Samson 3222-5757, 3222-5725, 3222-5724 User Manual

Page 1
Electric Control Valves/ Controller with Electric Actuator
Type 3222/5724, Type 3222/5725 and Type 3222/5757
Type 3222/5725 Globe Valve mounted on Controller with Electric Actuator
Type 3222/5757 Globe Valve mounted on Controller with Electric Actuator
Mounting and Operating Instructions
EB 5766 EN
Edition July 2008
Page 2
Contents
Contents Page
1 Design and principle of operation . . . . . . . . . . . . . . . . . . . 4
1.1 Versions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.2 Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2.1 Mounting position . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2.2 Strainer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2.3 Additional installation instructions . . . . . . . . . . . . . . . . . . . . 9
3 Attaching the actuator to the valve . . . . . . . . . . . . . . . . . . 10
3.1 Type 5757/-7 Controller with Electric Actuator . . . . . . . . . . . . . 10
3.2 Type 5724/5725 Controller with Electric Actuator . . . . . . . . . . . 10
4 Electrical connections . . . . . . . . . . . . . . . . . . . . . . . . . 11
4.1 Type 5757-7 Controller with Electric Actuator. . . . . . . . . . . . . . 11
4.2 Type 5757 Controller with Electric Actuator. . . . . . . . . . . . . . . 11
4.3 Type 5724/5725 Controller with Electric Actuator . . . . . . . . . . . 12
5 Manual override . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
5.1 Type 5757/-7 Controller with Electric Actuator . . . . . . . . . . . . . 13
5.2 Type 5724/5725 Controller with Electric Actuator . . . . . . . . . . . 13
6 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
7 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
8 Dimensions in mm and weights . . . . . . . . . . . . . . . . . . . . 16
9 Appendix. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
9.1 Wiring for Type 5757-7 . . . . . . . . . . . . . . . . . . . . . . . . 18
9.2 Wiring for Type 5757 . . . . . . . . . . . . . . . . . . . . . . . . . 20
9.3 Wiring for Type 5724/5725 . . . . . . . . . . . . . . . . . . . . . 22
2 EB 5766 EN
Typetest
The Type 5725 Controller with Electric Actuators with safety function used in conjunction with Type 3222 Valves are typetested according to DIN 32730 by the German technical inspectorate TÜV.
Register number available on request.
Page 3
General safety instructions
General safety instructions
The control valves may only be mounted, started up or serviced by fully
4
trained and qualified personnel, observing the accepted industry codes and practices. Make sure employees or third persons are not exposed to any danger. All safety instructions and warnings in these mounting and operating instructions, particularly those concerning assembly, start-up and maintenance, must be observed.
The control valves fulfill the requirements of the European Pressure Equip
4
ment Directive 97/23/EC. Valves with a CE marking have a declaration of conformity which includes information about the applied conformity assess ment procedure. The declaration of conformity is available on request.
For appropriate operation, make sure that the control valve is only used in
4
applications where the operating pressure and temperature do not exceed the operating values which are based on the valve sizing data submitted in the order. The manufacturer does not assume any responsibility for damage caused by external forces or any other external influence! Any hazards which could be caused in the control valve by the process medium, the operating pressure, the signal pressure or by moving parts are to be prevented by means of the appropriate measures.
Proper shipping and appropriate storage of the control valve are assumed.
4
-
-
Caution!
For installation and maintenance, make sure the relevant section of the
4
pipeline is depressurized and, depending on the process medium, drained as well. If necessary, allow the control valve to cool down or warm up to reach ambient temperature prior to starting any work on the valve.
The electric actuators have been designed for use in electrical power
4
installations. For wiring and maintenance, you are required to observe the relevant safety regulations.
Only use power interruption devices which are protected against
4
unintentional reconnection of the power supply. Take special care when making adjustments on live parts. Do not remove
4
any covers!
EB 5766 EN 3
Page 4
Design and principle of operation
1 Design and principle of
operation
The control valves consist of a single-seated Type 3222 Globe Valve and either a Type 5757, Type 5757-7 or Type 5724 Controller with Electric Actuator or a Type 5725 Controller with Electric Actuator with safety function.
