Samsung MCM-A202DN Installation Manual

Page 1
Page 2
OnOff Controller
MCM-A202DN
Air Conditioner
installation manual
This manual is made with 100% recycled paper.
imagine the possibilities
Thank you for purchasing this Samsung product.
DB68-03721A(1)
Page 3
Safety Precautions
This installation manual indicates you to install the OnOff controller which is connected to the indoor unit. For installation of other optional accessories, see an appropriate installation manual.
Read carefully this installation manual before installation and check
WARNING
whether the OnOff controller is installed correctly after installation.
Do not attempt to install or repair this OnOff controller by yourself.
This OnOff controller contains no user-serviceable parts. Always
consult authorized service personnel for repairs.
When moving, consult authorized service personnel for
disconnection and installation of the OnOff controller.
Ensure that the wall is strong enough to support the weight of the
OnOff controller.
The OnOff controller must be installed according to the national
electrical rules by an installation specialist.
When wiring, connect the supplied wires firmly and fasten them
securely so that external force cannot be applied to the terminal connection area.
Position all the wires correctly so that the cover of the electric
equipment section doesn’t float. Then securely fasten the cover.
Before handling or adjusting the power loading terminal, switch
off the power supply.
When you want to disuse the OnOff controller, consult authorized
installation center.
Do not use inflammable gases near the OnOff controller.
CAUTION
2
Do not install the OnOff controller in a location where it will come
into contact with the combustible gases, machine oil, sulphide gas, etc.
Avoid a location where acid/alkali solution or special spray is used.
 
Choose a location that is dry and sunny, but not exposed to direct sunlight. Available temperature is between 0°C(32°F) and 39°C(102°F).
Do not spill water into the OnOff controller.
Do not give tensile strength to the cable to avoid disconnection. Do not press buttons with a pointed thing.
 
