Samsung RD040MHXCA Series, RD050MHXCA Series Installation Manual

FJM RD040MHXCA_IM_00000_E_2.23.10.indd 1 2010-2-24 19:56:20
E-2
Contents
SAFETY PRECAUTIONS
3
PREPARING THE INSTALLATION

Locating the Units
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6
INSTALLING THE UNIT

Installing the Refrigerant Pipe Work
. . . . . . . . . . . . . . . . . . . . . . . . . . .
14

Electrical Connections
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
25
COMPLETING THE INSTALLATION

Setting the Option Switch and Function of the Keys
. . . . . . . . . .
31

Pump Down Procedure
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
33

Completing the Installation
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
36

Final Checks and Trial Operation
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
36

Pump Down Procedure (When removing the product)
. . . . . . . .
37

Troubleshooting
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
38
FJM RD040MHXCA_IM_00000_E_2.23.10.indd 2 2010-2-24 19:56:20
ENGLISH
E-3
R410a refrigerant is used for Super FJM air conditioner.
- When using R410a, moisture or foreign substances may affect to the capacity and reliability of the product. Safety precautions must be taken when installing the refrigerant pipe.
- The design pressure of the unit is 4.1MPa(594.6psi). Select appropriate material and thickness according to the regulations.
- R410a is a quasi-azeotrope of two refrigerants. Make sure to charge liquid one when adding refrigerant. If you charge gaseous refrigerant, it may affect the capacity and reliability of the product as a result of change formation of the refrigerant.
Connect only the indoor units fit on R410a refrigerant. Check whether the indoor units can be
connected with the product’s catalogue. (When incorrect indoor units are connected, they cannot operate normally.)
When installing, use tools and materials for R410a only. If you use tools and materials for R22,
there is potential risk of bursting, injury, electric shock and fire because the pressure of R410a is higher than the pressure of R22(conventional).
Safety Precautions
You must install the product by qualified installer. If you install the product on your own or by unqualified
person, Samsung is not responsible for any damages which may occur due to incorrect installation.
Make sure to read the following safety precautions carefully before installation. Make sure to observe the cautions specified in this manual. Conduct a test run of the unit after installation and then explain all system functions to the owner.
Follow IEC (International Electrotechnical Commission) standards for the power input and
ISO (International Standards Organization) standards for input current.
FJM RD040MHXCA_IM_00000_E_2.23.10.indd 3 2010-2-24 19:56:20
E-4
WARNING
Hazards or unsafe practices that may result in severe personal injury or death.
 Installation must be carried out by a qualified installer. Do not attempt to repair, move, modify or reinstall
the unit on your own since such act may cause fire, electric shock or water leakage.
 Install the unit in a place where it is strong enough to hold the product weight. When installed in place
where it is not strong enough to withhold the product weight, the unit could fall and cause injury.
 The unit should be installed in accordance with the National Electrical regulations. Check if the voltage
and the frequency of the main power supply are those required for the unit to be installed and check the connection.
Do not share the power outlet with other appliances. Incomplete connection, defective
insulation or exceeding the permissible current may cause electric shock or fire.
 Use the specified wires to connect the indoor and outdoor units securely and attach the wires firmly to
the terminal block connecting sections so that the pressure is not applied to the sections. Inappropriate connection and fixing could cause fire.
 Attach the electrical cover to the indoor and outdoor unit securely without any gaps. If there are any
gaps, there is potential risk of fire or electric shock due to dust or water.
 Make sure to use the part provided or specified parts for the installation work. The use of defective parts
could cause an injury or leakage of water due to a fire, an electric shock, the unit falling, etc.
 Make sure that the refrigerant gas does not leak after completing the installation. If the refrigerant gas of
the indoor unit leaks and comes into contact with the fan heater, space heater or stove, harmful gas will be generated.
 Ensure that the national safety code requirements have been followed for the main supply circuit. Ensure
