SAMSUNG AS18A2QB_COR.31002.1.16 Service Manual

Page 1
ROOM AIR CONDITIONER
INDOOR AQT24A1QE/B AQT24B1QE/B AQ18A1QE/B AQ18B1QE/B SH24ZV SH18ZV
SERVICE
INDOOR AQT24A2QE/B AQT24B2QE/B AQ18A2QE/B AQ18B2QE/B
Manual
CONTENTSAIR CONDITIONER
1. Pre c a u t i o n s
2. Product Specifications
3. Operating Instructions and I n s t a l l a t i o n
4. Disassembly and Reassembly
5. Exploded Views and Parts List
6. Block Diagrams
7. PCB Diagrams
8. Wiring Diagrams
9. Schematic Diagrams
Page 2
© Samsung Electronics Co., Ltd. JAN.1999.
Printed in Korea. Code No. DB81-00030A(1)
Page 3
1. Precautions
1 . Warning: Prior to re p a i r, disconnect the
power cord from the circuit bre a k e r.
2 . Use proper parts: Use only exact re p l a c e-
ment parts. (Also, we recommend re p l a c i n g parts rather than repairing them.)
3 . Use the proper tools: Use the proper tools
and test equipment, and know how to use them. Using defective tools or test equip­ment may cause problems later- i n t e r m i t t e n t contact, for example.
4 . Power Cord: Prior to re p a i r, check the
power cord and replace it if necessary.
5 . Avoid using an extension cord, and avoid
tapping into a power cord. This practice may result in malfunction or fire .
6 . After completing repairs and re a s s e m b l y,
check the insulation resistance. Pro c e d u re : Prior to applying power, measure the re s i s­tance between the power cord and the g round terminal. The resistance must be g reater than 30 megohms.
Fig. 1-1 Avoid Dangerous Contact
Fig. 1-2 No Tapping and No Extension Cords
7 . Make sure that the grounds are adequate.
8 . Make sure that the installation conditions
a re satisfactory. Relocate the unit if neces­s a r y.
9 . Keep children away from the unit while it is
being re p a i re d .
1 0 . Be sure to clean the unit and its surro u n d-
ing are a .
Fig. 1-3 No Kids Nearby!
Fig. 1-4 Clean the Unit
Samsung Electronics
1-1
Page 4
M E M O
1-2
Samsung Electronics
Page 5
2. Product Specifications
2-1 Table
Item
Power Sourse
Perfor­mance
Electrical
Rating
Features
D i m e n s i o n s
&
Weight
Model
UNIT Capacity Air circulation (High) m3/min Moisture removal (High) Liters/h Available voltage range V Running amperes A Power input kw Power factor % Energy efficiency ratio BTU/wh Compressor locked rotor amperes A Controls/Temperature control Control unit Timer Fan speed Indoor/Outdoor Airflow direction (indoor) Horizontal
Vertical Comperssor Refrigerant/Amount charged at rating g Refrigerant control (Sound pressure) Indoor Hi/Me/Lc dB-A
Outdoor-Hi dB-A Refrigerant tubing connections Max. allowable tubing length at shippint m Refrigerant tube diameter Narrow tube (in.)
Wide tube (in.) Refrigerant tube kit/Accessories
Unit dimensions Height mm
Width mm
Depth mm Package dimensions Height mm
Width mm
Depth mm Weight Net kg
Shipping kg
AQT24A1(B1)QE / AQT24A2(B2)QE / SH24ZV
Cool Heat
220-240V~, 50Hz
BTU KW BTU KW
24,000BTU/h 6.80KW 24,000BTU/h 6.90KW
14.0 14.0 14.5 14.5
3.0
198 ~ 264
12.5 12.5 13.0 13.0
2.6 2.6 2.7 2.65
86.7 86.7 86.5 84.9
9.2 - 8.9 ­82
Microprocessor / I.C Thermostat
Wireless remote control
Q-Timer / 24-Hour ON or OFF
3 Steps and Turbo / 1 Step
Manual
Auto
Reciprocating(Tecumseh)
R22 / 1,600g
Capillary tube
45 / 43 / 41
58
Flare type
10
6.35(1/4”)
15.88(5/8”)
Optional / Hanger-plate
Indoor unit Outdoor Indoor unit Outdoor Indoor unit Outdoor Indoor unit Outdoor
275
1080
204 372
1153
272
13 16
638 880 310 851
1023
413
63.0
67.0
24,000BTU/h - 24,000BTU/h -
AQT24A1(B1)QB / AQT24A2(B2)QB
Cool Heat
220V~, 60Hz
BTU KW BTU KW
14.0 - 14.5 -
3.0
187 ~ 253
13.0 - 13.5 -
2.6 - 2.7 -
90.9 - 90.9 -
9.2 - 8.9 ­73
Microprocessor / I.C Thermostat
Wireless remote control
Q-Timer / 24-Hour ON or OFF
3 Steps and Turbo / 1 Step
Manual
Auto
Reciprocating(Tecumseh)
R22 / 1,600g
Capillary tube
45 / 43 / 41
58
Flare type
10
6.35(1/4”)
15.88(5/8”)
Optional / Hanger-plate
275
1080
204 372
1153
272
13 16
638 880 310 851
1023
413
63.0
67.0
AQ18A1(B1)QE / AQ18A2(B2)QE / SH18ZV
Cool Heat
220-240V~, 50Hz
BTU KW BTU KW
18,000BTU/h 5.10KW 20,000BTU/h 5.60KW
13.5 13.5 14.0 14.0
2.5
198 ~ 264
8.3 8.3 8.5 8.5
1.85 1.80 1.95 1.85
92.9 90.4 95.6 90.7
9.7 - 10.3 ­35
Microprocessor / I.C Thermostat
Wireless remote control
Q-Timer / 24-Hour ON or OFF
3 Steps and Turbo / 1 Step
Manual
Auto
Rotary(SAMSUNG)
R22 / 1,550g
Capillary tube
45 / 42 / 39
55
Flare type
10
6.35(1/4”)
12.70(1/2”)
Optional / Hanger-plate
275
1080
204 372
1153
272
13 16
620 787 320 680 926 451
46.0
50.0
AQ18A1(B1)QB / AQ18A2(B2)QB
Cool Heat
220V~, 60Hz
BTU KW BTU KW
18,000BTU/h - 20,000BTU/h -
13.5 - 14.0 -
2.5
187 ~ 253
8.5 - 9.0 -
1.85 - 1.95 -
98.9 - 98.5 -
9.7 - 10.3 ­35
Microprocessor / I.C Thermostat
Wireless remote control
Q-Timer / 24-Hour ON or OFF
3 Steps and Turbo / 1 Step
Manual
Auto
Rotary(SAMSUNG)
R22 / 1,550g
Capillary tube
45 / 42 / 39
55
Flare type
10
6.35(1/4”)
12.70(1/2”)
Optional / Hanger-plate
275
1080
204 372
1153
272
13 16
620 787 320 680 926 451
46.0
50.0
Remarks : Rating Conditions are :
Indoor air temperature ISO(50Hz) : 27˚C DB/19.0˚C WB, ISO(60Hz) : 27.0˚C DB/19.5˚C WB Outdoor air temperature ISO : 35.0˚C DB/24.0˚C WB
Samsung Electronics
2-1
Page 6
2-2 Major Component specifications
Indoor unit
Model
Part No.
PCB
Fan &
Fan
Motor
S-Motor
H e a t
E x c h .
Controls Control circuit fuse Type Dia. and length mm Fan motor model Pols,rpm(at 240V) Normal out W
Coil resistance(Ambient temp.20˚C) Safety devices Type
Operating temp. Open ˚C
Run capacitor µF x VAC Type Model Rating
Coil resistance (Ambient temp. 25˚C) Coil
Rows x Steps Fin pitch mm Face area m
AQT24A1(B1)QE / AQT24A2(B2)QE / SH24ZV
PD-Q24B1Q-03
Microprocessor
250V, 3.15A
Cross-Flow
ø95/L = 842
IC-9430SKJ5A
4P, 1350 RPM
40W
MAIN : 160
SUB : 227
17AM034A5
135 ± 5°C
1.2µF X 450VAC MSFCC20A03
DC 12V
530
AL-FIN/Copper tube
2 x 15
2
1.2
0.315
AQT24A1(B1)QB / AQT24A2(B2)QB
PD-Q24B1Q-03
Microprocessor
250V, 3.15A
Cross-Flow
ø95/L = 842 IC-9430SKF6A 4P, 1350 RPM
40W
MAIN : 140
SUB : 280
17AM034A5
135 ± 5°C
1.2µF X 450VAC MSFCC20A03
DC 12V
530
AL-FIN/Copper tube
2 x 15
1.2
0.315
AQ18A1(B1)QE / AQ18A2(B2)QE / SH18ZV
PD-Q24B1Q-09
Microprocessor
250V, 3.15A
Cross-Flow
ø95/L = 842
IC-9430SKJ5A
4P, 1350 RPM
40W
MAIN : 160
SUB : 227
17AM034A5
135 ± 5°C
1.2µF X 450VAC MSFCC20A03
DC 12V
530
AL-FIN/Copper tube
2 x 15
1.5
0.315
AQ18A1(B1)QB / AQ18A2(B2)QB
PD-Q24B1Q-09
Microprocessor
250V, 3.15A
Cross-Flow
ø95/L = 842
IC-9430SKF6A
4P, 1350 RPM
40W
MAIN : 140
SUB : 280
17AM034A5
135 ± 5°C
1.2µF X 450VAC MSFCC20A03
DC 12V
530
AL-FIN/Copper tube
2 x 15
1.5
0.315
Outdoor unit
C o m p re s s o r
Fan &
Fan
Motor
Heat
E x c h .
