1. Warning: Prior to repair, disconnect the
power cord from the circuit breaker.
2. Use proper parts: Use only exact replacement parts. (Also, we recommend replacing
parts rather than repairing them.)
3. Use the proper tools: Use the proper tools
and test equipment, and know how to use
them. Using defective tools or test equipment may cause problems later-intermittent
contact, for example.
4. Power Cord: Prior to repair, check the
power cord and replace it if necessary.
5. Avoid using an extension cord, and avoid
tapping into a power cord. This practice
may result in malfunction or fire.
6. After completing repairs and reassembly,
check the insulation resistance. Procedure:
Prior to applying power, measure the resistance between the power cord and the
ground terminal. The resistance must be
greater than 30 megohms.
dangerous
Fig. 1-1 Avoid Dangerous Contact
Fig. 1-2 No Tapping and No Extension Cords
7. Make sure that the grounds are adequate.
8. Make sure that the installation conditions
are satisfactory. Relocate the unit if necessary.
9. Keep children away from the unit while it is
being repaired.
10. Be sure to clean the unit and its surrounding area.
Fig. 1-3 No Kids Nearby!
Fig. 1-4 Clean the Unit
Samsung Electronics
1-1
MEMO
1-2
Samsung Electronics
2. Product Specifications
2-1 Table
Item
T ype
CoolingBtu/h
Dehumidifyingl/h
HeatingBtu/h
Low temp. heatingBtu/h
Air volumeCoolingm3/min
Perfor-
mance
NoiseCoolingdB
Energy CoolingBtu/h.W
Efficiency ratioHeatingBtu/h.W
Power Ø-V-Hz
Power CoolingW
ConsumptionHeatingW
Operating CurrentCoolingA
Power factorCooling%
Power
Starting currentA
Power cordLengthm
Fuse capacityA
OuterWidth x Heightmm
dimension x Depthinch
Weightkg
Refrigerant pipeLiquidOD(mm) x L(m)
Drain hoseID(mm)x L(m)
Size
Compressor T ype
Blower Type
Heat exchanger
Refrigerant control unit
Freezer oil capacity
Refrigerant to charge(R-407C)
Protection device
Cooling test condition
Heating test condition
Maximum operation Condition
Heatingm3/min
HeatingdB
HeatingA
Heating%
Number of core wire
GasOD(mm) x L(m)
Motor T ype
Rated outputW
Motor T ype
Rated outputW
Model
SH07CA1
AQ07ACVE
Indoor unitOutdoor unit
Wall-mounting
7000
1.0
8000
-
5.3-
5.73549
4949
8.7
9.7
1-220/240-50
800
820
3.6
3.6
98.2
98.0
17
2-
250V 10/16A
3.15-
815x298x182720x532x245
32.08x11.73x7.17 28.35x20.94x9.65
9.632
ø6.35 x 5
ø9.52 x 5
ø17 x 2
-Rotary
--
-800
Cross-fanPropeller
ResinSteel
3520
2Row 12Step 1Row 20Step
Capillary tube
362
650
-MRA12086
-12008
Indoor unit : DB27˚C WB19˚COutdoor unit : DB35˚C WB24˚C
Indoor unit : DB20˚C WB15˚COutdoor unit : DB 7˚C WB 6˚C
Indoor unit : DB32˚C WB23˚COutdoor unit : DB43˚C WB26˚C
SH09CA1
AQ09ACVE
Indoor unitOutdoor unit
Wall-mounting
8700
1.1
10.000
-
6.5-
7.03950
3950
9.3
11.1
1-220/240-50
930
900
4.3
4.5
96.6
96.2
22
2-
250V 10/16A
3.15-
815x298x182762x532x280
32.08x11.73x7.17 30.00x20.94x11.02
9.634
ø6.35 x 5
ø9.52 x 5
ø17 x 2
-Rotary
--
-900
Cross-fanPropeller
ResinSteel
3520
2Row 12Step 1Row 20Step
Capillary tube
362
750
-MRA12037
-12007
815x298x182762x532x280
32.08x11.73x7.17 30.00x20.94x11.02
2Row 12Step 2Row 20Step
SH12CA1
AQ12ACVE
Indoor unitOutdoor unit
Wall-mounting
12000
1.8
13500
-
8.0-
8.54253
4253
8.5
8.7
