Samsung AQA07C5ME, AQA09CBME, AQA12CBME, SH07AC5, SH09ACB Service Manual

...
ROOM AIR CONDITIONER
INDOOR UNIT
AQA07C5(6)ME AQA09CA(B)ME AQA12CA(B)ME SH07AC5(6) SH09ACA(B) SH12ACA(B)
SERVICE
UQA07C5(6)ME UQA09CA(B)ME UQA12CA(B)ME SH07AC5(6)X SH09ACA(B)X SH12ACA(B)X
Manual
CONTENTSAIR CONDITIONER
1. Precautions
2. Product Specifications
3. Operating Instructions and Installation
4. Disassembly and Reassembly
5. Troubleshooting
6. Exploded Views and Parts List
7. Block Diagrams
8. PCB Diagrams
9. Wiring Diagrams
10. Schematic Diagrams
1. Precautions
1. Warning: Prior to repair, disconnect the power cord from the circuit breaker.
2. Use proper parts: Use only exact replace­ment parts. (Also, we recommend replacing parts rather than repairing them.)
3. Use the proper tools: Use the proper tools and test equipment, and know how to use them. Using defective tools or test equip­ment may cause problems later-intermittent contact, for example.
4. Power Cord: Prior to repair, check the power cord and replace it if necessary.
5. Avoid using an extension cord, and avoid tapping into a power cord. This practice may result in malfunction or fire.
6. After completing repairs and reassembly, check the insulation resistance. Procedure: Prior to applying power, mea­sure the resistance between the power cord and the ground terminal. The resistance must be greater than 30 megaohms.
Fig. 1-1 Avoid Dangerous Contact
Fig. 1-2 No Tapping and No Extension Cords
7. Make sure that the grounds are adequate.
8. Make sure that the installation conditions are satisfactory. Relocate the unit if necessary.
9. Keep children away from the unit while it is being repaired.
10. Be sure to clean the unit and its surround­ing area.
Fig. 1-3 No Kids Nearby!
O.K
Fig. 1-4 Clean the Unit
1-1Samsung Electronics
MEMO
Samsung Electronics1-2
2. Product Specifications
2-1 Table
Item
Type
Cooling KW Dehumidifying Heating KW Low temp. heating Btu/h Air volume Cooling m
Perfor-
mance
Noise Cooling dB
Energy Cooling KW/KW Efficiency ratio Heating KW/KW Power Ø-V-Hz Power Cooling W Consumption Heating W Operating Current Cooling A
Power factor Cooling %
Power
Starting current A Power cord Length m
Fuse capacity A Outer Width x Height mm dimension x Depth inch Weight kg Refrigerant pipe Liquid OD(mm) x L(m)
Drain hose ID(mm)x L(m)
Size
Compressor Type
Blower Type
Heat exchanger Refrigerant control unit Freezer oil capacity Refrigerant to charge(R-410A) Protection device
Cooling test condition Heating test condition Maximum operation Condition
Heating m
Heating dB
Heating A
Heating %
Number of core wire
Gas OD(mm) x L(m)
Motor Type
Rated output W
Motor Type
Rated output W
Model
\/h
3
/min
3
/min
AQA07C5(6)ME
SH07AC5(6)
Indoor unit Outdoor unit
Wall-mounting
2.30
0.9
2.35
-
5.4 -
5.5 ­35 50 35 50
2.80
3.18
1-220/240-50
820 740
3.7
3.3
97.3
97.3
14.5
-­250V 10/16A
3.15 -
790x245x165 660x494x235
31.10x9.65x6.50
Cross-fan Propeller
Resin Steel
2Row 12Step 1Row 20Step
25.98x19.57x9.25
7.7 27.5 ø6.35 x 5 ø9.52 x 5
ø17 x 2
- Rotary