Model
Type Compressor model Normal output W Comperssor oil kind Comperssor oil cc Oil Specific gravity Coil resistance(Ambient temp.25˚C)
Safety devices Type
Overloal relay Operating temp. Open ˚C
Close ˚C
Operating amp(Ambient temp.) Run capacitor µF x VAC Type Dia. and length mm Fan motor model Pols, rpm(at240V) Normal output W Coil resistance(Ambient temp.20˚C)
Safety devices Type
Operating temp. Open ˚C
Close ˚C Run capacitor µF x VAC Coil Rows x Steps Fin pitch mm Face area m
UQT24A1(B1)QE / UQT24A2(B2)QE / XSH24ZV
Reciprocating
AWG5532EXC
2660
WITCO LP200 OR EQUIVALENT
INITIAL : 1125 REFILL : 1066
0.92
Start winding : 2.49
Run winding : 0.81
15HM2415-148
Internal Line Break
120
69
73.0 AT 2-10 SECOND 45MF X 370VAC
Propeller
ø460
OSME-716SRC
6P, 850 RPM
70W
MAIN : 58 - 88
SUB : 85 - 150
17AM034A5
135±5°C
3µF x 450VAC
AL-FIN / Copper tube
2 x 24
1.7
2
0.5376
UQT24A1(B1)QB / UQT24A2(B2)QB
Reciprocating
AWG5528EXN
2830
WITCO LP200 OR EQUIVALENT
INITIAL : 1125 REFILL : 1066
0.92
Start winding : 1.94
Run winding : 0.88
15HM2415-148
Internal Line Break
120
69
73.0 AT 2-10 SECOND 35MF X 370VAC
Propeller
ø460
OSME-716SRC
6P, 850 RPM
70W
MAIN : 58 - 88
SUB : 85 - 150
17AM034A5
135±5°C
3µF x 450VAC
AL-FIN / Copper tube
2 x 24
1.7
0.5376
UQ18A1(B1)QE / UQ18A2(B2)QE / XSH18ZV
Rotary
48B180JV1E7
1885
SUNSO-4GSD-T
600
0.92
Common to main : 1.84
Common to sub : ­MRA12016-12007
External Line Break
165°C
74°C
120·°C : 10.7A 130°C : 9.4A
40µF X 450VAC
Propeller
ø405
AMASS-035AVEB
4P, 1050 RPM
35W
MAIN : 186
SUB : 210
17AM037A5
150±5°C
2.5µF x 450VAC
AL-FIN / Copper tube
2 x 24
1.7
0.504
UQ18A1(B1)QB / UQ18A2(B2)QB
Rotary
48B190IV2E7
1885
SUN1SO-4GSD-T
600
0.92
Common to main : -
Common to sub : ­MRA12016-12007
External Line Break
165°C
74°C
120·°C : 10.7A 130°C : 9.4A
40µF X 450VAC
Propeller
ø405
AMASS-035ZTEA
4P, 1050 RPM
35W
MAIN : 127
SUB : 165 17AM037A5
150±5°C
2.5µF x 450VAC
AL-FIN / Copper tube
2 x 24
1.7
0.504
2-2
Samsung Electronics
Page 7
2-3 Dimensions
2-3-1 Indoor Unit
(Front view)
(Remote control)
(Rear view)
2-3-2 Outdoor Unit
2-3-2(a) 24K BTU
1080 204
58 22
Samsung Electronics
(Front view) (Rear view)
660
878
2-3
Page 8
Product Specifications
2-3-3(b) 18K BTU
(Front view) (Rear view)
582 787
340
2-4
Samsung Electronics
Page 9
2-4 Pressure Graph
24K BTU
18K BTU
Samsung Electronics
2-5
Page 10
M E M O
2-6
Samsung Electronics
Page 11
3. Operating Instructions and Installation
3-1 Operating Instructions
3-1-1 Name & Function of Key in remote controller
NO
1 2
3
4 5
6
7
8
NAMED OF KEY
MODE
TURBO
OFF
(UP)
(DOWN)
FUNCTION OF KEY On/Off Button. Use this button to start and stop air conditioner. Temp. up button. If the button is pressed once,
the setting temperature is increased by 1°C Temp. down button. If the button is pressed once,
the setting temperature is decreased by 1°C
Each time you press this button,
MODE is changed in the following order.
Use this button to provide heavy duty cooling & Heating for 30 minutes. Set up the reserve or cancel the timer on and timer off quickly
Use this button for sleep operation. (The SLEEP mode can be selected at COOL and HEAT mode.)
Adjusts air flow vertically.
Each time you press this button, FAN SPEED is changed in the following order.
: Auto Mode : Cool Mode : Dry Mode
: Fan Only Mode : Heat Mode
9
C O
10
V E R
11 12 13
14
15
Samsung Electronics
T
I
M
E R
ON TIMER OFF TIMER
SET CANCEL
TIME
(UP)
(DOWN)
Set up the time that operation start. Set up the time that operation stop.
Use this button to reserve the timer on. Use this button to reserve or cancel the timer on and timer off.
If the button is pressed once, the time increase by one minute during the time set mode, and ten minutes during the timer set mode.
If the button is pressed once, the time decrease by one minute during the time set mode, and ten minutes during the timer set mode.
Without regard to ON/OFF condition in remote controller, use this button to set current time. Adjust the current time using button. (Data can be transmitted after setting up the time)
3-1
Page 12
Operating Instructions and Installation
3-1-1 Name & Function of Key in remote controller
1. A U TO MODE : In this mode, operation mode(COOL, HEAT) is selected automati­cally by the room temperature of initial o p e r a t i o n .
Room Temp Tr 21°C+T 21°C +T>Tr
T= -2°, -1°C, 0°C+1°C+2°CT is controlled by setting temperature
up( )/down( ) key of re m o t e c o n t ro l l e r
2. C O O L MODE : The unit operates accord i n g to the diff e rence between the setting and room temperature. (18°C~30°C)
3. H E AT MODE : The unit operates accord i n g to the diff e rence between the setting and room temperature.(16°C~30°C) * P revention against cold wind : For about 3~5 minutes after initial operation, thermo c o n t rol or “de-ice”, the indoor fan will either not operate or operate very slowly, then switch to the selected fan speed. This period is to allow the indoor unit's heat­exchanger to prewarm before emitting warm air. *High temperature release function : The outdoor unit for and compressor ON/OFF c o n t rol for safety operation, when the over­heat is heat exchanger of indoor unit. *De-ice : Deicing operation is controlled by indoor unit's heat exchanger temperature and accumulating time of compre s s o r ' s o p e r a t i o n . De-ice end by sensing of the pro c e s s i n g time by de-ice Condition.
Cool Operation (Set Temp:24°C+T)
Heat Operation (Set Temp : 22°C+T)
Operation Type
4. D RY MODE : The unit operates in DRY m o d e . *Co m p ressor ON/OFF Time is contro l l e d compulsorily(can not set up the fan speed, always bre e z e ) . * P rotective function : Low temperature release. (Prevention against fre e z e )
5. TURBO MODE : This mode is available in A U TO, COOL, HEAT, DRY, FAN MODE. When this button is pressed at first, the air conditioner is operated “powerful” state for 30 minutes re g a rdless of the set tempera­t u re, room temperature . When this button is pressed again, or when the operating time is 30 minutes, turbo operation mode is canceled and returned to the previous mode. *But, if you press the TURBO button in DRY or FAN mode that is changed with A U TO mode automatically.
6 . S L E E P MODE : Sleep mode is available
only in COOL or HEAT mode. The operation will stop after 6 hours. *In COOL mode : The setting temperature is automatically raised by 1°C each 1hour When the temperature has been raised by total of 2°C, that temperature is main­t a i n e d . *In HEAT mode : The setting temperature is automatically droped by 1°C each 1hour. When the temperature has been droped by total of 2°C, that temperature is main­t a i n e d .
7. FAN SPEED : Manual / Auto Fan speed automatically varies depending on both the diff e rence between setting and the room temperature .
3-2
Samsung Electronics
Page 13
Operating Instructions and Installation
8 . C O M P U L S O RY O P E R ATION :
For operating the air conditioner without the remote contro l l e r. * A U TO : The operating is the same func­tion that A U TO MODE in the remote con­t ro l l e r.
9 . SWING : BLADE-H is rotated vertically by
the stepping motor. *Swing Set / Auto : Press the button under the remote control is displayed on LCD the , and the blades move up and down, about 43°. If the one more time pre s s the button, blatles location is stop.
1 0 . Quick OFF TIMER: OFF timer (quick timer)
allows reservation or cancel the timer on and timer off quickly When OFF timer button is pressed at oper­ating state, LCD displays the polling state s e q u e n t i a l l y. The LCD also displays the time re m a i n i n g .
11 . 24-Hour ON/OFF Real Setting Ti m e r. : The
air conditioner is turned ON at a specified time using .
ON TIMER
OFF TIMER : The air Conditioner is turned OFF at a specified time using .
OFF TIMER
*ON TIMER : Only timer LED lights on. *OFF TIMER : Both timer and operation LED lights on.
1 2 . SELF Diagnosis
LED DISPLAY
o p e r-
T I M E R
a t i o n
FA N
Tu r b o
Check Point
I n t e r ruption of electric power and Power on. Abnormal condition of the room sensor. Abnormal condition of the indoor unit's heat exchanger sensor.
Indoor unit fan motor lock.
