINTENANCE ...................................................................................... 16
9 FAULT FINDING AND SERVICING .....................................................17
10 USER INSTRUCTIONS ..........................................................................19
11 GUARANTEE ........................................................................................... 20
3
TABEL 1: OPERATIONAL SUMMARY
IMPORTANT: PLEASE READ ALL THESE INSTRUCTIONS BEFORE COMMENCING INSTALLATION
THE INFORMATION CONTAINED IN THESE INSTRUCTIONS DETAILS HOW TO CONNECT THE PREMIER PLUS SOLAR CYLINDER TO A SO­LAR PRIMARY CIRCUIT. OTHER CONTROLS WILL BE NECESSARY TO PROVIDE CONTROL OVER THE SOLAR PRIMARY CIRCUIT, REFER TO THE INSTRUCTIONS SUPPLIED WITH THE SOLAR CONTROLS AND ANCILLARY EQUIPMENT FOR DETAILS OF HOW TO INTEGRATE THEM WITH THE PREMIER PLUS SOLAR CYLINDER.
Operating Pressure of Unit
16.0 ba r
3.5 b ar
Maximum water supply pressure to PRV
3.5 b ar
Expansion vessel charge pressure
6.0 b ar
Expansion valve setting Nominal storage capacity
(see Section 2 Table 2) Max. primary working pressure (Auxillary Coil) Max. primary working pressure (Solar Coil)
3.0 b ar (indirects only)
6.0 b ar
Opening temperature of T&P Relief Valve
90°C
Opening pressure of T&P Relief Valve
10.0 b ar
4
Table 3: Standing heat losses
Table 2: Unit weights
1.0 INTRODUCTION
The Santon Premier Plus Solar is a purpose designed unvented solar water heater. The unit has a stainless
steel inner vessel which ensures an excellent stan-
dard of corrosion resistance. The outer casing is a combination of resilient thermoplastic mouldings and corrosion proofed steel (Plastisol) sheet. All Premiers are insulated with CFC/HCFC free polyurethane foam
to meet the latest European heat loss requirements
(see Table 3).
The unit is supplied complete with all the necessary safety and control devices needed to allow connec­tion to the cold water mains. All these components
are pre-adjusted.
NOTE: Prior to installation the unit should be stored in an upright position in an area free from excessive damp
or humidity.
This appliance complies with the requirements of the CE marking directive and is KIWA approved to show compliance with Building Regulations (Sec-
tion G3).
The following instructions are offered as a guide to
installation which must be carried out by a competent plumbing and electrical installer in accordance with
Building Regulation G3, The Building Standards
Type
Model
reference
Nominal capacity
(litres)
Weight of
unit full
(kg)
DIRECT PES170D 170 210
PES210D 210 259 PES260D 260 308 PES300D 300 362
INDIRECT PES190I 190 240
PES210I 210 264 PES250I 250 308 PES300I 300 367
per day
(kWh/24h)
per year
(kWh/365d)
190 1.52 555 210 1.70 621 250
300 2.28
Nominal
Capacity
(litres)
Standing Heat Loss
170 1.40 511
260 1.98 723
1.96 715
832
5
2.0 GENERAL REQUIREMENTS
2.1 COMPONENTS SUPPLIED
1. Premier Plus unvented solar water heater incor­porating immersion heater(s) and thermal controls
2. Factory tted Temperature/Pressure Relief Valve
3. Cold Water Combination Valve.
4. Expansion Vessel and mounting bracket.
5. Tundish.
6. Motorized Valve (Indirect models only).
7. Compression nuts and olives
8. Immersion heater key spanner
2.2 SITING THE UNIT
The Santon Premier Plus Solar must be installed verti­cally. Although location is not critical, the following
points should be considered:
The Santon Premier Plus Solar should be sited to ensure minimum dead leg distances, particularly to the point of most frequent use.
Avoid siting where extreme cold temperatures will be experienced. All exposed pipework should be
insulated.
The discharge pipework from the safety valves must have minimum fall of 1:200 from the unit and terminate in a safe and visible position.
Access to associated controls and immersion heaters should be possible to allow for periodic servic-
ing and maintenance.
Ensure that the base chosen for the Santon Pre­mier Plus Solar is level and capable of permanently supporting the weight when full of water (see Table
2).
2.3 OUTLET/TERMINAL FITTINGS (TAPS, ETC.)
The Santon Premier Plus Solar can be used with most types of terminal ttings. It is advantageous in many
mixer showers to have balanced hot and cold water
supplies. In these instances a balanced pressure cold
water connection should be placed between the Cold
Water Combination Valve and the Premier Plus water heater. Outlets situated higher than the Santon Premier Plus Solar will give outlet pressures lower than that at the heater, a 10m height difference will result in a
1 bar pressure reduction at the outlet.
2.5 LIMITATIONS
The Premier Plus unvented solar water heater should not be used in association with any of the following:
Solid fuel boilers or any other boiler in which the energy input is not under effective thermostatic control unless additional and appropriate safety measures are
installed.
Ascending spray type bidets or any other class 1 back syphonage risk requiring that a type A air gap
be employed.
Steam heating plants unless additional and ap­propriate safety devices are installed.
Situations where maintenance is likely to be neglected or safety devices tampered with.
Water supplies that have either inadequate pres-
sure or where the supply may be intermittent.
Situations where it is not possible to safely pipe away any discharge from the safety valves.
In areas where the water consistently contains a high proportion of solids, e.g. suspended matter that could block the strainer, unless adequate ltration can
be ensured.
6
3.0 INSTALLATION – GENERAL (FIGS 3 & 5)
3.1 PIPE FITTINGS
All pipe ttings are made via 22mm compression ttings directly to the unit. The ttings are threaded 3/4”BSP male parallel should threaded pipe connec-
tions be required.
3.2 COLD FEED
A 22mm cold water supply is recommended however, if a 15mm (1/2”) supply exists which provides suf­cient ow this may be used (although more ow
noise may be experienced).
