Samson 2040 Mounting And Operating Instructions

Page 1
Self-operated Temperature Regulators
Type 2040 Safety Temperature Monitor (STM)
Mounting and Operating Instructions
EB 2090 EN
Edition October 2014
Page 2
Contents Page
1 Design and principle of operation. . . . . . . . . . . . . . . . . . . . 4
2 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3 Set point adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3.1 New adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3.2 Set point adjuster with set point indication . . . . . . . . . . . . . . . . 7
4 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
5 Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
6 Dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
7 Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
8 Nameplate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2 EB 2090 EN
Contents
CAUTION!
Indicates a hazardous situation which, if not avoided, could result in minor or moderatein
-
jury.
Note! Indicates supplementary explanations, information and tips.
Definitions of the signal words used in these instructions
Page 3
EB 2090 EN 3
Safety instructions
General safety instructions
4
The regulator may only be mounted, started up or operated by trained and experienced personnel familiar with the product. According to these mounting and operating instructions, trained personnel refers to individuals who are able to judge the work they are assigned to and recognize possible dangers due to their specialized training, their knowledge and experience as well as their knowledge of the relevant standards. All safety instructions and warnings in these mounting and operating instructions, particularly those concerning assembly, start-up and maintenance, must be observed.
4
For appropriate operation, make sure that the regulator is only used in applications where the operating pressure and temperatures do not exceed the operating values based on the sizing data submitted in the order.
4
Note that the manufacturer does not assume any responsibility for damage caused by external forces or any other external factors. Any hazards which could be caused in the regulator by the process medium or operating pressure are to be prevented by means of appropriate measures.
4
The Type 2040 Safety Temperature Monitors do not have their own potential ignition source according to the ignition risk assessment stipulated in EN 13463-1: 2001, section 5.2, even in the rare incident of an operating fault. Therefore, they do not fall within the scope of Directive 94/9/EC.
4
The regulator complies with the requirements of the European Pressure Equipment Directive 97/23/EC. The declaration of conformity issued for a valve bearing the CE marking includes information on the applied conformity assessment procedure. The declaration of conformity can be provided on request.
TÜV typetesting/EC type examination
The Type 2040 Safety Temperature Monitors are typetested by TÜV (German technical surveil
­lance association). The test mark is available on request. An EC type examination according to Pressure Equipment Directive 97/23/EC, Module B has been performed on the Type 2040 Safety Temperature Monitor.
Page 4
1 Design and principle of oper
-
ation
The Type 2040 Safety Temperature Monitor protects downstream plants against exces
-
sively low temperatures in applications in
­volving the storage of cryogenic media as well as liquids, gases and vapors.
These safety temperature monitors close whenever the medium temperature falls be
­low the adjusted temperature set point (limit) to prevent cold media entering the connected consumer plant.
The safety temperature monitor consists of the body (1) with integrated temperature sensor (6) and set point adjuster (3). It operates ac
­cording to the liquid expansion principle.
The volume of the temperature-sensitive filling medium confined in the integrated tempera­ture sensor (6) expands as the temperature rises and contracts again as the temperature falls. The valve is normally open. If the me­dium temperature falls below the adjusted set point (when the medium is too cold), the liquid inside the sensor contracts and the tubular
plug (5) is pushed by the positioning springs (4) against the soft-sealed seat (2). As the me
­dium temperature drops, the plug moves in the closing direction, restricting the medium flow. If the medium temperature drops fur
­ther, the valve is closed completely when the temperature reaches the adjusted set point.
The set point temperature and the throttling range in front of it can be adjusted within the set point range. The valve first opens again when the medium temperature has exceeded the adjusted set point by 2 K.
The temperature span between the adjusted set point temperature T
set point
and the point at which the regulator starts to close is 17 K. The valve is fully open (KV= 5) at a medium tem
-
perature of >T
set point
+ 17 K. At a medium
temperature less than T
set point
+ 17 K the me­dium flow is already throttled and the KVcoef­ficient gets smaller (Fig. 2).
If the sensor system is defective, the valve closes (fail-safe position).