that a proper ground wire is in place. Do not connect the ground to a gas pipe, water pipe, lightning rod or telephone grounding. Defective grounding could cause electric shock.
 Do not install the unit in a place with direct sunlight, dangerous substances or where it is exposed to
inflammable gas leakage to prevent explosion, fire or personal injury.
 Perform the installation securely referring to the installation manual. Incomplete installation could cause
personal injury due to fire, electric shock and water leakage or from the unit falling.
 Check first the following situations before starting the operation during the installation.
- The pipe must be properly connected and make sure there is no leakage.
- Service valves must be open. If compressor is operated with the service valve closed, excessive pressure may damage parts of the compressor.
If leakage occurs on any of the connection, air inflow may also cause excessive pressure that could lead
to explosion.
 Stop the compressor before disconnecting the refrigerant pipe for pump-down operation. If you
disconnect the refrigerant pipe while compressor is operating with service valve open, air inflow will cause excessive pressure in the refrigerant cycle that could lead to explosion and personal injury.
 Do not assemble the power cord on your own, use two cables together to extend the cable length or
tangle the cable. Bad connection, isolation and over voltage may cause fire or electric shock.
 Make sure to turn off the main power when setting up the indoor unit electrical circuit or power cords.
There is a risk of electric shock.
 Make sure that proper circuit breaker and safety switches are installed. Install a ground leakage breaker
depending on the installation place (where it is humid). If not, it may cause electric shock.
 Do not install the unit by yourself (owners). Incorrect installation of the unit could cause injury due to
fire, electric shock and water leakage or from the unit falling. Consult a dealer or a qualified installer.
 Use the unit on a single outlet circuit. Do not share the power outlet with other appliances. Obtain the
consent by a qualified installer before connecting the unit to the power supply system. An all pole disconnection from the power supply must be incorporated in the fixed wiring with a contact opening of >3mm(1/8in)
.
 Manufacturer is not responsible for accidents due to incorrect installation. When you install the air conditioner in a small room, you consider a proper ventilation to prevent a
leakage level within the maximum permissible limit.
- In that case, you may die from suffocation by some possibility.
Fix the outdoor unit securely to prepare against strong wind or earthquake.
- If the outdoor unit is not properly fixed, it turns over and accidents may occur.
Safety Precautions (Continued)
WARNING
Hazards or unsafe practices that may result in severe personal injury or death.
CAUTION
Hazards or unsafe practices that may result in minor personal injury or property damage.
FJM RD040MHXCA_IM_00000_E_2.23.10.indd 4 2010-2-24 19:56:21
ENGLISH
E-5
CAUTION
Hazards or unsafe practices that may result in minor personal injury or property damage.
 Perform the drainage/piping work securely according to the installation manual. If not, water could
drop from the unit and household goods could get wet and damaged.
Fasten a flare nut with a torque wrench as specified in this installation manual. When fastened too
tight, a flare nut may break after a long period of time and cause refrigerant leakage.
Wear thick gloves during the installation process. If not, personal injury may occur due to the air
conditioner parts.
Be careful not to touch the outdoor unit inlet or aluminum pins. You may get personal injury. Do not install the outdoor unit in a place where animals could live. If an animal get contact with the
electric parts, damage or fire may occur. In addition ask the customer to maintain a clean installation place around it.
After completing the installation run the trial operation. If no error occurs, explain to the customer
how to use and clean the air conditioner according to the user’s manual. In addition give the installation manual and the user’s manual to the customer.
Check the unit for damage that may have taken place during transportation and do not install or use
damaged equipment.
All of the manufacturing and packaging material used for your new appliance are compatible with
the environment and can be recycled.
Dispose of the packaging material in accordance with the local requirements. This product is an air conditioning system and contains a coolant that must be recovered and
disposed of in an appropriate way by qualified personnel. At the end of the life cycle, take it to a proper recycling or disposal center or return it to the dealer so that it can be disposed correctly.
