Capacity table
PAC
AC100KNPDEH/EU + AC100KXADEH/EU
Cooling TC(Total Capacity), SHC(Sensible Heat Capacity), PI(Power Input)
Outdoor Air
Temp.
(DB)
Indoor temperature (ºC)
20 (DB) 22 (DB) 25 (DB) 27 (DB) 28 (DB) 30 (DB) 32 (DB)
14 (WB) 16 (WB) 18 (WB) 19 (WB) 20 (WB) 22 (WB) 24 (WB)
TC(kW) SHC(kW) PI(kW) TC(kW) SHC(kW) PI(kW) TC(kW) SHC(kW) PI(kW) TC(kW) SHC(kW) PI(kW) TC(kW) SHC(kW) PI(kW) TC(kW) SHC(kW) PI(kW) TC(kW) SHC(kW) PI(kW)
-15.0 9.80 7.60 2.65 10.30 7.90 2.70 10.70 8.10 2.76 11.00 8.40 2.81 11.20 8.30 2.84 11.80 8.20 2.87 12.40 8.00 2.93
21.0 9.30 7.30 2.79 9.80 7.50 2.84 10.20 7.70 2.90 10.50 8.00 2.96 10.70 7.90 2.99 11.20 7.80 3.02 11.80 7.70 3.08
35.0 8.80 6.90 3.48 9.30 7.20 3.55 9.70 7.40 3.63 10.00 7.60 3.70 10.20 7.50 3.74 10.70 7.40 3.77 11.20 7.30 3.85
46.0 7.40 6.30 3.65 7.80 6.50 3.73 8.10 6.70 3.80 8.40 6.90 3.88 8.60 6.80 3.92 9.00 6.80 3.96 9.40 6.60 4.04
50.0 6.60 5.90 3.75 7.00 6.10 3.82 7.30 6.30 3.90 7.50 6.50 3.98 7.70 6.40 4.02 8.00 6.30 4.06 8.40 6.20 4.14
Heating TC : Total Capacity, PI: Power Input
Outdoor Air
Temp.
(DB)
Indoor temperature (ºC)
16 (DB) 18 (DB) 20 (DB) 21 (DB) 22 (DB) 24 (DB)
TC(kW) PI(kW) TC(kW) PI(kW) TC(kW) PI(kW) TC(kW) PI(kW) TC(kW) PI(kW) TC(kW) PI(kW)
-20.0 8.60 4.51 8.50 4.46 8.40 4.42 8.30 4.38 8.20 4.33 8.20 4.29
-15.0 9.80 4.86 9.70 4.81 9.60 4.76 9.50 4.71 9.40 4.67 9.30 4.62
-5.0 11.20 4.84 11.10 4.79 11.00 4.75 10.90 4.70 10.80 4.65 10.70 4.61
0.0 11.70 4.15 11.50 4.11 11.40 4.07 11.30 4.03 11.20 3.99 11.10 3.95
7.0 11.40 3.46 11.30 3.42 11.20 3.39 11.10 3.36 11.00 3.32 10.90 3.29
24.0 13.90 3.43 13.70 3.39 13.60 3.36 13.50 3.33 13.30 3.29 13.20 3.26
AC140KNPDEH/EU + AC140KXADGH/EU
Cooling TC(Total Capacity), SHC(Sensible Heat Capacity), PI(Power Input)
Outdoor Air
Temp.
(DB)
Indoor temperature (ºC)
20 (DB) 22 (DB) 25 (DB) 27 (DB) 28 (DB) 30 (DB) 32 (DB)
14 (WB) 16 (WB) 18 (WB) 19 (WB) 20 (WB) 22 (WB) 24 (WB)
TC(kW) SHC(kW) PI(kW) TC(kW) SHC(kW) PI(kW) TC(kW) SHC(kW) PI(kW) TC(kW) SHC(kW) PI(kW) TC(kW) SHC(kW) PI(kW) TC(kW) SHC(kW) PI(kW) TC(kW) SHC(kW) PI(kW)
-15.0 13.10 10.00 3.09 13.80 10.30 3.15 14.30 10.60 3.22 14.80 10.90 3.28 15.10 10.80 3.32 15.80 10.70 3.35 16.60 10.50 3.42
21.0 12.40 9.50 3.25 13.10 9.80 3.32 13.60 10.10 3.39 14.10 10.40 3.46 14.40 10.30 3.49 15.10 10.20 3.53 15.80 10.00 3.60
35.0 11.90 9.10 4.07 12.50 9.30 4.15 13.00 9.60 4.23 13.40 9.90 4.32 13.70 9.80 4.36 14.40 9.70 4.41 15.10 9.50 4.49
46.0 9.70 8.30 4.60 10.20 8.50 4.70 10.70 8.80 4.79 11.00 9.10 4.89 11.20 9.00 4.94 11.80 8.90 4.99 12.40 8.70 5.09
50.0 8.60 7.70 4.89 9.00 7.90 4.99 9.40 8.20 5.10 9.70 8.40 5.20 9.90 8.40 5.25 10.40 8.30 5.30 10.90 8.10 5.41
Heating TC : Total Capacity PI: Power Input
Outdoor Air
Temp.
(DB)
Indoor temperature (ºC)
16 (DB) 18 (DB) 20 (DB) 21 (DB) 22 (DB) 24 (DB)
TC(kW) PI(kW) TC(kW) PI(kW) TC(kW) PI(kW) TC(kW) PI(kW) TC(kW) PI(kW) TC(kW) PI(kW)
-20.0 9.60 5.30 9.50 5.25 9.40 5.20 9.30 5.15 9.20 5.10 9.10 5.05
-15.0 13.80 6.89 13.60 6.82 13.50 6.75 13.40 6.68 13.20 6.62 13.10 6.55
-5.0 15.50 6.43 15.30 6.36 15.20 6.30 15.00 6.24 14.90 6.17 14.70 6.11
0.0 16.10 5.51 16.00 5.45 15.80 5.40 15.70 5.35 15.50 5.29 15.30 5.24
7.0 15.80 4.59 15.70 4.55 15.50 4.50 15.30 4.46 15.20 4.41 15.00 4.37
24.0 20.50 5.15 20.30 5.10 20.10 5.05 19.90 5.00 19.70 4.95 19.50 4.90
3
* Capacity table may be subject to change without prior notice.
1) Capacities are based on following conditions;
. Cooling mode indoor air temperature (°C, DB/WB) : 20/14, 22/16, 25/18, 27/19, 28/20, 30/22, 32/24
. Heating mode outdoor air : 85%RH. However, the condition rated capacity is 7°C DB / 6°C WB.
. Refrigerant piping length : 5m
. Level difference : 0m.