--
- 849
15 25
Capillary tube
280 560
-
RAC12126
-9622 Indoor unit : DB27˚C WB19˚C Outdoor unit : DB35˚C WB24˚C Indoor unit : DB20˚C WB15˚C Outdoor unit : DB 7˚C WB 6˚C Indoor unit : DB32˚C WB23˚C Outdoor unit : DB43˚C WB26˚C
AQA09CA(B)ME
SH09ACA(B)
Indoor unit Outdoor unit
Wall-mounting
2.80
1.1
2.90
-
6.6 -
7.0 ­38 51 38 51
2.83
3.09
1-220/240-50
990 940
4.5
4.2
97.0
97.0
23.0
-­250V 10/16A
3.15 -
790x245x165 740x525x230
31.10x9.65x6.50
Cross-fan Propeller
Resin Steel
2Row 12Step 1Row 24Step
29.1x20.7x9.1
7.7 28.0 ø6.35 x 5 ø9.52 x 5
ø17 x 2
- Rotary
--
- 1010
15 25
Capillary tube
280 650
-
RAC12131
-9622
AQA12CA(B)ME
SH12ACA(B)
Indoor unit Outdoor unit
Wall-mounting
3.50
1.5
3.80
-
8.0 -
8.5 ­41 53 41 53
2.92
2.81
1-220/240-50
1200 1350
5.4
6.0
97.0
97.0
27.0
-­250V 10/16A
3.15 -
790x245x165 740x525x230
31.10x9.65x6.50 29.1x20.7x9.1
7.7 34.5 ø6.35 x 5 ø9.52 x 5
ø17 x 2
- Rotary
--
- 1300
Cross-fan Propeller
Resin Steel
15 25
2Row 12Step 2Row 24Step
Capillary tube
500 970
-
RAC12128
-9622
2-1Samsung Electronics
2-2 Dimensions
245
165
790
2-2-1 Indoor Unit
Air out
(Front view)
Air in
(Rear view)
(Remote control)
115
2245
Installation plate
Samsung Electronics2-2
2-2-2 Outdoor Unit
230
506
270
525
740
57
20
11
UQA12CA(B)ME SH12ACA(B)X UQA09CA(B)ME SH09ACA(B)X
Operating Instructions and Installation
UQA07C5(6)ME SH07AC5(6)X
235
249
497
492
660 50
11
20
2-3Samsung Electronics
2-3 Pressure Graph
11
10
9
8
7
20 30
Outdoor drybulb temperature [deg C]
Low Pressure [kg/cm
2
G]
40
30.6/22.5
27/19
21.5/14.6
10
9
8
7
3
20 30
Outdoor drybulb temperature [deg C]
Low Pressure [kg/cm
2
G]
40
30.6/22.5
27/19
21.5/14.6
10
9
8
7
6
20 30
Outdoor drybulb temperature [deg C]
Low Pressure [kg/cm
2
G]
40
30.6/22.5
27/19
21.5/14.6
AQA07C5(6)ME
SH07AC5(6)
AQA09CA(B)ME
SH09ACA(B)
AQA12CA(B)ME
SH12ACA(B)
Samsung Electronics2-4
3. Operating Instructions and Installation
3-1 Operating Instructions
3-1-1 The Feature of Key in remote controller
NO
NAMED OF KEY
1
(UP)
2
(DOWN)
3
4
5
Power On/Off button to start and stop airconditioner or timer set up.
Temp. up button. To increase the temperatute by the pressing the temperature button.
Temp. down button. To decrease the temperature by the pressing the temperature button.
Each time you press this button Mode is changed in the following order
Press until the appearance. the air condition cools or heats the room as quickly as possible. after 30minutes, the air, the airconditioner is reset automatically to the previous mode.
Press until the appearance. the sleep timer can be used when you are cooling or heating your room to switch the air conditioner off automatically after a perriod of six hours.
Each time you press this button, FAN SPEED is changed in the following order.
FUNCTION OF KEY
: Auto Mode : Fan Only : Cool Mode : Heat Mode : Dry Mode
6
7
8
9
Adjust air flow vertically.
The ON Timer enables you to switch onthe air conditioner automatically after a given period of time that is from 30 minutes to 24 hours. To cancel, press the (Set/Cancel) button.
