2. Input setpoint
2-1. Function of setpoint key
2-2. Parameter
3. Block of basic processing
4. Operation & Setup
4-1. Program stop
4-2. Program run
4-3. Fix stop
4-4. Fix run
5. Main
5-1. Function
5-2. Reserve
5-3. Graph
5-4. Program
5-4-1. Pattern
5-4-2. Repeat
5-4-3. File edit
5-4-4. TS(Time signal)
5-4-5. Wait
5-4-6. Test name
5-5. LCD Light
5-6. Setup
5-6-1. Input
5-6-2. OUTPUT
5-6-3. IS(Inner signal)
5-6-4. PID Setting
5-6-4-1. Temp PID
5-6-4-2. HUMI PID
5-6-4-3. PID Group(PID1 ~9)
5-6-5. Do Config
5-6-6. Alarm
5-6-7. Comm
5-6-8. Display(Password/Language/Company Info)
5-7. Setup Password
6. Trouble
II - 1
II - 1
II - 1
II - 1
II - 2
II - 2
II - 2
II - 3
II - 4
II - 4
II - 5
II - 6
II - 6
II - 7
II - 7
II - 9
II - 10
II - 11
II - 12
II - 15
II - 17
II - 18
II - 20
II - 21
II - 21
II - 22
II - 23
II - 26
II - 27
II - 27
II - 29
II - 30
II - 31
II - 33
II - 34
II - 35
II - 35
III - 3
III - 3
III - 4
III - 4
III - 5
III - 6
III - 7
III - 8
III - 9
III - 10
4. D-REGISTER
4-1. Process
4-2. Functions
4-3. Reservation
4-4. IS & Alarm
5. Set program pattern
5-1. Program
5-2. Reading program pattern
5-3. Writing program pattern
5-4. Pattern copy/delete & segment insert/delete
5-5. PTTN_INFO
D-REGISTER DETAIL
III - 11
III - 12
III - 14
III - 15
III - 16
III - 17
III - 17
III - 18
III - 18
III - 19
III - 20
IM TEMI550E_C 2nd Edition: Sep. 1. 2003. 3/3
I. INSTALLATION
1. Introductions and Power Unit
Thank you for purchasing our Industrial Controller.
This manual explains suitable effective way of using and installing this product.
Please read carefully to apply it to controller of environmental chamber or others.
1-1. Introduction
Regarding This Document
(1) Keep the manual for the last user who can get easy access to the manual.
(2) Make sure read this manual carefully and fully understand how to operate this product.
(3) This manual is intended to describe the functions of this product.
Samwontech Co., Ltd.(hereinafter simply referred to as We) does not guarantee the application
of these functions for any particular purpose.
(4) Redistribution & use this manual, with or without modification, are prohibited.
(5) The contents of this manual are subject to change without prior notice.
(6) Every effort has been made to ensure accuracy in the preparation of this manual. However,
should any errors be found or important information be omitted, please contact your nearest our
representative or our sales office.
Regarding Protection, Safety and Prohibition
(1) In the interest of protecting and ensuring the safety of this product and the system, which is
controlled by this product, ensure that all instructions and precautions and precautions in this
manual relating to safety are strictly adhered to in the use of this product.
(2) Take note that if you handle the product in contradiction to these instructions, we does not
guarantee safety.
(3) If s eparate protection and/or sa fety circuits are to b e installed for this product or the s ystem, whic h
is controlled by this product, ensure that such circuits are installed external to the product.
(4) When you replace parts or consumables of the product, use those specified by us.
Limited WARRANTY
(1) We makes no warranties regarding the product except those mentioned in the WARRANTY.
(2) In cases where the use of this product results in damage or loss to the user or a third party, we will
not be responsible for any incidental or consequential damage or loss, or any damage or loss
suffered by the user or third party resulting from a defect or defects in this product which could not
be foreseen by us.
IM TEMI 770E_C 2nd Edition: Sep. 1. 2003. 1/15
Warranty Policy
(1) Warranty term is 1year parts and labor. We make warranties
regarding the product only those mentioned in the WARRANTY.
