ŷThank you for purchasing this Samsung air conditioner.
ŷBefore operating this unit, please read this manual carefully and retain it for future reference.
2
Contents
Safety precautions ......................................................................................................... 3
Outdoor unit type ......................................................................................................... 5
Installation combination ................................................................................................... 5
Deciding to where to install the outdoor unit ............................................................................... 6
Installation location ........................................................................................................ 8
Installation and base ground work for an outdoor unit .................................................................... 10
Refrigerant pipe installation .............................................................................................. 12
Wiring work .............................................................................................................. 31
Grounding work .......................................................................................................... 36
Basic segment display .................................................................................................... 37
Setting outdoor unit option switch and key function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Checking lists after nishing installation .................................................................................. 45
Inspection and check operation ........................................................................................... 46
Automatic refrigerant amount detection function (Checking th amount of refrigerant) .................................... 49
Trial operation ............................................................................................................ 51
3
ENGLISH
Safety precautions
WARNING
State of California Proposition 65 Warning (US only) This product contains chemicals known to the State of California to cause cancer and birth defects or other reproductive harm. Carefully follow the precautions listed below because they are essential to guarantee the safety of the equipment.
WARNING
t Always disconnect the air conditioner from the power supply before servicing it or
accessing its internal components.
t Verify that installation and testing operations are performed by qualied personnel. t Verify that the air conditioner is not installed in an easily accessible area.
General information
X Carefully read the content of this manual before installing the air conditioner and store the manual in a safe place in order
to be able to use it as reference after installation.
X For maximum safety, installers should always carefully read the following warnings.X Store the operation and installation manual in a safe location and remember to hand it over to the new owner if the air
conditioner is sold or transferred.
X This manual explains how to install an indoor unit with a split system with two SAMSUNG units. The use of other types
of units with dierent control systems may damage the units and invalidate the warranty. The manufacturer shall not be responsible for damages arising from the use of non compliant units.
X The manufacturer shall not be responsible for damage originating from unauthorized changes or the improper
connection of electric and requirements set forth in the “Operating limits” table, included in the manual. Making such changes or improper connections may damage the units and invalidate the warranty.
X The air conditioner should be used only for the applications for which it has been designed: the indoor unit is not suitable
to be installed in areas used for laundry.
X Do not use the units if damaged. If problems occur, switch the unit o and disconnect it from the power supply.X In order to prevent electric shocks, res or injuries, always stop the unit, disable the protection switch and contact
SAMSUNG’s technical support if the unit produces smoke, if the power cable is hot or damaged or if the unit is very noisy.
X Always remember to inspect the unit, electric connections, refrigerant tubes and protections regularly. These operations
should be performed by qualied personnel only.
X The unit contains moving parts, which should always be kept out of the reach of children.X Do not attempt to repair, move, alter or reinstall the unit. If performed by unauthorized personnel, these operations may
cause electric shocks or res.
X Do not place containers with liquids or other objects on the unit.X All the materials used for the manufacture and packaging of the air conditioner are recyclable.X The packing material and exhaust batteries of the remote controller(optional) must be disposed of in accordance with
current laws.
X The air conditioner contains a refrigerant that has to be disposed of as special waste. At the end of its life cycle, the air
conditioner must be disposed of in authorized centers or returned to the retailer so that it can be disposed of correctly and safely.
X This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental
capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety. Children should be supervised to ensure that they do not play with the appliance.
X When the product operates in heat mode during winter time, it operates protection mode when the outdoor
temperature drops below 0°C(32°F). Therefore, supply the power during winter time. If the power is not supplied, compressor protection mode will not operate and cause product malfunction.
4
Safety precautions
Installing the unit
IMPORTANT: When installing the unit, always remember to connect rst the refrigerant tubes, then the electrical lines. Always
disassemble the electric lines before the refrigerant tubes.
X Upon receipt, inspect the product to verify that it has not been damaged during transport. If the product appears
damaged, DO NOT INSTALL it and immediately report the damage to the carrier or retailer (if the installer or the authorized technician has collected the material from the retailer.)
X After completing the installation, always carry out a functional test and provide the instructions on how to operate the air
conditioner to the user.