L E D
:
b l i n k i n g
: LED off
1 3 . BUZZER SOUND : Whenever the ON/OFF
button is pressed or whenever change occurs to the condition which is set up or select, the compulsory operation mode, buzzer is sounded "beep"
Samsung Electronics
3-3
Page 14
3-2 Installation
3-2-1 Selecting Area for Installation
Select an area for installation that is suitable to the customer's needs.
3-2-1(a) Indoor Unit
1 . Make sure that you install the indoor unit in
an area providing good ventilation. It must not be blocked by an obstacle affecting the airflow near the air inlet and the air outlet.
2 . Make sure that you install the indoor unit in
an area allowing good air handling and endurance of vibration of the indoor unit.
3. Make sure that you install the indoor unit in an area where there is no source of heat or vapor nearby.
4 . Make sure that you install the indoor unit in
an area from which hot or cool air is spre a d evenly in a ro o m .
5 . Make sure that you install the indoor unit in
an area away from TVs, audio units, cord­less phones, fluorescent lighting fixture s and other electrical appliances (at least 1 m e t e r ) .
6 . Make sure that you install the indoor unit in
an area which provides easy pipe connec­tion with the outdoor unit, and easy drainage for condensed water.
(Fix the unit firmly if it is mounted in a
high place.)
3 . Make sure that you install the outdoor unit
in area providing good ventilation and which is not dusty. It must not be blocked by any obstacle affecting the airflow near the air inlet and the air outlet.
4 . Make sure that you install the outdoor unit
in area free from animals or plants.
5 . Make sure that you install the outdoor unit
in area not blocking the traff i c .
6. Make sure that you install the outdoor unit in area easy to drain condensed water fro m the indoor unit.
7. Make sure that you install the outdoor unit in area which provides easy connection within the maximum allowable length of a coolant pipe(10 meters).
N o t e
1. Add (18XX:20g, 24XX:30g) of re f r i g e r a n t (R-22) for every 1 meter if the pipe length exceeds the standard pipe length of 5 meters.
2. Maintain a height between the indoor and outdoor units of less than 3 meters.
8 . Make sure that you install the outdoor unit
in an area which is large enough to accom­modate the measurements
shown in figure on the next page.
7. Make sure that you install the indoor unit in an area which is large enough to accomo­date the measurements shown in figure on the next page.
3-2-1(b) Outdoor Unit 1 . Make sure that you install the outdoor unit
in area not exposed to the rain or direct sun l i g h t .
(Install a separate sunblind if exposed to
d i rect sun light.)
2 . Make sure that you install the outdoor unit
in area allowing good air moment, not amplifying noise or vibration, especially to avoid disturbing neighbours.
Caution :
It is harmful to the air conditioner if it is used in the following environments: greasy areas (including areas near machines), salty areas such as coast areas, areas where sulfuric gas is present such as hot spring areas. Contact your dealer for advice.
3-4
3-2-1(c) Remote Control Unit 1 . Make sure that you install the remote con-
t rol unit in an area free from obstacles such as curtains etc, which may block signals f rom the remote control unit.
2. Make sure that you install the remote con­t rol unit in an area not exposed to d i rect sunlight, and where there is no sourc e of heat.
3. Make sure that you install the remote con­t rol unit in an area away from TVs, audio units, cordless phones, fluorescent lighting f i x t u res and other electrical appliances (at least 1 meter).
Samsung Electronics
Page 15
3-2-2 Installation diagram of indoor unit and outdoor unit
Operating Instructions and Installation
A Indoor unit gas leak test check point
Indoor unit
Piping
1
3
2
Tape vinyl
B Drain hose installation
Cut the piping hole sloped slightly
5 6
125mm or more
Piping may be laid to the rear, left, right or down .
Right
Rear
Down
Rear
Left
125mm or more
1 2
3 4 5
Samsung Electronics
4
10
Piping (Liquid) 1/4" Clamper tube
18K BTU Piping(Gas) 1/2” 24K BTU Piping(Gas) 5/8”
Installation tube Pipe-connection Vinyl tape Screw Putty Drain hose
6 7
8 9
10
Remote control
Remote control holder
Installation plate
3-5
Page 16
Operating Instructions and Installation
3-2-2(a) Fixing the Installation Plate
(Unit : mm)
(Unit : mm)
Installation plate
512
415
1. Determine the position of the pipe and drain hose hole using the right figure and drill the hole with an inner diameter of 65mm so that it slants slightly downwards.
2. If you are fixing the indoor unit to a… Then follow Steps…
Wall 3.
Window frame 4 to 6.
3. Fix the installation plate to the wall in a manner appro­priate to the weight of the indoor unit.
227288
If you are mounting the plate on a concrete wall with anchor bolts, the anchor bolts must not project by more than 20mm.
4. Determine the positions of the wooden uprights to be attached to the window frame.
3-2-2(b) Purging the Unit
5. Attach the wooden uprights to the window frame in a manner appropriate to the weight of the indoor unit.
6. Using tapped screws, attach the installation plate to the wooden uprights, as illustrated in the last figure oppo­site.
On delivery, the indoor unit is loaded with an inert gas. All this gas must therefore be purged before connecting the assembly piping. To purge the inert gas, proceed as fol ­lows.
Unscrew the caps at the end of each pipe.
Result : All inert gas escapes from the indoor unit.
To prevent dirt or foreign objects from getting into
the pipes during installation, do NOT remove the caps completely until you are ready to connect the piping.
3-6
Samsung Electronics
Page 17
3-2-2(c) Connecting the Assembly Cable.
The indoor unit is powered from the outdoor unit via the assembly cable. If the outdoor unit is more than five metres away from the indoor unit, the cable must first be extended to a maximum of 15 m e t re s .
1 . Extend the assembly cable if necessary. 2 . Open the front grille by pulling on the tabs on the lower right and
left sides of the indoor unit.
Indoor unit
Outdoor unit
3 . Remove the screw securing the connector cover. 4 . Pass the assembly cable through the rear of the indoor unit and
connect the assembly cable to terminals 1 to 5.
• Each wire is labelled with the corresponding terminal number.
5 . Firmly fix the ass’y cable with clamp wire holder. 6 . Pass the other end of the cable through the 65mm hole in the wall.
7 . Replace the connector cover, carefully tightening the scre w. 8 . Close the front grille. 9 . For further details on how to plug the other end of the assembly
cable into the outdoor unit, refer to page 3-8.
Operating Instructions and
3-2-2(d) Installing and Connecting the Indoor Unit Drain Hose
C a re must be taken when installing the drain hose for the indoor unit to ensure that any condensa ­tion water is correctly drained outside.l When passing the drain hose through the 65mm hole drilled in the wall, check that none of the following situations occur.
The hose must NOT slope upw ards.
To install the drain hose, proceed as follows.
1. If necessary, connect the 2-metre extension to the drain hose. 2 . If you are using the extension, insulate the inside part of the extension drain hose with a shield.
3. Pass the drain hose under the refrigerant piping, taking care to keep the drain hose tight.
4. Pass the drain hose through the hole in the wall, making sure that it is sloping downwards, as shown in the illustrations above.
The end of the drain hose must NOT be placed in water.
Do NOT bend the hose in different directions.
Keep a clearance of at least 5cm between the end of the hose and the ground.
Do NOT place the end of the drain hose in a hollow.
Shield
Drain hose Extension drain hose
Samsung Electronics
3-7
Page 18
Operating Instructions and Installation
3-2-2(e) Outdoor unit installation
AUXILIARY POWER S/W
A u x i l i a ry power S/W should be installed near indoor unit so that each access is possible.Main/Outdoor unit power c o rds are connected to upper/lower terminal of auxiliary power S/W.
WIRING CONNECTION
distributind board
Auxiliary
power S/W
Indoor unit connector wire should be connected to both indoor unit connector and outdoor unit terminal board as shown in the f i g u re below.
INSTALLATION OF DRAIN LINE
In heating and deice operation, condensed water may be generated. Install drain line as following pro c e d u re .
1. Insert the drain plug into base hole
2. And then connect drain hose to drain plug.
INDOOR OUTDOOR
(POWER CABLE)
(ASSEMBLY CABLE)
Hole
EARTH WIRE
EARTH WIRE
Base
Drain plug
Drain Hose
3-8
Samsung Electronics
Page 19
3-2-2(f) Flare Modification
• Tools used
Flare modification procedure
Operating Instructions and Installation
1 ) Cut the pipe using a pipe cutter.
Oblique Raughness Burr
3 ) Insert a flare nut into the pipe and
modifty flare .
2 ) Remove burrs at the tip of the pipe cut.
Caution : Burrs not removed may result in
leakage of gas.
Pipe
Reamer
D
A
Outer diameter A(mm)
ø6.35mm 1.3 ø9.52mm 1.8
ø12.7mm 2.0 ø15.8mm 2.2
* Unproper flaring
Samsung Electronics
Inclined Surface
damaged
Cracked Uneven
thickness
3-9
Page 20
Operating Instructions and Installation
3-2-2(g) Air-Purge Procedure
• Use the refrigerant of the outdoor unit to purge air inside indoor unit and pipe.
1. Remove the caps from the 2-way valve(B) and the 3-way valve(A).
2 Turn the 2-way valve cock approx. 45°
counterclockwise to open it. Close it about 10 seconds later.
Valve stem
3 Check refrigerant leakage of each joint parts
(A, B, C & D in right figure)
Valve stem
Stopper
not
Leaking
leaking
If leaking, tighten the flare nut one more time. If continues to leak, although the pipe fixing area has been tightened again, repair the leaking area.
4. Open the 2-way valve again.
5. Open the service valve cap of the 3-way valve and press the needle valve to discharge gas for 3 seconds and leave it for about 1 minute. Repeat the above procedure for 3 times to purge air.