(2) A/S is needed actual expenses, after warranty period.
(3) Regarding Force Majeure
This warranty does not cover damage due to loss password, accident,
fire, flood and/or other acts of God; misuse, instability, improper
installation, improper or unauthorized repairs, commercial adjustments
which are explained in the instruction manual are not covered under the
terms of this warranty. This warranty will automatically be voided
for any unit found with a missing or altered serial number.
(4) All warranty repairs must be performed by a our authorized service center.
Symbols Used in This Manual The symbols used in this user manual have the following meanings:
I. INSTALLATION
(1) or
These symbols are used for danger or warning.
(1) Product : Indicates an imminently hazardous situation which,
if not avoided will result in serious injury or out of order.
(2) User manual : Indicates an imminently hazardous situation which,
if not avoided, will result in serious injury or death.
(2)
Ground
This symbol indicates that the terminal must be connected to ground prior
to operation of equipment.
(3) or
Draws attention to information essential for understanding the operation and features.
(4) ☞
See also
Gives the reference locations for further information on the topic.
1-2. Power Unit
Power supply voltage rating ; 100-240VAC, Max 0.1A, 50/60Hz
Power consumption : Max 18W, Max 22VA.
Mains supply voltage fluctuations : 100-240VAC(±10%)
IM TEMI 770E_C 2nd Edition: Sep. 1. 2003. 2/15
I. INSTALLATION
2. Package checklist
Check the following when removing the controller from its package. Check the contents of the
package against the Package List to make sure that all accessories are included in the package.
2-1. Model and suffix codes
Check the controller for any apparent physical damage.
Check point : Model number which is located right side of box and left side of controller.
MODEL OPTION DESCRIPTIONS
1 Standard I/O Board(10Points)
TEMI 770 –
TEMI 570 –
TEMI 550N –
2 Additional I/O Board(10Points)
0 RS232C
1 RS485
☞ (Ex) Standard is TEMI 770-10(Standard I/O Board + RS232C)
2-2.Components
Check that the following items are provided.
MODEL CODE DESCRIPTIONS
Controller 1 TEMI 770-10, -11, -20 or 21
Brackets 2 ST5300AF (Mount Assy)
Manual 1 This book
2-3. Missing or damaged items
If any of these items are missing or damaged, please contact your agent
or sales representative for assistance.
2-4. Life time of the parts in the controller
Check the life time for parts and we strongly recommend replace it if the life time finish.
■ RELAY (ST3300PJ) JW2SN-DC24V : Around ON/OFF 300,000 times
■ BATTERY (ST5100RX) SBAA02(3.6V) 1/2AA : Around 200,000 Hours
☞ Danger of explosion if battery is incorrectly replaced. Replace only with the same or equivalent
type.(SBAA02) Dispose of used battery separately from other waste.
IM TEMI 770E_C 2nd Edition: Sep. 1. 2003. 3/15
I. INSTALLATION
3. Installation
3-1. Location
IMPORTANT
NEVER touch the terminals or else you will get an electrical shock, if the unit is power-on.
To install the controller, select a location where:
■ No one may accidentally touch the terminals,
■ Mechanical vibrations are minimal,
■ Corrosive gas is minimal,
■ Temperature can be maintained between 10℃ to 50℃ and fluctuation is minimal,
■ Indoor use only,
■ Altitude is up to 2,000m
■ No direct radiant heat or ultraviolet rays is present,
■ No magnetic disturbances are caused,
■ No wind blows against the terminal board(reference junction compensation element),
■ No dust or salt content,
■ No flammable materials are around,
Although, the case of this system and the bezel are made of fire retardant SPCC-SD&ABS/PC
respectively, do not install the system near inflammable materials. Also, avoid placing the system
on inflammable materials directly.
3-2.Caution
CAUTION
■ There in little influence fro electromagnetic fields and noise
■ No moisture can get into the system.