A stopcock or servicing valve should be incorporated into the cold water supply to enable the Santon Premier Plus Solar and its associated controls to be isolated
and serviced.
3.3 COLD WATER COMBINATION VALVE (FIG
1)
The Cold Water Combination Valve can be connected
anywhere on the cold water mains supply prior to the
Expansion Vessel (see Fig. 5). The Cold Water Combi­nation Valve is installed as a complete one-piece unit. The valve incorporates the Pressure Reducer, Strainer, Expansion Valve and Check Valve. Ensure that the valve is installed with the direction of ow arrows
pointing in the right direction. No other valves should
be placed between the Cold Water Combination Valve and the Premier Plus Solar unit. The Expansion Valve connection must not be used for any other purpose.
3.5 EXPANSION VESSEL
The Expansion Vessel accommodates expansion that results from heating the water inside the unit. The unit is pre-charged at 3.5 bar. The Expansion Vessel
must be connected between the Cold Water Combi-
nation Valve and the Santon Premier Plus Solar (see Fig. 5). The location of the Expansion Vessel should
allow access to recharge the pressure as and when
necessary, this can be done using a normal car foot pump. It is recommended that the Expansion Vessel is adequately supported. An Expansion Vessel wall mounting bracket is supplied for this purpose.
NO TE: DO NOT USE THE PO TABLE WATER EXPANSION VESSEL SUPPLIED WITH THE PREMIER PLUS SOLAR FOR ANY OTHER PURPOSE. IT IS NOT SUIT­ABLE FOR USE ON A SOLAR PRIMARY CIRCUIT.
3.7 OUTLET
The hot water outlet is a 22mm compression tting located at the top of the cylinder. Hot water distribu­tion pipework should be 22mm pipe with short runs of 15mm pipe to terminal ttings such as sinks and basins. Pipe sizes may vary due to system design.
3.4 DRAIN TAP
A suitable draining tap should be installed in the cold water supply to the Premier Plus Solar unit between the Cold Water Combination Valve and the heater at as low a level as possible. It is recommended that the outlet point of the drain pipework be at least 1 metre below the level of the heater (this can be achieved by
attaching a hose to the drain tap outlet spigot).
3.6 SECONDARY CIRCULATION
If secondary circulation is required it is recommended
that it be connected to the Premier as shown in Fig. 2
The secondary return pipe should be in 15mm pipe and incorporate a check valve to prevent backow. A suitable WRAS approved bronze circulation pump will be required. On large systems, due to the increase in system water content, it may be necessary to t an
additional expansion vessel to the secondary circuit.
This should be done if the capacity of the secondary circuit exceeds 10 litres.
Pipe capacity (copper)
15mm o/d = 0.13 l/m (10 litres = 77m) 22mm o/d = 0.38 l/m (10 litres = 26m) 28mm o/d = 0.55 l/m (10 litres = 18m) Secondary circulation is NOT recommended for di­rect electric units being used on Off Peak electricity tariffs.
7
COLD MAINS CONNECTION (22mm)
EXPANSION VALVE
EXPANSION VALVE OUTLET (15mm)
OUTLET CONNECTION (22mm) TO PREMIER PLUS
PRESSURE REDUCING VALVE / CHECK VALVE HOUSING
FIG. 2 Secondary circulation connection
FIG. 1 Cold Water Combination Valve
SECONDARY RETURN CONNECTION
CHECK VALVE
SECONDARY CIRCULATION PUMP
OUTLET
SECONDARY RETURN
FIG. 3 General Dimensions and features
370
433
412
29
A
B
C
D
E
8
9
2
1
3
4
7
5
10
6
F
20°
25°
30°
1 SOLAR PRIMARY RETURN 2 SOLAR PRIMARY FLOW 3 AUXILLARY BOILER RETURN (INDIRECT MODELS ONLY) 4 AUXILLARY BOILER FLOW (INDIRECT MODELS ONLY) 5 T&P VALVE 6 SECONDARY RETURN 7 BOOST IMMERSION HEATER (DIRECT MODELS ONLY) 8 AUXILLARY CONTROL HOUSING 9 INLET 10 SOLAR CONTROL HOUSING
Ø
594
550
45°
81
A B C D E F
TYPE
DIMENSIONS (mm)
AUXILLARY
VOLUME
(litres)
AUXILLARY COIL
SURFACE
AREA
(sq.m)
RATING
(kW)
RECOVERY
(mins)
HEATING
TIME
DIRECT
(MINS)
SOLAR
SURFACE
AREA
(sq.m)
NOMINAL CAPACITY
(litres)
E = DIRECT
B = INDIRECT
170
E
NOTES:
1. Recovery time based on heating 70% of auxillary volume through 45°C
2. Direct heating times assume use of lower element only and auxillary cylinder volume being heated.
1221
740 925 1.1
190 B
1372 803 923732 1019 1.1
120
0.61 11.9 22
120
126
210
E
1473
778 1184 1.1
140
1471000
210 B
1473 925 10951009 1184 1.1
120
0.68 18.3 17
260
E
1792
842 1440 1.1
170
1781072
300
E
2038
933 1715 1.1
200
2101409
250 B
1731 1072 12581160 1391 1.1
145
0.79 20.0 19
300 B
2038 1243 15731438 1715 1.1
175
0.79 20.0 22
8
Worked example of discharge pipe sizing
The example below is for a G1/2 temperature relief
valve with a discharge pipe (D2) having 4 No. elbows and length of 7m from the tundish to the point of dis­charge.
From Table 4: Maximum resistance allowed for a straight length of 22mm copper discharge pipe (D2) from a G1/2 tempera­ture relief valve is 9.0m. Subtract the resistance for 4 No. 22mm elbows at 0.8m each = 3.2m Therefore the permitted length equates to: 5.8m
5.8m is less than the actual length of 7m therefore calcu­late the next largest size. Maximum resistance allowed for a straight length of 28mm pipe (D2) from a G1/2 temperature relief valves
equates to 18m.
