Samsomatic 3962-9, 3962 Series Mounting And Operating Instructions

Series 3962 Ex d Solenoid Valve Type 3962-9
Fig. 1 · Type 3962-9
Mounting and Operating Instructions
EB 3962-1 EN
Contents
Contents Page
1 Mounting............................................................................................................4
1.1 Wall mounting....................................................................................................4
1.2 Mounting on rotary actuators with NAMUR interface acc. to VDI/VDE 3845...........4
1.3 Mounting on linear actuators with NAMUR rib acc. to IEC 60534-6-1 using
adapter plates.....................................................................................................5
1.4 Mounting on linear actuators using CrNiMo pipe fittings........................................5
2 Pneumatic connections........................................................................................6
2.1 General..............................................................................................................6
2.2 Connecting line...................................................................................................6
2.3 Operating medium for the booster valve................................................................6
2.4 Auxiliary air for the pilot valve.............................................................................6
2.5 Converting to external auxiliary air routing through connection 9............................7
2.5.1 Type 3962-9XXX14.............................................................................................7
2.5.2 Type 3962-9XXX13.............................................................................................7
3 Electrical connections..........................................................................................9
3.1 Cable entries.......................................................................................................9
4 Certificates.......................................................................................................12
2 EB 3962-1 EN
Safety instructions
EB 3962-1 EN 3
General safety instructions
The solenoid valves are to be assembled, started up or operated only by trained
and experienced personnel familiar with the product.
According to these mounting and operating instructions, trained personnel is referred to as individuals who are able to judge the work they are assigned to and recognize possible dangers due to their specialized training, their knowledge and experience as well as their knowledge of the applicable standards
.
Proper shipping and storage are assumed.
Explosion-protected solenoid valve versions are to be operated only by per-
sonnel who has undergone special training or instructions or who is author­ized to work on explosion-protected devices in hazardous areas
. For technical data, order specifications, spare parts and accessories refer to Data Sheet T 3962.
Make sure the maximum permissible supply pressure is not exceeded. If neces-
sary, reduce the supply pressure using a suitable supply pressure regulator.
The solenoid valves can be installed in any desired position. Make sure the filter
in the lid and the cable entries point vertically down. If this mounting position is not possible, install the solenoid valves with the filter and cable entries in hori­zontal position.
Important!
For installation and maintenance work on the solenoid valves, make sure the
relevant plant section has been depressurized and, depending on the pro­cess medium, drained as well. Due to the high surface resistance, avoid electrostatic charging when mounting or servicing the solenoid valves in hazardous areas. Do not loosen the enameled screws on the housing.
The solenoid valves can be mounted on rotary actuators, linear actuators or
control valves with a NAMUR rib using mounting kits. Observe the associ­ated mounting instructions.
Mounting
1Mounting
1.1 Wall mounting
Types 3962-9XXX13 and 3962-9XXX14
The solenoid valves can be mounted using the through holes and screws.
Fig. 2 · Booster valve without solenoid valve head
(dimensions in mm)
1.2 Mounting on rotary actuators with NAMUR interface acc. to VDI/VDE 3845
Type 3962-9XXX0
The solenoid valves can be mounted on rotary actuators with NAMUR interface us­ing the following adapter plates (Fig. 3):
1400-9741 for ¼” or – 1400-9743 for ½”.
The adapter plates are not included in the scope of delivery.
Before mounting, check that the two O-rings are properly positioned. Use the grub screw to adjust the direction of action on the con­necting flange of the rotary actuator. Use two screws for attachment.
Fig. 3 · ¼” NAMUR interface (dimensions in mm)
4 EB 3962-1 EN
Grub screw
Mounting
1.3 Mounting on linear actuators with NAMUR rib acc. to IEC 60534-6-1 using adapter plates
Type 3962-9XX00
The solenoid valves can be mounted on lin­ear actuators with NAMUR rib using ad­apter plates (Fig. 4). When additionally mounting positioners or limit switches on lin­ear actuators in DN 50, an additional bracket is required (order no. 0320-1416).
Fig 4 · Adapter plate with NAMUR rib (dimensions in
mm)
1.4 Mounting on linear actuators using CrNiMo pipe fittings
Types 3962-9XX0130 and 3962-9XX0142
The solenoid valves can be mounted on lin­ear actuators (e.g. SAMSON Type 3271 or Type 3277) using CrNiMo pipe fittings (Fig. 5). For mounting instructions on the SAMSON actuators, refer to Mounting and Operating Instructions EB 8310 EN and EB 8311 EN.
Fig. 5 · Mounting on linear actuators using CrNiMo
pipe fittings
Actuator size Connection Order no.
80/240 cm² G ¼ or G ¼ 1400-6759
350/700 cm²
G ⅜ or G ¼ 1400-6761
G ⅜ or G ½ 1400-6735 1400 cm² G ¾ or G ½ 1400-6736 2100 cm²
G 1 or G ½ 1400-6737
2800 cm²
EB 3962-1 EN 5