■ Ambient temperature and humidity : 10~50℃, 20~90%RH. (At non-freezing status)
■ Storage temperature and humidity : -25~70℃, 5~95%RH. (At non-freezing status)
■ If you want to use it after keeping it under 0°C, you need to warm it up for 2 hours at
room temperature before plugging it in and warm it up for 30minute after plugging it in.
Otherwise, it may not function normally and the product may be damaged.
■ Do not use around any machine, which heat up.
■ Avoid installing it with the front facing slant.
■ Transient over voltage category is category II.
■ Applicable rated pollution degree is pollution degree II.
■ Before starting wiring, be sure to turn off the system or else you will get an electrical shock.
■ Install the guard panel under the controller for your safety and installation with easy.
■ The I/O relay board must be installed inside of Temperature & Humidity Chamber.
■ The I/O relay board must be tied up with 4piese of bolt and nut at the 4hole on the I/O
relay board.
IM TEMI 770E_C 2nd Edition: Sep. 1. 2003. 4/15
(
)
(
(
)
3-3. External and Panel Cutout Dimensions
I. INSTALLATION
180.80 (7.12) 14.32 (0.56)
93.4 (3.71)
133.90 (5.27)
Panel Thickness : 1 (0.04)~10(0.39)
Unit: mm, ( ): Inch
3-4. Panel cutting
5.30
0
+0.8
134.5
174
+0.8
0
(6.85)
Min 250
65.2 (2.58)
5.30
0
+0.8
9.84)
Min 200 (7.87)
Unit: mm, ( ): Inch
134.5
174
+0.8
0
(6.85)
76 (2.99)
IM TEMI 770E_C 2nd Edition: Sep. 1. 2003. 5/15
3-5. Installation (Mount)
Panel
Mount
I. INSTALLATION
Screwdriver
Insert
Unit: mm, ( ): Inch
Panel Thickness: 1(0.04)~10(0.39)
1) Cut the mounting panel as Section 3-4. PAN EL CUT T ING.
2) Insert the unit from its back terminal board side.
3) Attach the left and right brackets to the unit to fix the unit to the mounting panel. (Use screwdriver)
CAUTION (Mount) Do not tighten the mounting screw excessively, or the unit case
or bracket may be damage.
3-6. Installation (Wiring for ground)
SSR/SCR, Recorder
(Transmission output)
Circuit Breaker
L1 L2
L 1
L 2
N 1
N 2
N1 N2
G 1
G 2
G1 G3
CAUTION (Wiring for ground)
INPUT1INPUT2
SUPPLY
★
★
★★
CAUTION
100 - 240VAC
RS232
Relay Contact Output
Contact Input
Chamber
Case
DI
I/O Board
1. Make sure ground with temp. & humi chamber case when install power injection.
2. Make sure wiring of ground power source with circuit breaker in the temp. & humi. chamber.
3. Make sure wiring of ground with controller circuit breaker in temp. & humi. chamber.
IM TEMI 770E_C 2nd Edition: Sep. 1. 2003. 6/15
I. INSTALLATION
4. Wiring
CAUTION
■ Before carrying out wiring, turn off the power to the controller and check that the cables to be
connected are not alive with a tester or the like because there is a possibility of electric shock.
Personnel who have basic electrical knowledge and practical experience must carry out wiring.
■ The controller must be wired directly from circuit breaker output on inside of temperature &
humidity Chamber for avoid damage of controller or temperature & humidity Chamber.
4-1-2. Applicable tightening torques
Please use-tightening torque with insulating sleeve for M3.5 screws as shown in the following Figure:
4-1-3. Noise rejections
■ Reason making noise
(1) Relay and relay contact point (2) Solenoid coil, solenoid valve
(3) Power source line (4) Inductive load
(5) Invertors (6) Commentators of motor
(7) Phase-angle SCR (8) Wireless communication
(9) Welder (10) High-tension igniter, etc.
■ Solutions
When wiring, comply with the following to protect the controller from noise sources:
5.8mm or
less
Φ3.0mm or more
5.8mm
Φ3.0mm or more
or less
(1) Keep away the cables to the input circuit from the power supply
circuit or the grounding circuit as much as possible.