Subtract the resistance of 4 No. 28mm elbows at 1.0m each = 4.0m Therefore the maximum permitted length equates to:
14m
As the actual length is 7m, a 28mm (D2) copper pipe will be satisfactory.
3.8 DISCHARGE PIPEWORK
It is a requirement of Building Regulation G3 that any discharge from an unvented system is conveyed to where it is visible, but will not cause danger to persons in or about the building. The tundish and discharge pipes should be tted in accordance with the require­ments and guidance notes of Building Regulation G3. The G3 Requirements and Guidance section 3.9 are reproduced in the following sections. Information Sheet No. 33 available from the British Board of Agrement gives further advice on discharge
pipe installation. For discharge pipe arrangements not
covered by G3 Guidance or BBA Info Sheet No.33 advice should be sought from either your local Build­ing Control Ofcer or Santon.
G3 REQUIREMENT
“...there shall be precautions...to ensure that the
hot water discharged from safety devices is safely
conveyed to where it is visible but will not cause
danger to persons in or about the building.”
G3 GUIDANCE SECTION 3.9
The discharge pipe (D1) from the vessel up to and
including the tundish is generally supplied by the
manufacturer of the hot water storage system. Where otherwise, the installation should include the discharge pipe(s) (D1) from the safety device(s). In either case the tundish should be vertical, located in the same
space as the unvented hot water storage system and
be tted as close as possible and within 500mm of the safety device e.g. the temperature relief valve. The discharge pipe (D2) from the tundish should terminate in a safe place where there is no risk to persons in the vicinity of the discharge, preferably be of metal and: a. be at least one pipe size larger than the nominal outlet size of the safety device unless its total equiva­lent hydraulic resistance exceeds that of a straight pipe 9m long i.e. discharge pipes between 9m and
18m equivalent resistance length should be at least
two sizes larger than the nominal outlet size of the safety device, between 18 and 27m at least 3 sizes larger , and so on. Bends must be taken into account in calculating the ow resistance. Refer to Diagram 4, Table 4 and the worked example. An alternative approach for sizing discharge pipes would be to follow BS 6700:1987 Specification
for design installation, testing and maintenance of services supplying water for domestic use within buildings and their curtilages, Appendix E, section
E2 and table 21.
b. have a vertical section of pipe at least 300mm long, below the tundish before any elbows or bends in the pipework. c. be installed with a continuous fall.
d. have discharges visible at both the tundish and the
nal point of discharge but where this is not possible or is practically difcult there should be clear vis­ibility at one or other of these locations. Examples of
acceptable discharge arrangements are:
i. ideally below a xed grating and above the water
seal in a trapped gully. ii. downward discharges at low level; i.e. up to
100mm above external surfaces such as car parks, hard standings, grassed areas etc. are acceptable providing
that where children may play or otherwise come into contact with discharges a wire cage or similar guard
is positioned to prevent contact, whilst maintaining
visibility. iii. discharges at high level; e.g. into a metal hopper
and metal down pipe with the end of the discharge pipe clearly visible (tundish visible or not) or onto a roof capable of withstanding high temperature discharges of water and 3m from any plastics guttering system
that would collect such discharges (tundish visible).
iv. where a single pipe serves a number of discharges, such as in blocks of ats, the number served should
be limited to not more than 6 systems so that any instalation discharging can be traced reasonably eas-
ily. The single common discharge pipe should be at least one pipe size larger than the largest individual discharge pipe (D2) to be connected. If unvented hot
water storage systems are installed where discharges
from safety devices may not be apparent i.e. in dwell­ings occupied by blind, inrm or disabled people, consideration should be given to the installation of an
electronically operated device to warn when discharge
takes place. Note: The discharge will consist of scalding water and steam. Asphalt, roong felt and non-metallic rainwater
goods may be damaged by such discharges.
3.9 WARNINGS
9
Fixed grating
Discharge below fixed grating (Building Regulation G3 section 3.9d gives alternative points of discharge)
Trapped gully
Discharge pipe (D2) from tundish, with continuous fall. See Building Regula tion G3 section 3.9d i-iv, Table 4 and worked exam ple
300mm minimum
500mm maximum
Metal discharge pipe (D1) from Temperature relief valve to tundish
Tundish
Safety device (e.g. Temperature relief valve)
Table 4 Sizing of copper discharge pipe (D2) for common temperature relief valve outlet
FIG. 4 Typical discharge pipe arrangement (extract from Building Regulation G3 Guid­ance section 3.9)
• Underno circumstances should the factorytted
Temperature/Pressure Relief Valve be removed other than by authorised Santon personnel. To do so will invalidate any guarantee or claim.
• TheColdWaterCombinationValvemustbetted
to the mains water supply to the Premier Plus unit.
• No control or safety valves should be tampered
with.
• The discharge pipe should not be blocked or used
for any other purpose.
• The tundish should not be located adjacent to any
electrical components.
Valve out let size
Minimum size of
discharge pipe
D1
Minimum size of
discharge pipe
D2 from tundish
Maximum
resist ance
allowed, expr essed
as a lengt h of
st raight pipe (i.e.
no elbows or
bends)
Res istance
create d by each
elbow or bend
G1/2 15mm
22mm 28mm 35mm
up to 9m up to 18m up to 27m
0.8m
1.0m
1.4m
G3/4 22mm
28mm 35mm 42mm
up to 9m up to 18m up to 27
m
1.0m
1.4m
1.7m
G1 28mm
35mm 42mm 54mm
up to 9m up to 18m up to 27m
1.4m
1.7m
2.3m
10
1
2
GREEN/YELLOW
13 AMP MAINS
SUPPLY. 1.5mm
2
MIN. CABLE SIZE
TO INDIRECT SYSTEM
CONTROLS JUNCTION
BOX - SEE FIGS. 8/9
GREEN/
YELLOW
BROWN
BLUE
3
DIRECT THERMOSTAT
B
A
112
2
3
INDIRECT THERMOSTAT
INDIRECT THERMAL CUT-OUT
FIG. 5 Typical installation - schematic
FIG. 6 Electrical Connections (Schematic)
DIRECT MODELS AUXILLARY HEATING CONTROL
Note: On models tted with two elements each element must be wired indi­vidually in accordance with the diagram above.