4 EB 2090 EN
Design and principle of operation
K
v
-200
0
-3
5
T
T
[˚C]
Fig. 2 · Control behavior
T = 17 K temperature differential between
open and closed (throttling range)
T
set point
= –20 °C (point at which the
regulator is fully closed)
The regulator starts to close when the medium temperature has dropped below a value which is still approx. 17 K above the adjusted set point.
Closed
Open
–20
T
set point
Normal range of
medium temperature
–3
Page 5
EB 2090 EN 5
Design and principle of operation
3
1 2
4
5 6
7
3.1
3.2
Fig. 3 · Functional diagram of Type 2040 Safety Temperature Monitor
1 Body with connection 2 Valve seat with soft sealing 3 Set point adjuster
3.1 Cap
3.2 Lock nut 4 Positioning spring 5 Tubular plug 6 Temperature sensor 7 Connection nut with spherical liner (accessories) 8 Connection nut with flat gasket (accessories)
8
Connection nut with flat gasket · Connection with soldering nipples (brass) or welding ends (stain
-
less steel)
Connection nut with soldering nipples (brass) or welding ends (stainless steel)
Page 6
2 Installation
Connection fittings (accessories) must be pro
-
vided at the site of installation.
Note!
Do not install the regulator directly next to an air vaporizer. Otherwise, the regulator could close due to the low outdoor temperature. The closing function of the regulator does not de
­pend on whether the sensor temperature is determined by the outdoor air or by the me
­dium.
For outdoor installation, we recommend an adjusted set point temperature of –37 °C to­gether with the point at which the regulator is fully closed at –20 °C (set point range –45 to –10 °C).
The following points generally apply:
4
The regulator can be installed in any de
-
sired position
4
The direction of flow must match the ar
-
row on the valve body
3 Set point adjustment
See Figs. 3 and 4
The safety temperature monitor has been ad
-
justed by the manufacturer to a set point tem
-
perature (limit) of T
set point
= –10 °C (set point range from –30 to +10 °C) or –37 °C (set point range from –45 to –10 °C).
After removing the cap (3.1) and undoing the lock nut (3.2), the required set point temperature (T
set point
) can be adjusted within the set point range using the set point adjuster (3).
6 EB 2090 EN
Installation
2.0
1.5
1.0
0.5
0.5
1.0
1.5
2.0
10-10 -5 0 5-30 -25 -20 -15
[˚C]
Fig. 4 · Adjustment diagram at a set point temperature T
set point
= –10 °C (point at which regulator is fully closed)
Turns of the set point adjuster
T
set point
Turns of the set point adjuster
Page 7
Use the adjustment diagram (Fig. 4) as a guide to change the set point temperature from the default setting. One turn of the set point adjuster corresponds to a change in set point temperature of approx. 13 K.
The set point temperature together with the point at which the regulator is fully closed shift to lower temperatures when the set point adjuster (3) is turned clockwise P.
3.1 New adjustment
Adjustment of the set point temperature from an unknown setting:
Note! The ambient temperature must be within the set point range.
4
Remove cap (3.1) and undo lock nut (3.2). Make sure that the medium flow and outside air have the same tempera­ture.
4
Turn the set point adjuster (3) counter­clockwise until the flow noise inside the regulator ceases, i.e. the valve is closed.
4
Calculate the temperature difference be
­tween the momentary ambient temperature and the required set point temperature (T
set point
) to be adjusted.
4
Divide the calculated temperature differ
­ence by 13. The result shows how may turns of the set point adjuster (Fig. 4) are required.
4
Turn the set point adjuster clockwise by the determined number of turns.
4
Lock set point adjuster (3) with the lock nut (3.2) and screw cap (3.2) back on.
4
Secure setting, if necessary, with sealing wire through the holes in the cap and valve.
3.2 Set point adjuster with set point indication
In a special version, the set point adjuster is fitted with a marked ring for set point indication. The distance between two marks corresponds to a temperature difference of approx. 10 K (10 °C).
EB 2090 EN 7
Set point adjustment
Page 8
4 Maintenance
CAUTION!
Prior to performing any work on the regula
-
tors, decommission the plant by slowly clos
-
ing the shut-off valves. Depressurize and, de
­pending on the process medium, drain the plant section as well.
