Samsung AQ07ACVE, AQ09ACVE, AQ12ACVE, SH07CA1, SH09CA1 Service Manual

...
ROOM AIR CONDITIONER
INDOOR UNIT AQ07ACVE AQ09ACVE AQ12ACVE SH07CA1 SH09CA1 SH12CA1
SERVICE
OUTDOOR UNIT UQ07ACVE UQ09ACVE UQ12ACVE
SH07CA1X SH09CA1X SH12CA1X
Manual
CONTENTSAIR CONDITIONER
1. Precautions
2. Product Specifications
3. Operating Instructions and Installation
4. Disassembly and Reassembly
6. Exploded Views and Parts List
7. Block Diagrams
8. PCB Diagrams
9. Wiring Diagrams
10. Schematic Diagrams
ELECTRONICS
© Samsung Electronics Co., Ltd. Mar. 2000.
Printed in Korea. Code No. DB81-00143A(1)
1. Precautions
O.K
1. Warning: Prior to repair, disconnect the power cord from the circuit breaker.
2. Use proper parts: Use only exact replace­ment parts. (Also, we recommend replacing parts rather than repairing them.)
3. Use the proper tools: Use the proper tools and test equipment, and know how to use them. Using defective tools or test equip­ment may cause problems later-intermittent contact, for example.
4. Power Cord: Prior to repair, check the power cord and replace it if necessary.
5. Avoid using an extension cord, and avoid tapping into a power cord. This practice may result in malfunction or fire.
6. After completing repairs and reassembly, check the insulation resistance. Procedure: Prior to applying power, measure the resis­tance between the power cord and the ground terminal. The resistance must be greater than 30 megohms.
dangerous
Fig. 1-1 Avoid Dangerous Contact
Fig. 1-2 No Tapping and No Extension Cords
7. Make sure that the grounds are adequate.
8. Make sure that the installation conditions are satisfactory. Relocate the unit if neces­sary.
9. Keep children away from the unit while it is being repaired.
10. Be sure to clean the unit and its surround­ing area.
Fig. 1-3 No Kids Nearby!
Fig. 1-4 Clean the Unit
Samsung Electronics
1-1
MEMO
1-2
Samsung Electronics
2. Product Specifications
2-1 Table
Item
T ype
Cooling Btu/h Dehumidifying l/h Heating Btu/h Low temp. heating Btu/h Air volume Cooling m3/min
Perfor-
mance
Noise Cooling dB
Energy Cooling Btu/h.W Efficiency ratio Heating Btu/h.W Power Ø-V-Hz Power Cooling W Consumption Heating W Operating Current Cooling A
Power factor Cooling %
Power
Starting current A Power cord Length m
Fuse capacity A Outer Width x Height mm dimension x Depth inch Weight kg Refrigerant pipe Liquid OD(mm) x L(m)
Drain hose ID(mm)x L(m)
Size
Compressor T ype
Blower Type
Heat exchanger Refrigerant control unit Freezer oil capacity Refrigerant to charge(R-407C) Protection device
Cooling test condition Heating test condition Maximum operation Condition
Heating m3/min
Heating dB
Heating A
Heating %
Number of core wire
Gas OD(mm) x L(m)
Motor T ype
Rated output W
Motor T ype
Rated output W
Model
SH07CA1
AQ07ACVE
Indoor unit Outdoor unit
Wall-mounting
7000
1.0
8000
-
5.3 -
5.7 ­35 49 49 49
8.7
9.7
1-220/240-50
800 820
3.6
3.6
98.2
98.0 17
2-
250V 10/16A
3.15 -
815x298x182 720x532x245
32.08x11.73x7.17 28.35x20.94x9.65
9.6 32 ø6.35 x 5 ø9.52 x 5
ø17 x 2
- Rotary
--
- 800
Cross-fan Propeller
Resin Steel
35 20
2Row 12Step 1Row 20Step
Capillary tube
362 650
- MRA12086
-12008
