Santerno DCREG2.20, DCREG2, DCREG4.20, DCREG2.40, DCREG4.40 User Manual

...
15P0059B3
DCREG2 DCREG4
USER MANUAL
28/05/18 R.07
SOFTWARE VERSION D5.02
• This manual is an integral and essential part of the product. Carefully read the instructions contained
herein as they provide important hints for use and maintenance safety.
• This device shall be used only for the purposes it is aimed at. Any other use is to be considered as improper and dangerous. The manufacturer is not responsible for any possible damage caused by improper, erroneous and irrational uses.
• Elettronica Santerno are responsible for the device in its original setting.
• Any changes to the structure or operating cycle of the device must be performed or authorized by
Elettronica Santerno’s Engineering Department.
• Elettronica Santerno are not responsible for the consequences resulting from the use of non-original
spare parts.
• Elettronica Santerno reserve the right to make any technical changes to this manual and the device
without prior notice. Any misprint or spelling mistake will be edited in the new versions of this manual.
• Elettronica Santerno are responsible for the information contained in the original version of the Italian manual.
• The information contained herein is Elettronica Santerno’s property and cannot be reproduced.
Elettronica Santerno enforce their rights on the drawings and catalogues according to the law.
En gl ish
8
5
7 6 4
1
2
3
NOTE
The standard equipment may be supplied on terminals 53-54 (control section) with a single-phase alternate voltage between 380 … 500 Vac. On
demand, the device may be supplied on terminals 53-54 a with single-phase alternate voltage between 200 … 240 Vac.
The standard equipment may be supplied through terminals E1-2 (field
regulator) with a single-phase voltage ranging from 200 to 500 Vac.
Maintenance tasks
Minimum frequency
What to do
Check heatsink; clean, if required
Depending on dust concentration (every 6…12 months)
See Heatsink section below
Check cooling fans; replace, if required [*]
Depending on dust concentration (every 6…12 months)
See Cooling fans section below
Replace cooling fans [*]
Every 6 years
See Cooling fans section below
NOTE
Whenever the display shows an alarm condition, it is necessary to reset it by
simultaneously pressing the “PROG” and “SAVE” keys on the front keypad, or
by means of one of the configurable digital inputs, by programming parameters C130(131)(132)(133)(134)(135) at the 0:Reset value (this configuration is a default value on MDI1, terminal 28). Should the alarm not disappear from the display (and therefore the alarm cause persists), refer to the ALARM PARAMETERS section of the manual.
NOTE
Before changing the above mentioned parameters and any other parameter, set the value of parameter P000 to 1.
NOTE
Any other setting up procedure described below should always be saved on the EEPROM. The non-observance of said instruction shall produce the loss
of all data while turning off the device.
NOTE
The programming level is set in parameter P003; its default value is called
0:Basic. This parameter allows to access and modify few other parameters only, as it is used for a quick and simple starting. If during the start-up procedure some parameters which are not included in said programming level must be changed, set parameter P003 to 1:Advanced.
Drive OK – D5.01
DCREG4.100 P440
NOTE
The displaying of warning message W003 (Imax[T2] <100%) means that it is necessary to turn the T2 trimmer completely clockwise, since a partial rotation clockwise could result in a disagreement between the current limit and the armature maximum current values to be obtained. More precisely, the armature maximum current value could be lower than the one required. The trimmer is located on the right side of the control board, near the two seven-segment displays which can be seen through the small slot on the drive cover.
NOTE
Any value being set for parameters C074 and P010 should be programmed in
such a way that product C074•P010 does not exceed 25V if C070 = 0, 80V if C070 = 1, 250V if C070 = 2. Otherwise, this will cause drive speed control
failure.
NOTE
Any value being set in parameters C072 and P010 should be programmed in such a way that product C072•P010 does not exceed 102.400k Hz (value obtained from an enP/Nr supplying 1024 pulse/rev that can rotate at a speed
of max. 6000 RPM:
60
60001024
102400
), in order to avoid possible speed
control faults caused by the drive.
NOTE
Whenever a (0)4 … 20 mA reference is to be used, refer to the chapter dealing with MILLIAMPERE INPUT/OUTPUT SIGNALS to know the value to be programmed in the parameters relating to the Gain and Bias operators.
ATTENTION
Make sure that, at maximum speed and maximum voltage, the output armature voltage does not exceed the motor rated value.
NOTE
The operation stability is generally more critical when the speed maximum value being set according to the maximum reference decreases. In order to set maximum speed values being especially low, it is therefore recommended to reduce the reference amplification through the Gain function relating to the selected analog input (see the SPEED CONTROL OPTIONS chapter), instead of adjusting the feedback.
NOTE
Between ramp times and rounding times, a certain ratio of inequality should be proved. Said value is reported in the note in chapter RAMPS OVER REFERENCE.
NOTE
For this operating mode, the speed reference should allow to keep the drive in current limit condition at any time.
NOTE
A current reference setting may be performed on any REF, IN1, IN2, IN3 analog inputs, after programming them accordingly. In particular, if the REF main input between terminals 5 and 7 is to be used, the Gain, Bias and Polarity operators use distinct parameters (i.e. different from the parameters enabled in case of voltage / speed reference). In particular, the Gain function is programmed in parameter P125(default value: 100%), the Bias function is programmed in parameter P124 (default value: 0%), while the Polarity function is programmed in parameter P123 (default value: Bipolar). By contrast, if auxiliary analog input IN 1(2)(3) is to be used, parameter C120(121)(122) is to be set at value 2:I loop add. ref. In addition, main reference REF is to become a current reference, either permanently by programming parameter C050 at value 3:Iref=Vref or temporarily by closing a digital input set at value 6:Slave Enabled. For each of those two modes, main input REF is to be connected to zero volt.