The process medium flows through the globe valve in the direction indicated by the arrow on the body. The position of the valve plug determines the flow rate over the cross-sec tional area of flow released between the plug (3) and valve seat (2). The plug stem (4) with plug is connected with the stem of the actuator (10) by a force-locking connec­tion. The valve is opened by the valve spring (5) following the retracting movement of the actuator stem. A special version is required for water above 150 °C and for steam (Fig. 1). The plug is moved by a change in the control signal acting on the actuator.
The electric actuator with safety function (Type 5725) has a spring mechanism and an electromagnet that can be connected to a safety control circuit. When the control cir cuit is interrupted or the power supply fails, the magnet disengages the gear from the self-locking motor and releases the spring mechanism. The valve is closed in the event of a safety situation (fail-safe action “actuator stem extends”).
The electric actuators contain a digital con troller integrated into the actuator. The con trolled variable is recorded over the directly connected Pt 1000 sensor (see Table 2).
The output signal of the digital controller acts as a three-point stepping signal on the
-
-
-
synchronous motor of the actuator and is transferred over the connected gear as a positioning force onto the actuator stem.
The Type 5757, Type 5724 and Type 5725 are particularly suitable for DHW heating in instantaneous heating systems and for fixed set point control circuits in mechanical engi neering applications.
Type 5757-7 is suitable for heating applica tions.
1.1 Versions
PN DN EB
Electric control valve/Controller with electric actuator
Type 3222/5757 Type 3222/5757-7 Type 3222/5724 … with safety function Type 3222/5725
1)
Refer to the listed Mounting and Operating Instructions (EB) for details on the controllers with electric actuators
2)
Controller with electric actuator for domestic hot water heating in instantaneous heating systems and for fixed set point control circuits in mechanical engineering applications
3)
Controller with electric actuator for heating applications
-
2)
25 15 to 25 5757
3)
25 15 to 25 5757-7
2)
25 15 to 50 5724
2)
25 15 to 50 5724
-
-
1)
4 EB 5766 EN
Page 5
1 Valve body 2 Seat 3 Plug 4 Plug stem 5 Valve spring 6 Guide nipple 7 Balancing bellows 8 Balancing piston
10 Controller with electric
actuator
Design and principle of operation
Type 3222/5757
Fig. 1 · Type 3222/5757 and Type 3222/5724 Electric Control Valves/Controller with Electric Actuator
Special version for temperatures up to 200 °C and
Type 3222/5724
with plug balanced by a bellows
EB 5766 EN 5
Page 6
Design and principle of operation
1.2 Technical data
1. Single-seated Type 3222 Globe Valve
Nominal size DN 15 20 25 32 40 50
Version with threaded ends
Thread size G ½¾1 –––
Version with female thread – Nominal pressure PN 25 Seat/plug sealing Metal sealing for K Rated travel mm 6 12 Rangeability 50 : 1 Leakage class acc. to DIN EN 1349 Class I (< 0.05 % of K
Version for water, oil and other liquids
Max. permissible temperature 150 °C Max. permissible differential pressureΔp in bar
Types 5724 and 5725 20 12
Type 5757 20
Version for water and steam
Max. permissible temperature 200 °C Max. permissible differential pressureΔp in bar
Types 5724 and 5725 20 · 10 for 3.6≤K
Type 5757 20
Materials
Valve body Red brass CC491K · EN-JS1049 (flanged body) Seat Stainless steel 1.4104 Plug 1.4104/CW509L with soft sealing · 1.4104 for 0.1≤K Valve spring Stainless steel 1.4310 K Packing EPDM/FPM (FKM) · Oil-resistant version: FPM Welding ends St 37 Threaded ends Red brass CC491K Screwed-on flanges St 37.2
with flanges
as flanged body
••••••
2.5 · Soft sealing for K
VS
coefficient)
VS
1, 2)
88
3)
4)
· 5
VS
5–
3.6
VS
2.5
VS
6 EB 5766 EN
Page 7
Design and principle of operation
Nominal size DN 15 20 25 32 40 50 Thread size G ½¾1–––
coefficients
K
VS
Version with female thread 3.6 5.7 7.2 – Version with male thread 4 6.3 8 16 20 25
Reduced K
coefficients
VS
0.1· 0.16 · 0.25 · 0.4
0.63 · 1.0 · 1.6 · 2.5
Rated travel mm 6 12
1)
Use an intermediate insulating piece for temperatures above 130 °C to protect the actuator
2)