(2) Using a shielded cable is effective in avoiding noise from electrostatic induction. Connect a
shielded cable to the grounding terminal as required. Avoid two-point grounding.
(3) To avoid noise from electromagnetic induction, it is relatively
effective to mutually twist the input cables at regular short intervals.
IM TEMI 770E_C 2nd Edition: Sep. 1. 2003. 7/15
4-2. Terminal wiring diagram
RS485
I. INSTALLATION
Figure 4-2-B TEMI 770-11 Type
SUPPLY
★
100~240VAC
100-240VAC
INPUT1INPUT2
★
★★
CAUTION
I/O1 LINK
RS232
TXD
RXD
RTX+ RTX-
SG
I/O 2 LINK
Figure 4-2-C TEMI 770-20 Type
RS232
RS485
TXD
RXD
RTX+ RTX-
I/O 2 LINK
SG
Figure 4-2-D TEMI550-21 Type
Figure 4-2-A TEMI 770-10 Type
※ This shapes are depends on model.
*External Contact Switch
It is working
together as
“AND” condition
with RELAY 10.
RET1+ RET1- RET2+ RET2-
AOUT1+ AOUT1- AOUT2+ AOUT2-
(TEMP) (HUMI)
P7
Additional board does not have those parts.
DI_1 DI_2 DI_3 DI_4 DI_5 DI_6 DI_7 DI_8 DI_COM
GND
P3
RLY8_NC RLY8_NO COM2 RLY7_NO RLY7_NC
RLY10_NC RLY10_NO COM3 RLY9_NO RLY9_NC
COM1 RLY6 RLY5 RLY4 RLY3 RLY2 RLY1
Figure 4-2-E Standard I/O board and Additional I/O board
CAUTION
★ (8Ea) are not for connection terminals, these are only for install.
Avoid used those place, it might make damage to system or out of order.
CAUTION
Before carrying out wiring, turn off the power to the controller and check
that the cables to be connected are not alive with a tester or the like because
there is a possibility of electric shock. Wiring must be carried out by personnel
who have basic electrical knowledge and practical experience.
IM TEMI 770E_C 2nd Edition: Sep. 1. 2003. 8/15
4-2-1. Grounding
■ Use a cable 2 ㎟ or more thick for grounding with class 3 grounding(grounding
resistance a 100Ω or less) or higher. Do not extend the grounding cable over 20m.
■ Ground from the ground terminal with a one-point contact.
Do not wire between ground terminals.
■ Use appropriate cables equivalent to vinyl insulation cable(KSC 3304) or more.
100~240V AC
100-240VAC
50/60 Hz
0.1A, 50/60Hz
FG
Class 3 Ground
Ground FRAME GROUND (FG) EXACTLY.
4-2-2. Analog input
CAUTION
Before starting analog input wiring, be sure to turn off the system or else you
I. INSTALLATION
will get an electrical shock.
IMPORTANT
■ When connection, do not mix up the input polarity. Connecting with the wrong
polarity can cause the unit to malfunction.
■ For input wiring, use a shielded cable. Ground the shield at one point.
and grounding circuits as possible.
(1) Resistance Temperature Detector (RTD) INPUT
RTD
SHIELD
A
b
RTD
B
SHIELD
A
b
B
Class 3 Ground Class 3 Ground
(2) DC VOLTAGE INPUT (3) DC CURRENT INPUT
INPUT 2INPUT 1
DCV
SHIELD
+
_
mA
SHIELD
+
R
_
Class 3 Ground Class 3 Ground
V : 1 ~ 5 V
R = 2 5 0 Ω : 1 ~ 5 V
IM TEMI 770E_C 2nd Edition: Sep. 1. 2003. 9/15
4-2-3. Analog output
CAUTION
Before starting analog output wiring, be sure to turn off the system or else
you will get an electrical shock.
