1. Warning: Prior to repair, disconnect the
power cord from the circuit breaker.
2. Use proper parts: Use only exact replacement parts. (Also, we recommend replacing
parts rather than repairing them.)
3. Use the proper tools: Use the proper tools
and test equipment, and know how to use
them. Using defective tools or test equipment may cause problems later-intermittent
contact, for example.
4. Power Cord: Prior to repair, check the
power cord and replace it if necessary.
5. Avoid using an extension cord, and avoid
tapping into a power cord. This practice
may result in malfunction or fire.
6. After completing repairs and reassembly,
check the insulation resistance.
Procedure: Prior to applying power, measure the resistance between the power cord
and the ground terminal. The resistance
must be greater than 30 megaohms.
Fig. 1-1 Avoid Dangerous Contact
Fig. 1-2 No Tapping and No Extension Cords
7. Make sure that the grounds are adequate.
8. Make sure that the installation conditions
are satisfactory.
Relocate the unit if necessary.
9. Keep children away from the unit while it is
being repaired.
10. Be sure to clean the unit and its surrounding area.
Fig. 1-3 No Kids Nearby!
O.K
Fig. 1-4 Clean the Unit
1-1Samsung Electronics
MEMO
Samsung Electronics1-2
2. Product Specifications
2-1 Table
Item
Type
CoolingKW
Dehumidifying
HeatingKW
Low temp. heatingBtu/h
Air volumeCoolingm
Perfor-
mance
NoiseCoolingdB
Energy CoolingKW/KW
Efficiency ratioHeatingKW/KW
Power Ø-V-Hz
Power CoolingW
ConsumptionHeatingW
Operating CurrentCoolingA
Power factorCooling%
Power
Starting currentA
Power cordLengthm
Fuse capacityA
OuterWidth x Heightmm
dimension x Depthinch
Weightkg
Refrigerant pipeLiquidOD(mm) x L(m)
Drain hoseID(mm)x L(m)
Size
Compressor Type
Blower Type
Heat exchanger
Refrigerant control unit
Freezer oil capacity
Refrigerant to charge(R-410A)
Protection device
Cooling test condition
Heating test condition
Maximum operation Condition
Heatingm
HeatingdB
HeatingA
Heating%
Number of core wire
GasOD(mm) x L(m)
Motor Type
Rated outputW
Motor Type
Rated outputW
Model
\/h
3
/min
3
/min
AQA07C5(6)ME
SH07AC5(6)
Indoor unitOutdoor unit
Wall-mounting
2.30
0.9
2.35
-
5.4-
5.53550
3550
2.80
3.18
1-220/240-50
820
740
3.7
3.3
97.3
97.3
14.5
-250V 10/16A
3.15-
790x245x165 660x494x235
31.10x9.65x6.50
Cross-fanPropeller
ResinSteel
2Row 12Step 1Row 20Step
25.98x19.57x9.25
7.727.5
ø6.35 x 5
ø9.52 x 5
ø17 x 2
-Rotary
--
-849
1525
Capillary tube
280
560
-
RAC12126
-9622
Indoor unit : DB27˚C WB19˚COutdoor unit : DB35˚C WB24˚C
Indoor unit : DB20˚C WB15˚COutdoor unit : DB 7˚C WB 6˚C
Indoor unit : DB32˚C WB23˚COutdoor unit : DB43˚C WB26˚C
AQA09CA(B)ME
SH09ACA(B)
Indoor unitOutdoor unit
Wall-mounting
2.80
1.1
2.90
-
6.6-
7.03851
3851
2.83
3.09
1-220/240-50
990
940
4.5
4.2
97.0
97.0
23.0
-250V 10/16A
3.15-
790x245x165 740x525x230
31.10x9.65x6.50
Cross-fanPropeller
ResinSteel
2Row 12Step 1Row 24Step
29.1x20.7x9.1
7.728.0
ø6.35 x 5
ø9.52 x 5
ø17 x 2
-Rotary
--
-1010
1525
Capillary tube
280
650
-
RAC12131
-9622
AQA12CA(B)ME
SH12ACA(B)
Indoor unitOutdoor unit
Wall-mounting
3.50
1.5
3.80
-
8.0-
8.54153
4153
2.92
2.81
1-220/240-50
1200
1350
5.4
6.0
97.0
97.0
27.0
-250V 10/16A
3.15-
790x245x165 740x525x230
31.10x9.65x6.50 29.1x20.7x9.1
7.734.5
ø6.35 x 5
ø9.52 x 5
ø17 x 2
-Rotary
--
-1300
Cross-fanPropeller
ResinSteel
1525
2Row 12Step 2Row 24Step
Capillary tube
500
970
-
RAC12128
-9622
2-1Samsung Electronics
2-2 Dimensions
245
165
790
2-2-1 Indoor Unit
Air out
(Front view)
Air
in
(Rear view)
(Remote control)
115
2245
Installation plate
Samsung Electronics2-2
2-2-2 Outdoor Unit
230
506
270
525
740
57
20
11
UQA12CA(B)ME
SH12ACA(B)X
UQA09CA(B)ME
SH09ACA(B)X
Operating Instructions and Installation
UQA07C5(6)ME
SH07AC5(6)X
235
249
497
492
66050
11
20
