Samson 2408 Mounting And Operating Instructions

Page 1
Self-operated Pressure Regulators
Excess Pressure Valve Type 2408
Fig. 1· Type 2408 Excess Pressure Valve
Edition June 2010
Mounting and Operating Instructions
Page 2
Contents Page
1 Design and principle of operation . . . . . . . . . . . . . . . . . . . . . . 4
1.1 Process medium, application range, versions. . . . . . . . . . . . . . . . . 4
2 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.1 Mounting position . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.2 Strainer. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.3 Shut-off valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.4 Pressure gauge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.5 Control line . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3.1 Start-up. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3.2 Adjusting the set point. . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3.3 Decommissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
4 Maintenance and troubleshooting . . . . . . . . . . . . . . . . . . . . . . 8
4.1 Pressure fluctuations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
5 Nameplate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
6 Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
7 Technical data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
8 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2 EB 2528 EN
Contents
CAUTION!
Indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.
NOTICE
Indicates a risk of property damage.
Note! Indicates supplementary explanations, information and tips.
Definitions of the signal words used in these instructions
Page 3
EB 2528 EN 3
Safety instructions
General safety instructions
Observe the following instructions on installation, start-up and operation of the regulator for your own safety:
4
The regulator is to be mounted, started up or serviced by fully trained and qualified personnel only, observing the accepted industry codes and practices. Make sure employees or third persons are not exposed to any danger. All safety instructions and warnings in these mounting and operating instructions, particularly those concerning assembly, start-up and maintenance, must be observed.
4
According to these mounting and operating instructions, trained personnel is referred to as individuals who are able to judge the work they are assigned to and recognize possible dangers due to their specialized training, their knowledge and experience as well as their knowledge of the applicable standards.
4
The regulator fulfils the requirements of the European Pressure Equipment Directive 97/23/EC.
4
For appropriate operation, make sure that the regulator is only used in areas where the operating pressure and temperatures do not exceed the operating values specified in the order that the valve sizing data are based on.
4
The manufacturer does not assume any responsibility for damage caused by external forces or any other external influence!
4
Any hazards that could be caused in the regulator by the process medium, the operating pressure or by moving parts are to be prevented by means of the appropriate measures.
4
Proper shipping and storage are assumed.
Note! Non-electric valve versions whose bodies are not lined with an insulating material coat
­ing do not have their own potential ignition source according to the risk assessment stipulated in EN 13463-1:2001, section 5.2, even in the rare incident of an operating fault. Therefore, such valve versions do not fall within the scope of Directive 94/9/EC.
Page 4
1 Design and principle of opera
-
tion
See also Fig. 2, page 5.
The process medium flows through the valve in the direction indicated by the arrow on the body. The position of the valve plug (3) deter
­mines the flow rate across the area released between the valve's plug and seat (2).
In pressureless state (control line not con
­nected or no pressure applied), the valve is closed by theforce of the set point springs (7).
The upstream pressure p
1
to be controlled is tapped upstream of the regulator. Using an external control line, this pressure is transmit­ted to the tapped connection (9) on the actua­tor housing (6) where it is converted into a po­sitioning force by the diaphragm plate with operating diaphragm (5). This positioning force is used to move the plug stem (4) and thus the valve plug depending on the force of the set point springs (7). The spring force can be adjusted on the set point adjuster (8).
When the force resulting from the upstream pressure p
1
exceeds the adjusted set point, the valve opens proportionally to the change in pressure.
1.1 Process medium, application
range, versions
Excess pressure valve for set points between
5 mbar to 1000 mbar for gases at tempera
­tures from –20 to +60 °C. Valves with flanged body in DN 15 and DN 25 as well as with G ½, G ¾ and G1fe
­male thread.
2 Installation
See also Fig. 2, page 5.
NOTICE
Install a strainer (e.g. SAMSON Type 2 NI) upstream of the regulator (refer to sec
­tion 2.2). Make sure the regulator is mounted free of stress. If necessary, support the piping near the connecting flanges. Never attach supports directly to the valve or actuator.
2.1 Mounting position
Mounting position (preferable)
– Install the regulator in a
horizontal pipeline with the actuator housing and set point adjuster pointing ver­tically up,
– The direction of flow must correspond to
the arrow on the body,
– Install the control line with a downward
slope of approx. 10 % towards the tapping point to allow condensed liquid to flow back into the tank or pipeline.
Other mounting positions
Install the regulator in a vertical pipeline with the actuator housing and set point adjuster pointing to
the side.
Note! Higher system deviations may occur in
this mounting position.
Make sure the direction of flow matches the arrow on the body (from bottom to top).
