SAMSUNG AWH126JE0K_ALM.ME12.1.16 Service Manual

ROOM AIR CONDITIONER
FANCOOLHEATDEICE
POWER / MODE
°C
Hour
AWH126JE AWH127JE
Manual
SERVICE
AIR CONDITIONER CONTENTS
1. Precautions
2. Product Specifications
3. Installation and Operating Instructions
5. Troubleshooting
6. Exploded Views and Parts List
7. Block Diagram
8. PCB Diagram
9. Wiring Diagram
10. Schematic Diagrams
ELECTRONICS
Samsung Electronics Co., Ltd. MAR. 1998.
©
Printed in Korea. Code No. DB81-10152A
1. Precautions
1. Warning: Prior to repair, disconnect the power cord from the circuit breaker.
2. Use proper parts: Use only exact replacement parts. (Also, we recommend replacing parts rather than repairing them.)
3. Use the proper tools: Use the proper tools and test equipment, and know how to use equipment may cause problems later­intermittent contact, for example.
4. Power Cord: Prior to repair, check the power cord and replace it if necessary.
5. Avoid using an extension cord, and avoid tapping into a power cord. This practice may result in malfunction or fire.
6. After completing repairs and reassembly, check the insulation resistance, Procedure: Prior to applying power, measure the resistance between the power cord and the ground terminal. The resistance must be greater than 30 megohms.
Fig. 1-1 Avoid Dangerous Contact
Fig. 1-2 No Tapping and No Extension Cords
7. Make sure that the grounds are adequate.
8. Make sure that the installation conditions are satisfactory. Relocate the unit if necessary.
9. Keep children away from the unit while it is being repaired.
10. Be sure to clean the unit and its surrounding area.
Fig. 1-3 No Kids Nearby!
Fig. 1-4 Clean the Unit
Samsung Electronics 1-1
2. Product Specifications
2-1 Table
Item
T ype Dimensions: (Width X Height X Depth) Packing Size (Width X Height X Depth) Voltage: Phase Frequency Operating Current Power Consumption Refrigerant Type Refrigerant Charge Cooling Capacity EER Net Weight Condenser Condenser Fan Evaporator Evaporator Fan Fan Motor Compressor(Rotary) Overload Protect Compressor Capacitor Fan Motor Capacitor Fan Speed Control Thermo Control OFF Timer
Unit of Measure
-
mm
mm
Volt
-
Hz
A
W
FREON
g
BTU/h
BTU/h.W
kg Row Type Row Type
W
Model
­µF/ VAC µF/ VAC
-
-
hr
AWH126/127JE (COOL/HEAT)
Window
600
X 394 X 555
X 470 X 655
715
220 - 240
Single
50
5.9 / 5.3
1,350 / 1,210
R-22
680
11,500 / 11,500
8.5 / 9.5 45
X 14
2
Propeller Fan
2 X 14
Blower
AMAFS100ATEA
48H124JV1E4
MRA12030-12008
30 / 450
3.5 / 450
Fan speed switch (High & Low)
Thermistor
DUAL TYPE
24
Remarks
Samsung Electronics 2-1
2-2 Dimensions
600
394 595
FANCOOLHEATDEICE
POWER / MODE
°C
Hour
2-2-1 Main Unit
Front view Side view
Unit : mm
2-2-2 Remote Control
Mode selection Buttons
(FAN, HEAT, COOL)
Temperature adjustment buttons
Fan speed adjustment Buttons
(HIGH, LOW)
2-2 Samsung Electronics
Timer setting buttons
ON/OFF Buttons
Air flow swing button
3. Installation and Operating Instructions
3-1 Installation
When selecting the area for installing the unit, be sure to obtain approval of the customer.
*
1. Make sure that you install the unit in an area that provides good ventilation.
The air conditioner must not be blocked by any obstacle affecting the air flow near the air inlet and air outlet.
2. Make sure that you install the unit in an area which can endure the weight and vibration of the unit.
3. Make sure that you install the unit away from heat or vapor.
4. Make sure that you install the unit in an area where the cooled air can be evenly spread in a room.
5. Make sure that you install the unit in an area away from TVs, audio units, cordless phones, fluorescent lighting fixtures and other electrical appliances. (obtain a clearance of at least one meter)
Caution:
6. Make sure that you install the unit in an area which provides easy drainage for condensed water.
7. Make sure that you install the unit in an area not exposed to rain or direct sunlight. (Install a separate sunblind if exposed to direct sun-
light.)
8. Do not install the unit in an area subjected to noise or vibration amplification which may affect your neighbor. (Fix the unit firmly if mounted in a high place.)
Do not use the air conditioner in such areas as a greasy area(including machine oil), saline area(sea side), or sulphuric area(hot spring). When using the air conditioner in these areas, special maintenance is required. Contact your local dealer or our service center for advice.