2-3Samsung Electronics
2-3 Pressure Graph
11
10
9
8
7
2030
Outdoor drybulb temperature [deg C]
Low Pressure [kg/cm
2
G]
40
30.6/22.5
27/19
21.5/14.6
10
9
8
7
3
2030
Outdoor drybulb temperature [deg C]
Low Pressure [kg/cm
2
G]
40
30.6/22.5
27/19
21.5/14.6
10
9
8
7
6
2030
Outdoor drybulb temperature [deg C]
Low Pressure [kg/cm
2
G]
40
30.6/22.5
27/19
21.5/14.6
■ AQA07C5(6)ME
■ SH07AC5(6)
■ AQA09CA(B)ME
■ SH09ACA(B)
■ AQA12CA(B)ME
■ SH12ACA(B)
Samsung Electronics2-4
3. Operating Instructions and Installation
3-1 Operating Instructions
3-1-1 The Feature of Key in remote controller
NO
NAMED OF KEY
1
(UP)
2
(DOWN)
3
4
5
Power On/Off button to start and stop airconditioner or timer set up.
Temp. up button. To increase the temperatute by the pressing
the temperature button.
Temp. down button. To decrease the temperature by the pressing
the temperature button.
Each time you press this button
Mode is changed in the following order
Press until the appearance. the air condition cools or heats
the room as quickly as possible. after 30minutes, the air,
the airconditioner is reset automatically to the previous mode.
Press until the appearance. the sleep timer can be used when
you are cooling or heating your room to switch the air conditioner off
automatically after a perriod of six hours.
Each time you press this button,
FAN SPEED is changed in the following order.
FUNCTION OF KEY
: Auto Mode: Fan Only
: Cool Mode: Heat Mode
: Dry Mode
6
7
8
9
Adjust air flow vertically.
The ON Timer enables you to switch onthe air conditioner automatically
after a given period of time that is from 30 minutes to 24 hours.
To cancel, press the (Set/Cancel) button.
The Off Timer enables you to switch off the air conditioner automatically
after a given period of time that is from 30 minutes to 24 hours.
To cancel, press the (Set/Cancel) button.
To select the 5 way function with the remote control, press the 5 way
button one or more times until the desired mode is selected.
Each time you press the 5 way button
Each 5 way indicator on the indoor unit comes on in order.
3-1Samsung Electronics
Operating Instructions and Installation
3-1-2 Name & Function of Key in remote controller
1. AUTO MODE : In this mode, operation
mode(COOL, HEAT) is selected automatically by the room temperature of initial
operation.
Room Temp
Tr≥ 21°C+∆T
21°C +∆T>Tr
Cool Operation (Set Temp: 24˚C+∆T)
Heat Operation (Set Temp : 22°C+∆T)
Operation Type
∆T= -1°C, -2°C, 0°C+1°C+2°C
∆T is controlled by setting temperature
up/down key of remote controller
2. COOL MODE : The unit operates according
to the difference between the setting and
room temperature. (18°C~30°C)
3. HEAT MODE : The unit operates according
to the difference between the setting and
room temperature.(16°C~30°C)
*Prevention against cold wind : For about
3~5 minutes after initial operation, thermo
control or “de-ice”, the indoor fan will
either not operate or operate very slowly,
then switch to the selected fan speed. This
period is to allow the indoor unit's heatexchanger to prewarm before emitting
warm air.
*High temperature release function : The
outdoor unit for and compressor ON/OFF
control for safety operation, when the overheat is heat exchanger of indoor unit.
*De-ice : Deicing operation is controlled by
indoor unit's heat exchanger temperature
and accumulating time of compressor's
operation.
De-ice end by sensing of the processing
time by de-ice Condition.
4. DRY MODE : Has 3 states, each determined
by room temperature.
The unit operates in DRY mode.
*Compressor ON/OFF Time is controlled
compulsorily(can not set up the fan speed,
always breeze).
*Protective function : Low temperature
release. (Prevention against freeze)
5. TURBO MODE : This mode is available in
AUTO, COOL, HEAT, DRY, FAN MODE.