THERMOSTAT
EARTH CONNECTION
FUSED (13A) DOUBLE POLE ISOLATING SWITCH
1.5mm2 3 CORE
HOFR SHEATHED CABLE
B
R
O
W
N
B
L
U
E
G
R
E
E
N
/ Y
E
L
L
O
W
A
B
11
5.0 INSTALLATION - DIRECT UNITS
5.1 PLUMBING CONNECTIONS
Direct units require the following pipework connec­tions.
Cold water supply to and from inlet controls.
Outlet to hot water draw off points.
Discharge pipew or k from valve outlets to
tundish.
5.2 ELECTRICAL SUPPLY (FIG. 6)
Premier Plus solar units are tted with two 3kW immersion heaters (Except 170Ltr) as standard. It is
recommended that these should be wired via a suitable
controller to BSEN 60730. The Premier Plus Solar MUST be earthed.
All wiring to the unit must be installed in accordance with the latest IEE Wiring Regulations and the circuit must be protected by a suitable fuse and double pole isolating switch with a contact separation of at least 3mm in both poles. The Live and Neutral connections
are made directly onto the combined thermostat and thermal cut-out located under the terminal cover(s) mounted on the side of the unit. The Earth connec­tion should be made to the earth connection located to
the side of the immersion heater boss(es). The supply
cable must be routed through the cable gland located on the unit casing beneath the terminal housing.
DO NOT operate the immersion heaters until the San-
ton Premier Plus Solar has been lled with water.
4.0 INSTALLATION - SOLAR PRI­MARY
4.1 CONNECTION TO PRIMARY CIRCUIT
The lower (solar) coil of the Premier Plus Solar must be connected to a fully pumped solar primary circuit. The connections are suitable for 22mm copper pipe direct to the compression ttings provided. The con­nections are also threaded 3/4” BSP male parrallel should BSP be required. The solar primary circuit should have its own dedi­cated circulating pump and safety controls which must be installed as per the manufacturers’ instructions.
4.2 CONTROL OF PRIMARY CIRCUIT
Temperature control of the Premier Plus Solar must be carried out using a suitable proprietory Solar Con­troller/Programmer. The cylinder temperature sensing
probe (supplied with the solar controller) should be
fully insterted into the pocket provided on the Premier Plus Solar and its cable secured using the cable clamps
on the controls housing. (see Fig.7)
Connection to the solar controller should be in ac-
cordance with manufacturers instructions. The solar
controller should be programmed to give a cylinder
temperature of approximately 60°C (maximum 70°C).
The solar controller and solar primary circulation
pump must be wired via the over-temperature thermal cut-out mounted in the lower solar controls housing
(see Fig. 7). This will ensure that the heat input to the solar coil is interrupted in the event of the cylin­der over-heating. There must also be suitable check (non-return) valves installed in the solar primary ow and return to prevent the possibility of any thermo­syphoning if the solar circulation is stopped.
5.3 SAFETY DISCONNECT FROM THE MAINS SUPPLY BEFORE REMOVING ANY COVERS.
Never attempt to replace the immersion heater(s)
other than with the recommended Santon immersion
heater(s).
DO NOT BYPASS THE THERMAL CUT-OUT(S) IN ANY CIRCUMSTANCES. Ensure the two male
spade terminations on the underside of the combined thermostat and thermal cut-out are pushed rmly onto
the corresponding terminations on the element plate assembly.
In case of difculty contact Santon service, Tel: 0844 8711530.
Cylinder Temperature
Control Probe Pocket
Cable Clamp
Solar Cylinder Controls Housing (cover not shown)
FIG. 7 Solar Coil Control Connections
Over-temperature
Cut-out
12
6.0 INSTALLATION - AUXILLARY HEATING COIL
6.1 PLUMBING CONNECTIONS
Indirect units require the following pipework con­nections.
Cold water supply to and from inlet controls.
Outlet to hot water draw off points.
Discharge pipew or k from valve outlets to
tundish
Connection to the auxillary primary circuit.
Primary connections are 22mm compression. How­ever, 3/4”BSP parallel threaded ttings can be tted to the primary coil connections if required.
6.2 ELECTRICAL SUPPLY (FIG. 6)
All Indirect units are tted with a 3kW immersion
heater and a combined thermostat and thermal cut-out to control the primary heating source. The Premier
Plus Solar MUST be earthed.
All wiring to the unit must be installed in accordance with the latest IEE Wiring Regulations and the supply circuits must be protected by a suitable fuse and double pole isolating switch with a contact separation of at least 3mm in both poles. All connections are made to the terminal block located under the terminal cover mounted on the side of the unit. The supply cable(s)
must be routed through the cable grip(s) in the termi­nal housing.
DISCONNECT FROM MAINS SUPPLY BE­FORE REMOVING ANY COVERS. DO NOT BYPASS THE THERMAL CUT-OUTS IN ANY CIRCUMSTANCES. Ensure the thermostat and
thermal cut-out sensing bulbs are pushed fully into the pockets on the element plate assembly.
6.3 BOILER SELECTION
The boiler should have a control thermostat and non self-resetting thermal cut-out and be compatible with
unvented storage water heaters.
Where use of a boiler without a thermal cut-out is unavoidable a “low head” open vented primary cir­cuit should be used. The Feed and Expansion cistern head above the Premier Plus Solar should not exceed
2.5m.
6.4 AUXILLARY CIRCUIT CONTROL
The 2 port motorised valve supplied with the Premier Plus Solar indirect units MUST be tted to the primary auxillary circuit ow to the Premier Plus solar heat
exchanger and wired in series with the indirect ther-
mostat and thermal cut-out tted to the unit.