Samsung Electronics 3-1
3-2 Function Description
FANCOOLHEATDEICE
POWER / MODE
°C
Hour
Remote control sensor
Deice indicator
Operating mode indicator
Temperature/Timer settings
Temperature indicator Timer indicator
POWER/MODE button
3-2-1 Cooling operation mode
The compressor is turned on and off according to the ambient temperature and set temperature.
1. Compressor on and off control ¥ Compressor on and off control according to the ambient temperature.
The compressor is turned off when "ambient temperature = set temperature -1ûC"
*
The compressor is turned on when "ambient temperature = set temperature +1ûC"
*
2. Default value after power reset set temperature = 18ûC
FAN SPEED = HIGH
3. Set temperature indicating (setting) range : 1ûC interval from 18ûC to 30ûC.
3-2-2 Heating operation mode
The compressor is turned on and off according to the ambient temperature and set temperature.
1. Compressor on and off control. ¥ Compressor on and off control according to the ambient temperature.
The compressor is turned off when "ambient temperature = set temperature +1ûC"
*
The compressor is turned on when "ambient temperature = set temperature -1ûC"
*
2. Default value after power reset set temperature = 24ûC
FAN SPEED = HIGH
3. Set temperature indicating (setting) range : 1ûC interval from 16ûC to 30ûC.
3-2-3 Fan operation mode
1. If "Fan operation mode" signal is received from remocon.
the compressor is immediately turned off and only fan motor is operated at set blowing speed.it changes such as "HIGH → LOW HIGH"( if Fan speed is selected).
2. The initial FAN speed is set to "HIGH".
3. The set temperature can not be indicated and set.
3-2 Samsung Electronics
3-2-4 LED lamp and LED display indication in case of error detection
ERROR OPERATION
ROOM THERMISTOR
(OPEN OR SHORT)
INDOOR PIPE THERMISTOR
(OPEN OR SHORT)
OUTDOOR PIPE THERMISTOR
(OPEN OR SHORT)
LED LAMP DISPLAY
COOL HEAT FAN
7-SEG
LED DISPLAY
E1 displayed E5 displayed
E6 displayed
Lamp blinking at every second (on for 0.5s and off for 0.5s)
LED lamp off
1. Set operation in case of error occurrence. ¥ Malfunction of each temperature sensor (open, short)
- Error mode display, warning sound.
- The operation status is off.
2. The "outdoor pipe thermistor" error mode carry out checking only during heating operation and
do not carry out checking during "COOLING" and "FAN" operation.
3-2-5 Panel key operation
Key discription
Key name
Power/Mode 1. Operation mode change and POWER OFF(in case of model option heat pump) TACT
at every ON
*
- Selected as "OFF –> COOL –> HEAT –> FAN –> OFF". (Default=OFF) Continuous operation is not available.
*
Key operational function Key Type
Samsung Electronics 3-3
3-2-6 LED lamp operation specifications
LAMP name Operations specifications
COOL The mode is set to "COOL" –> ON
Others –> OFF
HEAT The mode is set to "HEAT" –> ON
Others –> OFF
FAN The mode is set to "FAN" –> ON
Others –> OFF
ûC The set temperature is displayed or set -> ON
Others –> OFF
HR During setting of the convenient reserve (OFF TIMER) time -> blinking
After setting of the convenient reserve (OFF TIMER) time -> ON Others –> OFF
DEICE Till the "DEICING" operation is completed during heating opertion -> ON
Others –> OFF
In case of (set) temperature display
-> NO. (1) 7 seg. LED display indicates temperature of the tens digit (ûC, ûF)
-> NO. (2) 7 seg. LED display indicates temperature of the units digit (ûC, ûF) In case of time (OFF TIMER) display
(1) (2)
-> NO. (1) 7 seg. LED display indicates time of the tens digit
-> NO. (2) 7 seg. LED display indicates time of the units digit
3-4 Samsung Electronics
3-2-7 Resistor values table of “ROOM THERMISTOR”, “INDOOR PIPE THERMISTOR”
and “OUTDOOR PIPE THERMISTOR” for each temperature
1. Room thermistor (SPEC : 103AT)
Temperature
[˚C]
70 69 68 67 66 65 64 63 62 61 60
59 58 57 56 55 54 53 52 51 50
49 48 47 46 45 44 43 42 41 40
39 38 37 36 35 34 33 32 31 30
THERMISTOR RESISTOR
[Kohm]
2.229
2.296
2.365
2.437
2.512
2.589
2.669
2.752
2.838
2.928
3.021
3.116
3.216
3.319
3.426
3.537
3.652
3.772
3.897
4.026
4.161
4.300
4.444
4.594
4.749
4.912
5.080
5.256
5.439
5.630
5.828
6.033
6.246
6.468
6.699
6.941
7.192
7.455
7.729
8.015
8.313
Temperature
[˚C] 29
28 27 26 25 24 23 22 21 20