Indoor unit : DB27˚C WB19˚C Outdoor unit : DB35˚C WB24˚C Indoor unit : DB20˚C WB15˚C Outdoor unit : DB 7˚C WB 6˚C Indoor unit : DB32˚C WB23˚C Outdoor unit : DB43˚C WB26˚C
SH09CA1
AQ09ACVE
Indoor unit Outdoor unit
Wall-mounting
8700
1.1
10.000
-
6.5 -
7.0 ­39 50 39 50
9.3
11.1
1-220/240-50
930 900
4.3
4.5
96.6
96.2 22
2-
250V 10/16A
3.15 -
815x298x182 762x532x280
32.08x11.73x7.17 30.00x20.94x11.02
9.6 34 ø6.35 x 5 ø9.52 x 5
ø17 x 2
- Rotary
--
- 900
Cross-fan Propeller
Resin Steel
35 20
2Row 12Step 1Row 20Step
Capillary tube
362 750
- MRA12037
-12007
815x298x182 762x532x280
32.08x11.73x7.17 30.00x20.94x11.02
2Row 12Step 2Row 20Step
SH12CA1
AQ12ACVE
Indoor unit Outdoor unit
Wall-mounting
12000
1.8
13500
-
8.0 -
8.5 ­42 53 42 53
8.5
8.7
1-220/240-50
1400 1550
6.4
6.9
96.9
96.8 30
2-
250V 10/16A
3.15 -
9.6 39 ø6.35 x 5 ø12.7 x 5
ø17 x 2
- Rotary
--
- 1445
Cross-fan Propeller
Resin Steel
35 20
Capillary tube
602
1100
- MRA12074
-12007
Samsung Electronics
2-1
2-2 Dimensions
815 182
298
2-2-1 Indoor Unit
(Front view) (Remote control)
Air in
115
Air out
2-2-2 Outdoor Unit
AQ07ACVE SH07CA1
(Rear view)
245
267
532
(Front view)
720
2245
Installation plate
11
20
496
(Rear view)
55
AQ09ACVE / AQ12ACVE SH09CA1 / SH12CA1
2-2
295
280
(Front view)
532
555
762
(Rear view)
Samsung Electronics
2-3 Refrigerating Cycle Block Diagram
INDOOR UNIT
Heat exchanger (Evaporator)
OUTDOOR UNIT
Capillary tube
1
T
Liquid side
Cross fan
2
T
Gas side
2-way valve
3-way valve
Check valve
Capillary tube
Compressor
Heat exchanger (Condenser)
Propeller fan
4-way valve
Cooling
Heating
Gas leak check point
Samsung Electronics
2-3
MEMO
2-4
Samsung Electronics
3. Operating Instructions and Installation
3-1 Operating Instructions
3-1-1 Name & Function of Key in remote controller
NO
1
2
3
4
5
NAMED OF KEY
(UP)
(DOWN)
FUNCTION OF KEY
Power On/Off button to start and stop airconditioner or timer set up
Temp. up button. To increase the temperatute by the pressing the temperature button
Temp. down button. To decrease the temperature by the pressing the temperature button
Each time you press this button Mode is changed in the following order
Press until the appearance. the air condition cools or heats the room as quickly as possible. after 30minutes, the air, the airconditioner is reset automatically to the previous mode
Press until the appearance. the sleep timer can be used when you are cooling or heating your room to switch the air conditioner off automatically after a perriod of six hours.
Each time you press this button, FAN SPEED is changed in the following order.
: Auto Mode : Fan Only : Cool Mode : Heat Mode : Dry Mode
6
7
8
Samsung Electronics
Adjust air flow vertically.
The ON Timer enables you to switch onthe air conditioner automatically after a given period of time that is from 30 minutes to 24 hours. To cancel the On Time, press the (Set/Cancel) button.
The Off Timer enables you to switch off the air conditioner automatically after a given period of time that is from 30 minutes to 24 hours. To cancel the On Time, press the (Set/Cancel) button.
3-1
Operating Instructions and Installation
3-1-1 Name & Function of Key in remote controller
1. AUTO MODE : In this mode, operation mode(COOL, HEAT, DRY) is selected auto­matically by the room temperature of initial operation.