Primary circulation to the Premier Plus Solars heat exchangers must be pumped, gravity circulation WILL NOT WORK.
13
FIG. 8 Schematic wiring diagram - Basic 2 x 2 port valve system
FIG. 9 Schematic wiring diagram - 3 port mid position valve system. N.B. Must be used in conjunction with 2 port zone valve supplied
Control terminal numbering may differ from those shown. Refer to instructions with controls
selected
A DOUBLE POLE ISOLATING SWITCH MUST BE INSTALLED IN THE MAINS SUPPLY. ALL EARTH CONNECTIONS BE CONNECTED BACK TO THE MAINS EARTH SUPPLY
Control terminal numbering may differ from those shown. Refer to instructions with controls
selected
A DOUBLE POLE ISOLATING SWITCH MUST BE INSTALLED IN THE MAINS SUPPLY. ALL EARTH CONNECTIONS BE CONNECTED BACK TO THE MAINS EARTH SUPPLY
NOTE: CONTROL CIRCUIT FOR AUXILLARY HEATING BOILER ONLY. SEPERATE CONTROLS WILL BE RE­QUIRED FOR THE SOLAR
PRIMARY CIRCUIT
NOTE: CONTROL CIRCUIT FOR AUXILLARY HEATING BOILER ONLY. SEPERATE CONTROLS WILL BE RE­QUIRED FOR THE SOLAR
PRIMARY CIRCUIT
14
7.0 COMMISSIONING
7.1 FILLING THE UNIT WITH WATER
Check Expansion Vessel pre-charge pressure. The
vessel is supplied pre-charged to 3.5 bar to match the
control pressure of the Pressure Reducing Valve. The pre-charge pressure is checked using a car tyre gauge
by unscrewing the plastic cap opposite the water con­nection.
Check all connections for tightness including the
immersion heater(s). An immersion heater key spanner is supplied for this purpose.
Ensure the drain cock is CLOSED.
Open a hot tap furthest from the Santon Premier
Plus Solar.
Open the mains stop cock to ll the unit. When
water ows from the tap, allow to run for a few min­utes to thoroughly ush through any residue, dirt or swarf, then close the tap.
Open successive hot taps to purge the system of
air.
7.2 SYSTEM CHECKS
Check all water connections for leaks and rectify
as necessary.
Remove the Pressure Reducing Valve headwork
to access the strainer mesh, clean and re-t.
Manually open, for a few seconds, each relief
valve in turn, checking that water is discharged and runs freely through the tundish and out at the discharge
point.
Ensure that the valve(s) reseat satisfactorily.
7.3 SOLAR PRIMARY CIRCUIT
Fill the solar primary circuit following the instruc­tions provided with the solar hydraulic controls. The
cylinder temperature control probe supplied with the
solar controller must be fully inserted into the pocket
in the lower controls housing and the cable securely
clamped. Heating by the solar primary circuit is con­trolled by the solar controller, refer to the manufactur­ers installation instructions for details of how to set up and connect the solar primary circuit. The solar
controller should be programmed to give a maximum
storage temperature in the Premier Plus Solar of 70oC, 60oC is recommended to minimise scaling.
7.5 Secondary Heating Coil
Fill the indirect secondary circuit following the boiler manufacturer’s commissioning instructions. To ensure the Premier Plus Solar auxillary heat exchanger is lled, the 2 port motorised valve (supplied) should be
manually opened by moving the lever on the motor
housing to the FLUSHING ONLY setting. When the circuit is full return the lever to the NORMAL USE position. Switch on the boiler, ensure the programmer is set to Domestic Hot Water and allow the Premier Plus Solar to heat up to a normal working temperature (60oC recommended, approximately graduation 4 on the thermostat). If necessary the temperature can be adjusted by inserting a at bladed screwdriver in the adjustment knob (located on top of the thermostat mounting bracket - see Fig.9) and rotating. The mini­mum thermostat setting is 10oC. The adjustment range 1 to 5 represents a temperature range of 30o to 70oC. Check the operation of the indirect thermostat and 2 port motorised valve and that no water has issued from the Expansion Relief Valve or Temperature/Pressure Relief Valve during the heating cycle.
7.6 BENCHMARKTM LOG BOOK
On completion of the installation and commissioning of the Premier Plus Solar the BenchmarkTM “Installa­tion, Commissioning and Service Record Log Book” should be completed and signed off by the competent
installer or commissioning engineer in the relevant sections.
The various system features, location of system con­trols, user instructions and what to do in the event of a system failure should be explained to the customer. The customer should then countersign the Bench­markTM log book to accept completion. The log book should be left with the customer along with these instructions. The log book includes sections that should be lled out when any subsequent service
or maintenance operation is carried out on the Premier Plus system.
7.4 DIRECT UNITS
Switch on electrical supply to the immersion heater(s) and allow the Premier Plus Solar to heat up to normal working temperature (60ºC recommended, approxi­mately graduation 4 on the thermostat). If necessary the temperature can be adjusted by inserting a at bladed screwdriver in the adjustment knob on top of
the immersion heater thermostat and rotating.
The adjustment range 1 to 5 represents a tempera­ture range of 10o to 70oC. Check the operation of thermostat(s) and that no water has issued from the Expansion Relief Valve or Temperature/Pressure Relief Valve during the heating cycle.
15
FIG. 10 Indirect thermostat and thermal cut-out
CABLE CLAMPS
TERMINAL BLOCK
INDIRECT THERMOSTAT
THERMOSTAT ADJUSTMENT
INDIRECT THERMAL CUT-OUT
INDIRECT THERMAL CUT-OUT RESET BUTTON
NOTE: THE HOUSING COVER AND ELEMENT ASSEMBLY HAVE BEEN REMOVED FROM THIS VIEW FOR CLAR­ITY
16
Carefully remove any scale from the surface of the element(s). DO NOT use a sharp implement as dam­age to the element surface could be caused. Ensure sealing surfaces are clean and seals are undamaged, if in doubt t a new gasket.
