Salus Controls Installation Guide Operating and mounting instructions

SALUS RT 10
Electronic room thermostat for radiant panel,
radiator and convector heating systems
Installation and
operating instructions
General
Congratulations on choosing to purchase a SALUS room thermostat. In selecting the room temperature controller that can boast some considerable advantages over its con­ventional, mechanical counterparts. This controller is very simple to use with its stan­dard rotary knob and, with its state-of-theart electronics, it can offer you unparalleled ease of control for all manner of heating systems.
The RT 10‘s features, which are described in detail below, ensure that you can control your heating system in a precise, easy and energy-saving way.
Technical characteristics
Pulse width modulation (PWM) Radiant panel heating systems tend to have a problem with overshooting, i.e. rooms conti­nue to be heated even after the desired tem­perature has been reached and the valve has been closed. The RT 10 solves this problem electronically and especially effectively using what is known as pulse width modulation. By continuously comparing set temperature with actual temperature, the lengths of opening times for the valve actuators are regulated in such a way that the temperature is almost completely prevented from exceeding or fal­ling below the set temperature. In this way, the required temperature setting is regulated in a precise and convenient way.
Note: When the RT 10 is used with radiator or convector heating systems, pulse width modulation can be switched off if necessary (see ‚Basic settings‘ section).
Valve protection function To ensure that valves remain movable and ready for use even when they are unused for considerable periods – e.g. over the summer – the RT 10 includes a valve protection func­tion. Briefly once a week, even when there is no requirement for any heat, the valve actua­tors open the valves that they control.
Temperature reduction Timed and demand-oriented heating control are amongst the best ways of managing hea­ting energy in an economical way. The RT10 has an integrated temperature reduction function which enables you to automatically reduce the set temperature by 4K with no need for any costly add-on installation on the boiler controller. This ‚night reduction‘ can be activated by an external signal, e.g. time control from a terminal strip, or using a stan­dard external timer.
Installation
The RT 10 room thermostat is designed as an electronic temperature controller for the electrical fine adjustment of hot-water based heating systems, and is used for controlling electro-thermal valve actuators or other elec­trical devices. It is vitally important that the maximum switching current specified in the technical specifications should not be excee­ded! We are not liable for any form of impro­per use.
This equipment must only be installed by anauthorised, qualified engineer, and only in accordance with the wiring diagram. Instal­lation must also be in accordance with the latest VDE regulations as well as your electri­city supplier‘s regulations. The system must be in a de-energised state whilst installation is carried out, and all safety instructions must be followed to the letter.
The control may only be mounted on a non­conductive surface. Find a position for the thermostat where it is not covered by curta­ins, furniture or anything else. The controller must not be installed too close to any heat source (lights, stove, direct sunlight etc.), nor should it be installed in a position where it will be exposed to draughts. The control­ler must be installed in a suitable location in order for room temperature to be monitored accurately and accordingly regulated with precision.
Important: The thermostat must be dis­connected from its power supply before its housing is opened.
Wall mounting The housing cover must be separated from the base plate before the controller is fitted. Follow the steps listed below:
Carefully pull off the adjuster wheel.1. Remove the screw from under the adju-2. ster wheel. Open the housing by pulling off its cover 3. on the adjuster wheel (right) side.
Now, using the screws supplied, screw the base plate firmly to the wall or the flush­mounted socket.
Connection
The thermostat must be wired in accordance with the wiring diagram below:
RT 10 230 V Model
Terminal
Lead for temperature reduction
N Neutral conductor supply lead
L 230VAC power supply
Switch output (valve actuator, terminal strip)
RT 10 24 V Model
Terminal
Lead for temperature reduction
L2 Neutral
NC Circuit closed once temperature reached
1
Common
NO Circuit open once temperature reached
2
L1 24VAC power supply
1
e.g. cooling unit 2 e.g. heating unit
Basic settings
RT 10 Jumpers
Switch
Function ON OFF
VP
Valve protection function
PWM
Pulse width modulation
Temperature reduction
The factory setting for all these functions is ON. You can change these settings according to your own requirements by moving the contact terminals on the jumpers.
Important: The contact terminals should not be removed.
As long as the installation is carried out to a professional standard, the criteria for protec­tion class II will be satisfied.
Operation
The RT 10 electronic room thermostat is used for regulating the temperature in dry, enclosed rooms with a normal environment and maximum humidity of 95% (nonconden­sing).
It is extremely simple and convenient to set the desired room temperature using the rotary knob. This electronic control system ensures that the set room temperature is maintained virtually without fluctuation and, when required, automatically activates a red­uction in temperature.
Never use anything other than a soft, dry cloth to clean the unit. Never use any clea­ning agents containing solvents or any sharp objects to clean the unit!
Technical data 230 V 24 V
Product no.: 412.100 412.101
Operating voltage: 230VAC / 50Hz 24VAC / 50 Hz
Electronic switch output
Max. switching current: 10 (2) A
Rated impulse voltage: 4000 V
Max. no. of valve actuators: 5 units - 3 W
Temperature range: 5°C - 30°C
Degree of protection through casing: IP 30
Automatic function: type 1.C (EN 60730-1)
Degree of contamination: 2 (Household)
Dimensions W/H/D in mm: 75 / 75 / 27
Operating temperature: 0°C - 50°C
Storage temperature: -25°C - 65°C
Control pollution: Normal