CAUTION!
Regulators for oxygen service are labeled to indicate that the regulators must be kept free of oil and grease for oxygen service.
These versions are cleaned and assembled under special conditions. Gloves must be worn when exchanging parts which come into contact to oxygen. These parts must not come into contact with oil or grease. When returning regulators for oxygen service to SAMSON for repair, the sender is respon­sible for ensuring that the regulators are han
­dled in conformance with the specifications in the German regulation VBG 62 or equivalent regulations until receipt at SAMSON. If this is not the case, SAMSON AG will not assume any responsibility for the suitability of these regulators for oxygen service.
If the point at which the regulator closes devi
­ates strongly from the adjusted set point, shut
­off may be impaired because the seat and plug are clogged up with dirt or due to natu
­ral wear.
In this case, remove the regulator from the pipeline and clean it. If necessary, replace the plug seal with a new one.
5 Service
If malfunctions or defects occur, contact the SAMSON After-sales Service for support.
The addresses of SAMSON AG, its subsidiar
­ies, representatives and service facilities worldwide can be found on the Internet at www.samson.de, in a SAMSON product cat
­alog or on the back of these mounting and operating instructions.
Include the following details when making in
­quiries:
4
Type and nominal size of the regulator
4
Process medium
4
Set point temperature range
4
Production number 3- ...
4
Model number with modification index
4
Flow rate in m³/h
4
Installation drawing indicating the exact location of the regulator (e.g. outdoors or indoors) and all additionally mounted units (shut-off valves, pressure gauges etc.)
8 EB 2090 EN
Maintenance
Page 9
6 Dimensions
EB 2090 EN 9
Dimensions
ØD
Ød
ØD
Ød
L1±1
H1
133±1
L3 ±3
L3 ±3
L2 ±1
H1
133±1
Fig. 5 · Dimensions
Dimensions in mm DN 15 DN 25
L3
100
d
For pipe∅16 For pipe∅28
Soldering nipple (brass)
Dimensions in mm DN 15 DN 25
L1
155
L2
165
d
16.1 28.5
D
21.3 33.7
Welding ends (stainless steel)
Height H1
Without set point indication: H1 = 108±1 mm With set point indication: H1 = 116±1 mm Weight: 1.8 kg (without connecting parts)
Connecting parts with spherical liner
Connecting parts with flat gasket
Page 10
7 Technical data
10 EB 2090 EN
Technical data
Table 1 · Technical data · All pressures in bar (gauge)
Type 2040 Safety Temperature Monitor
Body connection
G 1¼ (see Fig. 4 for connecting parts)
K
VS
coefficient
5
Set point ranges
–30 °C to +10 °C
–45 °C to –10 °C
1)
Max. perm. operating pressure
40 bar
Max. perm. differential pressure∆p
25 bar
Leakage rate
0.05 % of KVSat –10 °C
0.1 % of KVSat –45 °C
Hysteresis
2 K
Accuracy
±
1 °C
Permissible temperature range
–60 °C to +60 °C
Temperature differential between open/closed
17 K
1)
On request
Table 2 · Materials · Material number according to DIN EN
Type 2040 Safety Temperature Monitor
Body
CC491K (G-CuSn5ZnPb)
Bellows
CW453K (CuSn8F40)
Spring
1.4310
O-ring
NBR
Seat
CW617N (CuZn40Pb2)/NBR
Tubular plug
1.4571/1.4404
Page 11
8 Nameplate
Laser inscription on the regulator body
EB 2090 EN 11
Nameplate
Fig. 6 · Nameplate specifications
Flow of direction
Production number: 3- ...
Model number with modification index
Valve coefficient KVS= 5
Set point temperature with unit
Test mark
1)
Keep regulator free of oil and grease
1)
Omitted at a set point temperature between –31 °C and –45 °C
Page 12
SAMSON AG · MESS- UND REGELTECHNIK Weismüllerstraße 3 · 60314 Frankfurt am Main · Germany Phone: +49 69 4009-0 · Fax: +49 69 4009-1507 Internet: http://www.samson.de
EB 2090 EN
S/Z 2016-12
Loading...