The Off Timer enables you to switch off the air conditioner automatically after a given period of time that is from 30 minutes to 24 hours. To cancel, press the (Set/Cancel) button.
To select the 5 way function with the remote control, press the 5 way button one or more times until the desired mode is selected. Each time you press the 5 way button
Each 5 way indicator on the indoor unit comes on in order.
3-1Samsung Electronics
Operating Instructions and Installation
3-1-2 Name & Function of Key in remote controller
1. AUTO MODE : In this mode, operation mode(COOL, HEAT) is selected automati­cally by the room temperature of initial operation.
Room Temp Tr21°C+∆T 21°C +∆T>Tr
Cool Operation (Set Temp: 24˚C+∆T)
Heat Operation (Set Temp : 22°C+∆T)
Operation Type
T= -1°C, -2°C, 0°C+1°C+2°CT is controlled by setting temperature
up/down key of remote controller
2. COOL MODE : The unit operates according to the difference between the setting and room temperature. (18°C~30°C)
3. HEAT MODE : The unit operates according to the difference between the setting and room temperature.(16°C~30°C) *Prevention against cold wind : For about 3~5 minutes after initial operation, thermo control or “de-ice”, the indoor fan will either not operate or operate very slowly, then switch to the selected fan speed. This period is to allow the indoor unit's heat­exchanger to prewarm before emitting warm air. *High temperature release function : The outdoor unit for and compressor ON/OFF control for safety operation, when the over­heat is heat exchanger of indoor unit. *De-ice : Deicing operation is controlled by indoor unit's heat exchanger temperature and accumulating time of compressor's operation. De-ice end by sensing of the processing time by de-ice Condition.
4. DRY MODE : Has 3 states, each determined by room temperature. The unit operates in DRY mode. *Compressor ON/OFF Time is controlled compulsorily(can not set up the fan speed, always breeze). *Protective function : Low temperature release. (Prevention against freeze)
5. TURBO MODE : This mode is available in AUTO, COOL, HEAT, DRY, FAN MODE. When this button is pressed at first, the air conditioner is operated “powerful” state for 30 minutes regardless of the set tempera­ture, room temperature. When this button is pressed again, or when the operating time is 30 minutes, turbo operation mode is canceled and returned to the previous mode. *But, if you press the TURBO button in DRY or FAN mode that is changed with AUTO mode automatically.
6. SLEEP MODE : Sleep mode is available only in COOL or HEAT mode. The operation will stop after 6 hours. *In COOL mode : The setting temperature is automatically raised by 1°C each 1hour When the temperature has been raised by total of 2°C, that temperature is main­tained. *In HEAT mode : The setting temperature is automatically droped by 1°C each 1hour. When the temperature has been droped by total of 2°C, that temperature is main­tained.
7. FAN SPEED : Manual (3 step), Auto (4 step) Fan speed automatically varies depending on both the difference between setting and the room temperature.
Samsung Electronics3-2
Operating Instructions and Installation
8. COMPULSORY OPERATION : For operating the air conditioner without the remote controller. *AUTO : The operating is the same func­tion that AUTO MODE in the remote con­troller. And each time you press the button the 5WAY func-tion is changed as follow.
STD NATURE POWER SAVING SILENCE POWER OFF STD(standard)( ) : General operation
Mode
NATURE( ) : The unit is operated
according to health pattern control
POWER( ) : The unit is operated in
powerful state
SAVING( ) : The unit is operated in
power saving state
SILENCE( ) : The unit is operated
quitely Each mode has Auto, Cool, Heat and SLEEP operation designed in advance.
9. SWING : BLADE-H is rotated vertically by the stepping motor. *Swing Set : Press the button under the remote control is displayed on LCD the and the blades move up and down. If the one more time press the button, blades loca­tion is stop.
11. SELF Diagnosis
LED DISPLAY
SILENCE
Check Point
Indoor unit room temperature sensor error(open or short)
Indoor unit heat exchanger temperature sensor error(open or short)
Indoor fan mal function
EEPROM error
Option error(option wasn’t set up or option data error)
LED
:
blinking
: LED off
TIMER STD NATURE POWER SAVING
12. BUZZER SOUND : Whenever the ON/OFF button is pressed or whenever change occurs to the condition which is set up or select, the compulsory operation mode, buzzer is sounded "beep".