Replace immersion heater(s) ensuring the lower (right
angled) element hangs vertically downwards towards
the base of the unit. It may be helpful to support the
immersion heater using a round bladed screwdriver
inserted into one of the thermostat pockets whilst the backnut is tightened. Replace thermostat (Direct models) or thermostat capillaries into pocket (Indirect models), rewire, check, close and secure immersion
heater housing cover(s).
8.5 PREMIER PLUS SOLAR EXPANSION VESSEL CHARGE PRESSURE
Remove the dust cap on top of the vessel. Check the charge pressure using a tyre pressure gauge. The pres-
sure (with system de-pressurised) should be 3.5bar.
If it is lower than the required setting it should be re-charged using a tyre pump (Schrader valve type). DO NOT OVER CHARGE. Re-check the pressure
and when correct replace the dust cap.
8.6 RE-COMMISSIONING
Check all electrical and plumbing connections are se­cure. Close the drain cock. With a hot tap open, turn on the cold water supply and allow unit to rell. DO NOT
switch on the immersion heater(s) or boiler until the
unit is full. When water ows from the hot tap allow to ow for a short while to purge air and ush through
any disturbed particles. Close hot tap and then open successive hot taps in system to purge any air.
When completely full and purged check system for leaks. The heating source (immersion heater(s), boiler
or solar primary circuit) can then be switched on.
8.7 BENCHMARKTM LOG BOOK
On completion of any maintenance or service of the Premier Plus the BenchmarkTM “Installation, Com­missioning and Service Record Log Book” should be lled in to record the actions taken and the date the work was undertaken.
8.3 STRAINER
Turn off the cold water supply, boiler and immer­sion heaters. The lowest hot water tap should then be opened to de-pressurise the system. Remove the Pressure Reducing Valve by unscrewing it housing. Pull the Reducing Valve cartridge from the Check Valve housing to access the strainer mesh. Wash any particulate matter from the strainer under clean water. Re-assemble ensuring the seal is correctly tted, DO NOT use any other type of sealant.
8.4 DESCALING IMMERSION HEATER(S)
Before removing the immersion heater(s) the unit
must be drained. Ensure the water, electrical supply, boiler and solar primary circuit are OFF before draining. Attach a hosepipe to the drain cock having
sufcient length to take water to a suitable discharge point below the level of the unit. Open a hot tap close to the unit and open drain cock to drain unit.
Direct models:
Open the cover(s) to the immersion heater housing(s)
and disconnect wiring from the thermostat mounted on top of the immersion heater(s). Remove the thermostat by carefully pulling outwards from the immersion heater. Unscrew immersion heater backnut(s) and remove immersion heater from the unit. A key spanner is supplied with the Premier Plus Solar unit for easy removal/tightening of the immersion heater(s). Over time the immersion heater gasket may become stuck to the mating surface. To break the seal insert a round bladed screwdriver into one of the pockets on the im-
mersion heater and gently lever up and down.
8.0 MAINTENANCE
8.1 MAINTENANCE REQUIREMENTS
Unvented hot water systems have a continuing main­tenance requirement in order to ensure safe working and optimum performance. It is essential that the Relief Valve(s) are periodically inspected and manu­ally opened to ensure no blockage has occurred in the valves or discharge pipework. Similarly cleaning of the strainer element and replacement of the air in the Expansion Vessel will help to prevent possible operational faults.
The maintenance checks described below should be performed by a competent installer on a regular basis,
e.g. annually to coincide with boiler maintenance.
8.2 SAFETY VALVE OPERATION
Manually operate the Temperature/Pressure Relief Valve for a few seconds. Check water is discharged and that it flows freely through the tundish and discharge pipework. Check valve reseats correctly
when released. NOTE: Water discharged may be very hot!
Repeat the above procedure for the Expansion Valve.
Indirect models:
Open the cover(s) to the immersion heater housing(s)
and disconnect wiring from immersion heater(s). Re­move thermostat capillary sensors from the pockets on the immersion heater. Unscrew immersion heater backnut(s) and remove immersion heater from the unit. A key spanner is supplied with the Premier Plus Solar unit for easy removal/tightening of the immer­sion heater(s). Over time the immersion heater gasket may become stuck to the mating surface. To break the seal insert a round bladed screwdriver into one of the pockets on the immersion heater and gently lever
up and down.
17
9.0 FAULT FINDING AND SERVICING
9.1 IMPORTANT
Servicing should only be carried by authorised
Santon Service Engineers or Agents or by competent
installers in the installation and maintenance of un-
vented water heating systems.
Any spare parts used MUST be authorised Santon
parts.
Disconnect the electrical supply before removing
any electrical equipment covers.
NEVER bypass any thermal controls or operate
system without the necessary safety valves.
Water contained in the Premier Plus Solar unit
may be very hot, especially following a thermal
control failure. Caution must be taken when drawing
water from the unit.
9.2 SPARE PARTS
A full range of spare parts are available for the Premier
Plus range. Refer to the Technical Data label on the
unit to identify the model installed and ensure the
correct part is ordered.
Description Part no.
