Samsung max mini-split units, AQN12VFUAGM, AQX12VFUAGM, AQN24VFUAGM, AQX24VFUAGM Technical Manual

...
BASIC TECHNICAL INFORMATION FOR:
SAMSUNG MAX
MINI-SPLIT UNITS
Distributed by:
WWW.SUNLIGHTSUPPLY.COM
Distributed by:
Samsung MAX 12,000 BTU Mini-Split
Indoor Unit: #700550 (AQN12VFUAGM) Outdoor Unit: #700552 (AQX12VFUAGM)
POWER VOLTAGE:
Power Voltage: 208/230V - 1 Ph - 60 Hz Control Voltage: DDC Fuzzy Logic Main Breaker Size: 15 A
LINE SIZES:
“Liquid” (expanded gas) line: 1/4” Suction: 3/8”
BOTH LINES MUST BE INSULATED SEPARATELY
INTERCONNECT LENGTH:
Maximum/Minimum Length: 50 feet / 10 feet Vertical Lift: 26 feet
Note: Condenser can be above or below evaporator
CHARGING:
Unit is charged for: 25 ft. (Factory Charge 31.7oz. R410A) Additional Charge of R410A: 0.16 oz./ft. over 25 ft.
CHARGE FOR LINE RUN LENGTHS:
Length: 25 35 45 50 Added Charge (oz.): 0 1.6 3.3 4.0
INTERCONNECTING WIRING:
Gauge:
14 AWG Power & 16 AWG Shielded Communication
Number of Interconnecting Wires: 3x14 AWG Power & 2x16 AWG Control = 5 Total
F2 F1
G L1 L2
F2 F1
G L1 L2
Separate all Power & Communications Wiring by 2”
Indoor Unit (Ground)
WWW.SUNLIGHTSUPPLY.COM
Outdoor
Unit
208/230V
Breaker
Samsung MAX 24,000 BTU Mini-Split
Indoor Unit: #700554 (AQN24VFUAGM) Outdoor Unit: #700556 (AQX24VFUAGM)
POWER VOLTAGE:
Power Voltage: 208/230V - 1 Ph - 60 Hz Control Voltage: DDC Fuzzy Logic Main Breaker Size: 20 A
LINE SIZES:
“Liquid” (expanded gas) line: 1/4” Suction: 5/8”
BOTH LINES MUST BE INSULATED SEPARATELY
INTERCONNECT LENGTH:
Distributed by:
Maximum/Minimum Length: 98 feet / 10 feet Vertical Lift: 50 feet (Trap required at 26 ft.)
Note: Condenser can be above or below evaporator
CHARGING:
Unit is charged for: 25 ft. (Factory Charge 58.1oz. R410A) Additional Charge of R410A: 0.16 oz./ft. over 25 ft.
CHARGE FOR LINE RUN LENGTHS:
Length: 25 35 45 55 65 75 85 95 98 Added Charge (oz.): 0 1.6 3.2 4.8 6.4 8.0 9.6 11.2 11.68
INTERCONNECTING WIRING:
Gauge:
14 AWG Power & 16 AWG Shielded Communication
Number of Interconnecting Wires: 3x14 AWG Power & 2x16 AWG Control = 5 Total
F2 F1
G L1 L2
F2 F1
G L1 L2
Separate all Power & Communications Wiring by 2”
Indoor Unit (Ground)
Outdoor
Unit
208/230V
Breaker
WWW.SUNLIGHTSUPPLY.COM