Sangamo Q550, Q551, Q553 Installation Instructions

Fit & forget...
Q550, Q551 & Q553
User Instructions
Introduction
These installation and user instructions cover all solar variants in the Q550 series - a range of reliable and highly accurate 24-hour solar dial time switches which offer, according to
the specic model, a range of features suited
to individual applications.
See quick reference chart later.
1. The installation of this time switch should
be carried out by a qualied electrician
in accordance with current IEE wiring regulations.
2. Sangamo cannot be held responsible or liable for circuit connection other than those directly associated with our products.
3. To comply with safety requirements it is recommended that the time switch be installed with the base provided.
4. Terminals are for xed wiring only. Provision must be made in the xed wiring
for a means of disconnection from the supply having a contact separation of at least 3mm on all poles.
5. The time switch must be earthed.
6. This product is suitable for ‘Ordinary’ conditions only. It is not protected against dripping or moisture and so should be housed in a suitable IP rated enclosure.
7. DO NOT REMOVE THE 2 SCREWS AT
REAR OF SWITCH BASE.
8. Rotate cover anticlockwise and lift clear.
9. Remove extended terminal cover (E) by unscrewing captive screw (F).
10. Withdraw plug-in mechanism from switch
base, by grasping & pulling rmly on the dial.
11. Clear plastic from three xing holes
provided, removing debris. a. Use no8 wood screws or 2BA countersunk
screws for xing. b. Fix with suitable wall plugs for the surface
intended. c. When mounting the time switch on a metal surface, ensure the metal is adequately earthed to cover the 20A rating in accordance with IEE Regulations.
12. Strip back insulation by 6mm to ensure satisfactory connection with terminals. Connect switch to supply and load as in wiring diagrams above.
13. For Q553 - WHERE SEPARATE MOTOR
& SWITCH CIRCUIT SUPPLIES ARE NOT AVAILABLE - FIT A LINK BETWEEN TERMINALS 1 & 3.
Q550 Q551
Q553
14. Connect earth lead to earth connection
(T).
15. Plug mechanism into base.
16. Cut & trim breakouts in the extended terminal cover (E) as necessary if wiring routed on the surface. Ret extended terminal cover (E) to base using captive screw (F). This will lock the mechanism inside
the base.
17. Follow setting instructions for the time switch then ret cover.
Setting a Solar Dial
This type of dial automatically adjusts, once set, for seasonal changes in sunset and sunrise time during the year to suit lighting
applications. Depending on the model , xed
operations can also be set.
1. Remove dial screw (B) and pull dial free
from the mechanism. This makes adjustment easier.
2. DO NOT LOOSEN SERRATED CENTRE
NUT.
3. Turn date wheel (D) in either direction,
until correct calendar position is indicated in
date aperture (C). Each month is subdivided into six equal divisions, representing 5 days.
4. Sunset On & Sunrise Off operating arms
(K) & (A) each have an operating pin at the
center point. This center point equates to the
Greenwich Meridian (or 0° Longitude)
location in the country.
5. Adjustment for longitudinal variation can
be made by moving the operating pins (N)
along the slot on BOTH operating arms (K) & (A), up to a maximum of +/- 45mins from
center. To assist setting, each slot is marked with 15 minute divisions.
Locations EAST of Greenwich Meridian – move pins ANTI-CLOCKWISE. Locations WEST of Greenwich Meridian – move pins CLOCKWISE. (see zone map later)
6. Further adjustment to advance the Sunset ON and delay the Sunrise OFF settings and increase the overall ON time to suit darker
environment applications, i.e. Stairwells, may
be possible.(Depending on the longitudinal variation used). Move operating pin (N) along
each operating arm as follows.
ADVANCE – move pin ANTI -CLOCKWISE on the Sunset ON operating arm (K). DELAY – move pin CLOCKWISE on the Sunrise OFF operating arm (A).
7. Ret dial onto mechanism ensuring dial hub engages cross-pin on center shaft. Ret dial screw (B) . Turn dial in direction of the
arrow until pointer P indicates correct time.
8. DIAL SHOULD RUN SET TO WINTERTIME
THROUGHOUT THE YEAR.
Fixed off between 20:30 & 01:00
1. Remove dial screw (B) and pull dial free
from the mechanism. This makes adjustment easier.
2. DO NOT LOOSEN SERRATED CENTRE
NUT.
3. Models Q551.14 & Q553.14 - (DEFAULT 24:00) - Move Pin already tted on Midnight Bridge (S) to required setting.
4. Models Q550.13, Q551.13 & Q553.13 -
Transfer Pin (N) to Midnight Bridge (S). Unscrew & Transfer the Operating pin (N) from operating arm (A) onto the midnight bridge (S), to enable a xed off to be set as an
alternative to sunrise.
Note orientation of Operating pin prior to
transfer & ensure when re-positioned it is
securely xed using screw and will operate
the outer lever mechanism.
5. Midnight bridge (S) is calibrated in 15
minute intervals. Set Operating Pin at any time between 20.30 & 01.00, however see point 6.