X Do not use the air conditioner in environments with hazardous substances or close to equipment that release free ames
to avoid the occurrence of res, explosions or injuries.
X Our units should be installed in compliance with the spaces shown in the installation manual, to ensure accessibility from
both sides and allow repairs or maintenance operations to be carried out. The unit’s components should be accessible and easy to disassemble without endangering people and objects.
X For this reason, when provisions of the installation manual are not complied with, the cost required to access and repair
the units (in SAFETY CONDITIONS, as set out in prevailing regulations) with harnesses, ladders, scaolding or any other elevation system will NOT be considered part of the warranty and will be charged to the end customer.
Power supply line, fuse or circuit breaker
X Always make sure that the power supply is compliant with current safety standards. Always install the air conditioner in
compliance with current local safety standards.
X Always verify that a suitable grounding connection is available.X Verify that the voltage and frequency of the power supply comply with the specications and that the installed power is
sucient to ensure the operation of any other domestic appliance connected to the same electric lines.
X Always verify that the cut-o and protection switches are suitably dimensioned.X Verify that the air conditioner is connected to the power supply in accordance with the instructions provided in the
wiring diagram included in the manual.
X Always verify that electric connections (cable entry, section of leads, protections…) are compliant with the electric
specications and with the instructions provided in the wiring scheme. Always verify that all connections comply with the standards applicable to the installation of air conditioners.
X Devices disconnected from the power supply should be completely disconnected in the condition of overvoltage
category.
5
ENGLISH
Outdoor unit type
Shape
Model Cooling and Heating 1phase AM060XMDCH
Installation combination
X You must install the indoor unit that uses R410A only.X If sum capacity of the combined indoor units exceeds the capacity of an outdoor unit, the capacity of each indoor unit is
reduced below the rated capacity. Therefore, keeping the combination of indoor units within the capacity of an outdoor unit is recommended.
Outdoor unit
Outdoor unit capacity
[HP(Ton)]
The maximum number of
connectable indoor units
Total capacity of the
connected indoor units
[kW(MBH)]
AM060MXMDCH 7(5) 10 8.8~22.8(30~ 78)
6
Deciding to where to install the outdoor unit
Decide the installation location based on the following condition and obtain the user’s approval.
X Avoid a place that may disturb your neighbor. Noise may occur from the outdoor unit and the discharged air may run into
the neighborhood. (Be careful of the operation time in a residential area)
X Install the outdoor unit on a hard and even area that can support its weight.X Choose a at place where rainwater does not settle or leak.X Choose a place that will avoid strong winds.X Choose a place that is well ventilated and allows enough space for repairs and service.
(Discharge duct can be purchased privately.)
X Choose a place where the connection of refrigerant pipe between an indoor unit and outdoor unit is within allowed
distance.
X Make sure that the condensed water dripping from the drain hose runs out properly and safely.X Choose a place where ammable gas does not leak.X Choose a place where the unit could not come into contact with snow and rain.X When installing the outdoor unit near sea shore, make sure it is not directly exposed to sea breeze.
- When installing the outdoor unit near sea shore, consult the qualied installer since the places above require additional measures for corrosion resistance. (You should remove salt and dust of a heat exchanger at least once a year.)
When installing an outdoor unit near sea shore
X When installing an outdoor unit near sea shore, it should be placed behind a building or surrounded by wind protection
wall.
X Install the outdoor unit in a place where water can drain smoothly.
Outdoor unit
Sea breeze
Sea
Outdoor unit
Sea breeze
Sea
Protection wall
Outdoor unit
Sea breeze
Sea
Protection wall should be constructed with a solid material such as concrete to block the sea breeze and the height and
the width of the wall should be 1.5 times larger than the size of the outdoor unit. (Also, allow over 700mm (28 inch) space between the protection wall and the outdoor unit for ventilation of exhaust air.)
7
ENGLISH
t Install the indoor unit away from any interfering sources such as radio, computer, stereo equipment and also
select a place where the electrical wiring work and an indoor unit installation are possible.
- Especially keep the unit at least 3m (9.84ft) away from the electrical equipment in an area where weak electromagnetic waves are generated and install the protection tube to protect the main power cable and communication cable.