When this button is pressed at first, the air
conditioner is operated “powerful” state for
30 minutes regardless of the set temperature, room temperature.
When this button is pressed again, or when
the operating time is 30 minutes, turbo
operation mode is canceled and returned to
the previous mode.
*But, if you press the TURBO button in DRY
or FAN mode that is changed with AUTO
mode automatically.
6. SLEEP MODE : Sleep mode is available
only in COOL or HEAT mode.
The operation will stop after 6 hours.
*In COOL mode : The setting temperature
is automatically raised by 1°C each 1hour
When the temperature has been raised by
total of 2°C, that temperature is maintained.
*In HEAT mode : The setting temperature
is automatically droped by 1°C each 1hour.
When the temperature has been droped by
total of 2°C, that temperature is maintained.
7. FAN SPEED : Manual (3 step), Auto (4 step)
Fan speed automatically varies depending
on both the difference between setting and
the room temperature.
Samsung Electronics3-2
Operating Instructions and Installation
8. COMPULSORY OPERATION :
For operating the air conditioner without
the remote controller.
*AUTO : The operating is the same function that AUTO MODE in the remote controller. And each time you press the button
the 5WAY func-tion is changed as follow.
STD ➝ NATURE ➝ POWER ➝ SAVING ➝
SILENCE ➝ POWER OFF
❊ STD(standard)( ) : General operation
Mode
❊ NATURE( ) : The unit is operated
according to health
pattern control
❊ POWER( ) : The unit is operated in
powerful state
❊ SAVING( ) : The unit is operated in
power saving state
❊ SILENCE( ) : The unit is operated
quitely
Each mode has Auto, Cool, Heat and SLEEP
operation designed in advance.
9. SWING : BLADE-H is rotated vertically by
the stepping motor.
*Swing Set : Press the button under the
remote control is displayed on LCD the
and the blades move up and down. If the one
more time press the button, blades location is stop.
11. SELF Diagnosis
LED DISPLAY
SILENCE
Check Point
Indoor unit room temperature sensor
error(open or short)
Indoor unit heat exchanger temperature
sensor error(open or short)
Indoor fan mal function
EEPROM error
Option error(option wasn’t set up or
option data error)
LED
:
blinking
: LED off
TIMERSTDNATURE POWER SAVING
12. BUZZER SOUND : Whenever the ON/OFF
button is pressed or whenever change
occurs to the condition which is set up or
select, the compulsory operation mode,
buzzer is sounded "beep".
10. 24-Hour ON/OFF Real Setting Timer. : The
air conditioner is turned ON at a specified
time using .
OFF TIMER : The air Conditioner is turned
OFF at a specified time using .
*ON TIMER : Only timer LED lights on.
*OFF TIMER : Both timer and operation
LED lights on.
3-3Samsung Electronics
3-2 Installation
3-2-1 Selecting Area for Installation
Select an area for installation that is suitable
to the customer's needs.
3-2-1(a) Indoor Unit
1. Make sure that you install the indoor unit in
an area providing good ventilation. It must
not be blocked by an obstacle affecting the
airflow near the air inlet and the air outlet.
2. Make sure that you install the indoor unit in
an area allowing good air handling and
endurance of vibration of the indoor unit.
3. Make sure that you install the indoor unit in
an area where there is no source of heat or
vapor nearby.
4. Make sure that you install the indoor unit in
an area from which hot or cool air is spread
evenly in a room.
5. Make sure that you install the indoor unit in
an area away from TVs, audio units, cordless phones, fluorescent lighting fixtures
and other electrical appliances (at least 1
meter).
6. Make sure that you install the indoor unit in
an area which provides easy pipe connection with the outdoor unit, and easy
drainage for condensed water.
(Fix the unit firmly if it is mounted in a
high place.)
3. Make sure that you install the outdoor unit
in area providing good ventilation and
which is not dusty. It must not be blocked
by any obstacle affecting the airflow near
the air inlet and the air outlet.
4. Make sure that you install the outdoor unit
in area free from animals or plants.
5. Make sure that you install the outdoor unit
in area not blocking the traffic.
6. Make sure that you install the outdoor unit
in area easy to drain condensed water from
the indoor unit.
7. Make sure that you install the outdoor unit
in area which provides easy connection
within the maximum allowable length of a
coolant pipe(10 meters).
Note
1. Add 20 grams of refrigerant (R410A) for every
1 meter if the pipe length exceeds the standard
pipe length of 5 meters.
2. Maintain a height between the indoor and outdoor
units of less than 3 meters.