IMPORTANT
■ When connection, do not mix up the input polarity, Connecting with the
wrong polarity can cause serious accidents.
■ For input wiring, use a shielded cable. Ground the shield at one point.
(1) SSR/SCR
CAUTION Before starting ACTUATOR install/uninstall wiring, be sure to turn off
the system or else you will get an electrical shock.
I. INSTALLATION
■ Wiring for temp output(4~20mA/SSR) ■ Wiring for humi output(4~20mA/SSR)
CONTROL
VALVE
SHIELD
+
_
I/O 1 I/O 1
AOUT1+
AOUT1 -
조작단
CONTROL
VALVE
SHIELD
+
_
AOUT2+
AOUT2 -
Class 3 Ground Class 3 Ground
(2) Wiring for transmission output
CAUTION
Before starting receiver( or recorder, etc) install/uninstall wiring,
be sure to turn off the system or else you will get an electrical shock.
Before carrying out wiring, turn off the power to the controller and check that the cables to
be connected are not alive with a test because there is a possibility of electric shock.
I. INSTALLATION
30VDC 5A Less, 250VAC 5A Less
RLY 1
RLY 2
RLY 3
RLY 4
RLY 5
RLY 6
COM 1
I / O 1
30VDC 5A Less, 250VAC 5A Less
RLY9_NC
RLY9_N0
COM 3
RLY10_NO
RLY10_NC
RLY7_NC
RLY7_N0
COM 2
RLY8_NO
RLY8_NC
I / O 1 I / O 1
IM TEMI 770E_C 2nd Edition: Sep. 1. 2003. 11/15
I. INSTALLATION
4-2-5. External contact input: DI
CAUTION
Before starting external contact output:DI wiring, be sure to turn off
the system or else you will get an electrical shock.
■ For the external contact, use a no-voltage contact(including relay contact)
that can operate appropriately under the terminal voltage for a close
contact(approximate.. 5V) and the current for a opened contact(approximate.. 1mA).
■ When using an open collector, select one with the 2V or less voltage for
the closed contact, and 100µA or less leakage current for the open contact.
▲ RELAY contact input
Current when ON : approxi. 1mA
DI_1
DI_2
DI_3
DI_4
DI_5
DI_6
DI_7
DI_8
DI_COM
▲ TRANSISTOR contact input
DI_1
DI_2
DI_3
DI_4
DI_5
DI_6
DI_7
DI_8
DI_COM
+5 V
IM TEMI 770E_C 2nd Edition: Sep. 1. 2003. 12/15
4-2-6. Auxiliary Relay
CAUTION
If contact capacity is over 250VAC - resistance load 5A, 30VDC - resistance load 5A,
use auxiliary relay for ON/OFF load.
■ If you INDUCTANCE(L) load like as AUXILIARY RELAY or SOLENOIDE VALVE,
it might make go to wrong or out of order relay, please make sure insert to parallel circuit
with CR FILTER(AC) or DIODE(DC) by SURGE SUPPRESSOR of avoiding sparks.
■ Recommend CR FILTER
▶ Sung Ho Electronics : BSE104R120 25V (0.1μ+120Ω)
▶ HANA PARTS CO. : HN2EAC
▶ Songmi Electric Co., Ltd : CR UNIT 953, 955 etc
I. INSTALLATION
▶ Jiwol Electric Co., Ltd. : SKV, SKVB etc
▶ Shin young Com munication Co., Ltd. : CR-CFS, CR-U etc
(A) DC RELAY
(B) AC RELAY
Out DC power
Machine
R
RELAY
Use what a rated Relay Coil is must
be less than contact point capacity.
Out DC power
DIODE
Connect Relay Coil socket directly
RC Filter
R
Connect Relay Coil socket directly
Use what a rated Relay Coil is must
be less than contact point capacity.
RELAY
IM TEMI 770E_C 2nd Edition: Sep. 1. 2003. 13/15
(
)
I. INSTALLATION
4-2-7. Communication(RS485/RS232)
CAUTION Before starting communication wiring, be sure to turn off the system or
else you will get an electrical shock.