NOTE
For a drive couple operating in MASTER / SLAVE mode, the current reference to be supplied by the master drive may be obtained on terminal 8(10) by programming P150(153) = 4:Current ref. As the reference standard level supplied by the MASTER drive is 5V at its rated current (M003 = 100%), if also the SLAVE drive must supply its rated current - with said reference at REF main reference between terminals 5 and 7 - gain P125 (IrefGain) is to be set at 200%.
dt
dV
SIZE
DIMENSIONS
LxDxH (mm)
MODEL
ARMATURE
OUTPUT
VOLTAGE
(Vdc)
ARMATURE
RATED DI
CURRENT
(A)
FIELD
OUTPU
T
VOLTAGE
(Vdc)
FIELD
RATED
CURRENT
(A)
AC-SIDE
ULTRAFAST
FUSES
(FU1-2-3)
DC-SIDE
ULTRAFAST
FUSES
(FU4)
DISSIPATED
POWER
(W)
1
214x264x440
DCREG2.10 DCREG4.10
DCREG2
530 max
(440 Vin)
DCREG4
460 max
(440 Vin)
10
425 max
(500 Vin)
5
3540A
00T/80
3540A
00T/80
30
DCREG2.20 DCREG4.20
20
3540A
00T/80
3540A
00T/80
60
DCREG2.40 DCREG4.40
40
3540A
00T/80
50A
00T/80
120
DCREG2.70 DCREG4.70
70
80A
00T/80
100A
00T/80
210
DCREG2.100 DCREG4.100
100
100A
00T/80
125A
00T/80
300
DCREG2.150 DCREG4.150
150
15
160A
00T/80
200A
00T/80
450
DCREG2.180 DCREG4.180
180
160A
00T/80
250A
00T/80
540
DCREG2.250 DCREG4.250
250
250A
00T/80
315A
00T/80
750
DCREG2.350 DCREG4.350
350
315A
00T/80
375400A
00T/80
1050
2
333x360x596
DCREG2.410 DCREG4.410
410
35
450A 2T/80
550A 2T/80
1230
DCREG2.500 DCREG4.500
500
550A 2T/80
700A 3T/80
1500
DCREG2.600 DCREG4.600
600
630A 2T/80
800A 3T/80
1800
DCREG2.900 DCREG4.900
900
900A 3T/80
1250A
3T/80
2700
2A
333x453x685
DCREG2.1200 DCREG4.1200
1200
1100A
3T/80
1400A
3T/80
3600
NOTE
By request, Elettronica Santerno can provide drives of any size with a field rated current different than the standard value, which is 5A for DCREG.100max, 15A
for DCREG.150min Size 1 and 35A for DCREG Size 2, 2A and MODULAR.S
SIZE
DIMENSIONS
LxDxH (mm)
(For Modular
types,
measu
res
refer to
POWER
UNIT)
MODEL
ARMATURE
OUTPUT
VOLTAGE
(Vdc)
ARMATURE
RATED DI
CURRENT
(A)
FIELD
OUTPUT
VOLTAGE
(Vdc)
FIELD
RATED
CURRENT
(A)
AC-SIDE
ULTRAFAST
FUSES
(FU1-2-3)
DC-SIDE
ULTRAFAST
FUSES
(FU4)
DISSIPATED
POWER
(W)
1
214x264x440
DCREG2.10 DCREG4.10
DCREG2
600 max
(500 Vin)
DCREG4
520 max
(500 Vin)
10
425 max
(500 Vin)
5
3540A
00T/80
3540A
00T/80
30
DCREG2.20 DCREG4.20
20
3540A
00T/80
3540A
00T/80
60
DCREG2.40 DCREG4.40
40
3540A
00T/80
50A
00T/80
120
DCREG2.70 DCREG4.70
70
80A
00T/80
100A
00T/80
210
DCREG2.100 DCREG4.100
100
100A
00T/80
125A
00T/80
300
DCREG2.150 DCREG4.150
150
15
160A
00T/80
200A
00T/80
450
DCREG2.180 DCREG4.180
180
160A
00T/80
250A
00T/80
540
DCREG2.250 DCREG4.250
250
250A
00T/80
315A
00T/80
750
DCREG2.350 DCREG4.350
350
315A
00T/80
375400A
00T/80
1050
2
333x360x596
DCREG2.410 DCREG4.410
410
35
450A 2T/80
550A 2T/80
1230
DCREG2.500 DCREG4.500
500
550A 2T/80
700A 3T/80
1500
DCREG2.600 DCREG4.600
600
630A 2T/80
800A 3T/80
1800
DCREG2.900 DCREG4.900
900
900A 3T/80
1250A
3T/80
2700
2A
333x453x685
DCREG2.1200 DCREG4.1200
1200
1100A
3T/80
1400A
3T/80
3600
MODULAR.S
500x275x860 (Size F)
DCREG4.1400S
DCREG2
600 max
(500 Vin)
DCREG4
520 max
(500 Vin)
1400
425 max
(500 Vin)
35 - -
4200
500x275x860 (Size A)
500x375x1410 (Size G)
DCREG2.1600S DCREG4.1600S
1600
4800
500x275x860 (Size A)
500x375x1410 (Size G)
DCREG2.1800S DCREG4.1800S
1800
5400
500x275x860 (Size A)
500x375x1410 (Size G)
DCREG2.2000S DCREG4.2000S
2000
6000
620x360x884 (Size B)
620x495x1434 (Size H)
DCREG2.2300S DCREG4.2300S
2300
6900
620x360x884 (Size B)
620x495x1434 (Size H)
DCREG2.2500S DCREG4.2500S
2500
7500
712x395x945 (Size C)
712x495x1505 (Size I)
DCREG2.2700S DCREG4.2700S
2700
8100
712x395x945 (Size C)
712x495x1505 (Size I)
DCREG2.3000S DCREG4.3000S
3000
9000
784x415x1110 (Size D) 784x460x1790 (Size J)
DCREG2.3500S DCREG4.3500S
3500
10500
968x482x1250 (Size E) 988x543x2070 (Size K)
DCREG2.4500S DCREG4.4500S
4500
13500
NOTE
By request, Elettronica Santerno can provide drives of any size with a field rated current different than the standard value, which is 5A for DCREG.100max, 15A
for DCREG.150min Size 1 and 35A for DCREG Size 2, 2A and MODULAR.S