19 18 17 16 15 14 13 12 11 10
9 8 7 6 5 4 3 2 1 0
-1
-2
-3
-4
-5
-6
-7
-8
-9
THERMISTOR RESISTOR
[Kohm]
8.622
8.944
9.281
9.632
10.000
10.380
10.780
11.200
11.630
12.090
12.560
13.060
13.570
14.120
14.680
15.280
15.900
16.550
17.240
17.960
18.700
19.480
20.290
21.150
22.050
22.990
23.900
25.030
26.130
27.280
28.470
29.720
31.040
32.430
33.890
35.430
37.050
38.760
40.560
Samsung Electronics
3-5
2. Indoor pipe Thermistor and Outdoor pipe Thermistor (SPEC : 10KD)
Temperature
[˚C]
70 69 68 67 66 65 64 63 62 61 60
59 58 57 56 55 54 53 52 51 50
49 48 47 46 45 44 43 42 41 40
39 38 37 36 35 34 33 32 31 30
THERMISTOR RESISTOR
[Kohm]
1.670
1.729
1.791
1.855
1.922
1.992
2.065
2.141
2.220
2.303
2.390
2.480
2.574
2.672
2.775
2.882
2.994
3.111
3.234
3.362
3.496
3.635
3.780
3.932
4.091
4.257
4.432
4.614
4.806
5.007
5.217
5.438
5.669
5.912
6.167
6.435
6.716
7.012
7.322
7.649
7.993
Temperature
[˚C]
29 28 27 26 25 24 23 22 21 20
19 18 17 16 15 14 13 12 11 10
9 8 7 6 5 4 3 2 1 0
-1
-2
-3
-4
-5
-6
-7
-8
-9
-10
THERMISTOR RESISTOR
[Kohm]
8.354
8.734
9.135
9.556
10.00
10.46
10.94
11.45
11.99
12.55
13.15
13.78
14.44
15.14
15.88
16.66
17.48
18.36
19.28
20.25
21.28
22.38
23.54
24.76
26.06
27.44
28.90
30.45
32.10
33.85
35.66
37.59
39.64
41.82
44.14
46.60
49.22
52.01
54.98
58.14
3-6
Samsung Electronics
3-2-8 About the safety devices
1. High temperature release : If temperature of the indoor pipe thermistor increases over the specified value during heating operation, following operation is carried out for safety of the equipment.
A condition : temperature of indoor pipe thermistor is below 47ûC B condition : temperature of indoor pipe thermistor is between 58ûC and 63ûC C condition : temperature of indoor pipe thermistor is over 63ûC
1) High temperature release operation OFF condition = A condition
-> compressor ON (only in THERMO ON condition)
-> fan motor speed = set fan speed and cool blowing inhibiting operation
2) High temperature release operation ON condition = B condition
-> compressor ON
-> fan motor speed = HIGH operation if it was LOW = HIGH operation if it was HIGH
3) High temperature release operation ON condition = C condition
-> fan motor speed = set fan speed
-> compressor OFF
2. Low temperature release : If temperature of the indoor pipe thermistor decreases below the specified value during cooling operation, following operation is carried out for safety of the equipment.
A condition : temperature of indoor pipe thermistor is below -1ûC for more than 6 minutes B condition : temperature of indoor pipe thermistor is over 5ûC
1) Low temperature release ON condition = A condition
-> compressor OFF
-> fan motor "set fan speed"
2) Low temperature release OFF condition = B condition
-> The compressor is turned on if ON condition is satisfied after comparing the ambient temperature with the set temperature
-> fan motor "set fan speed"
[Detailed description]
1) If temperature of indoor pipe thermistor is below -1ûC for more than 6 minutes, the fan motor continues to operate at the set fan speed and the compressor is turned off(Low temperature release operation)
2) If temperature of the indoor pipe thermistor increases over +5ûC during low temperature release operation, normal operation is recovered : compressor ON, fan mtor set fan speed -> Low temperature release operation OFF
3) If temperature of indoor pipe thermistor increases over 0ûC during counting 6 minutes below -1ûC, the counter is reset.
Samsung Electronics 3-7
3. Deicing operation : If temperature of the outdoor pipe thermistor decreases below the specified value during heating opera­tion, following operation is carried out for safety of the equipment.
Outdoor pipe Thermistor
temperature (A-Condition) : STANDARD
12[ûC]
100min below
-4[ûC]
100min COUNT ON
Outdoor pipe Thermistor
temperature (B-Condition) : STANDARD
12[ûC]
-6[ûC]
30min COUNT ON
Outdoor pipe Thermistor
temperature (C-Condition) : STANDARD
12[ûC]
100min COUNT OFF
30min below
30min COUNT OFF
100min COUNT ON
30min COUNT ON
Deicing operation
100min
ON
5min
Deicing operation
ON
30min 5min
Deicing operation
OFF
Deicing operation
OFF
10min below
-8[ûC]
10min COUNT ON
10min COUNT OFF
10min COUNT ON
Deicing operation
ON
2min 5min
Deicing operation
OFF
3-8 Samsung Electronics