1-220/240-50
1400
1550
6.4
6.9
96.9
96.8
30
2-
250V 10/16A
3.15-
9.639
ø6.35 x 5
ø12.7 x 5
ø17 x 2
-Rotary
--
-1445
Cross-fanPropeller
ResinSteel
3520
Capillary tube
602
1100
-MRA12074
-12007
Samsung Electronics
2-1
2-2 Dimensions
815182
298
2-2-1 Indoor Unit
(Front view)(Remote control)
Air
in
115
Air out
2-2-2 Outdoor Unit
AQ07ACVE
SH07CA1
(Rear view)
245
267
532
(Front view)
720
2245
Installation plate
11
20
496
(Rear view)
55
AQ09ACVE / AQ12ACVE
SH09CA1 / SH12CA1
2-2
295
280
(Front view)
532
555
762
(Rear view)
Samsung Electronics
2-3 Refrigerating Cycle Block Diagram
INDOOR UNIT
Heat
exchanger
(Evaporator)
OUTDOOR UNIT
Capillary tube
1
T
Liquid side
Cross fan
2
T
Gas side
2-way valve
3-way valve
Check valve
Capillary tube
Compressor
Heat
exchanger
(Condenser)
Propeller fan
4-way valve
Cooling
Heating
Gas leak check point
Samsung Electronics
2-3
MEMO
2-4
Samsung Electronics
3. Operating Instructions and Installation
3-1 Operating Instructions
3-1-1 Name & Function of Key in remote controller
NO
1
2
3
4
5
NAMED OF KEY
(UP)
(DOWN)
FUNCTION OF KEY
Power On/Off button to start and stop airconditioner or timer set up
Temp. up button. To increase the temperatute by the pressing
the temperature button
Temp. down button. To decrease the temperature by the pressing
the temperature button
Each time you press this button
Mode is changed in the following order
Press until the appearance. the air condition cools or heats
the room as quickly as possible. after 30minutes, the air,
the airconditioner is reset automatically to the previous mode
Press until the appearance. the sleep timer can be used when
you are cooling or heating your room to switch the air conditioner off
automatically after a perriod of six hours.
Each time you press this button,
FAN SPEED is changed in the following order.
: Auto Mode: Fan Only
: Cool Mode: Heat Mode
: Dry Mode
6
7
8
Samsung Electronics
Adjust air flow vertically.
The ON Timer enables you to switch onthe air conditioner automatically
after a given period of time that is from 30 minutes to 24 hours.
To cancel the On Time, press the (Set/Cancel) button.
The Off Timer enables you to switch off the air conditioner automatically
after a given period of time that is from 30 minutes to 24 hours.
To cancel the On Time, press the (Set/Cancel) button.
3-1
Operating Instructions and Installation
3-1-1 Name & Function of Key in remote controller
1. AUTO MODE : In this mode, operation
mode(COOL, HEAT, DRY) is selected automatically by the room temperature of initial
operation.
Room Temp
Tr≥ 21°C+∆T
21°C +∆T>Tr
∆T= -1°C, -2°C, 0°C+1°C+2°C
∆T is controlled by setting temperature
up/down key of remote controller
2. COOL MODE : The unit operates according
to the difference between the setting and
room temperature. (18°C~30°C)
3. HEAT MODE : The unit operates according
to the difference between the setting and
room temperature.(16°C~30°C)
*Prevention against cold wind : For about
3~5 minutes after initial operation, thermo
control or “de-ice”, the indoor fan will
either not operate or operate very slowly(510 rpm), then switch to the selected fan
speed. This period is to allow the indoor
unit's heat-exchanger to prewarm before
emitting warm air.