4 EB 2528 EN
Design and principle of operation
Page 5
EB 2528 EN 5
Installation
1 Valve body 2 Seat 3 Plug 4 Plug stem 5 Diaphragm plate with operating diaphragm 6 Actuator housing 7 Set point spring 8 Set point adjuster 9 Control line connection (G ¼ tapped connection for upstream pressure p
1
)
10 Cap
10
Fig. 2 · Design and principle of operation, Type 2408 Excess Pressure Valve
Page 6
2.2 Strainer
Install a strainer upstream of the regulator (Fig. 3). Install the strainer with the direction of flow matching the arrow on the body. Make sure the filter element is vertically sus
­pended. Remember to leave enough space to remove it.
2.3 Shut-off valve
Install a hand-operated shut-off valve both upstream of the strainer and downstream of the regulator (Fig. 3) to be able to shut down the plant for cleaning and maintenance, and when the plant is not used for longer periods of time.
2.4 Pressure gauge
To monitor the pressures in the plant, install a pressure gauge both upstream and down
-
stream of the regulator (Fig. 3).
2.5 Control line
G ¼ tapped connection (9) at the actuator housing. Install a control line with at least 6 mm inside diameter on site, preferably an 8x1mmpipe made ofsteel or stainless steel.
Always attach the control line connection for pressure tapping directly to the tank or vessel as the medium is fully expanded and free of turbulence at this point.
6 EB 2528 EN
Installation
Fig. 3 · Sample installation
min.
2 x DN
min. 5 x DN
DN
241
p
1
p2
1
3
2
4
1
p
1 p2
1
4
3
2
min.
3 x DN
Type 2408
Type 2408
10 % slope towards pressure tapping point
10 % slope towards pressure tapping point
1 Shut-off valve 2 Pressure gauge (upstream pressure) 3 Strainer 4 Pressure gauge (downstream pressure)
Page 7
When tapping the pressure at a straight pipe
­line section, observe a minimum distance of at least twice the nominal valve size to the regulator.
Connect the control lines to the side or top of the main horizontal pipeline. If possible, in
­stall the tapping connection in a pipe expan
­sion.
Install other fittings that maycause flow turbu
­lence (e.g. shut-off valves, restrictions, bows, bends or branches) at an appropriate dis
­tance to the control line connection (at least three times the nominal valve size).
Note! If the gas to be controlled contains moisture, condensate may form in the control line, which can damage the regulator. To al­low the gas to flow back into the tank or pipe­line, install the control line with a downward slope of approx. 10 % towards the pressure tapping point.
3 Operation
3.1 Start-up
See also Fig. 2, page 5.
NOTICE
Do not start up the regulator before all com
­ponents have been installed. Make sure the control line is free of dirt or other contaminations that may impair the proper medium flow. Connect the line properly.
We recommend to open shut-off valves slowly from the downstream side. Avoid pressure surges.
NOTICE
The max. permissible pressure at the operat
-
ing diaphragm must not exceed 0.5 bar with A = 1200 cm², 1 bar with A = 640 cm², 2 bar with A = 320 cm² and 4 bar with A = 160 cm². Make sure this pressure is not exceeded, par
­ticularly when pressure-testing the plant with the regulator installed or when starting up the plant.
3.2 Adjusting the set point
Adjust the desired set point by tensioning the set point springs using the set point adjuster (SW 27/¾" adjustment screw).
4
Remove the cap (10).
4
Turn the adjustment screw using a socket wrench with width across flats SW 27.
4
Turn the adjuster clockwise P to increase the set point and counterclockwise
Q to
reduce it.
4
Remount the cap.
EB 2528 EN 7
Operation
Fig. 4 · Set point adjustment; view from top
Adjustment screw SW 27 (¾")
Page 8
Check the adjusted set point on the pressure gauge installed upstream of the regulator (Fig. 3).
3.3 Decommissioning
We recommend to close the upstream shut-off valve before closing the shut-off valve in
-
stalled downstream of the regulator.
4 Maintenance and trouble
-
shooting
The pressure regulator is maintenance free. Nevertheless, it is subject to natural wear, particularly at the seat, plug and operating diaphragm.
Depending on the operating conditions, the regulator needs to be checked at regular in­tervals to detect and remove possible mal­functions.
CAUTION!
For installation and maintenance work on the regulator, make sure the relevant plant sec
­tion has been depressurized and, depending on the process medium, drained as well. We recommend to remove the regulator from the pipeline. If necessary, allow the regulator to cool down to reach ambient temperature before starting any work on it. Disconnect or shut off the control line to avoid any hazards that could be caused by moving regulator parts. As valves are not free of cavities, remember that residual process medium might still be contained in the valve.
4.1 Pressure fluctuations
NOTICE
Pressure fluctuations (oscillation) may dam
-
age the regulator and plant. As a result, pre
­vent them from occurring or remove their cause immediately.
