Samsung AC0 KNZDCH Technical bulletin

TECHNICAL BULLETIN 2019-0008
Date: 06/03/2019 Subject: Multi-Position Air Handler Models: AC0**KNZDCH/AA, AM0**TNZDCH/AA, AM0**JNZDCH/AA
www.SamsungHVAC.com TB2019-0008 (REV 7/8/2020)
1
Multi-Position Air Handler Blower Troubleshooting
© 2020 Samsung HVAC
The motor rocks back and forth on start up.
This is normal operation. Genteq X13 constant torque blower motors have a rotor position circuit-built in. At start up, the motor rocks forward then backward to determine which direction it needs to turn for proper airflow. Do not remove the motor from the blower wheel and housing to test. Without a blower wheel attached, the motor will not be able to tell which direction to run. It will simply rock back and forth.
Airflow is insufficient
Make sure there are no restrictions to airflow such as dirty or restrictive air filters, closed dampers or registers, dirty indoor coil or blower wheel. Ensure the airflow settings are set properly by measuring total external static pressure and adjusting fan motor speed taps as needed. Refer to the service manual for blower performance charts that will show airflow for each speed tap at given static pressures.
Motor does not run
Genteq X13 constant torque blower motors should be supplied line voltage between L & N on the motor connector at all times even when there is no call for operation. Check for line voltage directly at the L & N connection of the motor.
Samsung HVAC maintains a policy of ongoing development, specifications are subject to change without notice.
230 VAC
TECHNICAL BULLETIN 2019-0008
www.SamsungHVAC.com TB2019-0008 (REV 7/8/2020)
2
Multi-Position Air Handler Blower Troubleshooting
If voltage is not present, check the electrical circuit feeding power. If voltage is present, turn the system on, initiate a demand from the wired controller and check for 24 VAC between the proper low voltage terminals of the motor. This should be done at the terminals at the motor directly. Voltage should be checked between the "C" terminal of the motor, and desired speed tap 1-5 depending on where the motor lead is connected.
Only one low voltage call should exist at a time. If more than one speed tap is engergized at a time the motor will not operate.
If both high and low voltage measurements are correct and the motor does not run the motor is defective and needs to be replaced.
24 VAC
Loading...