Do not connect the heater to the outdoor unit and do not install remodeled duct as you please.
- The capacity of the air conditioner may reduce, electric shock or fire may occur and it has a chance of occurrence of and accident like electric shock or fire.
Make sure that the condensed water dripping from the drain hose runs out properly and insulate the
drain pipe so that frost does not generate.
- Household goods may get wet if the drain pipe is not properly installed.
Install the power cable and communication cable of the indoor and outdoor unit at least 1.5m(5ft)
away from electric appliances.
- Noise may hear depending on the electric wave though the cables are installed away from electric appliances.
Install the indoor unit away from lighting apparatus using the ballast.
- If you use the wireless remote control, it may not operate normally.
The air conditioner should be used only for the applications for which it has been designed: the
indoor unit is not suitable to be installed in areas used for laundry.
Our units must be installed in compliance with the spaces indicated in the installation manual to
ensure either accessibility from both sides or ability to perform routine maintenance and repairs. The units’ components must be accessible and that can be disassembled in conditions of complete safety either for people or things.
For this reason, where it is not observed as indicated into the Installation Manual, the cost necessary to reach and repair the unit (in safety, as required by current regulations in force) with slings, trucks, scaffolding or any other means of elevation won’t be considered in-warranty and charged to end user.
If any gas or impurities except R410a refrigerant come into the refrigerant pipe, serious problem may
occur and it may cause injury.
Install the cables with supplied cables firmly. Fix them securely so that external force is not exerted to
the terminal board.
- If the connection or fixing is incomplete, it can cause trouble with a heat generation, electric shock or
fire and so on.
FJM RD040MHXCA_IM_00000_E_2.23.10.indd 5 2010-2-24 19:56:22
E-6
Locating the Units
PREPARING THE INSTALLATION
Decide the installation location regarding the following condition and obtain the user’s approval.
The outdoor unit must not be placed on its side or upside down, as the compressor lubrication oil will run
into the cooling circuit and seriously damage the unit.
Choose a location that is dry and sunny, but not exposed to direct sunlight
or strong winds.
Do not block any passageways or thoroughfares. Choose a location where the noise of the air conditioner when running and the discharged air do not
disturb any neighbours.
Choose a position that enables the pipes and cables to be easily connected to the indoor unit. Install the outdoor unit on a flat, stable surface that can support its weight and does not generate any
unnecessary noise and vibration.
Position the outdoor unit so that the air flow is directed towards the open area. Place the outdoor unit where there are no plants and animals because they may cause malfunction of
outdoor unit.
Maintain sufficient clearance around the outdoor unit, especially from a radio, computer, stereo system,
etc.
When installing the outdoor unit near seashore, make sure it is not directly exposed to sea breeze.
If you can not find a adequate place without direct see breeze, make sure to apply anti-corrosion coating on the heat exchanger.
Do not install the air conditioner in following places.
- The place where there is mineral oil or arsenic acid. There is a chance that parts may get damaged due to burned resin. The capacity of the heat exchanger may reduce or the air conditioner may be out of order.
- The place where corrosive gas such as sulfurous acid gas generates from the vent pipe or air outlet The copper pipe or connection pipe may corrode and refrigerant may leak.
- The place where there is a danger of existing combustible gas, carbon fiber or flammable dust. The place where thinner or gasoline is handled.
Deciding on Where to Install the Outdoor Unit
Do not install the outdoor unit in a snowy and cold area (low temperature and high humidity area
- where the temperature is below -7
°C(19.4°F) and humidity is higher than 85%) because according to operation condition (defrost, etc.), ice may be formed in the drain route. If the ice is accumulated, it may cause critical damage to the product. ex) lakeside of cold area in winter time, seashore, alpine region and etc.
CAUTION
- Install the outdoor unit in a place (such as near buildings etc.) where it can be prevented from sea breeze which can damage the outdoor unit.