SIZE
DIMENSIONS
LxDxH (mm)
(For Modular
types,
measures
refer to
POWER
UNIT)
MODEL
ARMATURE
OUTPUT
VOLTAGE
( Vdc)
ARMATURE
RATED DI
CURRENT
(A)
FIELD
OUTPUT
VOLTAGE
( Vdc)
FIELD
RATED
CURRENT
(A)
AC-SIDE
ULTRAFAST
FUSES
(FU1-2-3)
DC-SIDE
ULTRAFAST
FUSES
(FU4)
DISSIPATED
POWER
(W)
1
214x264x440
DCREG2.10 DCREG4.10
DCREG2
720 max
(600 Vin)
DCREG4
630 max
(600 Vin)
10
425 max
(500 Vin)
5
3540A
00T/80
3540A
00T/80
30
DCREG2.20 DCREG4.20
20
3540A
00T/80
3540A
00T/80
60
DCREG2.40 DCREG4.40
40
3540A
00T/80
50A
00T/80
120
DCREG2.70 DCREG4.70
70
80A
00T/80
100A
00T/80
210
DCREG2.100 DCREG4.100
100
100A
00T/80
125A
00T/80
300
DCREG2.150 DCREG4.150
150
15
160A
00T/80
200A
00T/80
450
DCREG2.180 DCREG4.180
180
160A
00T/80
250A
00T/80
540
DCREG2.250 DCREG4.250
250
250A
00T/80
315A
00T/80
750
DCREG2.350 DCREG4.350
350
315A
00T/80
375400A
00T/80
1050
2
333x360x596
DCREG2.410 DCREG4.410
410
35
450A 2T/80
550A 2T/80
1230
DCREG2.500 DCREG4.500
500
550A 2T/80
700A 3T/80
1500
DCREG2.600 DCREG4.600
600
630A 2T/80
800A 3T/80
1800
DCREG2.750 DCREG4.750
750
800A 3T/80
1000A
3T/80
2250
2A
333x453x685
DCREG2.900 DCREG4.900
900
900A 3T/80
1250A
3T/80
2700
MODULAR.S
500x275x665 (Size L)
DCREG2.1050S
DCREG2
720 max
(600 Vin)
DCREG4
630 max
(600 Vin)
1050
425 max
(500 Vin)
35 - -
3150
500x275x860 (Size F)
DCREG4.1250S
1250
3750
500x275x860 (Size A)
500x375x1410 (Size G)
DCREG2.1600S DCREG4.1600S
1600
4800
500x275x860 (Size A)
500x375x1410 (Size G)
DCREG2.1800S DCREG4.1800S
1800
5400
500x275x860 (Size A)
500x375x1410 (Size G)
DCREG2.2000S DCREG4.2000S
2000
6000
620x360x884 (Size B)
620x495x1434 (Size H)
DCREG2.2300S DCREG4.2300S
2300
6900
620x360x884 (Size B)
620x495x1434 (Size H)
DCREG2.2500S DCREG4.2500S
2500
7500
712x395x945 (Size C)
712x495x1505 (Size I)
DCREG2.2700S DCREG4.2700S
2700
8100
712x395x945 (Size C)
712x495x1505 (Size I)
DCREG2.3000S DCREG4.3000S
3000
9000
784x415x1110 (Size D) 784x460x1790 (Size J)
DCREG2.3500S DCREG4.3500S
3500
10500
968x482x1250 (Size E) 988x543x2070 (Size K)
DCREG2.4500S DCREG4.4500S
4500
13500
NOTE
By request, Elettronica Santerno can provide drives of any size with a field rated current different than the standard value, which is 5A for DCREG.100max, 15A for DCREG.150min Size 1 and 35A for DCREG Size 2, 2A and MODULAR.S
SIZE
DIMEN
SIONS
LxDxH (mm)
(For Modular
types,
measures
refer to
POWER
UNIT)
MODEL
ARMATURE
OUTPUT
VOLTAGE
( Vdc)
ARMATURE
RATED DI
CURRENT
(A)
FIELD
OUTPUT
VOLTAGE
( Vdc)
FIELD
RATED
CURRENT
(A)
AC-SIDE
ULTRAFAST
FUSES
(FU1-2-3)
DC-SIDE
ULTRAFAST
FUSES
(FU4)
DISSIPATED
POWER
(W)
1
214x264x440
DCREG2.10 DCREG4.10
DCREG2
800 max
(690 Vin)
DCREG4
720 max
(690 Vin)
10
425 max
(500 Vin)
5
3540A
00T/80
3540A
00T/80
30
DCREG2.20 DCREG4.20
20
3540A
00T/80
3540A
00T/80
60
DCREG2.40 DCREG4.40
40
3540A
00T/80
50A
00T/80
120
DCREG2.70 DCREG4.70
70
80A
00T/80
100A
00T/80
210
DCREG2.100 DCREG4.100
100
100A
00T/80
125A
00T/80
300
DCREG2.150 DCREG4.150
150
15
160A
00T/80
200A
00T/80
450
DCREG2.180 DCREG4.180
180
160A
00T/80
250A
00T/80
540
DCREG2.250 DCREG4.250
250
250A
00T/80
315A
00T/80
750
DCREG2.350 DCREG4.350
350
315A
00T/80
375400A
00T/80
1050
2
333x360x596
DCREG2.410 DCREG4.410
410
35
450A 2T/80
550A 2T/80
1230
DCREG2.500 DCREG4.500
500
550A 2T/80
700A 3T/80
1500
DCREG2.600 DCREG4.600
600
630A 2T/80
800A 3T/80
1800
DCREG2.750 DCREG4.750
750
800A 3T/80
1000A
3T/80
2250
2A
333x453x685
DCREG2.900 DCREG4.900
900
900A 3T/80
1250A
3T/80
2700
MODULAR.S
500x275x665 (Size L)
DCREG2.1050S DCREG4.1050S
DCREG2
800 max
(690 Vin)
DCREG4
720 max
(690 Vin)
1050
425 max
(500 Vin)
35 - -
3150
500x275x860 (Size F)
500x275x860 (Size A)
500x375x1410 (Size G)
DCREG2.1600S DCREG4.1600S
1600
4800
500x275x860 (Size A)
500x375x1410 (Size G)
DCREG2.2000S DCREG4.2000S
2000
6000
620x360x884 (Size B)
620x495x1434 (Size H)
DCREG2.2300S DCREG4.2300S
2300
6900
712x395x945 (Size C)
712x495x1505 (Size I)
DCREG2.2500S DCREG4.2500S
2500
7500
712x395x945 (Size C)
712x495x1505 (Size I)
DCREG2.2700S DCREG4.2700S
