5. Troubleshooting
5-1 Special Precautions
5-1-1 Check the voltage of the of power source.
The input voltage shall be 220 - 240V~ / 50Hz
The air conditioner may not operate properly if the voltage is out of this range.
5-1-2 Check weak and fragile parts. 5-1-3 Check the connection of terminals. 5-1-4 When a malfunction occurs:
No |
Malfunction |
Check point |
|
Causes |
|
|
|
|
|
|
Compressor does not run. |
1. check the thermostat position. |
1. |
Setting temp is lower than room temp. |
|
|
2. check the connection of the lead wire. |
2. |
Disconnection of the lead wire. |
|
|
3. check the over load protector. |
3. |
O.L.P is faulty |
|
|
4. check the compressor. |
4. |
Compressor is faulty |
|
|
|
|
|
|
Motor does not run. |
1. check the connection of the lead |
1. disconnection of the lead wire |
|
|
|
wire & switch. |
2. switch is faulty. |
|
|
|
2. check the motor |
3. motor is faulty |
|
|
|
|
|
|
|
Low cooling capacity |
1. check the refrigerant leakage. |
1. |
Caused by the pipe crack |
|
|
2. check the evaporator condition |
2. shortage of refrigerant |
|
|
|
( freezing, blocked with dusts, etc. ) |
3. clean the evaporator & air filter. |
|
|
|
Difference of temp. exists between |
|
|
|
|
the suction side and the discharge |
|
|
|
|
side at least 12°C |
|
|
|
|
Standard condition |
|
|
|
|
Indoor : 27°C outdoor : 35°C |
|
|
|
|
|
|
|
|
Noise |
1. check vibration of the pipe |
1. pipes are contact with the other parts. |
|
|
|
2. check the propeller fan and blower |
2. the hex. nut is loose |
|
|
|
( not loose or broken ). |
3. the parts are broken |
|
|
|
3. check bearing noise of the motor |
4. motor is faulty |
|
|
|
4. check the compressor noise against |
5. compressor is faulty |
|
|
|
|
|
that of other compressors. |
|
|
|
|
|
Samsung Electronics |
5-1 |