- Make sure that there is no equipment that generates electromagnetic waves. If so, malfunction of the control system may occur due to the eect of the electromagnetic wave. (For example: The remote control sensor of the indoor unit may not have good reception in an area with uorescent lamp style lighting.)
t Make sure the outdoor unit is installed in a safe place where it will not be obstructed by snowfall. The frame
should be installed in a place where the air inlet and heat exchanger of the unit are not buried in the snow.
t A ventilation system may be required when the outdoor unit is installed in a closed space or room, even though
R410a is not poisonous or ammable.
t Install railing around the outdoor unit to prevent it falling when the unit is installed on a high place such as the
roof of the building.
t Avoid installing the units in places near an exhaust pipe and ventilating opening exposed to corrosive gas,
oxides of sulfur, ammonia gas or sulfur gas herbicides. (These places need additional anticorrosive treatments. Please contact manufacture to avoid corroding copper pipes or soldered parts.)
t There shouldn’t be any inammable material such as wood and oil around the indoor unit. Otherwise, external
re may spread to the product.
t According to the condition of power supply, electric noise or unstable voltage can occur malfunction of electric
parts or control system. (At the ship or places using power supply from electric generator… etc)
CAUTION
Outdoor Unit
Indoor Unit
Remote Control
1m (3.28ft)
or more
1m (3.28ft)
or more
1.5m (4.92 ft)
or more
1.5m (4.92ft) or more
3m (9.84ft) or more
Breaker
Stereo
Breaker
1.5m (4.92ft) or more
X Make sure that the water dripping from the drain hose runs away correctly and safely.X You should repaint or protect the damaged part so that the paint of the cabinet does not peel o and become rusty
during installation. When the cabinet becomes rusty, the life of an outdoor will be reduced.
8
Installation location
X Make a space for ventilation and service as seen in the picture.X When multiple outdoor units are combined for installation, allow enough space for ventilation against a wall.
If the ventilation space is not allowed, product malfunction may occur.
X The side with logo is the front side of the outdoor unit.
Figure Description
Top view Side view
Back side : Air intake
Front side : Air outlet
Front side : Air outlet
Back side : Air intake
t , Air ow direction.
When installing 1 outdoor unit
Unit: mm (inch)
❋ When the air outlet is opposite the wall ❋ When the air outlet is toward the wall
300 (12) or more
1500 (60) or
more
❋ When 3 sides of the outdoor unit are blocked by the wall ❋ The upper part of the outdoor unit is blocked and the air
outlet is toward the wall
300 (12) or
more
150 (6) or more
600 (24) or more
1500 (60) or
more
2000 (80) or
more
The upper part of the outdoor unit is blocked and the air
outlet is opposite the wall
When the walls are blocking front and the rear of the
outdoor unit
500 (20) or
more
300 (12) or more
1500 (60) or
more
300 (12) or
more
9
ENGLISH
When installing more than 1 outdoor unit
Unit: mm (inch)
When 3 sides of the outdoor unit are blocked by the wall
300 (12) or
more
300 (12) or
more
600 (24) or
more
600 (24) or
more
600 (24) or
more
When the walls are blocking front and the rear of the outdoor units
300 (12) or
more
1500 (60) or
more
600 (24) or more 600 (24) or more
When front and rear side of the outdoor unit is toward the wall
1500 (60) or
more
600 (24) or
more
3000 (120) or
more
300 (12) or
more
3000 (120) or
more
t Should adopt bar type louver. Don’t use a type of rain resistance louver.
[Bar type louver]
[Rain resistance louver]
t Louver specications.
- Angle criteria : less than 20˚
- Opening ratio criteria : greater than 80%
WARNING
10
Installation location
Moving the Outdoor Unit
X Select the moving route in advance.X Be sure that moving route is safe from the weight of the outdoor unit.X Do not slant the product more than 30˚ when carrying it. (Do not lay the product down sideways.)X The surface of the heat exchanger is sharp. Be careful not to get injured while moving and installing.
When moving with a crane or wire rope
X When moving an outdoor unit to a higher place such as the rooftop.
- Fasten the wire rope as seen in the picture.
- Move the outdoor unit with the product packed to prevent possible product damage during the transportation.