2700
8100
712x395x945 (Size C)
712x495x1505 (Size I)
DCREG2.3000S DCREG4.3000S
3000
9000
784x415x1110 (Size D) 784x460x1790 (Size J)
DCREG2.3500S DCREG4.3500S
3500
10500
968x482x1250 (Size E) 988x543x2070 (Size K)
DCREG2.4500S DCREG4.4500S
4500
13500
NOTE
By request, Elettronica Santerno can provide drives of any size with a field rated current different than the standard value, which is 5A for DCREG.100max, 15A
for DCREG.150min Size 1 and 35A for DCREG Size 2, 2A and MODULAR.S
SIZE
MODEL
K
(par. P060, P061)
OVERLOAD
PERCENTAGE
Imot
BASE CURRENT
FOR SPECIFIED
OVERLOAD
(A)
Gr.1
DCREG2(4).10
150%
10
DCREG2(4).20
20
DCREG2(4).40
40
DCREG2(4).70
70
DCREG2(4).100
100
DCREG2(4).150
150
DCREG2(4).180
180
DCREG2(4).250
250
DCREG2(4).350
350
Gr.2 DCREG2(4).410
410
DCREG2(4).500
500
DCREG2(4).600
600
DCREG2(4).750
750
DCREG2(4).900
900
Gr.2A
DCREG2(4).900
900
DCREG2(4).1200
1200
MODULAR.S
DCREG2(4).1050
125%
1000
DCREG4.1250
1100
DCREG4.1400
1200
DCREG2(4).1600
1400
DCREG2(4).1800
1640
DCREG2(4).2000
1750
DCREG2(4).2300
2000
DCREG2(4).2500
2200
DCREG2(4).2700
2480
DCREG2(4).3000
2500
DCREG2(4).3500
3000
DCREG2(4).4500
3700
I
ARM
(A)
t
K • I
mot
I
arm nom
I
mot
1min
9min
4 4 4
4
NOTE
(*) Supply term. 53-54 with AC voltage OR term. 44-42 with DC voltage.
(*) VEDI NOTA (SEE NOTE)
NOTE
(*) Supply term. 53-54 with AC voltage OR term. 44-42 with DC voltage.
(*) VEDI NOTA (SEE NOTE)
TH2A
TH2B
TH1A
TH1B
L1
L2
TH3A
TH3B
TH4B
TH4A
L3
TH5A
TH5B
TH6B
TH6A
A1
+(-)
-(+)
A2
NOTE
TH1B ... 6B thyristors (4 quadrants operation) in DCREG4 only.
Terminal
Description
Notes
L1 L2 L3
Input bars for armature rectifier three-phase bridge power supply.
Decisive voltage class C according to EN 61800-5-1 Standard 440 Vac max Electrical connection: DCREG Size 1: 3xM8 (screw torque: 16 Nm / 142 lb/in) DCREG Size 2: 3xM10 (screw torque: 25 Nm / 221 lb/in) DCREG Size 2A: 3xM12 (screw torque: 40 Nm / 354 lb/in) DCREG MODULAR.S: see Power Section Overall Dimensions (See Note (1) below)
A1 A2
Direct current output bars for motor armature DC power supply. Positive potential on bar A1 compared to bar A2, with positive speed reference and drive not in regeneration state.
Decisive voltage class C according to EN 61800-5-1 Standard 600 Vdc for DCREG2, 520 Vdc per DCREG4 Electrical connection: DCREG Size 1: 3xM8 (screw torque: 16 Nm / 142 lb/in) DCREG Size 2: 3xM10 (screw torque: 25 Nm / 221 lb/in) DCREG Size 2A: 3xM12 (screw torque: 40 Nm / 354 lb/in) DCREG MODULAR.S: see Power Section Overall Dimensions (See Note (1) below)
E1 E2
Input for field single-phase bridge power supply.
Decisive voltage class C according to EN 61800-5-1 Standard 200 … 500 Vac DCREG.100max: 5 A max, DCREG.150min Size 1: 15 A max (screw torque: 2.53 Nm / 2227 lb/in) DCREG Size 2(A) and MODULAR.S: 35 A max (See Note (1) below)
F1 F2
Direct voltage output for motor field DC power supply. Positive potential on terminal F1 compared to terminal F2.
Decisive voltage class C according to EN 61800-5-1 Standard 425 Vdc max DCREG.100max: 5 A max, DCREG.150min Size 1: 15A max screw torque: 2.53 Nm / 2227 lb/in) DCREG Size 2(A) and MODULAR.S: 35 A max (See Note (1) below)
PV1 PV2
Cooling fans alarm relay contact.
Available on DCREG MODULAR.S only To be introduced in external sequence for any alarm signal
1F 2F
Internal ultrafast fuses micro­switches series.
Available on DCREG MODULAR.S only To be introduced in external sequence for any alarm signal
42 44
Input for control section from 24 Vdc direct voltage. Positive potential on terminal 44 compared to terminal 42.
Decisive voltage class A according to EN 61800-5-1 24 Vdc, 1.8A max (screw torque: 0.5 Nm / 4.4 lb/in)
51-52 (AV1-
AV2)
Single-phase alternating voltage input for cooling fans power supply. Note: not available for DCREG Size 1-2.
Decisive voltage class C according to EN 61800-5-1 DCREG Size 2A: 230 Vac, 1.5 A DCREG MODULAR.S: 230 Vac, 1.3 A max (See Note (1) below)
53 54
Input for control section power supply from single-phase alternating voltage.