DN 15 to 25 with Type 5757 Actuator: Use an intermediate insulating piece for temperatures above 110 °C to protect the actuator
3)
Differential pressure for KVS= 1 and 1.6
4)
Differential pressure for KVS= 2.5 and 4
5)
Version with male thread
6)
Version with female thread
1.0 · 1.6 · 2.5
5)
6)
· 3.6
4
–––
EB 5766 EN 7
Page 8
Design and principle of operation
2. Controllers with electric actuators
Type
Nominal size DN 15 to 25 15 to 25 15 to 25 32 to 50 15 to 25 32 to 50
Scope of application Heating
Safety function Without Without With Rated travel mm 6 6 6 12 12 6 6 12 12 Transit time for rated travel s 20 35 18 70 35 35 18 70 35 Transit time upon fail-safe
action
s 4466
Fail-safe action Stem extends Nominal thrust kN 0.3 0.7 0.5 Manual override Yes Yes Possible
Power supply 230 V (±10 %), 50 Hz Power consumption approx. VA 3 3 37375959 Permissible temperatures
Ambient °C 0 to 50 0 to 50 0 to 50 Storage °C –20 to 70 –20 to 70 –20 to 70 At connecting rod °C 0 to 110 0 to130 0 to 130
Degree of protection IP 42 IP 54 (upright position, acc. to DIN IEC 529)
Inputs and outputs of the digital controller
Temperature sensor Pt 1000 3 x 1 x 1 x 1 x
Setting range °C 1 to 150 0 to 150 1 to 150 1 to 150
Potentiometer input
1100/2000 Water flowmeter input 530 pulses/l 530 pulses/l 530 pulses/l Current input 4 (0) to20 mA 4 (0) to 20 mA 4 (0) to 20 mA
Binary input BE1
Binary input BE2
2)
2)
Op. mode switchover
230 V/50 Hz
Binary output BA
Cir. pump/Ex ternal demand
1)
Manual override using a 4 mm hex screwdriver (after removing the housing cover); always returns to fail-safe position after safety release.
2)
Recommendation for Type 5724, Type 5725 and Type 5757: With gold contacts
5757 5724 5725
5757-7 5757 -10 -13 -20 -23 -10 -13 -20 -23
DHW heating in instantaneous heating systems,
fixed set point control circuits in mechanical engineering
1)
1000 to
Ω
––
Switching between internal set points/
Deactivation of function to maintain temperature constant
Flow switch
-
––
8 EB 5766 EN
Page 9
2 Installation
Caution!
Versions designed to handle temperatures up to 200 °C must be fitted with the dark gray graphite supplied with the valve. Do not use the UDP seals available as accesso ries as they are only suitable for tempera tures up to 150 °C.
-
Installation
Install a strainer (SAMSON Type 2 NI)
4
upstream of the control valve to prevent any sealing parts, weld spatter or other foreign matter carried along by the pro cess medium from impairing the proper functioning of the valve, in particular, the
-
tight shut-off. The valve must be installed free of stress.
4
If necessary, support the piping near the connections.
-
2.1 Mounting position
Choose the place of installation where
4
the ambient temperature does not ex ceed or fall below the permissible limits specified for the actuator and that allows you to freely access the control valve even after the entire plant has been com­pleted. Flush the pipeline thoroughly before in-
4
stallation. Do not install the valve with the actuator
4
suspended downwards. Install versions for water and steam up to 200 °C with the actuator installed up right in a horizontal pipeline. If you wish to insulate the control valve,
4
install an intermediate insulating piece between valve and actuator. Make sure the insulation ends 25 mm above the valve body. Do not insulate the actuator and coupling nut as well.
2.2 Strainer
Install the strainer with the filter element
4
-
facing downwards upstream of the valve inlet. Choose the place of installation to allow
4
enough space to remove the filter. Install the strainer with the direction of
4
flow as indicated by the arrow on the body.
2.3 Additional installation instructions
-
We recommend to install a hand-operated shut-off valve both upstream of the strainer and downstream of the control valve to be able to shut down the plant for cleaning and maintenance, and when the plant is not used for longer periods of time.
EB 5766 EN 9
Page 10
Attaching the actuator to the valve
3 Attaching the actuator to the
valve
If the actuator has not already been mounted on the valve by the manufacturer or when the original actuator on a valve is to be replaced with a controller with electric actuator, proceed as follows.