Room Temp Tr21°C+∆T 21°C +∆T>Tr
T= -1°C, -2°C, 0°C+1°C+2°CT is controlled by setting temperature
up/down key of remote controller
2. COOL MODE : The unit operates according to the difference between the setting and room temperature. (18°C~30°C)
3. HEAT MODE : The unit operates according to the difference between the setting and room temperature.(16°C~30°C) *Prevention against cold wind : For about 3~5 minutes after initial operation, thermo control or “de-ice”, the indoor fan will either not operate or operate very slow­ly(510 rpm), then switch to the selected fan speed. This period is to allow the indoor unit's heat-exchanger to prewarm before emitting warm air. *High temperature release function : The outdoor unit for and compressor ON/OFF control for safety operation, when the over­heat is heat exchanger of indoor unit. *De-ice : Deicing operation is controlled by indoor unit's heat exchanger temperature and accumulating time of compressor's operation. De-ice end by sensing of the processing time by de-ice Condition.
Cool Operation (Set Temp:AUTO SETTING)
Heat Operation (Set Temp : 22°C+∆T)
Operation Type
4. DRY MODE : Has 3 states, each determined by room temperature. The unit operates in DRY mode. *Compressor ON/OFF Time is controlled compulsorily(can not set up the fan speed, always breeze). *Protective function : Low temperature release. (Prevention against freeze)
5. TURBO MODE : This mode is available in AUTO, COOL, HEAT, DRY, FAN MODE. When this button is pressed at first, the air conditioner is operated “powerful” state for 30 minutes regardless of the set tempera­ture, room temperature. When this button is pressed again, or when the operating time is 30 minutes, turbo operation mode is canceled and returned to the previous mode. *But, if you press the TURBO button in DRY or FAN mode that is changed with AUTO mode automatically.
6. SLEEP MODE : Sleep mode is available only in COOL or HEAT mode. The operation will stop after 6 hours. *In COOL mode : The setting temperature is automatically raised by 1°C each 1hour When the temperature has been raised by total of 2°C, that temperature is main­tained. *In HEAT mode : The setting temperature is automatically droped by 1°C each 1hour. When the temperature has been droped by total of 2°C, that temperature is main­tained.
7. FAN SPEED : Manual (3 step), Auto (4 step) Fan speed automatically varies depending on both the difference between setting and the room temperature.
3-2
Samsung Electronics
Operating Instructions and Installation
8. COMPULSORY OPERATION : For operating the air conditioner without the remote controller. *AUTO : The operating is the same func­tion that AUTO MODE in the remote con­troller.
9. SWING : BLADE-H is rotated vertically by the stepping motor. *Memory louver : When ON/OFF button is pressed at stop state, the BLADE-H returns to its original location which is operating state before stop *Swing Set : Press the button under the remote control is displayed on LCD the , and the blades move up and down, about 43°. If the one more time press the button, bla­tles location is stop.
10. Quick OFF TIMER: OFF timer (quick timer) allows reservation or cancel the timer on and timer off quickly When OFF timer button is pressed at oper­ating state, LCD displays the polling state sequentially. The LCD also displays the time remaining.
OFF TIMER : The air Conditioner is turned OFF at a specified time using .
OFF TIMER
*ON TIMER : Only timer LED lights on. *OFF TIMER : Both timer and operation LED lights on. *3 minutes delay timer.
12. SELF Diagnosis
LED DISPLAY
oper-
TIMER
ation
FAN
Turbo
Check Point
Interruption of electric power and Power on.
Abnormal condition of the room sensor.
Abnormal condition of the indoor unit's heat exchanger sensor.
Indoor unit fan motor lock.
LED
:
blinking
: LED off
13. BUZZER SOUND : Whenever the ON/OFF button is pressed or whenever change occurs to the condition which is set up or select, the compulsory operation mode, buzzer is sounded "beep"
11. 24-Hour ON/OFF Real Setting Timer. : The air conditioner is turned ON at a specified time using .
ON TIMER
Samsung Electronics
3-3
3-2 Installation
3-2-1 Selecting Area for Installation
Select an area for installation that is suitable to the customer's needs.
3-2-1(a) Indoor Unit
1. Make sure that you install the indoor unit in an area providing good ventilation. It must not be blocked by an obstacle affecting the airflow near the air inlet and the air outlet.
2. Make sure that you install the indoor unit in an area allowing good air handling and endurance of vibration of the indoor unit.