Wire rope/straps
Wood palette
When moving an outdoor unit with hands
X Moving the outdoor unit by lifting up and carrying due to the short travel distance.
- Two people should carry the outdoor unit by holding transportation handle.
- Be careful not to damage the heat exchanger of the rear side of the outdoor unit during transportation.
- Be careful not to get hurt by the sharp surface of the heat exchanger.
Installation and base ground work for an outdoor unit
X Install the outdoor unit 150mm (6inch) higher than the base ground and install the drain hole to connect the pipe to the
drainage.
X When the front fan of an outdoor unit is installed in a place where the average snowfall is more than 150mm (6inch), the
discharge duct should be attached to the outdoor unit.
X The concrete foundation should be 1.5 times larger than bottom of the outdoor unit.X It is necessary to install wire mesh or steel bar when outdoor units are installed on a soft foundation.X When installing multiple outdoor units at the same place, install the
H beam on the base ground. (When installing a number of outdoor units, you can install it on the base ground.)
X Install the H beam [150mm (6inch) x 150mm (6inch) x t10 : basic
specication] or vibration absorption frame to jut out from the base ground.
X After installing the H beam, apply corrosion protection.X Install a square pad [t=20mm (1inch) or more] to prevent vibration
from the outdoor unit onto the base ground. Place the outdoor unit on the H beam and x it with the bolt, nut and washer. (Fix with M10 basic anchor bolt, nut and washer.)
Outdoor unit
Anchor bolt
Nut, Spring washer
H beam
Square pad
A+10~20mm (0.5~1inch) or more
A
20mm
(1inch)
75mm
(3inch)
or more
11
ENGLISH
Base ground work
< When installing on the ground >
Drain hole
150mm (6inch) or more
< When installing on the roof >
Install the outdoor unit horizontally on the ground
150mm (6inch) or more
X The outdoor unit should be supported within the range of measurement below for base ground work.
Unit: mm (inch)
Anchor bolt position
330 (12.99)
620 (24.40) 940 (37.00)
360 (14.17)
384 (15.11)
X When the outdoor unit needs to be supported, x it with wire as shown in the
picture.
- Slightly unwind the four screws on the cover top of the outdoor unit.
- Wind wires round the four screws and fasten the screws again.
- Fix the wires to the ground.
t If the outdoor unit is not xed securely, product may fall and it might cause loss of life or property damage. t Do not install the outdoor unit on a wood palette. t Fix the outdoor unit securely to the base ground with anchor bolts. t The manufacturer is not responsible for the damage occurred by not adhering to the standard of the installation. t To protect the outdoor unit from external condition such as rain, install it on the base ground and connect the
drain pipe to the drainage.
CAUTION
12
Refrigerant pipe installation
Refrigerant pipe work
X The length of refrigerant pipe should be as short as possible and the height dierence between an indoor unit and
outdoor unit should be minimized.
X The piping length between the outdoor unit and the indoor unit may not exceed the allowable piping length, height
dierence, and the allowable length after branching is done.
X The pressure of the R410A is high. Use only certied refrigerant pipe and follow the installation method.X After pipe installation, charge the refrigerant according to the length of the pipe and R410A refrigerant should be used.X Use clean refrigerant pipe and there shouldn’t be any harmful ion, oxide, dust, iron content or moisture inside pipe.X Use tools and accessories that t on R410A only.
t When installing, make sure there is no leakage. When collecting the refrigerant, stop the compressor rst before
removing the connection pipe. If the refrigerant pipe is not properly connected and the compressor works with the service valve open, the pipe inhales the air and it makes the pressure inside of the refrigerant cycle abnormally high. It may cause explosion and injury.
WARNING
Tool Work If compatible with conventional tool
Pipe cutter
Refrigerant pipe work
Pipe cutting
Compatible
Flaring tool Pipe aring
Refrigerant oil
Apply refrigerant oil on ared part
Exclusive ether oil, ester oil, alkali benzene oil or synthetic oil
Torque wrench Connect are nut with pipe
Compatible
Pст.)ipe bender Pipe bending
Nitrogen gas
Air tightening test
Inhibition of oxidization
Brazing tool Pipe brazing
Manifold gauge
Air tightening test ~ additional refrigerant charging
Vacuuming, charging and checking operation
Need exclusive one to prevent mixture of R22 refrigerant oil use and also the measurement is not available due to the high pressure.