Note!
Fasten the actuator and valve together either at the valve connection or at the intermedi ate insulating piece, depending on the valve version, with a tightening torque of 20 Nm.
-
3.1 Type 5757/-7 Controller with Electric Actuator
1. Turn the handwheel (see section 5.1)
counterclockwise when the actuator is disconnected from the power supply to retract the actuator stem as far as it will go.
2. Place the actuator on the connection
piece and secure with the coupling nut.
3.2 Type 5724/5725 Controller with Electric Actuator
Type 5724
1. Turn the handwheel (see section 5.2)
counterclockwise to retract the actuator stem as far as it will go.
2. Place the actuator on the connection
piece and secure with the coupling nut.
Type 5725 with fail-safe action “Actuator stem extends”
1. Unfasten the front cover and place a
4 mm hex screwdriver on the actuator stem (see section 5.2).
2. Turn the screwdriver counterclockwise
only and only until the travel final value is reached at the maximum, which acti­vates the bottom torque switch.
Caution!
Turning the actuator too far will destroy it.
10 EB 5766 EN
3. Hold the screwdriver in place. Secure the
actuator and connection piece with the coupling nut.
4. Remove screwdriver and carefully
refasten the front cover.
Page 11
Electrical connections
4 Electrical connections
Upon installing the electrical cables, you are required to observe the regula tions concerning electrical power in stallations according to DIN VDE 0100 as well as the regulations of your local power supplier. Use a suitable power supply to ensure that no dangerous voltages from the system or parts of the system reach the device in standard operation or in case of a fault.
Warning!
Only connect the device to the main power network when the power is switched off. Make sure the power cannot be switched on unintentionally!
Perform the electrical wiring as required
4
depending on the application (refer to section 4.1 to 4.3).
As soon as the actuator is connected to the power supply, the initialization procedure starts: The actuator stem extends and the red and yellow LEDs located under the cover on top of the actuator light up. As soon as the actu ator stem has reached the final position, the red LED is turned off. The yellow LED re mains illuminated and indicates that the controller with electric actuator is ready for operation.
4.1 Type 5757-7 Controller with Electric Actuator
Heating application: The controller with
-
electric actuator requires a Pt 1000 temper
-
ature sensor to be connected to measure the flow temperature. Depending on the control task, an outdoor sensor or a room sensor or a room panel can be connected. Combining one of these sensors with a return flow sen sor is usually possible. Additionally, the con troller with electric actuator has a potenti ometer input 1000 to 1100/2000Ω. The non-floating pump output can alternatively be used as an binary output for an external request for heat demand.
The default setting (WE) is configured for an application with a flow sensor, outdoor sen­sor and return flow sensor as well as with an active binary input to switchover the op­erating modes (see Fig. 2).
-
-
-
-
4.2 Type 5757 Controller with Electric Actuator
Domestic hot water heating in instanta neous heating system: The controller with
electric actuator requires a Pt 1000 temper ature sensor to be connected for it to func
-
tion. Two set points W1 and W2 can be used for control. A binary input BE1 is used
-
to switch between them. In addition, a water flowmeter or a flow switch can be connected to quickly recog nize when hot water is being tapped.
The 0(4) to 20 mA current input can be used in place of the Pt 1000 sensor for control purposes.
-
-
-
-
EB 5766 EN 11
Page 12
Electrical connections
The default setting (WE) is configured for an application with a Pt 1000 flow temperature sensor and water flowmeter (see Fig. 3).
4.3 Type 5724/5725 Controller with Electric Actuator
Domestic hot water heating in instanta neous heating system: The electric wiring
options are the same as for the Type 5757 Controller with Electric Actuator, (see section 4.2). In addition, the pump control output can be configured as a fault alarm output.
The default setting (WE) is configured for an application of the electric actuator with a Pt 1000 flow temperature sensor, water flowmeter and pump control output (see Fig. 4).
-
VS
Pt 1000
or ye rd br blk gr br bl blk
Fig. 2 · Wiring of Type 5757-7 (default)
blk black bl blue br brown
Pt 1000
ASRüS
Pt 1000
Pt 1000
34 6521LL´N
* Caution! Live wires!
gr green or orange
1)
230 V, 50 Hz
rd red ye yellow
230V, 50Hz
*
Note!