To stop oscillation from occurring, the follow
­ing actions may be helpful:
4
Check the pressure tapping point at the control line (refer to section 2.5); if neces
-
sary, move the tapping point.
4
Screw a SAMSON restriction into the sleeve for the tapped connection (9): or­der no. 1991-7114 for 1200 and 640 cm², order no. 1991-7113 for 320 and 160 cm².
4
Check the regulator's sizing data. If nec­essary, change the K
VS
coefficient, seat di-
ameter or diaphragm area.
Contact SAMSON (refer to section 6) if the problems persist.
8 EB 2528 EN
Maintenance and troubleshooting
Page 9
5 Nameplate
6 Service
If malfunctions or defects occur, contact the SAMSON After-sales Service for support.
The addresses of SAMSON AG, its subsidiar­ies, representatives and service facilities worldwide can be found on the Internet at www.samson.de, in a SAMSON product cat
­alog or on the back of these mounting and operating instructions.
Include the following details when making in
­quiries:
4
Type and nominal size of the regulator
4
Configuration ID (Var-ID)
4
Upstream and downstream pressures
4
Temperature and process medium
4
Min. und max. flow rates
4
Has a strainer been installed?
4
Installation drawing indicating the exact location of the regulator and all addition­ally mounted units (shut-off valves, pres­sure gauges etc.)
EB 2528 EN 9
Nameplate
Fig. 5 · Nameplate
Legend
1 Configuration ID (VAR-ID) 2 Manufacturing data 3 Type designation (2408) 4 Max. perm. differential pressure
in bar 5 Max. perm. temperature in °C 6 Nominal size DN or connection
thread G 7KVScoefficient 8 Set point range in bar 9 Nominal pressure PN
1
2
4
6
9
SAMSON
7
8
3 5
Page 10
7 Technical data
10 EB 2528 EN
Technical data
Table 1 · Technical data
Connection · Nominal size G ½, G ¾ and G 1
Stainless steel
DN 15 and DN 25
Spheroidal graphite iron Nominal pressure PN 25 Control line connection for
8 x 1 mm pipe
G ¼
K
VS
coefficients 0.25 · 1.0 · 2.5 · 3.21)· 5.0
1)
Max. perm. differential pressureΔp 6 bar Max. perm. pressure at the actuator
Actuator area A = 1200 cm² Actuator area A = 640 cm² Actuator area A = 320 cm² Actuator area A = 160 cm²
0.5 bar 1 bar 2 bar 4 bar
Permissible temperature range of the medium
–20 to +60 °C
Leakage class acc. to DIN EN 60534-4 Soft seal, at least class IV
Set point ranges
5 to 15 mbar · 10 to 30 mbar · 25 to 60 mbar · 50 to 200 mbar
100 to 1000 mbar
1)
Only in conjunction with 100 to 1000 mbar set point range
Page 11
8 Dimensions
EB 2528 EN 11
Dimensions
Fig. 6 · Dimensions
Flanged body made of
spheroidal graphite iron
Body with screwed ends
made of stainless steel
Table 2 · Dimensions in mm
Connection G ½ G ¾ G 1 DN 15 DN 25
Female thread ½” ¾” 1” – Length L 65 75 90 130 160 Width across flats SW 34 34 46 – Height H3 45
5 to 15 mbar
Height H 360 Actuator Actuator Ø D = 490 mm, actuator area A = 1200 cm²
10 to 30 mbar
Height H 360 Actuator Actuator Ø D = 380 mm, actuator area A = 640 cm²
25 to 60 mbar
Height H 360 Actuator Actuator Ø D = 285 mm, actuator area A = 320 cm²
50 to 200 mbar
Height H 360 Actuator Actuator Ø D = 285 mm, actuator area A = 320 cm²
100 to 100 mbar
Height H 360 Actuator Actuator Ø D = 225 mm, actuator area A = 160 cm²
Approx. weight in kg
5 to 60 mbar set point range 15.5 15.7 15.9 17 18 50 to 1000 mbar set point range 12 12.2 12.4 13.5 14.5
Page 12
SAMSON AG · MESS- UND REGELTECHNIK Weismüllerstraße 3 · 60314 Frankfurt am Main · Germany Phone: +49 69 4009-0 · Fax: +49 69 4009-1507 Internet: http://www.samson.de
EB 2528 EN
S/Z 2010-08
Page 13
Conversion from chromate coating to iridescent passivation
We at SAMSON are converting the surface treatment of passivated steel parts in our production. As a result, you may receive a device assembled from parts that have be­en subjected to different surface treatment methods. This means that the surfaces of so­me parts show different reections. Parts can have an iridescent yellow or silver color. This has no effect on corrosion protection. For further information, go to u www.samson.de/chrome-en.html
Conversion from chromate coating to iridescent passivation
Loading...