*High temperature release function : The
outdoor unit for and compressor ON/OFF
control for safety operation, when the overheat is heat exchanger of indoor unit.
*De-ice : Deicing operation is controlled by
indoor unit's heat exchanger temperature
and accumulating time of compressor's
operation.
De-ice end by sensing of the processing
time by de-ice Condition.
Cool Operation (Set Temp:AUTO SETTING)
Heat Operation (Set Temp : 22°C+∆T)
Operation Type
4. DRY MODE : Has 3 states, each determined
by room temperature.
The unit operates in DRY mode.
*Compressor ON/OFF Time is controlled
compulsorily(can not set up the fan speed,
always breeze).
*Protective function : Low temperature
release. (Prevention against freeze)
5. TURBO MODE : This mode is available in
AUTO, COOL, HEAT, DRY, FAN MODE.
When this button is pressed at first, the air
conditioner is operated “powerful” state for
30 minutes regardless of the set temperature, room temperature.
When this button is pressed again, or when
the operating time is 30 minutes, turbo
operation mode is canceled and returned to
the previous mode.
*But, if you press the TURBO button in DRY
or FAN mode that is changed with AUTO
mode automatically.
6. SLEEP MODE : Sleep mode is available
only in COOL or HEAT mode.
The operation will stop after 6 hours.
*In COOL mode : The setting temperature
is automatically raised by 1°C each 1hour
When the temperature has been raised by
total of 2°C, that temperature is maintained.
*In HEAT mode : The setting temperature
is automatically droped by 1°C each 1hour.
When the temperature has been droped by
total of 2°C, that temperature is maintained.
7. FAN SPEED : Manual (3 step), Auto (4 step)
Fan speed automatically varies depending
on both the difference between setting and
the room temperature.
3-2
Samsung Electronics
Operating Instructions and Installation
8. COMPULSORY OPERATION :
For operating the air conditioner without
the remote controller.
*AUTO : The operating is the same function that AUTO MODE in the remote controller.
9.SWING : BLADE-H is rotated vertically by
the stepping motor.
*Memory louver : When ON/OFF button is
pressed at stop state, the BLADE-H returns
to its original location which is operating
state before stop
*Swing Set : Press the button under the
remote control is displayed on LCD the ,
and the blades move up and down, about 43°.
If the one more time press the button, blatles location is stop.
10. Quick OFF TIMER: OFF timer (quick timer)
allows reservation or cancel the timer on
and timer off quickly
When OFF timer button is pressed at operating state, LCD displays the polling state
sequentially.
The LCD also displays the time remaining.
OFF TIMER : The air Conditioner is turned
OFF at a specified time using .
OFF TIMER
*ON TIMER : Only timer LED lights on.
*OFF TIMER : Both timer and operation
LED lights on.
*3 minutes delay timer.
12. SELF Diagnosis
LED DISPLAY
oper-
TIMER
ation
FAN
Turbo
Check Point
Interruption of electric power and Power on.
Abnormal condition of the room sensor.
Abnormal condition of the indoor unit's heat exchanger sensor.
Indoor unit fan motor lock.
LED
:
blinking
: LED off
13. BUZZER SOUND : Whenever the ON/OFF
button is pressed or whenever change
occurs to the condition which is set up or
select, the compulsory operation mode,
buzzer is sounded "beep"
11. 24-Hour ON/OFF Real Setting Timer. : The
air conditioner is turned ON at a specified
time using .
ON TIMER
Samsung Electronics
3-3
3-2 Installation
3-2-1 Selecting Area for Installation
Select an area for installation that is suitable
to the customer's needs.
3-2-1(a) Indoor Unit
1. Make sure that you install the indoor unit in
an area providing good ventilation. It must
not be blocked by an obstacle affecting the
airflow near the air inlet and the air outlet.
2. Make sure that you install the indoor unit in
an area allowing good air handling and
endurance of vibration of the indoor unit.