Decisive voltage class C according to EN 61800-5-1 Standard 380 … 500V ac. (See Note (2) below) (screw torque: 0.40.6 Nm / 3.5-5.3 lb/in) (See Note (1) below)
55 56 57
Input for synchronizing phases from TS transformer secondary. N.B.: terminals available on DCREG Size 1 ... 2A only, for supply mains higher than 500 Vac.
Decisive voltage class C according to EN 61800-5-1 500 Vac max (See Note (1) below)
NOTE
Whenever requested, it is recommended to use ULTRAFAST FUSES of the same type and value indicated in the RATINGS tables, so as to avoid possible damages of the converter.
NOTE
Always install a three-phase remote control switch on the A.C. side, together with a suitable NO auxiliary contact directly in the terminal 24 (ENABLE) series, as indicated in the SIGNAL CONNECTIONS diagram. Do not connect other single-phase or three-phase loads in parallel to bars L1, L2, L3, since the remote control switch should only supply the above mentioned bars through the three-phase impedance.
NOTE
DO NOT OPEN the remote control switch during the braking phase with regeneration towards the mains.
NOTE
To optimise the rotation stability on a DCREG4-type converter, it is recommended to disable the possible STABILIZATION SERIES which has been fit on the motor winding.
Size
DCREG2 DCREG4
Model
Eyelet terminal
Screw
torque
Cable Cross-section to
AC and DC Side
Ultrafast fuses
AC Side
Ultrafast fuses
DC Side
AC1
Contactor
AC Side
Nm / lb/in
mm2
(AWG/kcmils)
A
A
A (model)
1
.10
M8
16 / 142
2.5 (12AWG)
See RATINGS
tables
See RATINGS
tables
25 (AF09)
.20
4 (10AWG)
25 (AF09)
.40
10 (6AWG)
50 (AF30)
.70
25 (4AWG)
100 (AF52)
.100
50 (1/0AWG)
125 (AF80)
.150
70 (2/0AWG)
200 (AF140)
.180
95 (4/0AWG)
225 (AF146)
.250
120 (250kcmils)
275 (AF190)
.350
2x120 (2x250kcmils)
400 (AF265)
2
.410
M10
25 / 221
2x120 (2x250kcmils)
500 (AF305)
.500
2x185 (2x350kcmils)
600 (AF400)
.600
2x240 (2x500kcmils)
700 (AF460)
.900
3x240 (3x500kcmils)
1050 (AF750)
2A
.1200
M12
40 / 354
4x240 (4x500kcmils)
1650 (AF1650)
CAUTION
Always use the correct cable cross-sections and activate the protective devices provided for DCREG. Failure to do so will cause the non­compliance to standard regulations of the system where the DCREG is installed.
CAUTION
Additional UL requirements: for the North American market, a 600 Vac cable is accepted for up to 500 Vac. A 1000 Vac cable is required above 500 Vac (below 600 Vac). The power cables must be rated for 75 °C (167 °F).
NOTE
For details on wiring and safety devices for a DCREG MODULAR.S please contact Elettronica Santerno.
Drive size
INDUCTANCE
L2 @ 500V TYPE
INDUCTANCE
L2 @ 600-690V TYPE
INDUCTANCE
L4 TYPE
P/N
P/N
P/N
DCREG.10
IM0126004 - 2000H
IM0127004 - 3451H
3 x IM0100354 - 150H
DCREG.20
IM0126044 - 1273H
IM0127044 - 2196H
3 x IM0100354 - 150H
DCREG.40
IM0126084 - 700H
IM0127084 - 1208H
3 x IM0100354 - 150H
DCREG.70
IM0126164 - 239H
IM0127164 - 412H
IM0122104 - 45H
DCREG.100
IM0126164 - 239H
IM0127164 - 412H
IM0122154 - 30H
DCREG.150
IM0126204 - 156H
IM0127204 - 268H
IM0122154 - 30H
DCREG.180
IM0126244 - 88H
IM0127244 - 151H
IM0122204 - 20H
DCREG.250
IM0126244 - 88H
IM0127244 - 151H
IM0122254 - 15H
DCREG.350
IM0126284 - 61H
IM0127284 - 105H
IM0122304 - 10H
DCREG.410
IM0126284 - 61H
IM0127284 - 105H
IM0122304 - 10H
DCREG.500
IM0126324 - 54H
IM0127324 - 93H
IM0122404 - 6.2H
DCREG.600
IM0126364 - 33H
IM0127364 - 58H
IM0122404 - 6.2H
DCREG.750
-
IM0127364 - 58H
IM0122504 - 4.5H
DCREG.900
IM0126404 - 23H
IM0127404 - 40H
IM0122504 - 4.5H
DCREG.1050
-
IM0127404 - 40H
IM0122604 - 3H
DCREG.1200
IM0126404 - 23H
-
IM0122604 - 3H
DCREG.1250
-
IM0127444 - 30H
IM0122604 - 3H
DCREG.1400
IM0126444 - 18H
-
IM0122704 - 2.5H
DCREG.1600
IM0126444 - 18H
IM0127444 - 30H
IM0122704 - 2.5H
DCREG.1800
IM0126484 - 11H
IM0127484 - 18H
IM0122804 - 1.6H
DCREG.2000
IM0126484 - 11H
IM0127484 - 18H
IM0122804 - 1.6H
DCREG.2300
IM0126484 - 11H
IM0127484 - 18H
IM0122804 - 1.6H
DCREG.2500
IM0126484 - 11H
IM0127484 - 18H
IM0122804 - 1.6H
DCREG.2700
IM0126524 - 8H
IM0127524 - 13H
IM0122904 - 1.1H
DCREG.3000
IM0126524 - 8H
IM0127524 - 13H
IM0122904 - 1.1H
DCREG.3500
IM0126524 - 8H
IM0127524 - 13H
IM0122904 - 1.1H
DCREG.4500 - -
-
NOTE
Listed Class CC fuses are provided in the supply line to control card and field supply terminals. Fuse ratings shall be as indicated below:
Control Card Supply Fuses – maximum 1 A, minimum 500 Vac. Field Supply Fuses – maximum 20 A, minimum 500 Vac.