8. Make sure that you install the outdoor unit
in an area which is large enough to accommodate the measurements shown in figure
on the next page.
7. Make sure that you install the indoor unit in
an area which is large enough to accomodate the measurements shown in figure on
the next page.
3-2-1(b) Outdoor Unit
1. Make sure that you install the outdoor unit
in area not exposed to the rain or direct sun
light.
(Install a separate sunblind if exposed to
direct sun light.)
2. Make sure that you install the outdoor unit
in area allowing good air moment, not
amplifying noise or vibration, especially to
avoid disturbing neighbours.
Caution :
It is harmful to the air conditioner if it is used in the following environments: greasy areas (including areas near machines),
salty areas such as coast areas, areas where sulfuric gas is present such as hot spring areas. Contact your dealer for advice.
3-2-1(c) Remote Control Unit
1.Make sure that you install the remote control unit in an area free from obstacles such
as curtains etc, which may block signals
from the remote control unit.
2. Make sure that you install the remote control unit in an area not exposed to direct
sunlight, and where there is no source of
heat.
3. Make sure that you install the remote control unit in an area away from TVs, audio
units, cordless phones, fluorescent lighting
fixtures and other electrical appliances (at
least 1 meter).
Samsung Electronics3-4
Cut the piping holesloped slightly
3-2-2 Installation diagram of indoor unit and outdoor unit
Operating Instructions and Installation
A Indoor unit gas leak test check point
Indoor unit
Piping
2
3
1
Tape vinyl
B Drain hose installation
Cut the piping hole
sloped slightly
Piping may be laid to the rear, left,
right or down .
1. Determine the position of the pipe and drain hose hole
using the right figure and drill the hole with an inner
diameter of 65mm so that it slants slightly downwards.
2.
If you are fixing the indoor unit to a… Then follow Steps…
Wall 3.
Window frame 4 to 6.
3. Fix the installation plate to the wall in a manner appropriate to the weight of the indoor unit.
If you are mounting the plate on a concrete wall with
anchor bolts, the anchor bolts must not project by more
than 20mm.
4. Determine the positions of the wooden uprights to be
attached to the window frame.
3-2-2(b) Purging the Unit
5. Attach the wooden uprights to the window frame in a
manner appropriate to the weight of the indoor unit.
6. Using tapped screws, attach the installation plate to the
wooden uprights, as illustrated in the last figure opposite.
On delivery, the indoor unit is loaded with an inert gas.
All this gas must therefore be purged before connecting the
assembly piping. To purge the inert gas, proceed as follows.
Unscrew the caps at the end of each pipe.
Result : All inert gas escapes from the indoor unit.
•To prevent dirt or foreign objects from getting into
the pipes during installation, do NOT remove the
caps completely until you are ready to connect the
piping.
3-6Samsung Electronics
3-2-2(c) Connecting the Assembly Cable.
N1 12
N1 123
NL
3
E231
N1
E
2
31
1
N1N1
N1
Indoor unit
Outdoor unit
Earth terminal
Earth terminal
The outdoor unit is powered from the indoor unit via the assembly
cable. If the outdoor unit is more than five metres away from the
indoor unit, the cable must first be extended to a maximum of ten
metres.
1. Extend the assembly cable if necessary.
2. Open the front grille by pulling on the tabs on the lower right and
left sides of the indoor unit.
3. Remove the screw securing the connector cover.
4. Pass the assembly cable through the rear of the indoor unit and
connect the assembly cable to terminals 1(N1) to 3.
• Each wire is labelled with the corresponding terminal number.
5. Firmly fix the ass’y cable with clamp wire holdet.
6. Pass the other end of the cable through the 65mm hole in the wall.
7. Replace the connector cover, carefully tightening the screw.
8. Close the front grille.
9. For further details on how to plug the other end of the assembly
cable into the outdoor unit, refer to page 3-8.
Operating Instructions and Installation
3-2-2(d) Installing and Connecting the Indoor Unit Drain Hose
Care must be taken when installing the drain hose for the indoor unit to ensure that any condensation water is correctly drained outside.l When passing the drain hose through the 65mm hole drilled
in the wall, check that none of the following situations occur.
5cm
less
The hose must
NOT slope upw
ards.
To install the drain hose, proceed as follows.
1. If necessary, connect the 2-metre extension to the drain hose.
2. If you are using the extension, insulate the inside part of the extension drain hose with a shield.
3. Pass the drain hose under the refrigerant piping, taking care to keep the drain hose tight.
4. Pass the drain hose through the hole in the wall, making sure that it is sloping downwards, as
shown in the illustrations above.
The end of the drain
hose must NOT be
placed in water.