Immersion heater (lower) 95 606 946 Immersion heater (upper) 95 606 947 Immersion heater gasket 95 611 822 Immersion heater backnut 95 607 869 Solar temperature probe pocket plate 95 607 064 Immersion heater key 95 607 861 Tundish 95 605 838 Expansion valve cartridge - 6bar 95 605 864 Expansion valve complete - 6bar 95 607 030 Cold water combination valve complete 95 605 022 Cold water combination valve body 95 605 030 Check valve housing 95 605 028 Pressure reducing valve cartridge 3.5bar 95 607 029 Pressure reducing valve housing 95 605 027 Temperature/Pressure Relief Valve 95 605 810 Expansion vessel 12 litre (100, 120 and 150 litre models) 95 607 863 Expansion vessel 18 litre (170 and
Cold Water Combination Valve - Exploded view
210 litre models) 95 607 864 Expansion vessel 25 litre (250 and 300 litre models) 95 607 612 Indirect Thermal cut-out (for Solar Coil) 95 612 698
Direct units only
Combined thermostat and thermal
cut-out 95 612 599 Terminal cover 95 607 836
Indirect units only
Indirect thermostat 95 612 697 Indirect Thermal cut-out 95 612 698 Motorised valve 2 port 95 605 819 Terminal housing 95 607 865 4 Way terminal block 95 607 902
Cable Gland
Combined
Thermostat &
Thermal Cut-out
- Direct models
Spare Part No:
95 612 599
Expansion Valve
Cartridge
Spare Part No. 95 605 864
Expansion Valve
Complete (6 bar)
Spare Part No. 95 607 030
Valve Body Spare Part No. 95 605 030
Check Valve Housing Spare Part No. 95 605 028
Pressure Reducing Valve Housing Spare Part No. 95 605 027
Pressure Reducing Valve Cartridge
(3.5 bar)
Spare Part No. 95 607 029
Strainer Mesh
Housing Securing Screws (4 off)
Cold Water Combination Valve Complete Spare Part No. 95 605 022
Indirect thermostat Spare Part No: 95 612 697
Indirect Thermal Cut-out Spare Part No: 95 612 698
4 Way Terminal Block Spare Part No: 95 612 697
18
9.3 FAULT FINDING
The Fault Finding chart below will enable opera­tional faults to be identied and their possible causes rectied. Any work carried out on the Premier Plus
unvented solar water heater and its associated con-
trols MUST be carried out by a competent installer for unvented water heating systems. In case of doubt contact the Santon Service Department (see contact details at foot of page 20).
DO NOT TAMPER WITH ANY OF THE SAFETY VALVES OR CONTROLS SUP­PLIED WITH THE PREMIER PLUS AS THIS WILL INVALIDATE ANY GUAR­ANTEE
TABLE 5 Fault Finding Chart
WARNING
F A U L T
No hot water o w
2. S trainer blo cked s tra iner and cl ean (s ee S ec tion 8.3)
3. Co ld W ater C om bi nation V alve
in co rrec tly tted
3. Check and re t as require d
W ater from h ot taps is col d
s wit che d on
1. Check and s witch on
2. DIR ECT im m ers ion heate r
therm al c ut -out has operat ed
2. Check. R es et b y pushing butt on.
3. INDIRE CT program mer s et t o
Central Heat ing only
3. C heck. S et t o a Do mes ti c Hot W ate r p rogram me
4. INDIRE CT boiler not work ing s us pect ed c onsult boile r m a
nufa c turer's in struc tions
5. INDIRE CT therm al cut -out has
operat ed
5. Check. R es et b y pushing butt on on c ut-out. C heck opera tion o f indirec t therm os tat
6. INDIRE CT m otoris ed valve not
c onnected correc tly
6. C heck wiri ng and/or p lum bing c onnect ions to m ot oris ed valve (s ee F ig . 8 or 9)
7. S O LA R Ins uc ient Sol ar Gai n,
with no aux illa ry heat ing s witc hed on
7. Check auxill ary heat s ourc e is s wit ched o n and i s c ontroled to p rovid e heat gain if no s olar out put is a va ilable .
W ater di schar
ges
from E xpans ion V alve
pressu re has reduc ed below
3.5bar
1. S ee S ec tion 8.5 for re-c harging proc edure
2. CO NTINUA LLY
a. Co ld W ater C om bi nation V alve P ressu re Reduc er not w ork ing c orrec tly
a. Check pre ssure from C old W a ter Com bination V al ve . If greater th an
3.5bar repla c e P ressu re Re duce r c art ridge
b. E x pansi on V alve seat dam aged.
b. Re move E x pansion V alve c artridge. Check c on dit ion of seat . If nec essary t new E xpans ion V al ve cartridge.
W ater di scharges from T&P Relie f V alve
1. Therm a l
c ontrol fa ilure N OTE
wat er wil l be ve ry hot
1. S wit ch o powe r to im mers ion heater(s ), s hut dow n bo ile r and s hut down so lar p rim ary c ircui t. DO N OT turn o  w ater s upply . W hen d ischarge s tops c heck all therm al controls , repla ce if faulty .
"M ilky" wat er O xygenated wa te r
releas es o xygen bubble s w hen owing. The m ilk iness will dis appear after a s hort whi le.
P OS S IB L E C AU S E
R E M E D Y
1. C heck and open s top c oc k1. M ain s suppl y o
2. Tu rn o wa ter s upply . R em ove
1. DIR ECT im m ers ion heate r not
4. C heck boiler operation. If fault is
1. INTE RM ITTE NTLY
E xpans ion Vesse l c harge
W ate r from a pre ssurised system
19
10.0 USER INSTRUCTIONS
10.1 WARNINGS IF WATER ISSUES FROM THE TEMPERA­TURE/PRESSURE RELIEF VALVE ON THE SANTON PREMIER PLUS SOLAR SWITCH OFF ELECTRICAL SUPPLY TO THE IMMER­SION HEATER(S) (DIRECT UNITS),SHUT DOWN THE BOILER (INDIRECT UNITS) AND SHUT DOWN THE SOLAR PRIMARY CIRCUIT. DO NOT TURN OFF ANY WATER SUPPLY. CONTACT A COMPETENT INSTALLER FOR UNVENTED WATER HEATERS TO CHECK THE SYSTEM.
DO NOT TAMPER WITH ANY OF THE SAFETY VALVES FITTED TO THE SANTON PREMIER PLUS SYSTEM. IF A FAULT IS SUSPECTED CONTACT A COMPETENT INSTALLER.
10.2 TEMPERATURE CONTROLS - SOLAR
Temperature control of the solar primary coil is by means of solar differential temperature controller. This will usually have been set during commissioning to give a storage temperature of approximately 60oC. Refer to user instructions supplied with the controller for details of how to adjust this if required.