DCREG Model
UL-approved Fuses Manufactured by:
SIBA Sicherungen-Bau GmbH
(200 kA
RMS
Symmetrical A.I.C.)
Bussmann Div Cooper (UK) Ltd
(100/200 kA
RMS
Symmetrical A.I.C.)
Mod. No.
Ratings
Mod. No.
Ratings
Current
Arms
Voltage Vac
Current
Arms
Voltage
Vac
DCREG.10
50 154 06.20
20
700
170M1410
20
700
DCREG.20
50 154 06.20
20
170M1410
20
DCREG.40
20 412 20.40
40
170M1413
40
DCREG.70
20 412 20.80
80
170M1416
80
DCREG.100
20 412 20.100
100
170M2664
100
DCREG.150
20 412 20.160
160
170M2666
160
DCREG.180
20 412 20.160
160
170M2666
160
DCREG.250
20 412 20.250
250
170M2668
250
DCREG.350
20 412 20.315
315
170M2669
315
Model
Input
Output
DCREG2
max
Voltage
[Vac]
Current
[A]
max
Voltage
[Vdc]
Current
[A]
max
Power
[kW]
max
Power
[HP]
SCCR
[kA rms]
.10
500
8.2
600
10
6
8.0
5
.20
16.4
20
12
16.1
.40
33
40
24
32.2
.70
57
70
42
56.3
10
.100
82
100
60
80.5
.150
123
150
90
120.7
.180
148
180
108
144.8
.250
205
250
150
201.2
18
.350
287
350
210
281.6
DCREG4
max
Voltage
[Vac]
Current
[A]
max
Voltage
[Vdc]
Current
[A]
max
Power
[kW]
max
Power
[HP]
SCCR
[kA rms]
.10
500
8.2
520
10
5.2
7.0
5
.20
16.4
20
10.4
13.9
.40
33
40
20.8
27.9
.70
57
70
36.4
48.8
.100
82
100
52
69.7
10
.150
123
150
78
104.6
.180
148
180
93.6
125.5
.250
205
250
130
174.3
.350
287
350
182
244.1
18
Model
Input
Output
DCREG2
max
Voltage
[Vac]
Current
[A]
max
Voltage
[Vdc]
Current
[A]
max
Power
[kW]
max
Power
[HP]
SCCR
[kA rms]
.10
600
8.2
720
10
7.2
9.7
5
.20
16.4
20
14.4
19.3
.40
33
40
28.8
38.6
.70
57
70
50.4
67.6
10
.100
82
100
72
96.6
.150
123
150
108
144.8
.180
148
180
129.6
173.8
.250
205
250
180
241.4
18
.350
287
350
252
337.9
DCREG4
max
Voltage
[Vac]
Current
[A]
max
Voltage
[Vdc]
Current
[A]
max
Power
[kW]
max
Power
[HP]
SCCR
[kA rms]
.10
600
8.2
630
10
6.3
8.4
5
.20
16.4
20
12.6
16.9
.40
33
40
25.2
33.8
.70
57
70
44.1
59.1
10
.100
82
100
63
84.5
.150
123
150
94.5
126.7
.180
148
180
113.4
152.1
.250
205
250
157.5
211.2
18
.350
287
350
220.5
295.7
DANGER
Always connect the converter grounding terminal to the grid grounding using a conductor complying with the safety regulations in force (see table below). Always connect the motor casing to the converter grounding to avoid dangerous voltage peaks and electric shock hazard. Always provide a proper grounding of the converter frame and the motor casing.
DANGER
The touch current in the ground protective conductor exceeds 3.5 mAac/10 mAdc. Please refer to the table below for the dimensioning of the protective conductors.
NOTE
To fulfil UL conformity requirements of the system where the converter is installed,
use a “UL R/C” or “UL Listed” lug to connect the converter to the grounding
system. Use a loop lug fitting the ground screw and having the same cross-section as the ground cable being used.
Cross-sectional area of phase
conductors
of the converter (mm2)
Minimum cross-sectional area of the
corresponding
protective earthing conductor (mm2)
S ≤ 10
10 (*)
10 < S ≤ 16
S (*)
16 < S ≤ 35
16
35 < S
S/2
NOTE
The values in the table above are valid only if the protective earthing conductor is made of the same metal as the phase conductors. If this is not so, the cross-sectional area of the protective earthing conductor shall be determined in a manner which produces a conductance equivalent to that which results from the application of the table above.
NOTE (*)
In any case, a cross-section of the protective earthing conductor of at least 10 mm
2
Cu or 16 mm2 Al is required to maintain safety in case of damage to or
disconnection of the protective earthing conductor (refer to EN 61800-5-1 about Touch current).
DCREG2: for
standard usage, supply the potentiometer between term. 1 and 2
TERM.
Description
I/O Ratings
1
+10V: +10V reference voltage output for analog inputs.
+10 Vdc / 10 mA max
2
0V: Zerovolt.
-
3
-10V: -10V reference voltage output for analog inputs.
-10 Vdc / 10 mA max
4
n OUT: Speed signal output for tachometer or any other use. Positive
polarity with bridge A running (not in regenerative state). The value 10V corresponds to the max. speed (voltage) feedback signal, i.e. parameter M001 (nFdbk) is equal to 100%. If the drive is in armature feedback mode, this output is not enabled.
-10 … +10 Vdc 5 mA max
5-7
REF: Main analog input (5: REF+ / 7: REF-).
If both signal wires are connected, the two terminals represent a differential input with a high rejection to interferences. Alternatively, with a signal to be reflected to the drive 0V, the two terminals represent a common mode input. This common mode input is a non-reversing input if the signal “hot wire” is connected to terminal 5 when terminal 7 is disconnected, whereas it is a reversing input if it is connected to terminal 7 when terminal 5 is disconnected. By setting jumper JP407 in the control board on pos. 2-3, the two terminals will represent an input for a signal expressed in milliAmperes: a positive reference is generated if the current enters terminal 5 and goes out through terminal 7. See also the MILLIAMPERE INPUT / OUTPUT SIGNALS chapter.