(1) RS485(Optional specification)
■ The slave side(TEMI 770) can accommodate up to 31 units in a MULTIDROP connection.
■ Be sure to connect a terminating resistance(220Ω 1/4W) to the units at the both
Termination
Resistance
RTX+
RTX-
SG
SHIELD
Class 3 Ground
(2) RS232C(Standard)
■ CONNECTOR : Wiring with 9 PIN
Master Station
D-Sub 9 Pin
Controller Controller
RTX+
RTX-
SG
RTX+
RTX-
SG
Class 3 Ground
(D-Sub 9 Pin Female)
Termination
Resistance
2
RD
TD
RTS
CTS
SG
SHIELD
3
7
8
5
2
RxD
TxD
3
SG
5
Class 3 Ground
IM TEMI 770E_C 2nd Edition: Sep. 1. 2003. 14/15
Blank
If you find any mistaken or wrong information in this manual
I. INSTALLATION
PLEASE mail to webmaster@samwontech.com
www.samwontech.com
IM TEMI 770E_C 2nd Edition: Sep. 1. 2003. 15/15
II.USERS
1. Setup button
TEMI 770 is easy to install & modify by touch screen as well as the map type menu. Enable to grasp the operation
of control system with easy through graph on vivid LCD screen.
1-1. Initial setup button
(Table 1-1)
MAIN
1
ON / OFF
2
SETPOINT
3
1
-2. Input Setpoint
1. Select Setpoint button.
2. It is showing the Figure 1-1 for input a data.
3. If user input data which is invalid, it makes 3 times buzzer, also there is -LIMIT ERR message
on the Setpoint display.
Parameter
Range Setpoint display
Button Function
Change the page.
MAIN
ON
OFF
0.0
On / Off & Selection
Switch to the page for input a Setpoint value data
Figure 1-1
Key Lock
1. KEY LOCK - ON -> Lock
2. KEY LOCK - OFF -> Unlock
☞ For more information, see 5.1 FUNCTION
1-3. Input error
User can check a number of buzzer times.
1) 1 time : Succeed set the data
2) 3 times : Failed set the data
Using the touch screen
Please do not use any pen/pencil, nail or any other sharp material.
Otherwise, the touch screen might be broken or out of order.
IM TEMI 770E_C 2nd Edition: Sep. 1. 2003. 1/40
II.USERS
2. Input Setpoint
All of the Setpoint data & test name on this controller is set-up by selecting Setpoint button. Setpoint is setting
up at the Setpoint page (Figure 1-1) by selecting Setpoint button.
☞ See 5-4-6.TEST NAME for how to input a test name.
2-1. Function of Setpoint key
① Parameter.
② Valid data range.
③ -LIMIT ERR display when user input invalid Setpoint.
④ Cancel input Setpoint.
⑤ Clear input data.
⑥ Decimal point. ⑦ Save input data and go to main page.
①
②
Figure 2-1
③
④
⑤
⑥
⑦
⑧
⑨
⑧ Modify the input data, delete one by one.
⑨ Input + or -.
2-2. Parameter
Following figure shown how to change Setpoint 0.0 to -50.0.
1. Select Setpoint button, user want.
2. Input the value and ENT key.
③⑤ ④
②
①
⑥
IM TEMI 770E_C 2nd Edition: Sep. 1. 2003. 2/40
II.USERS
3. Block of basic processing
[Start] ☞ Disappear in 2 second automatically
after power on.
☞ Modify at Display page.([MAIN] - [SETUP] - [DISPLAY])
[Operation]
POWER ON
Figure 3-1 Start page
PROG ☜ FUNCTION ☞ FIX
☞ : See 4.Operation & Setup
Figure 3-2 PROGRAM STOP Figure 3-3 FIX STOP
[Main]
☞ : See 5-1. FUNCTION
☞ : See 5-2. RESERVE
☞ : See 5-3. GRAPH
☞ : See 5-4. PROGRAM
☞ : See 5-5. (Back Light)
☞ : See 5-6. SETUP
STUP
ERROR
☞ : See 5-7.Setup PWD
Figure 3-5 Setup password
☞ : See 6.TROUBLE
Figure 3-6 TROUBLE
IM TEMI 770E_C 2nd Edition: Sep. 1. 2003. 3/40
4. Operation & Setup
4-1. PROGRAM STOP
①
⑤
II.USERS
Figure 4-1 PROGRAM STOP
① Main page(Figure 3-4)
② Temp : Present temperature.