6. Open the 2-way valve and 3-way valve
completely
Indoor Unit
Liquid pipe side
2-way valve 3-way valve
Gas pipe side
7. Close the cap of each valve.
8. Check each valve for leakage.
3-10
Outdoor Unit
Samsung Electronics
Page 21
Operating Instructions and Installation
3-2-2(h) Refrigerant Refill
• Refill an air-conditioner with refrigerant when refrigerant has been leaked at installing or using
1. Purge air(for new installation only).
2. Turn the 3-way valve clockwise to close, connect the pressure gauge(low pressure side) to the service valve, and open the 3-way valve again.
Suspension hook
3. Connect the tank to refill with Refrigerant
4. Set the unit to cool operation mode.
5. Check the pressure indicated by the pressure gauge(low pressure side). * Standard pressure is should be
4.5~5.5kg/cm2in a reqular, high operation mode.
6. Open the refrigerant tank and fill with refrig-
erant until the rated pressure is reached. * It is recommended not to pour the
refrigerant in too quickly, but gradually while operating a pressure valve.
Compound gauge
For mounting other and of hose when not in use
High pressure gauge
Hand wheel
Finger tight fittings
Connected to high pressure side
Charging line
7. Stop operation of the air conditioner.
8. Close the 3-way valve, disconnect the pressure gauge, and open the 3-way valve again.
9. Close the cap of each valve.
Samsung Electronics
3-11
Page 22
Operating Instructions and Installation
3-2-2(i) Refrigerant Adjustment
Class At installation At service
Connection
Pipe Length
5m Max.
5~10m
Air-Purge Method
Refer to the detailed Air-Purge Procedure
3-2-2(j) Flare unt fixing torque
Refrigerant Adjustment
Unnecessary
Add “A” of refrigerant (R-22) for every 1m.
Air-Purge Method
Purge air using a vaccum pump or an additional refrigerant cylinder.
MODEL 24K BTU 18K BTU
Refrigerant Quantity
refer to specification sheet
Add “A” of refrigerant (R-22) for every 1m.
“A” 30g 20g
Outter diameter
ø 6.35 mm
(Liquid Side)
ø 9.52 mm
(Gas Side)
ø 12.7 mm
(Gas Side)
ø 15.8 mm
(Gas Side)
Torque (kg-cm)
Fixing Torque Final Torque
160
300
500
700
200
350
550
750
3-12
Samsung Electronics
Page 23
Operating Instructions and Installation
3-2-2(k) "Pump down" Procedure
Pump down' shall be carried out when an evaporator is replaced or when the unit is relocated in another are a .
1. Remove the caps from the 2-way valve and the 3-way valve.
2 Turn the 3-way valve clockwise to close
and connect a pressure gauge(low pressure side) to the service valve, and open the 3-way valve again.
2-Way Valve
3. Set the unit to cool operation mode. (Check if the compressor is operating.)
4. Turn the 2-way valve clockwise to close.
5 When the pressure gauge indicates "0"
turn the 3-way valve clockwise to close.
6. Stop operation of the air conditioner.
7. Close the cap of each valve.
Relocation of the air conditioner
Refer to this pro c e d u re when the unit is re l o c a t e d .
1. Carry out the pump down pro c e d u re (re f e r to the details of 'pump down').
2. Remove the power cord .
3. Disconnect the assembly cable from the indoor and outdoor units.
4. Remove the flare nut connecting the indoor unit and the pipe. At this time, cover the pipe of the indoor unit and the other pipe using a cap or vinyl plug to avoid foreign material entering.
3-Way Valve
5. Disconnect the pipe connected to the outdoor u n i t . At this time, cover the valve of the outdoor unit and the other pipe using a cap or vinyl plug to avoid foreign material entering.
6. Make sure you do not bend the connection pipes in the middle and store together with the cables.
7. Move the indoor and outdoor units to a new l o c a t i o o n .
8. Remove the mounting plate for the indoor unit and move it to a new location.
Samsung Electronics
3-13
Page 24
4. Disassembly and Reassembly
4-1 Indoor Unit
Stop operation of the air conditioner and remove the power cord before repairing the unit.
No Parts Procedure Remark
1 Front Grille 1) Stop the air conditioner operation and block
the main power.
2) Seperate tape of front panel upper.
3) Contract the second finger to the left, and right handle and pull to open the inlet grille.
4) Take the left and right filter out.
5) Loosen one of the right fixing screw and seperate the terminal cover.
6) Loosen two fixing screws of front grille.
7) Pull the upper left and right of discharge softly for the outside cover to be pulled out.
8) Pull softly the lower part of discharge and push it up.
Caution;
Assemble the front panel and fix the hooks of left and right.
* Take the Deadorizing and Electrostatic fil-
ter out. (ONLY “1” and “5” Series models)
Page 25
Disassembly and Reassembly
No Parts Procedure Remark
2
3
4
Ass’y Tray Drain.
Electrical Parts
(Main PCB)
Heat Exchanger
1) Do “1”, above. Separate the drain hose from the extension drain hose.
2) Take the display PCB out. (Center of indoor unit)
3) Loosen two fixing screws of left and right
4) Pull tray drain out from the back body.
1) Do “1”, “2”, above
2) Take all the connector of PCB upper side out. (Inclusion Power cord)
3) Separate the outdoor unit connection wire from the terminal block.
4) If pulling the Main PCB up. it will be taken out. (Separate the TRANS hook. it before).
1) Do “1” and “2”, “3”, above
2) Loosen two fixing earth screws of right side.
3) Separate the connection pipe.
4) Separate the bush body at the upper side and holder at the rearside.
5) Loosen the two fixing screws of left side.
6) Lifting the heat exchanger up a little to push the up side for separation from the indoor unit.
Page 26
Disassembly and Reassembly
No Parts Procedure Remark
3 Fan Motor and
Cross Fan
1) Do “1” “2” ”3” “4”, above.
2) Loosen the fixing three screws and separate the motor holder.
3) Loosen the fixing screw of fan motor. (By use of M3 wrench)
4) Separate the fan motor from the fan.
5)Separate the fan from the left holder bearing.
Page 27
4-2 Outdoor Unit
No Parts Procedure Remark
1
2
Cabinet
Fan Motor & Propeller Fan
1) Turn off the unit and remove the power cable
2) Remove the top cover.
3) Remove the control box cover.
4) Unplug the ass'y cable.
5) Remove the cabi-side.
6) Remove the cabi-front.
* When you assemble the parts, check if the
each parts and electric connectors are fixed firmly.
1) Do Procedure 1 above.
2) Remove the nut flange. (Turn to the right to remove as it is a left turned screw)
3) Disassemble the propeller fan.
Page 28
M E M O
Page 29
5. Troubleshooting
5-1 Items to be checked first
1 ) Is the voltage of the power corre c t ?
The input voltage shall be rating voltage ±10%. The airconditioner may not operate properly if the voltage is out of this range.
2 ) Is the link cable linking the indoor unit and the outdoor unit linked pro p e r l y ?
The indoor unit and the outdoor unit shall be linked by 6 cables. Check the terminals if the indoor unit and outdoor unit are properly linked by the same number of cables. Otherwise the airconditioner may not operate pro p e r l y.
3 ) When a problem occurs due to the contents illustrated in the table below it is a symptom not related to the
malfunction of the airc o n d i t i o n e r.
NO Operation of air conditioner
1 The COOL operation indication LED (Green) blinks when a
power plug of the indoor unit is plugged in for the first time.
2 In a COOL operation mode, the compressor does not
operate at a room temperature higher than the setting
temperature that the INDOOR FAN should operate.
In a HEAT operation mode, the compressor does not
operate at a room temperatrue lower than the setting temperature that indoor fan should operate.
3 Fan speed setting is not allowed in AUTO or DRY mode.
4 Compressor stops operation intermittently in DRY mode.
5 Compressor of the outdoor unit is operating although it is
turned off in a HEAT mode.
6 Timer LED only of the indoor unit lights up and the
air conditioner does not operate.
7 The compressor and indoor fan stop intermittently in HEAT
mode.
8 Indoor fan and outdoor fan stop operation intermittently in
a HEAT mode.
9 The compressor stops intermittently in a COOL mode or DR Y
mode, and fan speed of the indoor unit decreases.
Explanation
It indicates power is on. The LED stops blinking if the operation ON/OFF button on the remote control unit is pushed.
In happens after a delay of 3 minutes when the compressor is reoper­ated. The same phenomenon occurs when a power is on. As a phenomenon that the compressor is reoperated after a delay of 3 minutes, the indoor fan is adjusted automatically with reference to a temperature of the air blew
The speed of the indoor fan is set to LL in DRY mode. Fan speed is 5 steps is selected automatically in AUTO mode.
C o m p ressor operation is controlled automatically in DRY mode depending on the room temperature and humidity.
When the unit is turned off while de-ice is activated, the comperssor continues operation for up to 9 minutes (maximum) until the deice is completed.
Timer is being activated and the unit is in ready mode. The unit operates normally if the timer operation is cancelled.
The compressor and indoor fan stop intermittently if room temperature exceeds a setting temperature in order to protect the compressor from overheated air in a HEAT mode.
The compressor operates in a reverse cycle to remove exterior ice in a HEAT mode, and indoor fan and outdoor fan do not operate intermt­tently for within 20% of the total heater operation
The compressor stops intermittently or the fan speed of the indoor unit decreases to prevent inside/outside air frozen depending on the inside/outside air temperature.
4 ) Indoor unit observes operation condition of the air conditioner, and displays self diagnosis details
on the display panel.