JP407 on pos. 1-2:
-10 … +10 Vdc Rin = 20 k
JP407 on pos. 2-3: 20 mA max Rin = 200
6
I OUT: Current signal output (filtered) for possible ammeter, or different use.
Positive polarity with bridge A in operation. The value is 6.67V according to the rated current of the drive (i.e. 100A for a DCREG.100). In case of a DCREG4, the mentioned signal can be set as bipolar or unipolar by means of the parameter P156 (IOutPol).
-10 ... +10 Vdc
8
OUT 1: Analog output 1 to be configured with parameter P150
(AnOut1Cfg). By setting jumper JP4010 in the control board on pos. 1-2, the terminal will represent an output for a voltage signal, while when the jumper is set on pos. 2-3, the term inal will represent an output f or a s ignal expressed in milliAmperes. An outgoing current only may be produced towards 0V potential. See also the MILLIAMPERE INPUT / OUTPUT SIGNALS chapter.
JP4010 on pos. 1-2:
-10 ... +10 Vdc 5 mA max
JP4010 on pos. 2-3: 0 ... 20 mA 10 V max
9
0V: Zerovolt.
-
10
OUT 2: Analog output 2 to be configured through parameter P153 (AnOut2Cfg).
By setting jumper JP409 in the control board on pos. 1-2, the terminal will represent an output for a voltage signal, while when the jumper is set on pos. 2-3, the terminal will represent an output for a signal expressed in milliAmperes. An outgoing current only may be produced towards 0V potential. See also the MILLIAMPERE INPUT / OUTPUT SIGNALS chapter.
JP409 on pos. 1-2:
-10 ... +10 Vdc 5 mA max
JP409 on pos. 2-3: 0 ... 20 mA 10 V max
11-13
IN 1: Analog input 1 (11: IN 1+ / 13: IN 1-) to be configured through
parameter C120 (AnIn1Cfg). If both signal wires are connected, the two terminals represent a differential input with a high rejection to interferences. Alternatively, with a signal to be reflected to the drive 0V, the two terminals represent a common mode input. This common mode input is a non-
reversing input if the signal “hot wire” is connected to terminal 11 when
terminal 13 is disconnected, whereas it is a reversing input if it is connected to terminal 13 when terminal 11 is disconnected. By setting jumper JP408 in the control board on pos. 2-3, the two terminals will represent an input for a signal expressed in Milliamperes: a positive reference is generated if the current enters terminal 11 and goes out through terminal 13. See also the MILLIAMPERE INPUT / OUTPUT SIGNALS chapter.
JP408 on pos. 1-2:
-10 … +10 Vdc Rin = 20 k
JP408 on pos. 2-3: 20 mA max Rin = 200
TERM.
Description
I/O Ratings
12
CH N: Zero position pulse of the enP/Nr.
-
14
CH A: Channel A of the enP/Nr.
102.4 k Hz max
15
+5V: +5V mains supply voltage for the enP/Nr. It is optoinsulated from the 0V
signal of analog inputs.
+5 Vdc 160 mA max
16
CH B: Channel B of the enP/Nr.
102.4 k Hz max
17
IN 2: Analog input 2 to be configured through parameter C121(AnIn2Cfg).
-10 … +10 Vdc 20 mA max Rin = 20 k
18
0V: Zerovolt.
-
19
IN 3: Analog input 3 to be configured through parameter C122 (AnIn3Cfg).
-10 … +10 Vdc Rin = 20 k
20
DT 25Vmax: Input for a tacho when it does not exceed the absolute value
equal to 25V. Polarity has to be a positive one with bridge A running (not in a regenerative state).
-25 … +25 Vdc Rin 5 k
21
0V: Zerovolt.
-
22
DT 80Vmax: Input for a tacho when it does not exceed the absolute value
equal to 80V. Polarity has to be a positive one with bridge A running (not in a regenerative state). Decisive voltage class B according to EN 61800-5-1
-80 … +80 Vdc Rin 80 k
23
DT 250Vmax: Input for a tacho when it does not exceed the absolute value
equal to 250V. Polarity has to be a positive one with bridge A running (not in a regenerative state). Decisive voltage class C according to EN 61800-5-1
-250 … +250 Vdc Rin 300 k
24
ENABLE: Drive operation command enabling. The signal is active when the
terminal is short-circuited with +24V (terminal 40). The contact related to this terminal, shown in the SIGNAL CONNECTIONS diagram, consists of a NO auxiliary contact of contactor KM energizing the drive power section. See Note (*).
Iin 9 mA
25-27
MDO 1: Digital output 1 to be configured through parameter P170 (MDO1Cfg).
Default configuration: 0:Drive OK. Decisive voltage class C according to EN 61800-5-1
5A / 250 Vac 5A / 30 Vdc
26
START: Enabling of the speed / voltage references or current references to be
found on analog inputs REF, IN 1, IN 2, IN 3 (summed up to the reference from serial connection, field bus and UpDownRef internal variable), or enabling of one of the run preset references. The signal is active when the terminal is short-circuited with +24V (terminal 40). When the contact on terminal 26 opens, a ramp down is set starting from the current speed / voltage signal. The ramp down time is set in parameter P034 or P035. See RAMPS OVER REFERENCE chapter for the inequality relations assuring that the times set for the stop ramps in par. P034 and P035 are exactly respected.
Iin 9 mA
28
MDI 1: Digital input 1 to be configured through parameter C130 (MDI1Cfg).
Default configuration: 0:Reset.
Iin 9 mA
29-31
MDO 2: Digital output 2 to be configured through parameter P176 (MDO2Cfg).
Default configuration: 1:SpeedThreshold. Decisive voltage class C according to EN 61800-5-1
5A / 250 Vac 5A / 30 Vdc
30
MDI 2: Digital input 2 to be configured through parameter C131 (MDI2Cfg).