Refer to the appendix of these instructions for other possible circuits with the necessary configuration settings or refer to the Mount ing and Operating Instructions EB 5757-7 EN, EB 5757 EN and EB 5724 EN of the corresponding controller with electric actuator.
12 EB 5766 EN
5V GND L N
or ye rd br gr blk
-
Fig. 3 · Wiring of Type 5757 (default)
1)
Water flowmeter
3)
Pump control output or fault alarm output
4)
Electromagnet, Type 5725 only
3)
230V, 50Hz
LL1 N 5V INS1 S2
4)
Fig. 4 · Wiring of Type 5724/5725 (default)
Pt 1000
1)
S1
Page 13
Manual override
5 Manual override
The direction of action and travel can be read off the travel indication scale.
5.1 Type 5757/-7 Controller with Electric Actuator
Caution!
Only activate the handwheel when the actu ator is disconnected from the power supply.
Turn handwheel clockwise to extend the
4
actuator stem Turn handwheel counterclockwise to
4
retract the actuator stem
5.2 Type 5724/5725 Controller with Electric Actuator
Type 5724
Adjust the travel by turning the handwheel (approx. 4 turns for 1 mm travel):
Turn clockwise to extend the actuator
4
stem Turn counterclockwise to retract the
4
actuator stem
Type 5725
Caution!
The actuator is live!
1. Undo the front cover and place a 4 mm hex screwdriver onto the red actuating shaft.
2. Turn the screwdriver counterclockwise
-
only, and only until the travel final value is reached at the maximum, which acti vates the bottom torque switch (switching off the motor).
Caution!
Turning the actuator too far will destroy it.
After the fail-safe action has been trig­gered by the magnet, the spring mecha­nism pushes the actuator stem out and the valve always move to its fail-safe position.
3. Remove screwdriver and carefully refasten the front cover.
-
Handwheel
Travel indication
Fig. 5 · Manual override of Type 5757/-7, Type 5724 and Type 5725 (from left to right)
Travel indication Travel indication
Handwheel
Handwheel
EB 5766 EN 13
Page 14
Operation
6 Operation
The controllers with electric actuators are adapted to the required control task by configuration and parameterization per formed in TROVIS-VIEW Operator Interface:
Type 5757-7: TROVIS-VIEW
4
6661-1066 Type 5757: TROVIS-VIEW 6661-1062
4
Type 5724 and Type 5725: TROVIS-
4
VIEW 6661-1060
Note!
Instructions on how to operate the TROVIS-VIEW Operator Interface as well as on the function and parameter settings are contained in the Mounting and Operating Instructions EB 5757-7 EN, EB 5757 EN and EB 5724 EN for the corresponding con­troller with electric actuator.
-
14 EB 5766 EN
Page 15
7 Maintenance
The control valve is subject to natural wear. Depending on the conditions the valve is op erated in, it needs to be checked at regular intervals. If leakage to the atmosphere occurs, remove the valve from the pipeline and replace the damaged parts.
Warning!
For maintenance work on the valve, make sure the relevant section of the pipeline is depressurized and, depending on the process medium, drained as well. For high medium temperatures, allow the section of the pipeline to cool down before you start. Make sure the control signal for the actuator is switched off.