3. Make sure that you install the indoor unit in an area where there is no source of heat or vapor nearby.
4. Make sure that you install the indoor unit in an area from which hot or cool air is spread evenly in a room.
5. Make sure that you install the indoor unit in an area away from TVs, audio units, cord­less phones, fluorescent lighting fixtures and other electrical appliances (at least 1 meter).
6. Make sure that you install the indoor unit in an area which provides easy pipe connec­tion with the outdoor unit, and easy drainage for condensed water.
(Fix the unit firmly if it is mounted in a
high place.)
3. Make sure that you install the outdoor unit in area providing good ventilation and which is not dusty. It must not be blocked by any obstacle affecting the airflow near the air inlet and the air outlet.
4. Make sure that you install the outdoor unit in area free from animals or plants.
5. Make sure that you install the outdoor unit in area not blocking the traffic.
6. Make sure that you install the outdoor unit in area easy to drain condensed water from the indoor unit.
7. Make sure that you install the outdoor unit in area which provides easy connection within the maximum allowable length of a coolant pipe(10 meters).
Note
1. Add 10 grams of refrigerant (R-22) for every 1 meter if the pipe length exceeds the standard pipe length of 5 meters.
2. Maintain a height between the indoor and outdoor units of less than 3 meters.
8. Make sure that you install the outdoor unit in an area which is large enough to accom­modate the measurements
shown in figure on the next page.
7. Make sure that you install the indoor unit in an area which is large enough to accomo­date the measurements shown in figure on the next page.
3-2-1(b) Outdoor Unit
1. Make sure that you install the outdoor unit in area not exposed to the rain or direct sun light.
(Install a separate sunblind if exposed to
direct sun light.)
2. Make sure that you install the outdoor unit in area allowing good air moment, not amplifying noise or vibration, especially to avoid disturbing neighbours.
Caution :
It is harmful to the air conditioner if it is used in the following environments: greasy areas (including areas near machines), salty areas such as coast areas, areas where sulfuric gas is present such as hot spring areas. Contact your dealer for advice.
3-4
3-2-1(c) Remote Control Unit
1. Make sure that you install the remote con­trol unit in an area free from obstacles such as curtains etc, which may block signals from the remote control unit.
2. Make sure that you install the remote con­trol unit in an area not exposed to direct sunlight, and where there is no source of heat.
3. Make sure that you install the remote con­trol unit in an area away from TVs, audio units, cordless phones, fluorescent lighting fixtures and other electrical appliances (at least 1 meter).
Samsung Electronics
Cut the piping hole sloped slightly
3-2-2 Installation diagram of indoor unit and outdoor unit
Operating Instructions and Installation
A Indoor unit gas leak test check point
Indoor unit
Piping
2
3
1
Tape vinyl
B Drain hose installation
Cut the piping hole sloped slightly
Piping may be laid to the rear, left, right or down .
Right
Rear
250mm or more
5
6
9
Down
70mm or more
7
Rear
200mm or more
Left
“H”metere s maximum
Remote control
Remote control holder
4
Model L H **7**
10
**9**
**12**
1 2 3 4 5
Piping (Liquid) 1/4" Clamper tube
7K/9K BTU Piping(Gas)3/8” 12K BTU Piping(Gas)1/2”
Installation tube Pipe-connection Vinyl tape Screw Putty Drain hose
6 7 8
9
10
Installation plate
15 7 10 7 15 7
Samsung Electronics
3-5
Operating Instructions and Installation
20
160
100
3-2-2(a) Fixing the Installation Plate
(Unit : mm)
(Unit : mm)
Installation plate
1. Determine the position of the pipe and drain hose hole using the right figure and drill the hole with an inner diameter of 65mm so that it slants slightly downwards.
Pipe hole (ø65mm)
2. If you are fixing the indoor unit to a… Then follow Steps…
Wall 3.
Window frame 4 to 6.
3. Fix the installation plate to the wall in a manner appro­priate to the weight of the indoor unit.
If you are mounting the plate on a concrete wall with
60
340280
anchor bolts, the anchor bolts must not project by more than 20mm.
4. Determine the positions of the wooden uprights to be attached to the window frame.
3-2-2(b) Purging the Unit
5. Attach the wooden uprights to the window frame in a manner appropriate to the weight of the indoor unit.
410~730
6. Using tapped screws, attach the installation plate to the wooden uprights, as illustrated in the last figure oppo­site.
