This product requires a three-prong grounded
outlet. The installer must perform a ground
continuity check on the power outlet box before
beginning the installation to ensure that the
outlet box is properly grounded. If not properly
grounded, or if the outlet box does not meet
electrical requirements noted (under ELECTRICAL
REQUIREMENTS), a qualified electrician should be
employed to correct any deficiencies.
CAUTION: For personal
safety, remove the
house fuse or open
the circuit breaker
before beginning the
installation to avoid
severe or fatal shock
injury.
CAUTION: For personal safety, the mounting
surface must be capable of supporting the
cabinet load in addition to the added weight
of this 69 pound product, plus additional oven
loads of up to 50 pounds or a total weight of
109 pounds.
CAUTION: For personal safety, do not install
this product in cabinetry configured as an
island or a peninsula. The microwave oven
must be mounted to BOTH a top cabinet AND
a wall.
NOTE: For easier installation and personal
safety, we recommend that two people install
this product.
IMPORTANT – PLEASE READ CAREFULLY.
FOR PERSONAL SAFETY, THIS APPLIANCE
MUST BE PROPERLY GROUNDED TO AVOID
SEVERE OR FATAL SHOCK.
The power cord of this
appliance is equipped
with a three-prong
(grounding) plug which
mates with a standard
three-prong (grounding)
Insure proper
ground exists
before use.
You should have the wall receptacle and circuit
checked by a qualified electrician to make sure
the receptacle is properly grounded.
If you have a standard two-prong wall
receptacle, it is very important to have it
replaced with a properly grounded threeprong wall receptacle, installed by a qualified
electrician.
DO NOT, UNDER ANY CIRCUMSTANCES, CUT,
DEFORM OR REMOVE ANY OF THE PRONGS
FROM THE POWER CORD. DO NOT USE WITH
AN EXTENSION CORD.
wall receptacle to
minimize the possibility
of electric shock hazard
from this appliance.
ELECTRICAL
REQUIREMENTS
Product rating is 120 volts AC, 60 Hertz, 14.5 amps
and 1.7 kilowatts.This product must be connected to
a supply circuit of the proper voltage and frequency.
Wire size must conform to the requirements of the
National Electrical Code or the prevailing local code
for this kilowatt rating. The power supply cord and
plug should be brought to a separate branch circuit
single grounded outlet of at least 15 A and max
of 20 A. The outlet box should be located in the
cabinet above the microwave oven. The outlet box
and supply circuit should be installed by a qualified
electrician and conform to the National Electrical
Code or the prevailing local code.
NOTE: Read these next two pages only if you plan to vent your exhaust to the outside. If you plan to
recirculate the air back into the room, proceed to page 11.
OUTSIDE TOP EXHAUST (EXAMPLE ONLY)
The following chart contains an example of one possible ductwork installation.
DUCT PIECES
Roof Cap24 ft.x(1)=24 ft.
EQUIVALENT
LENGTH
x
NUMBER
USED
=
EQUIVALENT
LENGTH
12 Ft. Straight Duct
(6" Round)
Rectangular-toRound Transition
Adaptor*
Equivalent lengths of duct pieces are based on actual tests
and reflect requirements for good venting performance with
any vent hood.
* IMPORTANT: If a rectangular-to-round transition adaptor is used, the bottom corners of the damper will have to be
cut to fit, using the tin snips, in order to allow free movement of the damper.
12 ft.x(1)=12 ft.
5 ft.x(1)=5 ft.
Total Length=41 ft.
OUTSIDE BACK EXHAUST (EXAMPLE ONLY)
The following chart contains an example of one possible ductwork installation.
DUCT PIECES
Wall Cap40 ft.x(1)=40 ft.
3 Ft. StraightDuct (3¼"
x 10" Rectangular)
90 ° Elbow10 ft.x(2)=20 ft.
EQUIVALENT
LENGTH
3 ft.x(1)=3 ft.
x
NUMBER
USED
EQUIVALENT
=
LENGTH
Equivalent lengths of duct pieces are based on actual tests
and reflect requirements for good venting performance with
any vent hood.
NOTE: For back exhaust, care should be taken to align the exhaust with the space between studs, or the wall should
be prepared at the time it is constructed by leaving enough space between the wall studs to accommodate exhaust.
NOTE: If you need to install ducts, note that the total
duct length of 3 ¼" x 10" rectangular or 6" diameter
round duct should not exceed 140 equivalent feet.
Outside ventilation requires a HOOD EXHAUST DUCT.
Read the following carefully.
NOTE: It is important that venting be installed using
the most direct route and with as few elbows as
possible. This ensures clear venting of exhaust and
helps prevent blockages. Also, make sure dampers
swing freely and nothing is blocking the ducts.
Exhaust connection:
The hood exhaust has been designed to mate with a
standard 3 ¼" x 10" rectangular duct.
If a round duct is required, a rectangular-to-round
transition adaptor must be used. Do not use less
than a 6" diameter duct.
Maximum duct length:
For satisfactory air movement, the total duct length
of 3 ¼" x 10" rectangular or 6" diameter round duct
should not exceed 140 equivalent feet.
Elbows, transitions, wall and roof
caps, etc. present additional resistance to airflow
and are equivalent to a section of straight duct which is
longer than their actual physical size. When calculating
the total duct length, add the equivalent lengths of all
transitions and adaptors plus the length of all straight
duct sections. The chart below shows you how to
calculate total equivalent ductwork length using the
equivalent length in feet of some typical ducts.
DUCT PIECES
Rectangular-to-Round
Transition Adaptor*
Wall Cap 40 ft.x( )=ft.
90 ° Elbow 10 ft.x( )=ft.
45 ° Elbow 5 ft.x( )=ft.
90 ° Elbow 25 ft.x( )=ft.
45 ° Elbow 5 ft.x( )=ft.
Roof Cap24 ft.x( )=ft.
Straight Duct 6" Round or
3¼" x 10" Rectangular
* IMPORTANT: If a rectangular-to-round
transition adaptor is used, the bottom
corners of the damper will have to be cut to
fit, using tin snips, to allow free movement
of the damper.
EQUIVALENT
LENGTH
5 ft.x( )=ft.
1 ft.x( )=ft.
NUMBER
x
USED
Total Ductwork =ft.
Equivalent lengths of duct pieces
are based on actual tests and reflect
the requirements for good venting
performance with any vent hood.