Do not connect the power cable to the control terminal.
If the OnOff controller is installed in a hospital or other special
places, it should not affect other electronic devices.
Do not install the product in an area where mineral oil is kept or
arsenic acid of oil and steam frequently exist such as a kitchen.
Do not install the product in an area where corrosive gases such as ammonia gas or sulfurous acid gas are generated e.g. an exhaust pipe of a toilet or an outlet of ventilating opening.
Do not install the product in an area where a machine that
generates electromagnetic waves is placed.
Do not install the product in an area where combustible gas
leakage is expected or volatile flammable material such as thinner and gasoline are handled.
Do not install the product in an area where carbon textile or
flammable dust float in the air.
Do not install the product in an area where corrosion is expected
such as shoreline and hot spring.
Page 4
OnOff Controller Installation
Accessories
OnOff
Controller (1)
Cable-tie (2) Cable Clamp (5) M4x16 Tapped
Screw (7)
User’s manual (1)
Installation manual (1)
Wiring Diagram
Number of indoor unit that connect to the same OnOff controller is up to 128. It can be connected to the communication terminal of the indoor unit.
OnO
controller
Outdoor unit
RMC(1) address
set to “0”
OnO
controller
Indoor unit
Outdoor unit
Indoor unit Indoor unit Indoor unit
RMC
00
Indoor unit
RMC
01
Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit
RMC
RMC
04
05
RMC
RMC
RMC
RMC
03
RMC
07
RMC
08
09
02
06
Outdoor unit
Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit
RMC
RMC
OA
OB
RMC
OC
RMC
OD
Selecting pressure connection terminal
Based on the normal dimension of the connecting power cable, select the pressure connection terminal.
Insulate the connection area between pressure connection terminal and the connecting power cable with sheath.
Silver soldering
ud
t
S
W
1 d
Φ
Wire range that can
be connectable
mm
AWG
(inch2)
0.25 ~
1.65
22~16
(0.0003 ~
0.0025)
Rated
Dimension
2
mm
(inch2)mm(inch)
1.5
(0.0023)3(0.1181)
2
Stud
Dimension
Basic dimension [mm (inch)]
t Φd1 E F W L
0.7
3.8
(0.1496)
4.5
(0.1771)
(0.2480)
(0.0275)
RMC
6.3
OE
5.5
(0.2165)
19.05 (0.75)
RMC
OF
3
Page 5
OnOff Controller Installation (Continued)
Setting up the installation option of Indoor Unit and OnOff Controller
In Case of Installing OnOff Controller Only
Set the Indoor Unit installation option SEG5 to “1”.
1
It means use the OnOff controller.
Set the RMC(1) and RMC(2) address of Indoor Unit.
2
Example) RMC(1) = SEG11 = 0~F, RMC(2) = SEG12 = 0~F However, when RMC(1) = F, RMC(2) can be set between 0~E
OnOff Controller
SW22
SW21
RMC(1) address (SW01) = 0~F
SW22
SW21
OFF : Left
DIP Switch
Cooling
Heating
ON : Right
Cooling/Heating switch
You must reset the OnOff controller to apply the changed RMC(1) address.
4
Page 6
Indoor Unit option code system
SEG2 SEG3 SEG4 SEG5 SEG6 SEG7 SEG8 SEG9 SEG10 SEG11 SEG12
SEG1
X X X X X 1 X X X X X
0
SEG14 SEG15 SEG16 SEG17 SEG18 SEG19 SEG20 SEG21 SEG22 SEG23 SEG24
SEG13
X X X X X 3 X X X X X
2
SEG2
= A : Address option = 2 : Installation option
X
SEG5
= 0 : not use the OnOff controller = 1 : use the OnOff controller
X
- When setting the installation option
SEG11 SEG12
X X X
Note
= RMC(1), RMC(2)
address (00~FE)
Detailed method about Installation option establishment refers to Indoor
Unit manual.
Installation option must set the SEG2 value as "2" in Indoor Unit option code
Address option must set the SEG2 value as “A" in Indoor Unit option code
SEG9
- When setting the address option = 1: RMC address setting
5
Page 7
OnOff Controller Installation (Continued)
Different Levels of the OnOff Controller
Adjust the DIP switch in the OnOff controller PCB and set a level. This will enable the user to control the indoor units connected to the OnOff controller according to the set level.
Switch
No.
LEVEL 0
LEVEL 1
LEVEL 2
DIP Switch
1 2
OFF OFF
ON OFF
OFF ON
Cooling
Heating
SW22
SW22
SW21
Meaning
Among the various controllers, such as the OnOff controller, wired/wireless controller and the indoor unit button, the air conditioner will only be able to operate with the most recently used controller
The wired/wireless controller can only be used when the OnOff controller is powered on.
The air conditioner can only be operated with the OnOff controller.
RMC(1) address (SW01) = 0~F
SW22
SW21
OFF : Left ON : Right
Cooling/Heating switch
Note The LEVEL of the OnOff controller is ‘0’ when all the
switches are in the 'OFF' position.
Changed LEVEL will be applied immediately when you
turn on or off the operation with an OnOff controller.
Level application and authorization for controlling from OnOff controller can be restricted depending on the Level setting from the upper controller with priority.
Ex) OnOff controller cannot control the indoor units if the control
level set from the DMS is higher than the level of OnOff controller.
6
Page 8
Setting the option for OnOff controller
You can adjust the DIP switch (SW21) on PCB of the OnOff
1
controller to set the option and control the OnOff controller according to the selected option.
SW21
1 2
ON -
OFF -
All the DIP switches of the OnOff controller is set to OFF as factory default setting.
SW21 setting of the DIP switch will be applied instantly.
Option setting for communication can be executed regardless of the Level setting.
Disable OnOff controller usage
Enable OnOff controller usage
Contents
7
Page 9
OnOff Controller Installation (Continued)
Control layer connection
To install 128 units to 16 or less number of outdoor units. (Group control of units)
OnO
controller
RMC(1) address set to “0”
Indoor Unit #1~#15 assign
OnO
controller
RMC(1) address set to “1”
Indoor Unit #16~#31 assign
Outdoor unit
RMC(1) address set to “2”
Indoor Unit #32~#64 assign
8
OnO
controller
Page 10
Indoor unit
0
Indoor unit
1
Indoor unit
2
Indoor unit
13
Indoor unit
14
Indoor unit
15
Indoor unit
ADDRESS
Indoor unit
31
Indoor unit
ADDRESS
Indoor unit
32
Indoor unit
ADDRESS
Indoor unit
63
RMC(1) RMC(2)
Indoor unit
30
RMC(1) RMC(2)
Indoor unit
33
RMC(1) RMC(2)
Indoor unit
62
0
0 1 2 3 4 5 6 7 8 9 A B C D E F
Indoor unit
29
Indoor unit
18
Indoor unit
17
Indoor unit
16
1
0 1 2 3 4 5 6 7 8 9 A B C D E F
Indoor unit
34
Indoor unit
45
Indoor unit
46
Indoor unit
47
2
0 1 2 3 4 5 6 7 8 9 A B C D E F
Indoor unit
61
Indoor unit
50
Indoor unit
49
Indoor unit
48
Indoor unit
ADDRESS
RMC(1) RMC(2)
2
0 1 2 3 4 5 6 7 8 9 A B C D E F
9
Page 11
OnOff Controller Installation (Continued)
Set layer connection
To install 80 units for 1 outdoor unit (Group control of units)
OnO
controller
RMC(1) address set to “0”
Indoor Unit #1~#15 assign
OnO
controller
RMC(1) address set to “1”
Indoor Unit #16~#31 assign
Outdoor unit
RMC(1) address set to “2”
Indoor Unit #32~#64 assign
10
OnO
controller
Page 12
Indoor unit
0
Indoor unit
1
Indoor unit
2
Indoor unit
13
Indoor unit
14
Indoor unit
15
Indoor unit
ADDRESS
Indoor unit
31
Indoor unit
ADDRESS
Indoor unit
32
Indoor unit
ADDRESS
Indoor unit
63
RMC(1) RMC(2)
Indoor unit
30
RMC(1) RMC(2)
Indoor unit
33
RMC(1) RMC(2)
Indoor unit
62
0
0 1 2 3 4 5 6 7 8 9 A B C D E F
Indoor unit
29
Indoor unit
18
Indoor unit
17
Indoor unit
16
1
0 1 2 3 4 5 6 7 8 9 A B C D E F
Indoor unit
34
Indoor unit
45
Indoor unit
46
Indoor unit
47
2
0 1 2 3 4 5 6 7 8 9 A B C D E F
Indoor unit
61
Indoor unit
50
Indoor unit
49
Indoor unit
48
Indoor unit
ADDRESS
RMC(1) RMC(2)
2
0 1 2 3 4 5 6 7 8 9 A B C D E F
11
Loading...