6. For correct unadjusted all year operation of the Sunset operating arm (K) and the xed
off on the midnight bridge (S), the xed off should be set after 22.30. Fixed off’s set prior
to this will interfere with sunset operating
arm (K) during April – September and cause
the switch to operate for a short period when not required.
7. Ret dial onto mechanism ensuring dial hub engages cross-pin on centre shaft. Ret dial screw (B) . Turn dial in direction of the arrow until pointer (P) indicates WINTERTIME
(GMT).
8. All xed times need to be adjusted for the winter/summer clock changes to be uniform
during the year.
March – Move time setting back, i.e. 24:00 to
23:00
October – Move time setting forward, i.e.
23:00 to 24:00
Fixed early on 03:15 & 08:30
Models Q551.14 & Q553.14 (DEFAULT 05:00)
1. The adjustment is made to the rear of the
solar dial. Remove dial screw (B) and pull dial
free from the mechanism to gain access.
2. DO NOT LOOSEN SERRATED CENTRE
NUT
3. Slacken 8BA nut on underside of sector bridge and move spring tensioned lever 2, along sector bridge 1, until slot 4 coincides with time required. The Sector bridge is calibrated in 15 minutes intervals. Tighten 8BA nut.
4. Ret dial onto mechanism ensuring dial hub engages cross-pin on centre shaft. Ret dial screw (B) . Turn dial in the direction of the arrow until pointer (P) indicates
WINTERTIME(GMT).
5. Fixed operation will be obtained at the time set except in summer where the sunrise operating arm (A) operates earlier.
6. All xed times need to be adjusted for the winter/summer clock changes to be uniform
during the year.
March – Move time setting back, i.e. 05:00 to
04:00
October – Move time setting forward, i.e.
04:00 to 05:00
Setting Day Omit Device
Model Q550.13
1. Day omitting device (D) prevents ‘On’
operation occurring on a chosen day or days of the week.
2. To OMIT operations on a given day, turn insert 1 clockwise on a given day , with a
screwdriver, until ARROWHEAD POINTS
OUTWARDS.
4. Ensure dial is showing the correct time.
Note the position of the operating arm (K) which operates the day omitting device (D)
once every 24 hours. If this operating arm has
PASSED the Day omitting device (D) – turn black disc so the CURRENT day is set. If this operating arm (K) has NOT REACHED the Day omitting device (D) – turn black disc to the PRECEDING current day.
Quick Reference Chart
Model Dial Day Omit Base Pins Switch Type Specics Max Ops
Q550.13 Astro Suntracker ON 3 SPST 2
Q551.13 Astro Suntracker 3 SPST 2
Q551.14 Astro Suntracker 3 SPST Fixed On & Off 4
Q553.13 Astro Suntracker 4 SPST 2
Q553.14 Astro Suntracker 4 SPST Fixed On & Off 4
Specication
Current, Voltage, Frequency As shown on product label
Ambient Temperature 0 - 50°C
Live Parts Enclosed
Shock Protection Class 1
Dirt & Moisture Protection IP20
Contacts Micro-Disconnection
Battery Reserve 100 Hours (fully charged). NiMH rechargeable cell.
The battery is soldered into a PCB. After the battery’s
expectant life of 10 years the timeswitch will cease to
operate or run slow, depending on the environment. A battery replacement kit is available to order.
Cycle/Channel 24 Hour/1 Channel
Summer /Winter Time Change Not required, set dial to Wintertime (GMT). Note: any xed
times must be adjusted to be uniform throughout the year.
Clock Accuracy -/+ 5mins per year @23°C (Quartz)
Max Cable Size 6.0mm²
Power Consumption 0.6W
Noise A perpetual ticking noise is produced as internally a stepper
motor drives the gear train
Latitude Zones & Longitude Adjustment
CLOCKWISE
ANTI-CLOCKWISE
SERVICE AND WARRANTY
Your product is not user serviceable. PLEASE DO NOT TRY TO DISMANTLE THE UNIT. This product is guaranteed by your supplier for 5 years from the date of manufacture. If it should become defective
please contact your installer or supplier for a replacement unit or visit www.sangamo.co.uk/returns
This product must meet Waste Electronic and Electrical Equipment Regulations (WEEE) for suitable environmental recycling, recovery and/or disposal. End of life products should be handled in line with local regulations.
Alternatively return end of life product to Sangamo for correct disposal.
CUSTOMER CARE POLICY
As part of Sangamo’s continuous improvement program, the company operates a Customer Care policy. This means we welcome your comments and complaints, as it can help us to improve our services to you, our customer.
Due to our policy of continuous product improvement and development, the specications in this guide may be
subject to change without prior notice.
143700 B
Industrial Estate, Port Glasgow,
Sangamo Limited
Renfrewshire, PA14 5XG
United Kingdom
Tel +44 (0) 1475 745 131
Email: enquiries@sangamo.co.uk
Web: www.sangamo.co.uk
WEE/JH0069TY
Loading...