Refrigerant charging
hose
Need exclusive one due to the refrigerant leakage or inow of impurities.
Vacuum pump Vacuum drying
Compatible (Use products which contain the check valve to prevent the oil from owing backward into the outdoor unit.)
Use the one that can be vacuumed up to 100.7kpa(5Torr.-755mmHg).
Scale for refrigerant
charging
Compatible
Gas leak detector Gas leak test
Need exclusive one ( The one for R134A can be used)
Flare nut
You must use the are nut equipped with product. Refrigerant leakage may occur when the conventional are nut for R22 is used.
13
ENGLISH
Selecting refrigerant pipe
Temper grade and minimum thickness of the refrigerant pipe
Outer diameter [mm (inch)] Minimum thickness [mm (inch)] Temper grade
Ø6.35 (1/4) 0.7 (0.028)
Annealed
Ø9.52 (3/8) 0.7 (0.028)
Ø12.70 (1/2) 0.8 (0.031)
Ø15.88 (5/8) 1.0 (0.039)
Ø19.05 (3/4) 0.9 (0.035)
Drawn
Ø22.22 (7/8) 0.9 (0.035)
X Make sure to use C1220T-1/2H (Semi-hard) or C1220T-H pipe for more than Ø19.05mm (3/4inch). X In case of using C1220T-O (Soft) pipe for Ø19.05mm (3/4inch), pipe may be broken, which can result in an injury.
Pipe installation between an outdoor unit and the rst Y-joint
Outdoor unit capacity
[HP(Ton)]
Liquid pipe [mm (inch)] Gas pipe [mm (inch)]
One step upgraded pipe
[mm (inch)]
7(5) Ø9.52 (3/8) Ø19.05 (3/4) Ø22.22 (7/8)
X Install the refrigerant pipe according to main pipe size of each outdoor unit capacity.X When the pipe length between an outdoor unit and the farthest indoor unit including elbow exceeds 90m (295ft), the
gas pipe size should be upgraded one step among the main pipes from the outdoor unit to the rst Y-joint. (The liquid pipe size will be maintained.)
X If the capacity of the outdoor unit can decline due to the pipe length, upgrade the pipe size one step (gas pipe).
Main pipe size up
First Y-joint
Pipe installation between Y-joints
Indoor unit total capacity
[kW (Btu/h)]
1JQFEJBNFUFS0t%tNN
Liquid pipe [mm (inch)] Gas pipe [mm (inch)]
X ≤ 15.0 (51000)
Ø9.52 (3/8)
Ø15.88 (5/8)
15.0 (51000) < X ≤ 23.2 (79000) Ø19.05 (3/4)
14
Refrigerant pipe installation
Selecting Y-joint
X Select the rst Y-joint according to main pipe size of each outdoor unit capacity.X Select the other Y-joints according to the total indoor unit capacity under the selected Y-joint.
Selecting the rst Y-joint Other Y-joints
Outdoor unit capacity
[HP(Ton)]
Y-joint model
Total indoor unit capacity under the
selected Y-joint [kW (Btu/h)]
Y-joint model
7(5) MXJ-YA2512
X ≤ 15.0 (51000) MXJ-YA1509
15.0 (51000) < X ≤ 40.6 (138000) MXJ-YA2512
Keeping refrigerant pipe
To prevent foreign materials or water from entering the pipe, it is important to keep the refrigerant pipe clean and dry and to seal it during installation.
Apply correct sealing method depending on the environment.
Exposure place Exposure time Sealing type
Outside exposure
Longer than one month Pipe pinch
Shorter than one month Taping
Inside exposure - Taping
Refrigerant pipe brazing and safety information
Important information for refrigerant pipe work
X Make sure that there is no moisture inside the pipe.X Make sure that there are no foreign materials and impurities in the pipe.X Make sure that there is no leak.X Make sure to follow the instruction when brazing and keeping the pipe.