- If you cannot avoid installing the outdoor unit by the seashore, construct a protection wall around to block the sea breeze.
- Install the outdoor unit in a place where water can drain smoothly.
Protection wall should be constructed with a solid
material such as concrete to block the sea breeze and the height and the width of the wall should be 1.5 times larger than the size of the outdoor unit. Also, secure over 700mm(2.3ft) between the protection wall and the outdoor unit for exhausted air to ventilate.
Sea
Sea breeze
Outdoor unit
Sea
Sea breeze
Outdoor unit
Sea
Sea breeze
Outdoor unit
Protection wall
 If you cannot find a place satisfying above conditions, please contact manufacturer. Make sure to clean
the sea water and the dust on the outdoor unit heat exchanger.
RD040MHXCA_IM_32073_E_4.06.10.indd 6 2010-4-19 15:51:36
ENGLISH
E-7
PREPARING THE INSTALLATION
If the outdoor unit is installed at a height, ensure that its base is firmly fixed
in position.
Make sure that the water dripping from the drain hose runs away correctly
and safely.
If the paint on the cabinet comes off during installation, make sure to
re-paint or protect damaged area to prevent rust. If the cabinet becomes rusted, it may reduce durability of the outdoor unit.
You have just purchased a system air conditioner and it has been
installed by your installation specialist.
This device must be installed according to the national electrical rules.
With an outdoor unit having net weight upper th
an 60kg(132.3lb), we
suggest do not install it suspended on wall, but considering floor
standing one.
CAUTION
Outdoor Unit
Indoor Unit
Remote Control
1m(3.28ft)
or more
1m
(3.28ft
)
or more
1.5m(5ft) or more
1.5m(5ft) or more
3
m(10ft) or more
Breaker
Stereo
Breaker
1.5m(5ft) or more
Avoid a place that may disturb your neighbor. Noise may occur from the
outdoor unit and the discharged air may run into the neighborhood. (Be careful of the operation time in a residential area.)
Install the outdoor unit on a hard and even area that can support its weight. Choose a flat place that rainwater does not settle or leak. Choose a place avoiding strong winds. Maintain sufficient space for repairs and service. Choose a place where you can easily connect the pipes and cables to the indoor
unit.
Make sure that the condensed water dripping from the drain hose runs out
properly and safely.
If you install the outdoor unit by the sea or a spa, concern about corrosion. Build a support where may have a heavy snow so that the air intake is not
blocked by snow.
Install a protective safety fence to eliminate the possibility of falling.
FJM RD040MHXCA_IM_32073_E_3.17.10.indd 7 2010-3-17 18:53:10
E-8
Locating the Units
(Continued)
 Observe the clearances and dimensions as seen below when installing the outdoor unit.  If you install several outdoor units simultaneously, observe the space for ventilation and free airflow.
If the space for ventilation is insufficient, the air conditioner may be inefficient.
SAMSUNG logo is attached on the front side of the outdoor unit.
Space Requirements for Outdoor Unit
When installing 1 outdoor unit
300(12)
or more
1500(60) or more
1500(60)
or more
300(12)
or more
When the walls are blocking front and
the rear side of the outdoor unit
500(20) or more
300(12)
or more
The upper part of the outdoor unit and
the air outlet is opposite the wall
1500(60) or more
2000(80) or more
The upper part of the outdoor unit
and the air outlet is toward the wall
300(12) or more
150(6) or more
600(24) or more
When 3 sides of the outdoor unit
are blocked by the wall
When the air outlet is toward the wallWhen the air outlet is opposite the wall
Unit : mm(inch)
Figure Description
Top view Side view
Front side: Air outlet
Back side: Air intake
Back side: Air intake
Front side: Air outlet
, Air flow direction.
PREPARING THE INSTALLATION
FJM RD040MHXCA_IM_00000_E_2.23.10.indd 8 2010-2-24 19:56:25
ENGLISH
E-9
When installing more than 1 outdoor unit
Unit : mm(inch)
1500(60)
or more
When the air outlet is toward the wall
300(12)
or more
300(12) or more
1500(60) or more
600(24) or more 3000(120) or more 300(12)
or more
3000(120) or more
600(24) or more 600(24) or more
300(12)
or more
1500(60)
or more
600(24) or more 600(24) or more
600(24) or more
When 3 sides of the outdoor unit are blocked by the wall
When the walls are blocking front and the rear side of the outdoor units
When front and rear side of the outdoor unit is toward the wall
PREPARING THE INSTALLATION
600(24) or more
600(24) or more
FJM RD040MHXCA_IM_00000_E_2.23.10.indd 9 2010-2-24 19:56:25
E-10
Locating the Units
(Continued)
Install the indoor unit only for R410a.
Selecting Outdoor Unit Combination
When moving with a crane or straps
Select the moving route.
 