On delivery, the indoor unit is loaded with an inert gas. All this gas must therefore be purged before connecting the assembly piping. To purge the inert gas, proceed as fol­lows.
Unscrew the caps at the end of each pipe.
Result : All inert gas escapes from the indoor unit.
To prevent dirt or foreign objects from getting into
the pipes during installation, do NOT remove the caps completely until you are ready to connect the piping.
3-6
Samsung Electronics
3-2-2(c) Connecting the Assembly Cable.
N 1 2 3 4
1 5 E32 4
1
32 4 5 E
The outdoor unit is powered from the indoor unit via the assembly cable. If the outdoor unit is more than five metres away from the indoor unit, the cable must first be extended to a maximum of ten metres.
1. Extend the assembly cable if necessary.
2. Open the front grille by pulling on the tabs on the lower right and left sides of the indoor unit.
Indoor unit
Earth terminal
Outdoor unit
Earth terminal
3. Remove the screw securing the connector cover.
4. Pass the assembly cable through the rear of the indoor unit and connect the assembly cable to terminals 1(N) to 4.
• Each wire is labelled with the corresponding terminal number.
5. Firmly fix the ass’y cable with clamp wire holdet.
6. Pass the other end of the cable through the 65mm hole in the wall.
7. Replace the connector cover, carefully tightening the screw.
8. Close the front grille.
9. For further details on how to plug the other end of the assembly cable into the outdoor unit, refer to page 3-8.
Operating Instructions and Installation
3-2-2(d) Installing and Connecting the Indoor Unit Drain Hose
Care must be taken when installing the drain hose for the indoor unit to ensure that any condensa­tion water is correctly drained outside.l When passing the drain hose through the 65mm hole drilled in the wall, check that none of the following situations occur.
To install the drain hose, proceed as follows.
1. If necessary, connect the 2-metre extension to the drain hose.
2. If you are using the extension, insulate the inside part of the extension drain hose with a shield.
3. Pass the drain hose under the refrigerant piping, taking care to keep the drain hose tight.
4. Pass the drain hose through the hole in the wall, making sure that it is sloping downwards, as
The hose must NOT slope upw ards.
The end of the drain hose must NOT be placed in water.
shown in the illustrations above.
Shield
Do NOT bend the hose in different directions.
Keep a clearance of at least 5cm between the end of the hose and the ground.
Do NOT place the end of the drain hose in a hollow.
The hose will be fixed permanently into position once the whole installation has been tested for gas leaks;
Drain hose Extension drain hose
Samsung Electronics
3-7
Operating Instructions and Installation
3-2-2(e) Outdoor unit installation
Wiring connection
1. Remove the cover-E parts.
2. Firmly connect the cable connector in the terminal block.
3. Fasten the M4 ring terminal to the hole marked
4. Firmly fix the ass'y cable with clamp wire holder.
5. Assemble the cover-E parts.
6. To prevent the entry of water, form a trap of the ass'y cable as illustrated in the installation dia­gram of indoor and outdoor unit.
Ass’y cover valve (RO Hand cabi, RH)
N 1 2 3 4
Installing and Connecting the Outdoor Unit Drain Hose
When using the air conditioner in the heating, ice may accumulate.
Drain hole
3-8
Duting de-icing, the condensed water must be drained off safely. Consequently, you must install a drain hose on the outdoor unit, following the instructions below.
1. Insert the drain plug into the drain hole on the underside of the outdoor unit.
2. Connect the drain hose to the drain plug.
3. Ensure that the drained water runs off correctly and safely.
Samsung Electronics
3-2-2(f) Flare Modification
• Tools used
Flare modification procedure
Operating Instructions and Installation
1) Cut the pipe using a pipe cutter.
90
3) Insert a flare nut into the pipe and modifty flare.
Oblique Raughness Burr
2) Remove burrs at the tip of the pipe cut.
Caution : Burrs not removed may result in
leakage of gas.
Pipe
Reamer
D
D
A
A
Outer diameter A(mm)
ø6.35mm 1.3 ø9.52mm 1.8 ø12.7mm 2.0
* Unproper flaring
Samsung Electronics
Inclined Surface
damaged
Cracked Uneven
thickness
3-9