3. Make sure that you install the indoor unit in
an area where there is no source of heat or
vapor nearby.
4. Make sure that you install the indoor unit in
an area from which hot or cool air is spread
evenly in a room.
5. Make sure that you install the indoor unit in
an area away from TVs, audio units, cordless phones, fluorescent lighting fixtures
and other electrical appliances (at least 1
meter).
6. Make sure that you install the indoor unit in
an area which provides easy pipe connection with the outdoor unit, and easy
drainage for condensed water.
(Fix the unit firmly if it is mounted in a
high place.)
3. Make sure that you install the outdoor unit
in area providing good ventilation and
which is not dusty. It must not be blocked
by any obstacle affecting the airflow near
the air inlet and the air outlet.
4. Make sure that you install the outdoor unit
in area free from animals or plants.
5. Make sure that you install the outdoor unit
in area not blocking the traffic.
6. Make sure that you install the outdoor unit
in area easy to drain condensed water from
the indoor unit.
7. Make sure that you install the outdoor unit
in area which provides easy connection
within the maximum allowable length of a
coolant pipe(10 meters).
Note
1. Add 10 grams of refrigerant (R-22) for
every 1 meter if the pipe length exceeds
the standard pipe length of 5 meters.
2. Maintain a height between the indoor and
outdoor units of less than 3 meters.
8. Make sure that you install the outdoor unit
in an area which is large enough to accommodate the measurements
shown in figure on the next page.
7. Make sure that you install the indoor unit in
an area which is large enough to accomodate the measurements shown in figure on
the next page.
3-2-1(b) Outdoor Unit
1. Make sure that you install the outdoor unit
in area not exposed to the rain or direct sun
light.
(Install a separate sunblind if exposed to
direct sun light.)
2. Make sure that you install the outdoor unit
in area allowing good air moment, not
amplifying noise or vibration, especially to
avoid disturbing neighbours.
Caution :
It is harmful to the air conditioner if it is used in the following environments: greasy areas (including areas near machines),
salty areas such as coast areas, areas where sulfuric gas is present such as hot spring areas. Contact your dealer for advice.
3-4
3-2-1(c) Remote Control Unit
1.Make sure that you install the remote control unit in an area free from obstacles such
as curtains etc, which may block signals
from the remote control unit.
2. Make sure that you install the remote control unit in an area not exposed to
direct sunlight, and where there is no source
of heat.
3. Make sure that you install the remote control unit in an area away from TVs, audio
units, cordless phones, fluorescent lighting
fixtures and other electrical appliances (at
least 1 meter).
Samsung Electronics
Cut the piping holesloped slightly
3-2-2 Installation diagram of indoor unit and outdoor unit
Operating Instructions and Installation
A Indoor unit gas leak test check point
Indoor unit
Piping
2
3
1
Tape vinyl
B Drain hose installation
Cut the piping hole
sloped slightly
Piping may be laid to the rear, left,
right or down .
1. Determine the position of the pipe and drain hose hole
using the right figure and drill the hole with an inner
diameter of 65mm so that it slants slightly downwards.
Pipe hole
(ø65mm)
2. If you are fixing the indoor unit to a… Then follow Steps…
Wall 3.
Window frame 4 to 6.
3. Fix the installation plate to the wall in a manner appropriate to the weight of the indoor unit.
If you are mounting the plate on a concrete wall with
60
340280
anchor bolts, the anchor bolts must not project by more
than 20mm.
4. Determine the positions of the wooden uprights to be
attached to the window frame.
3-2-2(b) Purging the Unit
5. Attach the wooden uprights to the window frame in a
manner appropriate to the weight of the indoor unit.
410~730
6. Using tapped screws, attach the installation plate to the
wooden uprights, as illustrated in the last figure opposite.
On delivery, the indoor unit is loaded with an inert gas.
All this gas must therefore be purged before connecting the
assembly piping. To purge the inert gas, proceed as follows.
Unscrew the caps at the end of each pipe.
Result : All inert gas escapes from the indoor unit.