③ PTNO : Present Program pattern number.
User can set up pattern number, wised run.
④ Date & Time : It show present date & time also it is functioning turn off / on LCD back light.
Even if turn off the light automatically, controller still working and turn on the light
③
⑨
⑩
④
⑧
②
⑦
⑥
if user touch any point.
Back Light will be turn off automatically for saving Back Light life.
(Default : 10min) See Function 5-1
⑤ Program name
⑥ Start : Start a program and it is turning into STOP . ⑦ Humi : Present humidity.
⑧ State : Present working state.
■ RESERVE : Reserved working.(See 5-2. RESERVE)
■ PTEND : When the program finish, display PTEND. ⑨ Segment No : Present Segment number .
⑩ Alarm : Present Alarm state.
⑪ Display state of finish the running. (Display RUN DATE after set the RESERVE RUN)
When the select ⑥ on Figure 4-1, ③, ⑧ and ⑨ on Figure 4-2,
CONFIRM window appear.(Figure 5-4-9)
At this CONFIRM window , you can confirm if you really want doing job or not.
IM TEMI 770E_C 2nd Edition: Sep. 1. 2003. 4/40
4-2. PROGRAM RUN
II.USERS
①
Figure 4-3
Figure 4-2
⑦
⑧
⑨
⑫
②
⑤ ⑥
Figure 4-2 PROGRAM RUN (SP) Figure 4-3 PROGRAM RUN(SP,MV)
① PTN/SEG
② Remain time
③ Stop
④ Up
: Pattern & Segment number of present running.
: Remain time of present running segment.
: Stop the running and change to the program stop page.(Figure4-1)
: Display up state.(Temperature / Humidity)
: Stop the present segment and move to the run next segment.
: Hold on/off present SP.(Setpoint)
: Display present temperature and humidity SP.(Setpoint)
: State of pattern repeat.
: State of segment rep eat.
: Display present temperature and humidity MV.( Manipulate value)
: State of present IS.(Inne r Signal)
OS : State of present OS.(ON/OFF Signal)
TS : State of present TS.(Time Signal)
AL : State of present AL.(Alram Signal)
⑫ PROCESS TIME
: Total processing time.
IM TEMI 770E_C 2nd Edition: Sep. 1. 2003. 5/40
4-3. FIX STOP
FIX function can controller temperature & humidity by SP.
① Temperature : Setting box for temperature SP.
② Humidity : Setting box for humidity SP.
③ State : Flash present running state.
RESERVED : If reserved running, here is shown Reserved state.(See 5-2. RESER VE)
①
②
③
④
Figure 4-4 FIX STOP
II.USERS
④ Display stop state.(Display RUN DATE after reserved running.)
4-4. FIX RUN
① T-AT : Auto Tuning for temperature.
② H-AT : Auto Tuning for humidity.
▶ Both of keys be able to set HIDE/DISPLAY on page FUNCTION.(See 5-1. FUNCTION)
Figure 4-6 FIX RUN(SP,MV)
Figure 4-5 FIX RUN
Figure 4-5 FIX RUN
Figure 4-6 FIX RUN (SP,MV)
IM TEMI 770E_C 2nd Edition: Sep. 1. 2003. 6/40
5. MAIN
5-1. FUNCTION
Select FUNC button at the MAIN page.(Figure3-4)
II.USERS
Figure 5-1-1. FUNCTION Figure 5-1-2. FIX OP TIME
① OPERATION : Select PROGRAM Mode or FIX mode. ▶ PROG : Switch to 4.1 PROGRAM STOP page. ▶ FIX : Switch to 4.3 FIX STOP page. ② POWER MODE : Setup when re-start after power failure.