Maintenance
-
EB 5766 EN 15
Page 16
Dimensions in mm and weights
8 Dimensions in mm and weights
Nominal size DN 15 20 25 32 40 50 Thread size G ½¾1 –––
Pipe Ød 21.3 26.8 33.7 42 48 60 Threadsize RG ¾ G 1G1¼G1¾G 2G2½ Width across flats SW 30 36 46 59 65 82 Length L 65 70 75 100 110 130 Length with welding ends L1 210 234 244 268 294 330 Height H2 45.5 94
Versions for temperatures up to 200 °C
and with intermediate insulating piece Height H3 30 55 Weight without actuator approx. kg 1.4 1.8 2.3 4.0 4.4 6.8
Versions for temperatures up to 200 °C
and with intermediate insulating piece
Version with threaded ends (male thread)
Length L2 129 144 159 180 196 228 Male thread A G ½ G ¾ G 1 G1¼ G 1½ G 2 Weight without actuator approx. kg 1.4 1.8 2.3 4.0 4.4 6.8
Versions for temperatures up to 200 °C
and with intermediate insulating piece
Version with flanges
Length L3 130 150 160 180 200 230 Weight without actuator approx. kg 2.5 3.4 4.1 6.9 7.7 10.7
Versions for temperatures up to 200 °C
and with intermediate insulating piece
Version with female thread
Length L4 65 75 90 – Female thread G G ½ G ¾ G 1 – Weight without actuator approx. kg 1.2 1.4 1.5
Versions for temperatures up to 200 °C
and with intermediate insulating piece
Version with flanged valve body
Height H2 45.5 94 Length L3 130 150 160 180 200 230 Weight without actuator approx. kg 2.5 3.4 4.1 6.9 8.4 11.6
Versions for temperatures up to 200 °C
and with intermediate insulating piece
1.9 2.3 2.8 4.5 4.9 7.3
1.9 2.3 2.8 4.5 4.9 7.3
3.0 3.9 4.6 7.4 8.2 11.2
1.7 1.9 2.0
3.0 3.9 4.6 7.4 8.9 12.1
140 185
16 EB 5766 EN
Page 17
Dimensions in mm and weights
Weights of controllers with electric actuators
Type 5757/-7 5724 5725
Weight without valve, approx. kg 0.7 1.1 1.3
Intermediate
insulating piece
Type 3222/5757(-7),
only up to DN 25
Types 3222/5724 Types 3222/5725
Version with flanges
Version with threaded ends
Fig. 6 · Top: Valve dimensions (version with welding ends) · Bottom: Other valve versions
Flanged valve body version
Version with female thread
EB 5766 EN 17
Page 18
Appendix
9 Appendix
9.1 Wiring for Type 5757-7 (refer to EB 5757-7 EN)
Note! The pump output L´ is non-floating (230 V~). Note: Terminals at point of installation, not included in scope of delivery
blk black · bl blue · br brown · gr green · or orange · rd red · ye yellow
Application with flow, return flow, and outdoor sensors as well as binary input to switch between operating modes = Default setting (WE)
Functions WE Configuration
Control w. reference variable 1 F01 - 1 Outdoor sensor 0 F02 - 0 Potentiometer/binary input 0 F05 - 0 BA as pump control output 0 F09 - 0 Return flow sensor 1 F11 - 1
VS
Pt 1000
or ye rd br blk gr br bl blk
ASRüS
Pt 1000
Pt 1000
34 6521LL´N
230 V, 50 Hz
Application with flow sensor and outdoor sensor
Functions WE Configuration
Control w. reference variable 1 F01 - 1 Outdoor sensor 0 F02 - 0 BA as pump control output 0 F09 - 0
Diagram abbreviations: VS Flow sensor · RüS Return flow sensor · AS Outdoor sensor
18 EB 5766 EN
VS
Pt 1000
or ye rd br blk gr br bl blk
AS
Pt 1000
34 6521LL´N
230 V, 50 Hz
Page 19
Application with flow, return flow, and outdoor sensors as well as a potentiometer for adjusting the set points
Functions WE Configuration
Control w. reference variable 1 F01 - 1 Outdoor sensor 0 F02 - 0 Potentiometer/binary input 0 F05 - 1 Remote adjuster 0 F06 - 1 BA as pump control output 0 F09 - 0 Return flow sensor 1 F11 - 1
Application with flow, return flow, and room sensors with operating mode switchover and set point adjuster
Functions WE Configuration
Control w. reference variable 1 F01 - 1 Room sensor 0 F02 - 1 Potentiometer/binary input 0 F05 - 1 Type 5257-7 Room Panel 0 F06 - 0 BA as pump control output 0 F09 - 0 Return flow sensor 1 F11 - 1