10. 24-Hour ON/OFF Real Setting Timer. : The air conditioner is turned ON at a specified time using . OFF TIMER : The air Conditioner is turned OFF at a specified time using . *ON TIMER : Only timer LED lights on. *OFF TIMER : Both timer and operation LED lights on.
3-3Samsung Electronics
3-2 Installation
3-2-1 Selecting Area for Installation
Select an area for installation that is suitable to the customer's needs.
3-2-1(a) Indoor Unit
1. Make sure that you install the indoor unit in an area providing good ventilation. It must not be blocked by an obstacle affecting the airflow near the air inlet and the air outlet.
2. Make sure that you install the indoor unit in an area allowing good air handling and endurance of vibration of the indoor unit.
3. Make sure that you install the indoor unit in an area where there is no source of heat or vapor nearby.
4. Make sure that you install the indoor unit in an area from which hot or cool air is spread evenly in a room.
5. Make sure that you install the indoor unit in an area away from TVs, audio units, cord­less phones, fluorescent lighting fixtures and other electrical appliances (at least 1 meter).
6. Make sure that you install the indoor unit in an area which provides easy pipe connec­tion with the outdoor unit, and easy drainage for condensed water.
(Fix the unit firmly if it is mounted in a
high place.)
3. Make sure that you install the outdoor unit in area providing good ventilation and which is not dusty. It must not be blocked by any obstacle affecting the airflow near the air inlet and the air outlet.
4. Make sure that you install the outdoor unit in area free from animals or plants.
5. Make sure that you install the outdoor unit in area not blocking the traffic.
6. Make sure that you install the outdoor unit in area easy to drain condensed water from the indoor unit.
7. Make sure that you install the outdoor unit in area which provides easy connection within the maximum allowable length of a coolant pipe(10 meters).
Note
1. Add 20 grams of refrigerant (R410A) for every 1 meter if the pipe length exceeds the standard pipe length of 5 meters.
2. Maintain a height between the indoor and outdoor units of less than 3 meters.
8. Make sure that you install the outdoor unit in an area which is large enough to accom­modate the measurements shown in figure on the next page.
7. Make sure that you install the indoor unit in an area which is large enough to accomo­date the measurements shown in figure on the next page.
3-2-1(b) Outdoor Unit
1. Make sure that you install the outdoor unit in area not exposed to the rain or direct sun light.
(Install a separate sunblind if exposed to
direct sun light.)
2. Make sure that you install the outdoor unit in area allowing good air moment, not amplifying noise or vibration, especially to avoid disturbing neighbours.
Caution :
It is harmful to the air conditioner if it is used in the following environments: greasy areas (including areas near machines), salty areas such as coast areas, areas where sulfuric gas is present such as hot spring areas. Contact your dealer for advice.
3-2-1(c) Remote Control Unit
1. Make sure that you install the remote con­trol unit in an area free from obstacles such as curtains etc, which may block signals from the remote control unit.
2. Make sure that you install the remote con­trol unit in an area not exposed to direct sunlight, and where there is no source of heat.
3. Make sure that you install the remote con­trol unit in an area away from TVs, audio units, cordless phones, fluorescent lighting fixtures and other electrical appliances (at least 1 meter).
Samsung Electronics3-4
Cut the piping hole sloped slightly
3-2-2 Installation diagram of indoor unit and outdoor unit
Operating Instructions and Installation
A Indoor unit gas leak test check point
Indoor unit
Piping
2
3
1
Tape vinyl
B Drain hose installation
Cut the piping hole sloped slightly
Piping may be laid to the rear, left, right or down .