Nitrogen ushing brazing
X Use Nitrogen gas when brazing the pipes as shown in the picture.X If you do not perform nitrogen ushing when brazing the pipes, oxide may form inside the pipe. It can cause the damage
of the important parts such as compressor, valves.
X Adjust the ow rate of the Nitrogen ushing with a pressure regulator to maintain 0.05m3/h or less.
Brazing part
Nitrogen gas
Ø6.35(1/4") copper pipe
Shut-o valve
Taping
Flow meter
High pressure hose
Pressure regulator
15
ENGLISH
Direction of the pipe when brazing
X Brazing the pipe should be done with the pipe headed downward or horizontally.X Avoid brazing with the pipe headed upward.
t The test liquid used to detect leakage after pipe brazing should be the designated one.
The use of the test liquid containing sulfur element may cause pipe corrosion.
CAUTION
Cutting or Flaring the pipes
X Make sure that you prepared the required tools.
- Pipe cutter, reamer, aring tool and pipe holder, etc.
X If you want to shorten the pipe, cut it using a pipe cutter ensuring that the cut edge remains at 90° with the side of the pipe.
- There are some examples of correctly and incorrectly cut edges below.
Oblique Rough
Burr
Pipe
Pipe cutter
X To prevent a gas leak, remove all burrs at the cut edge of the pipe using a reamer.X Carry out aring work using aring tool as shown below.
A
Flaring bar
Pipe
Yor k
Flaring bar
Pipe
Flare nut
Clutch type Wing nut type
[Flaring tool]
Pipe diameter [mm (inch)]
A [mm (inch)]
Flare tool for R-410A
clutch type
Conventional are tool
Clutch type Wing nut type
Ø6.35 (1/4) 0~0.5 (0~0.776) 1.0~1.5 (0.039~0.059) 1.5~2.0 (0.059~0.079)
Ø9.52 (3/8) 0~0.5 (0~0.776) 1.0~1.5 (0.039~0.059) 1.5~2.0 (0.059~0.079)
Ø12.70 (1/2) 0~0.5 (0~0.776) 1.0~1.5 (0.039~0.059) 1.5~2.0 (0.059~0.079)
Ø15.88 (5/8) 0~0.5 (0~0.776) 1.0~1.5 (0.039~0.059) 1.5~2.0 (0.059~0.079)
X Check that you ared the pipe correctly.
- There are some examples of incorrectly ared pipes below.
Uneven ThicknessCrackedDamaged SurfaceInclinedCorrect
t If foreign matters or BURRs are not removed after cutting pipe, refrigerant gas may leak. t If foreign matters enter inside the pipe, the important interior parts of the unit may get damaged or product
eciency will be reduced. So, the direction of pipe should be downward during pipe cutting or aring.
CAUTION
16
Refrigerant pipe installation
Tightening are connection area
X Check that the aring is properly made.X Align the center of the piping and suciently tighten the are nut with ngers. Finally, tighten the are nut with torque
wrench until the wrench clicks. When tightening the are nut with torque wrench, ensure the direction for tightening follows the arrow on the wrench.
X Make sure to use ester oil to coat the are connection section.
Pipe
Flare nutFlare connection section
Outer diameter
[D, mm (inch)]
Connection torque
Flare dimension
[L, mm (inch)]
Flare shape [mm (inch)]
LHGtDN /tN
Ø6.35 (1/4) 140~180 14~18 8.70~9.10(0.343~0.358)
D
L
R 0.4~0.8 (0.016~0.032)
90° ±2°
45° ±2°
Ø9.52 (3/8) 350~430 34~42 12.80~13.20(0.504~0.520)
Ø12.70 (1/2) 500~620 49~61 16.20~16.60(0.638~0.654)
Ø15.88 (5/8) 690~830 68~82 19.30~19.70(0.760~0.776)
t Blowing Nitrogen gas should be done when brazing the pipe. t Make sure to use the provided are nut. t Make sure that there are no cracks on the bent pipe. t Do not fasten the are nut with excessive strength. t Use ester oil to coat the are connection area to prevent refrigerant leak. R410A is a high pressure refrigerant.
Therefore, there is a risk of refrigerant leakage if the are connection is not coated with ester oil.
CAUTION