10.3 TEMPERATURE CONTROLS – DIRECT
UNIT IMMERSION HEATER(S)
A combined adjustable thermostat and thermal cut-out is provided for each immersion heater. The thermostat is factory set to give a water storage temperature of
approx. 55o to 60oC. Access to the thermostat can be
made by opening the immersion heater cover - DIS­CONNECT THE ELECTRICAL SUPPLY BEFORE OPENING THE COVER(S). Temperature adjustment is made by inserting a at bladed screwdriver in the slot on the adjustment disc on top of the thermostat and rotating. The adjustment range 1 to 5 represents a temperature range of 10o to 70oC (60oC will be approximately position 4). If in any doubt contact a
competent electrician.
DO NOT bypass the thermal cut-out(s) in any circumstances.
10.4 TEMPERATURE CONTROLS – INDIRECT
UNITS (Fig. 9)
The Santon Premier Plus Solar Indirect units are t­ted with an Indirect Thermostat and Thermal Cut-out. These controls must be wired in series with the 2 port motorised zone valve supplied to interupt the ow of
primary water around the heat exchanger coil when the
control temperature has been reached. The controls are
located within the upper grey terminal housing along
with the immersion heater thermostat. The thermostat is factory set to give a water storage temperature of
approx. 55o to 60oC. Access to the thermostat can be
made by opening the terminal housing cover - DIS­CONNECT THE ELECTRICAL SUPPLY BEFORE OPENING THE COVER. Temperature adjustment is made by inserting a at bladed screwdriver in the adjustment knob and rotating. The minimum ther­mostat setting is 10oC. The adjustment range 1 to 5 represents a temperature range of 30o to 70oC (60oC will be approximately position 4). If in any doubt
contact a competent electrician.
On indirect units an immersion heater is also provided
for use should the indirect heat source be shut down for any purpose. The immersion heater control tem-
perature is set using the immersion heater (Direct)
thermostat, see section 10.3 for details.
DO NOT bypass the thermal cut-out(s) in any circumstances.
10.4 FLOW PERFORMANCE
When initially opening hot outlets a small surge in
ow may be noticed as pressures stabilise. This is quite normal with unvented systems. In some areas cloudiness may be noticed in the hot water. This is due to aeration of the water, is quite normal and will quickly clear.
10.5 OPERATIONAL FAULTS
Operational faults and their possible causes are de­tailed in Section 9.0. It is recommended that faults should be checked by a competent installer.
The air volume within the expansion vessel will peri-
odically require recharging to ensure expanded water
is accommodated within the unit. A discharge of water INTERMITTENTLY from the Expansion Valve will
indicate the air volume has reduced to a point where it can no longer accommodate the expansion.
20
SANTON
Hurricane Way, Norwich, Norfolk, NR6 6EA
Tel: 01603 420140
Service
Tel: 0844 8711530 Fax: 0844 8711528 E-mail: santonservice@heateam.co.uk
Specication
Tel: 01603 420128 Fax: 01603 420229 E-mail: specier@santon.co.uk
11.0 GUARANTEE
This product is guaranteed against faulty materials and manufacture for a period of 25 years from date of purchase (with the exception of the Expansion
Vessel which is guaranteed for a period of 5 years
andvalves,ttingsandelectricalpartswhichare
guaranteed for a period of 2 years) provided that:
The unit has been installed in accordance with the Installation and Service instructions and all relevant Codes of Practice and Regulations in force at the time of installation, and that all necessary inlet controls and safety valves have been tted correctly.
Any valves and controls are of the Santon recom­mended type and specication.
It has only been used for the storage of potable
water.
The unit has not been modied or tampered with in any way, and has been regularly maintained as detailed in the Installation and Service instructions.
Within 60 days of installation, the user completes and returns any Certicate of Registration that may
be supplied with the unit in order to register the prod­uct.
The unit is not guaranteed against damage by frost, and
the inner container with integral immersion heater(s) is not guaranteed against excessive scale build-up.
Periodic loss of charge pressure from the Expan­sion Vessel is normal (indicated by an intermittent discharge of water from the Expansion Valve) and is not covered under the product guarantee. Refer to Section 8.5 for details on how to restore the Expansion Vessel charge pressure.
This guarantee is not valid for installations outside the United Kingdom and the Republic of Ireland. For
installations outside these territories please contact
either the Santon Export Department (Tel: +44 1603
420191) or Baxi International (Tel: +44 1926 478323) for further details of the gaurentee terms and condi-
tions applicable.
This guarantee does not affect your statutory rights.
ENVIRONMENTAL INFORMATION
Santon products are manufactured from many recyclable materials. At the end of their useful life they should be disposed of at a Local Authority Recycling Centre in order to realise the full environmental benets.
Insulation is by means of an approved CFC/HCFC free polyurethane foam with an ozone depletion factor of zero.
The policy of Santon is one of continuous product development and, as such, we reserve the right to change specications without notice.
For the fast and efcient supply of spares please contact the stockists listed below.
Electric Water Heating Co.
2 Horsecroft Place, Pinnacles, Harlow, Essex, CM19 5BT Tel: 0845 0553811 E-mail: sales@ewh.co.uk
SPD
Special Products Division, Units 9 & 10, Hexagon Business Centre, Springeld Road, Hayes, Middle­sex, UB4 0TY Tel: 020 8573 0574
Parts Center
Network 65 Business Park, Bentley Wood Way, Burnley, Lancashire, BB11 5ST Tel: 01282 834403 www.partscenter.co.uk
Newey & Eyre
Specialist Products Division
Please contact your local branch
UK Spares Ltd.
Tower Lane, Warmley, Bristol, BS30 8XT Tel: 0117 961 6670
William Wilson Ltd.
Unit 3A, 780 South Street, Whiteinch, Glasgow, G14 0SY Tel: 0141 434 1530
12.0 SPARES STOCKISTS
Loading...