Do NOT bend the
hose in different
directions.
Keep a clearance of at
least 5cm between the
end of the hose and the
ground.
Do NOT place the end
of the drain hose in a
hollow.
Drain hoseExtension drain hose
Shield
The hose will be fixed permanently into position once
the whole installation has been tested for gas leaks;
3-7Samsung Electronics
Operating Instructions and Installation
3-2-2(e) Outdoor unit installation
Wiring connection
1. Remove the cover-E parts.
2. Firmly connect the cable connector in the terminal block.
3. Fasten the M4 ring terminal to the hole marked
4. Firmly fix the ass'y cable with clamp wire holder.
5. Assemble the cover-E parts.
6. To prevent the entry of water, form a trap of the ass'y cable as illustrated in the installation
diagram of indoor and outdoor unit.
Ass’y cover valve (RO Hand cabi, RH)
N1 1 2 3
Installing and Connecting the Outdoor Unit Drain Hose
Drain hole
When using the air conditioner in the heating, ice may accumulate.
Duting de-icing, the condensed water must be drained off safely.
Consequently, you must install a drain hose on the outdoor unit,
following the instructions below.
1. Insert the drain plug into the drain hole on the underside of the
outdoor unit.
2. Connect the drain hose to the drain plug.
3. Ensure that the drained water runs off correctly and safely.
Samsung Electronics3-8
3-2-2(f) Air-Purge Procedure
Operating Instructions and Installation
1. Connect each assembly pipe to the appropriate valve on the
outdoor unit and tighten the flare nut.
2. Connect the charging hose of low pressure side of manifold
gauge to the packed valve having a service port (3/8”
Packed valve) as shown at the figure.
3. Open the valve of the low pressure side of manifold gauge
counter-clockwise.
4. Purge the air from the system using vacuum pump for about
30 minutes.
- After that, please recheck that pressure is stabilization.
- Close the valve of the low pressure side of manifold gauge
clockwise.
- Remove the hose of the low pressure side of manifold
gauge.
Outdoor unit
Indoor unit
A
B
Gas pipe side
Liquid pipe side
C
D
5. Set valve cork of both liquid side and gas side of packed
valve to the open position.
6. Mount the valve stem nuts to the 2-way and 3-way valve.
And mount the service port cap to 3-way valve.
7. Check for gas leakage.
- At this time, especially check for gas leakage from the
3-way valve’s stem nuts, and from the service port cap.
B
(liquid)
A
(gas)
Vacuum Pump
Valve stem
Stem cap
3-9Samsung Electronics
Operating Instructions and Installation
3-2-2(g) Refrigerant Refill
• Refill an air-conditioner with refrigerant when refrigerant has been leaked at installing or using.
1. Vacuum system with pump (for new
installation, leakage).
2. Turn the 3-way valve clockwise to close,
connect the pressure gauge(low pressure
side) to the service valve, and open the
3-way valve again.
Suspension hook
3. Connect the tank to refill with Refrigerant
4. Set the unit to Low pressure checking mode.
* Press the ON/OFF switch for 5 seconds.
* All lamps blink on the indoor unit.
5. Check the pressure indicated by the
pressure gauge(low pressure side).
* Refer to Low pressure graph.
6. Open the refrigerant tank and fill with refrigerant until the rated pressure is reached.
* It is recommended not to pour the refriger-
ant in too quickly, but gradually while
operating a pressure valve.
Compound
gauge
For mounting
other end of
hose when
not in use
Finger tight
fittings
Connected to
high pressure
side
R410A
High
pressure
gauge
Hand
wheel
Vacuum
pump
7. Stop operation of the air conditioner.
8. Close the 3-way valve, disconnect the
pressure gauge, and open the 3-way valve
again.
9. Close the cap of each valve.
Samsung Electronics3-10
3-2-2(h) Refrigerant Adjustment
Operating Instructions and Installation
ClassFor installation
Connection
Pipe Length
5m Max.
5~10m
Air-Purge
Method
Refer to the
detailed Air-Purge
Procedure
3-2-2(i) Flare nut fixing torque
Outer diameter
ø 6.35 (Liquid Side)
ø 9.52 (Gas Side)
ø 12.7 (Gas Side)
Refrigerant
Adjustment
Unnecessary
Add 20g of refrigerant
R410A(Add as liquid
state) for every 1m.
Fixing Torque Final Torque
160
300
500
Air-Purge
Method
Purge air using a
vaccum pump
Torque (kg-cm)
For service
Refrigerant
Quantity
refer to
specification sheet
Add 20g of refrigerant
R410A(Add as liquid
state) for every 1m.
200
350
550
3-11Samsung Electronics