•To prevent dirt or foreign objects from getting into
the pipes during installation, do NOT remove the
caps completely until you are ready to connect the
piping.
3-6
Samsung Electronics
3-2-2(c) Connecting the Assembly Cable.
N 1 2 3 4
15E324
1
3245E
The outdoor unit is powered from the indoor unit via the assembly
cable. If the outdoor unit is more than five metres away from the
indoor unit, the cable must first be extended to a maximum of ten
metres.
1. Extend the assembly cable if necessary.
2. Open the front grille by pulling on the tabs on the lower right and
left sides of the indoor unit.
Indoor unit
Earth
terminal
Outdoor
unit
Earth
terminal
3. Remove the screw securing the connector cover.
4. Pass the assembly cable through the rear of the indoor unit and
connect the assembly cable to terminals 1(N) to 4.
• Each wire is labelled with the corresponding terminal number.
5. Firmly fix the ass’y cable with clamp wire holdet.
6. Pass the other end of the cable through the 65mm hole in the wall.
7. Replace the connector cover, carefully tightening the screw.
8. Close the front grille.
9. For further details on how to plug the other end of the assembly
cable into the outdoor unit, refer to page 3-8.
Operating Instructions and Installation
3-2-2(d) Installing and Connecting the Indoor Unit Drain Hose
Care must be taken when installing the drain hose for the indoor unit to ensure that any condensation water is correctly drained outside.l When passing the drain hose through the 65mm hole drilled
in the wall, check that none of the following situations occur.
To install the drain hose, proceed as follows.
1. If necessary, connect the 2-metre extension to the drain hose.
2. If you are using the extension, insulate the inside part of the extension drain hose with a shield.
3. Pass the drain hose under the refrigerant piping, taking care to keep the drain hose tight.
4. Pass the drain hose through the hole in the wall, making sure that it is sloping downwards, as
The hose must
NOT slope upw
ards.
The end of the drain
hose must NOT be
placed in water.
shown in the illustrations above.
Shield
Do NOT bend the
hose in different
directions.
Keep a clearance of at
least 5cm between the
end of the hose and the
ground.
Do NOT place the end
of the drain hose in a
hollow.
The hose will be fixed permanently into position once
the whole installation has been tested for gas leaks;
Drain hoseExtension drain hose
Samsung Electronics
3-7
Operating Instructions and Installation
3-2-2(e) Outdoor unit installation
Wiring connection
1. Remove the cover-E parts.
2. Firmly connect the cable connector in the terminal block.
3. Fasten the M4 ring terminal to the hole marked
4. Firmly fix the ass'y cable with clamp wire holder.
5. Assemble the cover-E parts.
6. To prevent the entry of water, form a trap of the ass'y cable as illustrated in the installation diagram of indoor and outdoor unit.
Ass’y cover valve (RO Hand cabi, RH)
N 1 2 3 4
Installing and Connecting the Outdoor Unit Drain Hose
When using the air conditioner in the heating, ice may accumulate.
Drain hole
3-8
Duting de-icing, the condensed water must be drained off safely.
Consequently, you must install a drain hose on the outdoor unit,
following the instructions below.
1. Insert the drain plug into the drain hole on the underside of the
outdoor unit.
2. Connect the drain hose to the drain plug.
3. Ensure that the drained water runs off correctly and safely.
Samsung Electronics
3-2-2(f) Flare Modification
• Tools used
Flare modification procedure
Operating Instructions and Installation
1) Cut the pipe using a pipe cutter.
90
3) Insert a flare nut into the pipe and
modifty flare.
Oblique RaughnessBurr
2) Remove burrs at the tip of the pipe cut.
Caution : Burrs not removed may result in
leakage of gas.
Pipe
Reamer
D
D
A
A
Outer diameterA(mm)
ø6.35mm1.3
ø9.52mm1.8
ø12.7mm2.0
* Unproper flaring
Samsung Electronics
InclinedSurface
damaged
CrackedUneven
thickness
3-9