Right
Rear
250mm or more
5
6
8
Down
70mm or more
7
Rear
200mm or more
Left
“H” metere s maximum
Remote control
Remote control holder
4
Model L H **7**
9
**9**
**12**
1 2 3 4 5
Piping (Liquid) 1/4" Clamper tube
7K/9K BTU 12K BTU
Piping(Gas)3/8” Installation tube Screw Vinyl tape Drain hose
6 7 8
9
Putty
Installation plate
15 7 15 7 15 7
3-5Samsung Electronics
Operating Instructions and Installation
60
30
252
275
14090
410~730
3-2-2(a) Fixing the Installation Plate
(Unit : mm)
(Unit : mm)
Installation plate
Pipe hole (ø65mm)
1. Determine the position of the pipe and drain hose hole using the right figure and drill the hole with an inner diameter of 65mm so that it slants slightly downwards.
2.
If you are fixing the indoor unit to a… Then follow Steps…
Wall 3.
Window frame 4 to 6.
3. Fix the installation plate to the wall in a manner appro­priate to the weight of the indoor unit.
If you are mounting the plate on a concrete wall with anchor bolts, the anchor bolts must not project by more than 20mm.
4. Determine the positions of the wooden uprights to be attached to the window frame.
3-2-2(b) Purging the Unit
5. Attach the wooden uprights to the window frame in a manner appropriate to the weight of the indoor unit.
6. Using tapped screws, attach the installation plate to the wooden uprights, as illustrated in the last figure oppo­site.
On delivery, the indoor unit is loaded with an inert gas. All this gas must therefore be purged before connecting the assembly piping. To purge the inert gas, proceed as fol­lows.
Unscrew the caps at the end of each pipe.
Result : All inert gas escapes from the indoor unit.
To prevent dirt or foreign objects from getting into
the pipes during installation, do NOT remove the caps completely until you are ready to connect the piping.
3-6 Samsung Electronics
3-2-2(c) Connecting the Assembly Cable.
N1 1 2
N1 1 2 3
NL
3
E231
N1
E
2
31
1
N1N1
N1
Indoor unit
Outdoor unit
Earth terminal
Earth terminal
The outdoor unit is powered from the indoor unit via the assembly cable. If the outdoor unit is more than five metres away from the indoor unit, the cable must first be extended to a maximum of ten metres.
1. Extend the assembly cable if necessary.
2. Open the front grille by pulling on the tabs on the lower right and left sides of the indoor unit.
3. Remove the screw securing the connector cover.
4. Pass the assembly cable through the rear of the indoor unit and connect the assembly cable to terminals 1(N1) to 3.
• Each wire is labelled with the corresponding terminal number.
5. Firmly fix the ass’y cable with clamp wire holdet.
6. Pass the other end of the cable through the 65mm hole in the wall.
7. Replace the connector cover, carefully tightening the screw.
8. Close the front grille.
9. For further details on how to plug the other end of the assembly cable into the outdoor unit, refer to page 3-8.
Operating Instructions and Installation
3-2-2(d) Installing and Connecting the Indoor Unit Drain Hose
Care must be taken when installing the drain hose for the indoor unit to ensure that any condensa­tion water is correctly drained outside.l When passing the drain hose through the 65mm hole drilled in the wall, check that none of the following situations occur.
5cm less
The hose must NOT slope upw ards.
To install the drain hose, proceed as follows.
1. If necessary, connect the 2-metre extension to the drain hose.
2. If you are using the extension, insulate the inside part of the extension drain hose with a shield.
3. Pass the drain hose under the refrigerant piping, taking care to keep the drain hose tight.
4. Pass the drain hose through the hole in the wall, making sure that it is sloping downwards, as shown in the illustrations above.
The end of the drain hose must NOT be placed in water.
Do NOT bend the hose in different directions.
Keep a clearance of at least 5cm between the end of the hose and the ground.
Do NOT place the end of the drain hose in a hollow.
Drain hose Extension drain hose
Shield
The hose will be fixed permanently into position once the whole installation has been tested for gas leaks;
3-7Samsung Electronics
Operating Instructions and Installation
3-2-2(e) Outdoor unit installation
Wiring connection
1. Remove the cover-E parts.
2. Firmly connect the cable connector in the terminal block.
3. Fasten the M4 ring terminal to the hole marked
4. Firmly fix the ass'y cable with clamp wire holder.
5. Assemble the cover-E parts.
6. To prevent the entry of water, form a trap of the ass'y cable as illustrated in the installation diagram of indoor and outdoor unit.