NO Display
1 Operating LED blinking (1Hz) 2 TIMER LED blinking (1Hz) 3 O P E R ATING and TIMER LED blinking (1Hz) 4 FAN LED blinking (1Hz)
Samsung Electronics
Restore from power failure (input initial power) Indoor unit Room sensor Error (open or short) Indoor unit heat exchanger temperature sensor Error (open or short) Indoor fan malfunctioning (for spead is Below 38Orpm)
Self Diagnosis
5-1
Page 30
5-2 Fault Diagnosis by Symptom
5-2-1 No Power (completely dead)-Initial diagnosis
1) Checklist :
(1) Is input voltage normal? (the rating voltage ±10% range) (2) Is AC power linked corre c t l y ? (3) Are connections between primary side, secondary side of the power transformer and PCB good. (4) Is output voltage of DC regulator IC KA7812 (IC01) normal? (11 V D C - 1 2 . 5 V D C ) (5) Is output voltage of DC regulator IC KA7805 (IC02) normal? (4.5VDC-5.5VDC)
2 ) Troubleshooting pro c e d u re
YES
Replace PCB
display
Is DC voltage of PCB
display normal?
NO
Is the input rating ±10%
range applied to the
primary side of the power
transformer?
NO
•Check linkage between power cord and
terminal tap
•Check fuse
Is 14~18VAC appear in
the secondary side of the
power transformer?
YESNO
Replace power
transformer
Replace resonator (X501)
Is operation normal?
YES
OK
NO
Remove power cord and plug in again
in approx. 5 seconds
Is operation lamp blinking?
Does operation start when
run/stop button on the remote
controller unit pushed?
Is transmission display of the remote
controller unit blinking?
Is "beep"sound heard from the main
NO
Is DC voltage of the PCB module
Are voltages of #57 (compressor),
#48 (4 way valve) and #58 (outdoor fan)
of the micom normal? (5VDC)
Is voltage of #1 (indoor fan) of the
DC5V
Is voltage at #32 terminal of the Micom normal? Is voltage at #64 terminal of the Micom normal?
Is voltage at #25 terminal of the micom
Are voltage at #30 and #31 of the
NO
NO
unit?
normal?
micom normal?
10ms
normal?
micom normal?
Replace
micom
YES
NO
YES
YES
YES
NO
YES
10ms
YES
YES
100ns
;
;
5VDC
0VDC
YES
NO
NO
YES
valve, outdoor fan and
NO
NO
Normal
Refer to remote control
unit fault diagnosis
Replace PCB
module.
Are voltages at RY71(Compressor)
RY73 (4 way vale) and RY 72 (Outdoor fan)
Is output voltage of ICO2 normal?(DC5V)
normal? (DC12V)
Is voltage at SS71(indoor fan)
YES
Check connections compressor 4-way
indoor fan.
YES
Check PCB pattern . Replace main PCB.
Is voltage output terminal of D101~D105(IN4007) normal?
YES
OK
Replace IN4007
Replace
RY71, RY73,
RY72 and
SS71
NO
Replace ICO2
NO
NO
5-2
Samsung Electronics
Page 31
5-2-2 When the Indoor Unit Fan Does Not Operate. (Initial Diagnosis)
1) Checklist : (1) Is the indoor unit fan motor properly connected with the connector (CN73)? (2) Is the AC voltage corre c t ? (3) Is HALL IC in indoor fan motor properly connected with the connector (CN43)? (4) Is the running capacitor properly connected with the solder part of the PCB?
2 ) Troubleshooting pro c e d u re
Troubleshooting
After unplugging out the power cord should
Does the operating lamp(Green) blink?
+
SS71+ SS71- 12V
be reconnected within five seconds.
YES
YES
Does the Solid State Relay(SS71) work
properly?
Test rod location
-
YES
Is the supply voltage of the fan
motor sufficient?
Normal Voltage
NO
NO
NO
Check as in the procedur “NO power parts” Refer tp
PCB is
out of order.
page 5-2.
Microcomputer is out of order.
PCB should be
replaced.
Test rod location
PCB CN73 Condition
Pin 3, Pin 5
Samsung Electronics
Normal voltage
Fan operate = AC 180V
YES
.
.
Fan motor
is out of order.
MF-C is out of order
Replace MFC
Fan motor
should be replaced.
5-3
Page 32
Troubleshooting
5-2-3 When the Outdoor Unit Does Not Operate. (Initial Diagnosis)
1 ) Checklist :
(1) Is input voltage normal? (the rating voltage ±10% range) (2) Is the set temperature of the remote control higher than room temperature in COOL m o d e ? (3) Is the set temperature of the remote control lower than room temperature in HEAT mode? (4) Is the POWER IN connector (CN78) linked corre c t l y ? (5) Is the outdoor unit properly connected with the TERMINAL BLOCK connector(7P)?
2 ) Troubleshooting pro c e d u re
After unplugging out the power cord should be recon-
nected within five seconds.
Does the operating lamp blink
YES
Does the timer lamp blink during operation ?
NO
Is the power relay RY71 operated by adjusting the room
temperature?
Test rod location Normal
+ - Condition Voltage
IC04 Pin #59 GND RY71 ON DC 4.8V
NO
Is the rating voltage ±10% range applied relay between
CN78 and .
NO
YES
PCB and Room tempera-
ture sensor should be
NO
NO
checked.
Check as in the procedure "No Power parts"
Power relay is
out of order
Refer to page 5-2.
Room temperature sensor is
out of order
PCB is
out of order.
Power relay should be
PCB should be
checked.
replaced.
5-4
YES
NO
Is the room sensor normal register?
(25°C 10K)
10°C 20°C 30°C
17.96k 12.09k 8.3k YES
Outdoor unit is
out of order.
Samsung Electronics
Page 33
5-2-4 When the UP/DOWN Louver Moter Does Not Operate. (Initial Diagnosis)
1) Checklist :
(1) Is input voltage normal? (the rating voltage ±10% range) (2) Is the UP/DOWN louver motor properly connected with the connector (CN61)?
2 ) Troubleshooting pro c e d u re
Remove power cord and plug in again in approx. 5 seconds.
Troubleshooting
Is operating lamp blinking?
Does operation start when swing button of the remote control unit pushed?
Voltage at pin #33-#36 of micom (ICO4) change?(Squarewave)
Volatge at pin #10, #11, #12, #13 of IC05 (KID65003)
change?(Squarewave)
UP/DOWN louver motor is faulty.
Check as in the procedure "No Power parts". Refer to page 5-2.
Normal
Micom (IC04) is faulty.
Driver IC05 (KID65003) is faulty.
5-2-5 In the Heat mode, When there is no warm air current. Check this first;
(1) Is the set temperature of Remote Control lower than room temperature in Heat mode? (2) Is the Indoor PCB properly connected with the CN71 and CN78 connector?
After training on, the heating operation should
start in five minutes.
Is the munber #48 of Micom (IC04) DC 4.8 V?
Is the munber #12 of IC07 (KID65003) LOW?
Is the voltage between CN71 #1 and CN78 #1 the rating voltage ±10% range?
Abnormal 4way valve of Outdoor Unit.
4 way valve should be replaced
or connecting Cable Check.
Samsung Electronics
NO
YES
YES
YES
or connecting Cable
YES
NO
NO
NO
Normal
Abnormal Micom
Abnormal IC07
Abnormal RY73
PCB should be replaced.
5-5
Page 34
Troubleshooting
5-2-6 If Operation By Remote Control Unit Is Impossible. (Initial Diagnosis)
1) Troubleshooting pro c e d u re
Remove power cord and plug in again approx. 5 Seconds
Is operation lamp blinking?
“ sound heard from the indoor unit when ON/OFF but-
ton on the remote control unit pushed?
Voltage of battery less than 2.5V (Remote Control Unit)?
LCD display status of REMOCON normal?
Transmission display lamp ( ) blinking when
ON/OFF button on the remote control unit pushed?
Voltage at PIN #30 of Remocon Micom change?
Voltage at collecter of Q601 or Q602 change?
Check as in the procedure “NO Power parts”.
Refer to page 5-2.
Normal
Replace battery.
LCD is faulty.
Replace button.
Micom is faulty.
Q601(C4375Y) or Q602(C1623Y) is faulty.
IR LED(CL-1L5EU) is faulty.
5-6
Voltage at pin #26 of micom (IC04) change (INDOOR UNIT)?
Micom (IC04) is faulty.
Receiver module is faulty.
Samsung Electronics
Page 35
5-3 PCB Inspection
5-3-1 Cautions for Part Replacement
1 . The human body carries much static
e l e c t r i c i t y. Before touching a part for re p a i r, replacement or the similar purpose, be sure to touch a grounded metallic portion by hand to let the static electricity go thro u g h the matallic portion to the earth. Espectially when handling any micro computer or IC, carefully remove such static electricity before touching them.
2 . When repairing any part on a work bench,
be sure to place an insulative sheet on the bench and always keep the sheet surface neat without any metal fragments. If any such fragment touches a part, a secondary t rouble will possibly be caused in the part.
3. B e f o re replacing any parts, be sure to turn o ff the power supply. If such replacement is done with the power supply kept on, an electric shock, short circuit or destruction of a part may re s u l t .
4. During replacement or repair of a part, c a refully handle it : The printed circ u i t b o a rd has fine lead wires (jumper wires) and glass-made parts (diode) on its substrate. So if a circuit board is roughly handled, such lead wires and parts will be easily broken or damaged by bending or shock.
5 . When soldering the lead wires of any new
part, be sure to polish them using an emery paper or the like before solding them. Since the lead wires of any new part are c o v e red with an oxide film, solder cannot a d h e re to the lead wires if not polished.
