Salus Controls ERT 20 Operating and mounting instructions

SALUS ERT 20
Electronic room temperature controller for
panel, radiator and convection
heating systems.
Operating and mounting instructions
General
Congratulations on choosing a SALUS brand room thermostat. In selecting the ERT20 model you have chosen an electronic room temperature controller which offers key ad­vantages over conventional mechanical prod­ucts: The controller is easy to operate using the conventional backlit adjusting dial and offers you unique control convenience for heating applications of all types thanks to the high quality device electronics.
The following characteristics of the ERT20 guarantee you precise, comfortable and en­ergy saving operation of you room heating system.
Technical characteristics
Pulse-Width-Modulation (PWM)
Panel heating has the basic problem of tem­perature overshoot. i.e. the room continues to be heated even when the valve is closed when the desired temperature has been reached. The ERT10 solves this problem elec­tronically and extremely effectively using so­called Pulse-Width-Modulation (PWM). Using a constant comparison of desired and actual
temperature, the opening period of the actu­ators is adjusted to avoid, to as larger degree as possible, exceeding or sinking below the desired room temperature. This achieves an exact and comfortable controlling of the set desired temperature.
Notice: When using ERT20 for radiators or convection heating systems, the Pulse-Width­Modulation (PWM) can be switched off (see basic settings section).
Switching between heating/cooling
The electronic room thermostat ERT20 offers you the option of selecting between heating and cooling operation. The thermostat facto­ry setting is for heating operation. to cooling, please switch the corresponding switch under the housing cover (marked with
To switch
“heat” and “cool”). When in cooling operation mode, the Pulse-Width-Modulation (PWM) is automatically switched off.
Valve protection feature
In order to ensure that the valves remain movable and functional even after long pe­riods out of operation - i.e. in summer - the ERT20 has a valve protection feature. The valves which are to be controlled are opened temporarily by the actuators once a week, even when no heating energy is required.
Notice: The valve protection feature can be deactivated is required (see basic settings section).
Temperature reduction
You can achieve particularly efficient heat­ing energy management with time-controlled demand-linked heating control. With the in­tegrated temperature reduction feature the ERT20 allows you to automatically reduce the set temperature by 4K, without the need to adjust the thermostat for the set tempera­ture. This ‘night reduction’ can be achieved via an external signal e.g. via time-control of a strip terminal or using a commercially available external clock timer.
Installation
The ERT20 room thermostat was designed as an electronic temperature controller for electrical readjustment of warm water heat­ing systems and serves to control electro­thermal actuators or other electrical devices. The maximum switching current indicated in the technical data must be observed! We ac­cept no liability for any form of misuse.
The installation may only be carried out by professional installers in accordance with the connection plan. Furthermore, the installa­tion must
also comply with the current VDE regulations and the specifications of your energy supplier. The installation is always to be carried out with the power supply discon­nected, the security specifications are to be observed.
Position the thermostat such that it is not cov­ered by curtains, pieces of furniture or other objects. The control cannot be installed close to heat sources (i.e. lamps, fireplaces/chim­neys, direct sunlight etc.) and should not be affected by draughts. This allows the room temperature to be exactly measured and cor­respondingly exactly controlled.
Important notice: Before opening the ther­mostat, separate it from the power supply.
Wall mounting
Before mounting the thermostat, separate the housing cover from the base plate. Please
Jumper settings
Different ERT20 features can be switched on or off with the jumpers:
proceed as follows:
Carefully remove the dial. 1.
Remove the screw on the underside.2.
Open the housing by lifting the hous-3. ing cover on the bottom edge and then lifting it.
Now firmly mount the base plate on the wall
ERT 20 switching bridges
Switch
VP
PAWM
Feature ON OFF
Valve protection feature
Pulse-Width­Modulation
Temperature reduction
or the flush-mounted socket with the screws provided.
All features are switched to on in the factory. You can change the settings in accordance
Connection
Wire the thermostat exclusively in accord­ance with the following connection plan:
ERT 20 230 V version
Terminals
Temperature Setback
N Neutral
L 230 VAC supply
Switching output (actuator, strip terminal)
with your requirements, by switching over the contact clamps on the jumpers.
Important notice: Please do not remove the clamps!
The requirements for protection rating II will be maintained through complete, profes­sional mounting.
Operation
The electronic ERT20 room thermostat con­trols the temperature in dry closed rooms
ERT 20 24 V version
Terminals
Temperature Setback
N Neutral
L 24 VAC supply
Switching output (actuator, strip terminal)
with normal environs and a maximum relative room humidity of 95% (non-condensing).
The desired room temperature can be set very easily and comfortably with the control dial. The electronic control ensures as stable as possible maintenance of the set room tem­perature as well as the automatic activation of temperature reduction where necessary.
Clean the device exclusively with a dry soft cloth. Please do not use any cleaners using solvents or strong cleaners!
V 42V 032atad lacinhceT
102.211002.211:.on elcitrA
Operating voltage: 230VAC / 50Hz 24VAC / 50 Hz
electronic switching output
A )3( 01:tnerruc gnihctiws .xaM
W3 - stinu 5:srotautca fo rebmun .xaM
K5.0:siseretsyH
03 PI:gnitar noitcetorP
mm 5.03 / mm 08 / mm 08:D/H/W snoisnemiD
C°03 - C°5:egnar erutarepmeT
C°06 - C°02-:erutarepmet egarotS
Loading...