Default configuration: 12:JogA.
Iin 9 mA
32
MDI 3: Digital input 3 to be configured through parameter C132 (MDI3Cfg).
Default configuration: 13:JogB.
Iin 9 mA
33-35
MDO 3: Digital output 3 to be configured through parameter P182 (MDO3Cfg).
Default configuration: 2:Iarm Threshold. Decisive voltage class C according to EN 61800-5-1
5A / 250 Vac 5A / 30 Vdc
34
MDI 4: Digital input 4 to be configured through parameter C133 (MDI4Cfg).
Default configuration: 1:Preset Speed A.
Iin 9 mA
TERM.
Description
I/O Ratings
36
MDI 5: Digital input 5 to be configured through parameter C134 (MDI5Cfg).
Default configuration: 4:Clim.
Iin 9 mA
37-39
MDO 4: Digital output 4 to be configured through parameter P188 (MDO4Cfg).
Default configuration: 5:Drive Running. Decisive voltage class C according to EN 61800-5-1
5A / 250 Vac 5A / 30 Vdc
38
MDI 6: Digital input 6 to be configured through parameter C135 (MDI6Cfg).
Default configuration: 5:Reverse.
Iin 9 mA
40
+24V (OPTO): +24V main voltage supply output for digital inputs operation
and/or to supply the enP/Nr. It is optoinsulated from the 0V signal of analog inputs.
+24 Vdc 200 mA max
41-43
MDO 5: Digital output 5 to be configured through parameter P194 (MDO5Cfg).
Default configuration: 4:CurrLimitation. Decisive voltage class C according to EN 61800-5-1
5A / 250 Vac 5A / 30 Vdc
42
0V(OPTO): Negative terminal of +24V external supply voltage (if any) to supply
the control section and/or the enP/Nr. It is optoinsulated from the 0V signal of analog inputs. If the digital inputs come from the static outputs of a PLC, 0V of the PLC is to be connected to this terminal.
-
44
+24V(EXT): Input for positive terminal of +24V external supply voltage to supply
the control section.
+24 Vdc / 2 A max
60
/
max
max
nrevpulses
f
100
10
100
)1(Re
BiasGain
VAnInfTerm
RL
Iin M014 (M010)
Jumper JP407
in the control board
in pos. 2-3
Jumper JP408
in the control board
in pos. 2-3
REF [Terminals 5 / 7]
Speed / voltage reference
REF [Terminals 5 / 7]
Armature current reference
IN 1 [Terminals 11 / 13]
Gain
Bias
Gain
Bias
Gain
Bias
0...20mA 0...+100%
P122=250%
P121=0%
P125=250%
P124=0%
P128=250%
P127=0%
0...20mA –100%...+100%
P122=500%
P121=–100%
P125=500%
P124=–100%
P128=500%
P127=–100%
4...20mA 0...+100%
P122=312.5%
P121=–25%
P125=312.5%
P124=–25%
P128=312.5%
P127=–25%
4...20mA –100%...+100%
P122=625%
P121=–150%
P125=625%
P124=–150%
P128=625%
P127=–150%
100
10
100
BiasGain
VAnOut
out
V
out
I
out
Jumper JP4010
in the control board
in pos. 2-3
Jumper JP409
in the control board
in pos. 2-3
OUT 1 [Terminal 8]
OUT 2 [Terminal 10]
Gain
Bias
Gain
Bias
0 ... 10V 0 ... 20mA
P152 = 100%
P151 = 0%
P155 = 100%
P154 = 0%
0 ... 10V 4 ... 20mA
P152 = 80%
P151 = 20%
P155 = 80%
P154 = 20%
10 ... +10V 0 ... 20mA
P152 = 50%
P151 = 50%
P155 = 50%
P154 = 50%
10 ... +10V 4 ... 20mA
P152 = 40%
P151 = 60%
P155 = 40%
P154 = 60%
NOTE
The keypad is not series installed on the drive and is to be delivered separately. The remotable keypad kit is to be ordered for the keypad assembly on a separate panel: see the REMOTABLE KEYPAD chapter.
REVERSE
FORWARD
NOTE
When operating, the drive uses the current parameter set, i.e. the parameters available at the moment. The parameter that has been updated with the “
” and “” keys will be immediately used instead of the previous parameter, even if it is not saved with the “SAVE” key. The new value will not obviously be
stored when the drive is turned off.
WARNING
the reference polarity indication supplied by LEDs REF, FORWARD and REVERSE when the drive is not yet running, do not consider any additional speed or current references.
P010 nFdbkMax 3000 RPM
Vref 14.5 % ****
Drive OK – D5.01 DCREG4.100 P440
P000 Key 1:Program Enable
current page
Key page
Keypad page
Status page
SA
REVERSE
FORWARD
WARNING
Before following the instructions below, turn off the equipment to avoid damaging it.
WARNING
Never press the CPU RESET key if the machine is running.
NOTE
Whenever two different sets of speed loop adjusting parameters have been considered through one of the MDIx configurable digital inputs being set at value 8:Second ParmSet, then the speed automatic tuning calculates the parameters relating to one of the two sets according to the state of the above mentioned digital input.
NOTE
The following inequality is to be verified between the ramp times programmed in parameter P030 ... P033 and the initial/final rounding times programmed in
parameters P038, P039:
)033)(032)(031(030
2
039
2
038PPP
NOTE
As the figure shows, for each ramp transient (rise ramp or fall ramp transient), the duration of the ramp really set is equal to the addition of the time programmed in the relevant parameter, of half the initial rounding time and half the final rounding time.
NOTE
In order to exactly respect the time set for the stop ramps in par. P034 and P035, the following equality relations are to be correct:
10
035
033 ;
10
034
031
P
P
P
P
.
0
)(lim
nn
c
BAI
n
I lim A(B)
k • P050(51)
k • P052(53)
k • P055
P010
P010 P057
P010 P054
n0
P010 P056
(k=C000 Imax[T2])
055050
057055056050
;
055050
)056057(055050
0
PP
PPPP
n
PP
PPPP
c
Loading...