6 . When soldering any part, care should be
e x e rcised not to apply any high-wattage soldering iron to the part for a long time. Some parts are of so low a heat re s i s t a n c e that they may be broken or have the p roperties changed if a soldering iron is so applied (Otherwise, the pattern may possibly be separated and raised).
7. The heat of the soldering iron should be t r a n s f e red to the entire object to be soldere d . If the solder pieces are not well fused due to i n s u fficient transfer of the heat from the soldering iron, no satisfactory electrical continuity can be assured even if the s o l d e red objects appear well connected to each other.
8 . The solder used should be limited to a
minimum. If excessive solder is used, it will cause inter-pattern contact, which may cause malfunction of the circ u i t .
5-3-2 Procedure
The parts should be replaced in the following pro c e d u re .
Check for any faulty part.
Detach the faulty part.
Replace it with a new part.
Check the operation of the new part.
The repair is completed.
Samsung Electronics
5-7
Page 36
Troubleshooting
5-3-3 Detailed Procedure
No.
Pull out the power plug from the
1
AC terminal and confirm the fuse on the PCB assembly
Turn the power on.
2
If lamp blinks trouble is not related to the items 1 through 4 on the right.
Set operating mode when RMC
3
switch pushed. Except for [FAN]mode and [TIMER] mode.
Malfunction
Checking point (symptoms)
1. Is the broken?
Voltage check
1. AC voltage at both end of transformer Primary? ; rating voltage ±10% range
2. AC voltage at both end of transformer secondary? ; 14- 18Vac
3. DC voltage at OUT and GND of IC01 (KA7812)? ; 12VDC
4. DC voltage at OUT and GND of IC02? ; 5VDC
5. DC voltage at Q201 Base and GND change? ; squarewave
Voltage check
1. Voltage of relay (RY71) coil Voltage at
PIN#11, PIN#12, PIN#15 of IC07 ; 12VDC
Causes
1. Voltage over
2. Indoor unit fan motor short-circuit.
1. Irregular power code or power fuse, or poor wiring.
2. Transformer is faulty.
3. Power circuit is faulty.
4. Power circuit is faulty.
5. Q201 is faulty.
D101~D104 (IN4007)
1. Relay(RY 71) coil is open.
IC07 is faulty.
Set operating mode when RMC
4
switch pushed.
1. COOL mode
2. TURBO operating
5
Set operating mode when RMC switch pushed.
1. HEAT mode
2. TURBO operating Set operating mode when
6
RMC switch pushed.
1. [FAN] mode
2. Fan speed [Hi]
3. Continuously operation
2. Voltage at Terminal Tap (TB71 or 72) and RY71 Terminal N0 4 ; rating voltage ±10% range
1. Compressor does not operate.
1. Compressor does not operate
1. Voltage at 3 5 both ends of CN73 :
above 180V~
2. Indoor unit fan motor does not operate.
2. Relay(RY 71) contactor is faulty.
1. PCB is faulty.
2. Connecting is faulty.
1. PCB is faulty.
2. Connecting is faulty.
1. Indoor unit fan motor is faulty.
2. Poor connection of indoor fan motor and connector of RPM sensing (CN43)
5-8
Samsung Electronics
Page 37
5-4 Fault Diagnosis of Major Parts
Parts
Temp.Sensor
Heat ex. Sensor
Indoor Fan Motor
Diagnosis Measure resistance with a tester. Normal 8K~27K at ambient temperature (+0°C ~ +30°C) Abnormal , O … open or short Measure resistance between terminals (CN73) with a tester Normal At ambient temperature (10°C ~ 30°C)
between Resistance
Red, Yellow 190±10
Red, Blue 170±10
Abnormal Measure the voltage between ground and signal wire of the fan motor Normal
between Voltage
Gray, Orange 0.5V~4.5V
Outdoor Fan Motor
Stepping Motor
(UP/DOWN swing motor)
Yellow, Orange 5V
Abnormal Abnormal if voltage does not change from 0V to 5V. Normal At ambient temperature (10°C ~ 30°C)
between Resistance
Black, White 350±10
Black, Red 270±10
Abnormal , O … open or short
Measure resistance between red wire and each terminal. Normal Approx. 380 at ambient temperature (20°C ~30°C)
Abnormal , O … open or short
Samsung Electronics
5-9
Page 38
6. Exploded Views and Parts List
6-1 Indoor Unit
6-1
Samsung Electronics
Page 39
Parts List
No.
1
2
3 4
4-1
4-2
4-3
5 6 7
8
8-1
8-2
9
10
11 11-1 11-2 11-3
12
13
14 14-1 14-2
14-3
15
16
17
18
19
20
21
CODE NO
DB64-10173A DB64-10151A DB64-70108A DB64-70077A DB63-30150B DB74-10101B DB61-10164B DB74-10082A DB74-10081A DB63-10466A DB92-70095A DB93-10599B DB93-10600B DB94-10083D DB31-10153B DB66-30181A DB75-40087G DB75-40087H DB67-30089A DB90-40162A DB61-40264A DB65-10108A DB65-40063A DB31-10151A DB31-10151B DB94-30162C DB90-40135A DB94-40003A DB61-40244A DB94-40007A DB93-10545B DB93-10545D DB93-10555E DB93-10555F DB32-10008E DB61-10163A DB94-20037B DB61-40264A DB70-10663A DB26-10065B
Description Specification
GRILLE AIR INLET GRILLE AIR INLET
PANEL CENTER DISPLAY
PANEL CENTERDISPLAY
GUARD AIR FILTER
CLEANER FILTER ASS’Y
CASE-CLEANER FILTER
DEODORIZING FILTER
CLEANER FILTER
POLYESTER/CARBON POLYESTER/COTTON
COVER TERMINAL
ASS´Y FRONT PANEL
ASS´Y PCB DISPLAY ASS´Y PCB DISPLAY
ASS´Y TRAY DRAIN
ASS´Y STEPPING MOTOR
BLADE-H ASS´Y EVAP ASS´Y EVAP
SPACER EVAP
ASS´Y HOLDER MOTOR
HOLDER MOTOR
CLIP EARTH WIRE
TERMINAL BLOCK ASS´Y
MOTOR FAN IN MOTOR FAN IN ASS´Y-C-F-FAN
ASS´Y HOLDER BEARING
RUBBER BEARING HOLDER BEARING
BEARING ASS´Y MAIN PCB ASS´Y MAIN PCB ASS´Y MAIN PCB ASS´Y MAIN PCB
ASS´Y-TERMISTOR
CASE-CONTROL
ASS´Y-BACK BODY
HOLDER PIPE
PLATE HANGER
TRANSFORMER
HIPS HIPS
PC
PC PP
ASS’Y
PP
ABS(V0)
HIPS ASS’Y ASS’Y ASS’Y
MSFCC20A03
ABS
PLATE1.2(5/8”)
SLIT1.5(1/2”)
PVC ASS’Y PP(VO)
SECC
5P,25A
IC-9430SKJ5A IC-9430SKF6A
ø95 x L
ASS’Y
CR
PP
PG5
PD-S18B1Q-03
PD-S18B1Q-06
PD-S18B1Q-09
PD-S18B1Q-11
103AT
ABS(VO)
HIPS
PP
SGCC-M
AC230V / DC17V
A Q T 2 4 A 1 ( B 1 ) Q E A Q T 2 4 A 2 ( B 2 ) Q E
S H 2 4 Z V
A Q T 2 4 A 1 ( B 1 ) Q B A Q T 2 4 A 2 ( B 2 ) Q B
1(A1,A2)
1(B1,B2) 1(A1,A2) 1(B1,B2)
2 1
2 1 1
1
1 1(A1,A2) 1(B1,B2)
1
1
1
1
­1 1
1 1 1
1
-
1
1 1 1
1
1(A1,B1) 1(A2,B2)
-
­1 1
1
1 1 1
1(A1,A2)
1(B1,B2)
1(A1,A2)
1(B1,B2)
2 1 2 1 1 1 1
1(A1,A2)
1(B1,B2)
1 1 1 1
­1 1 1 1 1
­1 1 1 1 1
1 1(A1,B1) 1(A2,B2)
-
-
1
1
1
1
1
1
Exploded Views and Parts List
Q’TY
A Q 1 8 A 1 ( B 1 ) Q E A Q 1 8 A 2 ( B 2 ) Q E
S H 1 8 Z V
1(A1,A2) 1(B1,B2) 1(A1,A2) 1(B1,B2)
2 1 2 1 1 1 1
1(A1,A2)
1(B1,B2)
1 1 1
­1 1 1 1 1 1 1
­1 1 1 1 1
-
-
1(A1,B1) 1(A2,B2)
1 1 1 1 1 1
A Q 1 8 A 1 ( B 1 ) Q B A Q 1 8 A 2 ( B 2 ) Q B
1(A1,A2)
1(B1,B2)
1(A1,A2)
1(B1,B2)
1(A1,A2)
1(B1,B2)
1(A1,B1) 1(A2,B2)
Remark
2 1 2 1 1 1 1
1 1 1
­1 1 1 1 1 1
­1
! !
! 1 1 1 1 1
-
-
1 1 1 1 1 1
!
Samsung Electronics
6-2
Page 40
6-2 Outdoor Unit
6-2-1 18K BTU
6-3
18-1
18-2, 18-3
18-5
18-4
18-6
Samsung Electronics
Page 41
Parts List(18K)
No.