Secure the strength of the carrying path to resist against the weight of the outdoor unit.
 
Do not slant the product more than 30˚ when carrying it. (Do not lay the product down sideways.)
 
The surface of the heat exchanger is sharp. Be careful not to be get injury while moving.
Moving the Outdoor Unit
Outdoor unit
(Series)
Capacity of the outdoor
unit (Btu/h)
Maximum of connected
indoor units
Total capacity of connected
indoor units
(Btu/h)
RD040MHXCA 36,000 6 20,000~45,000
RD050MHXCA 48,000 8 27,000~60,000
 
You may connect indoor units within 50~130% of the outdoor unit capacity. Smallest indoor unit(7,500Btu/h) was used to calculate ‘Maximum of connected indoor units’.
 
Connect maximum 6 to 8 indoor units to the selected outdoor unit.
 
Total capacity of connected indoor units must be within the capacity of outdoor unit.
 
If all indoor units operate simultaneously when total capacity of indoor units exceeds 100% of the outdoor unit, actual capacity of each indoor unit may be reduced a little as compared with its rated capacity.
PREPARING THE INSTALLATION
General Tools
Tools for test operations
Vacuum Pump(Backward flowing prevention)  Manifold Gauge Stud Finder  Torque Wrench  Pipe Cutter Reamer Pipe Bender  Spirit Level Screw Driver  Spanner  Drill L Wrench  Measuring Tape
Thermometer  Resistance Meter  Electroscope
Tools Required for Installation
When the moving distance of the product is close enough for
installation personnel to carry
- 2 people should move the product using the carry handle as shown in the picture.
- Be careful not to damage the heat exchanger.
- Be careful not to get injured by the sharp edge of the heat exchanger.
When moving by installation personnel
Wire rope/straps
Wood palette
In case of placing the outdoor unit on a high ground such as rooftop
- Fasten the wire rope as seen in the picture.
- Move the product with its package on, to prevent any damages caused by the rope.
FJM RD040MHXCA_IM_00000_E_2.23.10.indd 10 2010-2-24 19:56:27
ENGLISH
E-11
PREPARING THE INSTALLATION
1
Disassemble the three screws (with an electric driver) which fixes wood palette.
2
Disassemble the bottom-left screw with monkey spanner. Do not remove guard fan.
3
After removing the wood palette, move the outdoor unit to the installation place.
4
Fasten the bottom-left screw with monkey spanner first, and then fasten the other three anchor bolts.
Disassembling the Leg Base and Wood Palette / Fastening the Anchor Bolt
Monkey spanner
Wood palette
Screw
FJM RD040MHXCA_IM_00000_E_2.23.10.indd 11 2010-2-24 19:56:33
E-12
PREPARING THE INSTALLATION
Locating the Units
(Continued)
Install the outdoor unit higher than 150mm(6in) from the base surface and install the drain hole to connect the pipe to the drainage.
If forward fan outdoor unit is installed where has average fallen snow 150mm(6in) over, outward duct should be attached to the outdoor unit.
The concrete foundation should be 1.5 times larger than bottom of the outdoor unit.
When heating, condensed water may be generated. Pay attention to waterproof and drainage of the concrete foundation where the outdoor unit is installed. (An ice road may form on the base surface in winter
.)
Make up for wire mash or steel bar so that the outdoor unit is not damaged or broken when installing concrete foundation.
When installing the outdoor units in same place simultaneously, install the H beam inside concrete foundation. (When installing a number of outdoor unit, you can install it on the concrete foundation
.)
Install the H beam(150mm x 150mm x t10 (6inch x 6inch x t 3/8 inch) : basic specification) to jut out from the concrete foundation.
After installing the H beam, apply corrosion protection.
Install a square pad(t=20mm(3/4 inch) or more) to prevent vibration of the outdoor unit delivering to the base surface when installing the concrete for the outdoor unit.
Place the outdoor unit on the H beam and fix it with the bolt, nut and washer.
Installing the Outdoor Unit
Do not install the outdoor unit on a wood palette.
Fix the outdoor unit completely to the base surface with anchor bolts.
The manufacturer is not responsible for the damage occurred by not keeping standard of the installation.
CAUTION
Outdoor unit
Anchor bolt
Nut, Spring washer
H beam
Square pad
A+10~20mm(3/8~3/4 inch) or more
A
20mm
(3/4 inch)
75mm(3inch)
< When installing on the ground >
Drain hole 150(6) or more
< When installing on the roof >
Install the outdoor unit horizontally on the ground
150(6) or more
Base mount construction
Unit : mm(inch)
FJM RD040MHXCA_IM_00000_E_2.23.10.indd 12 2010-2-24 19:57:21
ENGLISH
E-13
PREPARING THE INSTALLATION
Outdoor unit base mount and anchor bolt position
When tightening the anchor bolt Tighten the rubber washer to prevent the outdoor unit bolt connection part
from corroding.
CAUTION
Rubber washer
When installing 1 outdoor unit
Outdoor unit
(Rear side)
More than 1/50 slope
Open to air
Drain plug
When installing more than 1 outdoor unit
Open the upside of connected parts of outdoor units to prevent inner pressure. Do not place a trap on the concentrated pipe. And install the drain pipe horizontally with a slope of 1/50 or more. Insulate the drain pipe and drain plug by using the insulation over 10mm(3/8inch). Install a self-regulation heat cable to prevent the drain pipe from freezing.
Installing the drain pipe
Unit : mm(inch) Anchor bolt position (ø7, 4 holes )
Parts shown in the picture is where the copper pipe may be passing by or the external plate may be near the copper
pipe. When using screw for installing the air direction changing device such as heating air cover, check and make sure that it does not damage the copper pipe.
Caution When Installing Cover for Heating Air Direction Change
< Internal view from bottom>
Iron washer
Outdoor unit
(Rear side)
More than 1/50 slope
Open to air
Drain plug
Outdoor unit
(Rear side)
Outdoor unit
(Rear side)
Drain pipe covered with
insulation
Drain pipe
Insulation
670(26-3/8)
932(36-11/16)
375(14-3/4)
403(15-7/8)
427(16-13/16)
FJM RD040MHXCA_IM_00000_E_2.23.10.indd 13 2010-2-24 19:57:22