Ass’y cover valve (RO Hand cabi, RH)
N1 1 2 3
Installing and Connecting the Outdoor Unit Drain Hose
Drain hole
When using the air conditioner in the heating, ice may accumulate. Duting de-icing, the condensed water must be drained off safely. Consequently, you must install a drain hose on the outdoor unit, following the instructions below.
1. Insert the drain plug into the drain hole on the underside of the outdoor unit.
2. Connect the drain hose to the drain plug.
3. Ensure that the drained water runs off correctly and safely.
Samsung Electronics3-8
3-2-2(f) Air-Purge Procedure
Operating Instructions and Installation
1. Connect each assembly pipe to the appropriate valve on the outdoor unit and tighten the flare nut.
2. Connect the charging hose of low pressure side of manifold gauge to the packed valve having a service port (3/8” Packed valve) as shown at the figure.
3. Open the valve of the low pressure side of manifold gauge counter-clockwise.
4. Purge the air from the system using vacuum pump for about 30 minutes.
- After that, please recheck that pressure is stabilization.
- Close the valve of the low pressure side of manifold gauge
clockwise.
- Remove the hose of the low pressure side of manifold
gauge.
Outdoor unit
Indoor unit
A
B
Gas pipe side
Liquid pipe side
C
D
5. Set valve cork of both liquid side and gas side of packed valve to the open position.
6. Mount the valve stem nuts to the 2-way and 3-way valve. And mount the service port cap to 3-way valve.
7. Check for gas leakage.
- At this time, especially check for gas leakage from the 3-way valve’s stem nuts, and from the service port cap.
B
(liquid)
A
(gas)
Vacuum Pump
Valve stem
Stem cap
3-9Samsung Electronics
Operating Instructions and Installation
3-2-2(g) Refrigerant Refill
• Refill an air-conditioner with refrigerant when refrigerant has been leaked at installing or using.
1. Vacuum system with pump (for new installation, leakage).
2. Turn the 3-way valve clockwise to close, connect the pressure gauge(low pressure side) to the service valve, and open the 3-way valve again.
Suspension hook
3. Connect the tank to refill with Refrigerant
4. Set the unit to Low pressure checking mode.
* Press the ON/OFF switch for 5 seconds. * All lamps blink on the indoor unit.
5. Check the pressure indicated by the pressure gauge(low pressure side).
* Refer to Low pressure graph.
6. Open the refrigerant tank and fill with refrig­erant until the rated pressure is reached.
* It is recommended not to pour the refriger-
ant in too quickly, but gradually while operating a pressure valve.
Compound gauge
For mounting other end of hose when not in use
Finger tight fittings
Connected to high pressure side
R410A
High pressure gauge
Hand wheel
Vacuum
pump
7. Stop operation of the air conditioner.
8. Close the 3-way valve, disconnect the pressure gauge, and open the 3-way valve again.
9. Close the cap of each valve.
Samsung Electronics3-10
3-2-2(h) Refrigerant Adjustment
Operating Instructions and Installation
Class For installation
Connection
Pipe Length
5m Max.
5~10m
Air-Purge Method
Refer to the detailed Air-Purge Procedure
3-2-2(i) Flare nut fixing torque
Outer diameter
ø 6.35 (Liquid Side)
ø 9.52 (Gas Side) ø 12.7 (Gas Side)
Refrigerant Adjustment
Unnecessary Add 20g of refrigerant
R410A(Add as liquid state) for every 1m.
Fixing Torque Final Torque
160 300 500
Air-Purge Method
Purge air using a vaccum pump
Torque (kg-cm)
For service
Refrigerant Quantity
refer to specification sheet
Add 20g of refrigerant R410A(Add as liquid state) for every 1m.
200 350 550
3-11Samsung Electronics