1
DB90-00033A
2
DB90-20160D
3
DB67-50063A
4
DB60-30020A
5
DB31-10119C DB31-10119A
6
DB61-20008C
7
DB94-50034A
8
DB75-30103A
9
DB90-40176B
10
DB64-60172A
11
DB90-40124A
12
DB95-10263B DB95-10263A
12-1
14-2
12-2 12-3 12-4
13 13-1 13-2
14 14-1
14-3
15
DB73-10004A DB60-30028A DB60-30018A DB63-10165A DB99-10134A DB62-40074C DB62-40036A DB99-10136A DB62-31800B DB62-40039B DB62-31802B DB93-00110B DB93-40736B
15-1
DB34-90057C
DB34-90057A 15-2 15-3 15-4
15-5
18-1
18-2
18-3 18-4 18-5 18-6
16 17
2501-001139 DB65-40022D DB95-90026B
3601-000236 DB72-50537A DB72-50544A DB39-20546A DB39-10058A DB39-20235A DB67-20011A DB60-30010A DB60-30010C
CODE NO
Description Specification
ASS’Y-WELD FRONT
ASS’Y-BASE OUT
ASS’Y-FAN
NUT FLANGE MOTOR FAN OUT MOTOR FAN OUT
BASE-MOTOR
PARTITION
ASS’Y-CONDENSER
ASS’Y COVER-CONTROL
ASS’Y-CABI BACK
TOP COVER COMPRESSOR COMPRESSOR
GROMMET ISOLATOR
NUT WASHER
NUT-FLANGE
COVER-TERMINAL
ASS’Y-4WAY V/V PACKED V/V 1/2”
4WAY V/V
ASS’Y CHECK V/V
TUBE-CAPI(C)
PACKED V/V 1/4”
TUBE-CAPI(H) ASS’Y CONTROL OUT ASS’Y CONTROL OUT
SWITCH MAGNET SWITCH MAGNET CAPACITOR DUAL TERMINAL BLOCK
SPARK KILLER
FUSE
CLOTH SOUND
CLOTH SOUND UPP
CONNECTOR POWER
CONNECTOR WIRE CONNECTOR WIRE
DRAIN ;LUG OUT NUT FLANGE 1/4” NUT FLANGE 1/2”
SC-90073T SC-90073T
AS+G/F20%
M6LF AMASS-035AVEB AMASS-035ZTEA
SGCC-M SGCC-M
ASS’Y
ABS(V5) SC-90073T SC-90073T
48B180JV1E7 48B190JV2E7
EPDM
M8 M5
NORYL
UQ18A1QE
10LT/MIN CHV-0201
UQ18A1QE
C1220T-0 1/4 INCH
C1220T-0 UQ18A1QE UQ18A1QB
45CG20ALB 45CG20AGB 40/2.5,450V
7P/20A
-
2A,250V
-
­3G,2.5mm 4G,1.0mm
2G,0.75mm
2
2
2
PP C3771BD C3771BD
U Q 1 8 A 1 ( B 1 ) Q E U Q 1 8 A 2 ( B 2 ) Q E
X S H 1 8 Z V
1 1 1 1 1
­1 1 1 1 1 1 1
­3 3 1 1 1 1 1 1 1 1 1 1
­1
­1 1 1 1 1 1 1 1 1 1 2 2
Exploded Views and Parts List
Q’TY
U Q 1 8 A 1 ( B 1 ) Q B
Remark
U Q 1 8 A 2 ( B 2 ) Q B
1 1
1
1
-
1
! !
1 1
1
1 1 1
­1
3
3 1 1
1
1 1
1 1 1
1
-
1
-
1 1 1
1
1
1 1
1
1
1 1 2
2
Samsung Electronics
6-4
Page 42
6-2-2 24K BTU
11
17
6
16
5
7
13-2
8
13
14-3
14
14-1
10
9
15-4
4
1
3
2
18-1
18-4
12
13-1
15-2
15-1
15
15-5
15-3
14-2
6-5
18-2, 18-3
18-5
18-6
Samsung Electronics
Page 43
Parts List(24K)
No.
1
DB90-10634A
2
DB90-20210A
3
DB67-50074A
4
DB60-20020A
5
DB31-10110E
6
DB95-20147A
7
DB94-50039A
8
DB75-30102D
9
DB90-40176B
10
DB64-60160C
11
DB90-10616A
12
DB95-10351A
DB95-10351E
13
DB99-10135A 13-1 13-2
14-1 14-2 14-3
14
15
DB62-40055F DB62-40036A DB96-10138C DB62-31798C DB62-40039C
DB62-31802F DB93-40735B DB93-40735D
15-1
DB34-90054A DB34-90054B
15-2
15-3
15-4
DB65-40022D DB95-90026B
15-5
16
DB72-50622A
17
DB72-50614A
18-1 18-2 18-3 18-4 18-5
18-6
DB39-20546A DB39-10058A DB39-20235A DB67-20011A DB60-30010A DB60-30010D
CODE NO
2501-001153 2501-001152
3601-000236
Description Specification
ASS’Y-WELD FRONT
ASS’Y-BASE OUT
ASS’Y-FAN
BOLT-SPECIAL
MOTOR FAN OUT
ASS’Y-MOTOR B/K
PARTITION
ASS’Y-CONDENSER
ASS’Y COVER-CONTROL
ASS’Y-CABI OUT
TOP COVER COMPRESSOR COMPRESSOR
ASS’Y-4WAY V/V PACKED V/V 1/2”
4WAY V/V
ASS’Y CHECK V/V
TUBE-CAPI (C)
PACKED V/V 1/4”
TUBE-CAPI (H) ASS’Y CONTROL OUT ASS’Y CONTROL OUT
SWITCH MAGNET SWITCH MAGNET
CAPACITOR DUAL CAPACITOR DUAL TERMINAL BLOCK
SPARK KILLER
FUSE
CLOTH SOUND COMP
CLOTH SOUND UPP
CONNECTOR POWER
CONNECTOR WIRE CONNECTOR WIRE
DRAIN PLUG OUT
NUT FLANGE 1/4”
NUT FLANGE 1/2”
SC-90073T SC-90073T
AS+G/F20%
M6LF
OSME-716SRC
SGCC-M SGCC-M
ASS’Y
ABS(V5) SC-90073T SC-90073T
AWG5532EXC AWG5532EXN UQT24A1QE/B
10LT/MIN CHV-0201
UQT24A1QE/B
C1220T-0 1/4 INCH C1220T-0
UQT24A1QE
UQT24A1QB
41NB21AL
41NB21AG 45/3.0, 450V 35/3.0, 450V
7P/20A
-
2A,250V
-
­3G,2.5mm 4G,1.0mm
2G,0.75mm
2
2
2
PP C3771BD C3771BD
Exploded Views and Parts List
U Q T 2 4 A 1 ( B 1 ) Q E U Q T 2 4 A 2 ( B 2 ) Q E
X S H 2 4 Z V
1 1 1 1 1 1 1 1 1 1 1 1
­1 1 1 1 1 1 1 1
­1
­1
­1 1 1 1 1 1 1 1 1 2 2
Q’TY
U Q T 2 4 A 1 ( B 1 ) Q B U Q T 2 4 A 2 ( B 2 ) Q B
Remark
1 1 1 1 1
!