Recognize to power failure if it is more than 3 seconds.
If re-start before 3 seconds, it will run to Hot mode automatically.
Figure 5-1-2 FIX OP TIME
▶ STOP : After power failure, go to default.
▶ COLD : After power failure, go to RUN on fix running or go to SEG1 on program running. ▶ HOT : After po wer failure, running by previous data before power failure.
③④ TEMP(HUMI) SLOPE : Temp/Humi. value goes to the SP gradually.
It is applied both of up and down.
⑤ AT KEY : Select HIDE or DISPLAY for T-AT and H-AT Key on FIX RUN page.
▶ HIDE : Invisible T-AT and H-AT Key.
▶ DISPLAY : Visible T-AT and H-AT Key.
⑥ KEY LOCK : Key lock / unlock.
▶ ON : Key lock (Disable to input data) ▶ OFF : Key unlock (Able to input data)
⑦⑧ FIX OP TIME : Set hour/Set minute.
⑨ FIX OP TIME : Set FIX OP TIME ON/OFF.
FIX OP TIME is for reserving FIX running within 9999 hours 59 min.
It is stop after running time automatically.
⑩ FUSSY SEL : Control over shoot by fussy sel.
OP TIME OPERATION TIME(H)0 ~ 9999 ABS 0
OP TIME OPERATION TIME(M)0 ~ 59 ABS 0
OP TIME OPERATION MODE OFF, ON ABS OFF
FUZZY FUZZY OFF, ON ABS OFF
BLGT TIME BACK LIGHT TIME 0 ~ 9999 MIN 10
☞ Ex) Set function of SLOPE
Temp gap 60℃
SP=100° C
SP= 40°
SP changing point
60℃/min
C
rate =60/1=60(℃/min)
IM TEMI 770E_C 2nd Edition: Sep. 1. 2003. 8/40
5-2 RESERVE
Select RESERVE at the Main page.
Figure 5-2-1.RESERVE
II.USERS
① NOW DATE : Display present date & time.
② RUN DATE : Set run date & time.
③ DATE SET : Set the date & time of NOW DATE.
④ RESERVE : Select ON / OFF
RESERVED is flashing if select ON at the working display area.
(Figure 3-2 PROG STOP, Figure 3-3 FIX STOP)
(Table 5-2) REVERSE PARAMETER
Name Function Valid Unit Default Value
RESERVE RESERVE ON/OFF OFF, ON ABS OFF
Y YEAR 0 ~ 99 ABS 0 / 1 / 0
M MONTH 1 ~ 12 ABS 0 / 1 / 0
D DAY 1 ~ 31 ABS 0 / 1 / 0
H HOUR 0 ~ 23 ABS 0 / 1 / 0
M MNUTE 0 ~ 59 ABS 1 / 0 / 1
IM TEMI 770E_C 2nd Edition: Sep. 1. 2003. 9/40
5-3. GRAPH
Select GRAPH at the Main page.(Figure 3-4)
⑥
II.USERS
Figure 5-3-1 GRAPH
① PATTERN NO
: Input the pattern, user want see.
② TEMPERATURE
: Switch scale to Humi to temp(④Temp/Humi scale) and switch the page.
③ TIME
: Switch the time scale to as below.
④
①
②
③
0 H 0 H
1 H 3 H
0 H
6 H
⑤
⑦
0 H
12 H
0 H
24 H
2 H 6 H
3 H
4 H
④ TEMP/HUMI
: Temp/Humi scale is switching by selecting TEMP button(②).
⑤ Time scale
⑥ Program pattern
⑦ Page up / down
Î
9 H
12 H
Î
Figure 5-3-2 Time scale
12 H
18 H
24 H
Î
24 H
36 H
48 H
Î
48 H
72 H
96 H
IM TEMI 770E_C 2nd Edition: Sep. 1. 2003. 10/40