Appendix
VS
Pt 1000
or ye rd br blk gr br bl blk
VS
Pt 1000
or ye rd br blk gn br bl blk
ASRüS
Pt 1000
RüS
Pt 1000
21LL´N
Pt 1000
34 6521LL´N
Type 5257-7
Room Panel
1432
34 65
100/
1000 Ω
1000 Ω
230 V, 50 Hz
230 V, 50 Hz
EB 5766 EN 19
Page 20
Appendix
9.2 Wiring for Type 5757 (refer to EB 5757 EN)
Note: Terminals at point of installation, not included in scope of delivery
1)
Water flowmeter
2)
Flow switch
blk black · bl blue · br brown · gr green · or orange · rd red · ye yellow
Operation with Pt 1000 sensor and water flowmeter
= Default setting (WE)
Functions WE Configuration
Hot water tapping recognition 1 F01 - 1 Water flowmeter 1 F02 - 1 Current input 0 F05 - 0
Pt 1000
or ye rd br gr blk
1)
5V GND L N
230V, 50Hz
Operation with Pt 1000 sensor
Functions WE Configuration
Hot water tapping recognition 1 F01 - 0 Current input 0 F05 - 0
Operation with Pt 1000 sensor and binary contact for switching between set points
Functions WE Configuration
Hot water tapping recognition 1 F01 - 0 Current input 0 F05 - 0 Binary input function 0 F08 - 1
20 EB 5766 EN
Pt 1000
5V GND L N
or ye rd br gr blk
Pt 1000
BE1
5V GND L N
or ye rd br gr blk
230V, 50Hz
230V, 50Hz
Page 21
Operation with Pt 1000 sensor and flow switch
Functions WE Configuration
Hot water tapping recognition 1 F01 - 1 Flow switch 1 F02 - 0 Current input 0 F05 - 0
Operation with Pt 1000 sensor and external set point over an mA signal
Functions WE Configuration
Hot water tapping recognition 1 F01 - 0 Current input 0 F05 - 0 Current input function 0 F06 - 1
Pt 1000
or ye rd br gr blk
+ 4(0)...20mA
Pt 1000
or ye rd br gr blk
2)
BE2
5V GND L N
5V GND L N
Appendix
230V, 50Hz
230V, 50Hz
Operation with mA signal input
Functions WE Configuration
Hot water tapping recognition 1 F01 - 0 Current input 0 F05 - 0 Current input function 0 F06 - 0
+ 4(0)...20mA
230V, 50Hz
5V GND L N
or ye rd br gr blk
EB 5766 EN 21
Page 22
Appendix
9.3 Wiring for Type 5724/5725 (refer to EB 5724 EN)
1)
Water flowmeter
2)
Flow switch
3)
Pump control output or fault alarm output
4)
Electromagnet, Type 5725
Domestic hot water heating in instantaneous heating system
Operation with Pt 1000 sensor und water flowmeter
= Default setting (WE)
Functions WE Configuration
Hot water tapping recognition 1 F01 - 1 Water flowmeter 1 F02 - 1 Current input 0 F05 - 0
Operation with Pt 1000 sensor
Functions WE Configuration
Hot water tapping recognition 1 F01 - 0 Current input 0 F05 - 0
3)
230V, 50Hz
LL1 N 5V INS1 S2
4)
3)
230V, 50Hz
LL1 N 5V INS1 S2
Pt 1000
Pt 1000
1)
S1
S1
Operation with Pt 1000 sensor and binary contact for switching between set points
Functions WE Configuration
Hot water tapping recognition 1 F01 - 0 Current input 0 F05 - 0 Binary input function 0 F08 - 1
22 EB 5766 EN
4)
3)
230V, 50Hz
LL1 N 5V INS1 S2
4)
Pt 1000
BE1
S1
Page 23
Operation with Pt 1000 sensor and flow switch
Functions WE Configuration
Hot water tapping recognition 1 F01 - 1 Flow switch 1 F02 - 0 Current input 0 F05 - 0
Mechanical engineering applications
Operation with Pt 1000 sensor and external set point over an mA signal input
Functions WE Configuration
Hot water tapping recognition 1 F01 - 0 Current input 0 F05 - 0 Current input function 0 F06 - 1
3)
230V, 50Hz
LL1 N 5V INS1 S2
4)
3)
230V, 50Hz
LL1 N 5V INS1 S2
4)
Pt 1000
S1
+–4(0) ... 20mA
Pt 1000
S1
BE2
Appendix
2)
Operation with mA sensor input
Functions WE Configuration
Hot water tapping recognition 1 F01 - 0 Current input 0 F05 - 0 Current input function 0 F06 - 0
3)
230V, 50Hz
LL1 N 5V INS1 S1S2
4)
+–4(0) ... 20mA
EB 5766 EN 23
Page 24
SAMSON AG · MESS- UND REGELTECHNIK Weismüllerstraße 3 · 60314 Frankfurt am Main · Germany Phone: +49 69 4009-0 · Fax: +49 69 4009-1507 Internet: http://www.samson.de
EB 5766 EN
2008-11
Loading...