1 1 1 1 1 1
­1 1 1 1 1 1 1 1
­1
­1
­1 1 1 1 1 1 1 1 1 1 2 2
Samsung Electronics
6-6
Page 44
6-3 Remote Control & PCB Box
6-3-1 Remote Control (DB93-30073B)
Parts List
No
1 2 3 4 5 6 7 8 9
10 11 12 13 14
15
16
17
6-7
CODE NO
DB61-10144A DB61-10145A DB64-20054A DB63-10477A DB74-10084A DB73-20110C DB64-40167A DB64-40166B DB68-10789B DB68-10790B
PH-M2 DB67-60061A DB67-60062A DB67-60063A
90 X 250 DB93-40179C DB61-40243A
Description
CASE UP
CASE LOW
DOOR REMOCON
COVER BATTERY
FILTER REMOCON
RUBBER REMOCON
INLAY LCD
INLAY REMOCON
LABEL REMOCON
LABEL DOOR
SCREW TAP SPRING BATTERY SPRING BATTERY SPRING BATTERY
PE BAG
ASS’Y PCB REMOCON
HOLDER REMOCON
Specification
ABS ABS ABS ABS
PC
SILICON
PC
PC ART 90 ART 90
PH-M2 SUS 304 SUS 304
SUS 304 90 X 250
ABS
Q’TY
1 1 1 1 1 1 1 1 1 1 6 1 1 1 1 1 1
Remark
Samsung Electronics
Page 45
6-3-2 PCB Box
Exploded Views and Parts List
3
4
Parts List
No
1
2
3
5
CODE NO Description
DB61-10151A
DB93-10545B
DB93-10545D
DB93-10555E
DB93-10555F
DB32-10008E
CASE-CONTROL
ASS'Y MAIN PCB
ASS'Y MAIN PCB
ASS'Y MAIN PCB
ASS'Y MAIN PCB
ASS'Y THERMISTOR
2
1
Q’TY
Specification
Remark
24K BTU 18K BTU
ABS
PD-Q24B1Q-03
PD-Q24B1Q-06
PD-Q24B1Q-09
PD-Q24B1Q-11
103AT 240/240
1
1(A1,B1)
1(A2,B2)
-
-
1
1
-
-
1(A1,B1)
1(A2,B2)
1
4
DB93-10600B
DB93-10599B
5
DB26-10065B
Samsung Electronics
ASS’Y PCB DISPLAY
ASS’Y PCB DISPLAY
TRANSFORMER
ROUND
EDGE
AC230V/DC17
1(B1,B2)
1(A1,A2)
1
1(B1,B2)
1(A1,A2)
1
6-8
Page 46
M E M O
6-9
Samsung Electronics
Page 47
7. Block Diagrams
7-1 Refrigerating Cycle Block Diagram
INDOOR UNIT
Heat exchanger (Evaporator)
OUTDOOR UNIT
Capillary tube
T
Liquid side
T
Gas side
2-way valve
3-way valve
Accumulator
Check valve
Capillary tube
Compressor
Heat exchanger (Condenser)
4-way valve
Cooling Heating
Gas leak check point
Samsung Electronics
7-1
Page 48
8. PCB Diagrams
8-1 Main PCB
8-1
B
B B
Samsung Electronics
Page 49
Parts List
PCB Diagrams
No
1 2 3 4 5 6 7 8 9
10
11
12 13 14
15 16 17 18 19
20 21 22
23 24
25 26 27
28 29 30
31 32
33 34 35
36 37 38
39 40
41 42 43
44 45
46 47 48
49 50 51
52
DESIGN LOCATION
F701 F701,F101 IC01 IC01 IC01 IC02 CR71 FT71 R903,904,905,906 R203 R202,301,409,501~509,513,519~525,601,604,606,902 R405,407 R201,204,405,401,402,404,603,606,608 R607 R602 R403 R910,912,913 R406,408 D101~105 SS71 BZ61 C202,402 C301,401 C102,104,201,203,403,404,501,502,902 C103 C105 C101 C601 IC04 IC03 X501 IC05,IC06,IC07 Q201,401,601,602 Q603 Q902, Q901 SW91 CN73 CN43 CN41 CN61 CN62 CN71 CN92 RY72,RY72,RY71 J1~J35, HR01~HR04, LR01~LR04, OPJ1, OPJ2, OPJ3 CN72 CN11 F101 IC08 R903 C701 C702
PART CODE NO
DE32-10037A DE47-40024A DE13-20008A DE62-30032A DE60-10100A DE13-10016A
2001-000776 2001-000588 2001-000065 2001-000036 2001-000042 2001-000855 2001-001088 2001-000890
A1000-0244 2004-001137 0402-000137
B4190-0016
DE30-20016A
2202-000783 2202-000796 2202-000780 2401-000710 2401-001397 2401-000180 2401-001573
DE09-10149A DE13-20009A
2802-000103
DE13-20024A
A4050-0168 0501-000292 0504-000144 3404-001013 3711-000262 3711-000879 3711-000940 3711-001038 3711-001036
3711-001154
B3068-0092
DE39-60001A
DB47-90053A
2305-001027
Description
FUSE
HOLDER-FUSE
IC-VOLT REGU
HEAT-SINK SCREW-PH
IC-VOLT REGU
C-FILM
FILTER NOISE
R-CARBON R-CARBON R-CARBON R-CARBON R-CARBON R-CARBON R-CARBON R-CARBON R-CARBON
R-METAL FILM
DIODE-RECT
THYRISTOR
BUZZER C-CERAMIC C-CERAMIC C-CERAMIC
C-ELEC C-ELEC C-ELEC C-ELEC
IC-MCU
IC
RSONATOR-CERAMIC
IC-DRIVE
TR-GENERAL TRANSISTOR TRANSISTOR
SWITCH-TACT CONNECTOR WAFER CONNECTOR WAFER CONNECTOR WAFER CONNECTOR WAFER CONNECTOR WAFER CONNECTOR WAFER CONNECTOR WAFER
RELAY
WIRE SO COPER
CONNECTOR WAFER
FUSE
EEORIM
R-CARBON
C-FILM, MPEF
Specification
FST 250V 3.15A
FH-51H 7.5A
KA7812A
AL H25
M3*6 FeFzY
KA7805A
CQS 450V 1.2µF
LSAO5230P 250V~2A 23mH*2
RD 1/2 T(S) 621-J
RD 1/4 TP 332-J RD 1/4 TP 103-J RD 1/4 TP 331-J RD 1/4 TP 102-J RD 1/4 TP 560-J
RD 1/2 T(S) 102-J
RD 1/4 TP 682-J RD 1/8 TP 332-J RD 1/4 TP 682-F
1N4007
G3MB-202PL
CBE 2220BA STICK
CA OA 50V 103Z CA OA 50V 102Z CA OA 50V 104Z
CE04 25V 222-M CE 04 25V 471-M CE 04 35V 102-M
47/50V
MB89635R-466
KA7533Z
10MHz
KID65003AP
KSC945Y
A708Y R2002
KPT-1115V
YW396-05AV WHT
SMW250-03 BLU
SMW250-04 WHT SMW250-06 WHT SMW250-06 BLUE
YW396-03AV BLK
SMW250-09 WHT
JQ1a-12V
PI0.6 SN T 52MM
YW396-03AV WHT
SMW250-03 RED
FST 250V~2A
93C5L
RD 1/2T(S) 471-J
224K
104K
Samsung Electronics
8-2
Page 50
8-2 ASS’Y DISPLAY & Module
•Round/Semi-Round/Lip-Type (DB93-10600B) • Edge Type (DB93-10599B)
Parts List TYPE
“Round”
“Semi-Round”
“Lip” Type
(DB93-10600B)
“Edge”
Type
(DB93-10599B)
NO
10 11 12 13 14 15 16 17
10 11 12 13 14 15 16 17 18
CODE-NO
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
DB41-10207B
0601-001333 0601-001059 0601-001060 0601-001196
DB32-50027A
2202-000780 2001-000515
2201-000283
0401-000005 DB39-20520A DB61-10194A
DB61-10195A
DB72-10238A DB72-10239A
DB41-10206B
0601-001333
0601-001059
0601-001060
0601-001196 DB32-50027A
2202-000780
2001-000515
2201-000283
0401-000005
DB39-20520A DB61-10192A
DB61-10193A DB72-10240A DB72-10240B
DB72-10239A
Description
PCB-DISPLAY
LED - LAMP LED - LAMP LED - LAMP
LED - LAMP
JUMP WIRE
MODULE REMOCON
C-CERAMIC
R-CARBON
CONNECTOR-WAFER
C-CERAMIC
DIODE SWITCHING
C/W DIS & MODULE
(R) CASE-CENTER PCB UP
(R) CASE-CENTER PCB LOW
SEAL C/T PCB UP
SEAL C/T PCB LOW
A
PCB-DISPLAY
LED - LAMP LED - LAMP LED - LAMP LED - LAMP
JUMP WIRE
MODULE REMOCON
C-CERAMIC
R-CARBON
CONNECTOR-WAFER
C-CERAMIC
DIODE SWITCHING
C/W DIS & MODULE
(R) CASE-CENTER PCB UP
(R) CASE-CENTER PCB LOW
SEAL C/T PCB UP (L) SEAL C/T PCB UP (R)
SEAL C/T PCB LOW
A
Specification
FR-1 T1.6 W16.5 L142.5 LTL-30EHJ(ORG/GRN) SY5511(YEL) SM5511(GRN) SO5511(ORG) 6mm PNA4612MOOXD CA OA 50V 104Z RD 1/8TP 221-J YWLA200-09P CA OA 50V 102Z IN4148 UL1007 AWG#26/9 PC(BLU) ABS(BLK) 30FOAM-PE, T=3 30FOAM-PE, T=3 DCR200H(BROWN)
FR-1 T1.6 W13 L141 LTL-30EHJ(ORG/GRN) SY5511(YEL) SM5511(GRN) SO5511(ORG) 6mm PNA4612MOOXD CA OA 50V 104Z RD 1/8TP 221-J YWLA200-09P CA OA 50V 102Z IN4148 UL1007 AWG#26/9 PC(BLU) ABS(BLK) 30FOAM-PE, T=3 30FOAM-PE, T=3 30FOAM-PE, T=3 DCR200H(BROWN)
Q’TY
1 1 1 1 1 4 1 1 2 1 1 1 1 1 1 1 1
1 1 1 1 1 3 1 1 1 1 1 1 1 1 1 1 1 1
8-3
Samsung Electronics
Page 51
9. Wiring Diagrams
9-1 Indoor Unit
Samsung Electronics
9-1
Page 52
9-2 Outdoor Unit
24K BTU
18K BTU
MARK NAME MARK NAME
52C MAGNETIC CONTACTOR TB 1,2 TERMINAL BLOCK 20S SOLENOID COIL CH CRANK CASE HEATER
C1 CAPACITOR FM1 FAN MOTOR
F FUSE(2A, 250V~) S SPARK KILLER
9-2
Samsung Electronics
Page 53
U P D A TE LOG SHEET
Application date Page Part# Note(Cause & Solution) S/Bulletin#
Use this page to keep any special servicing information. (Service Bulletin, etc.) If only parts number changes, Just change parts number directly on parts list.
And if you need more information, please see the service bulletin
Copyright
®œ 1995 by Samsung Electronics Co., Ltd. All rights reserved. This manual may not, in whole or in part, be copied, photocopied, reproduced, translated, or
converted to any electronic or machine readable
from without prior written permission of Samsung Electronics Co., Ltd.
SyncMaster 17GLi/CMG7387L Service Manual First edition June 1995.
Printed in Korea.
Tr a d e m a r k s
Samsung is a registered trademark and SyncMaster 17GLi/CMG7387L and MacMaster Cable Adapter are trademark of Samsung Electronics Co., Ltd.
Macintosh, Centris, Quadra, Duo Dock, and Power Macintosh are trademark of Apple computer, Inc.
All other trademarks are the property of their respective owners.
Page 54
10. Schematic Diagrams
10-1 Indoor Unit
PNA4612MOOXD
Samsung Electronics
10-1
Loading...