Receiver
COM
L
LNN
NO
AC 230 V
MAX
16 (5) A
WQ610 / WQ610RF
Button Functions
WQ610 / WQ610RF Thermostat WQ610RF Receiver
WQ610RF Wiring Diagram
TX thermostat
VOLT FREE
Receiver
7
8
Installer’s Quick Guide
Introduction
The SALUS Quantum WQ610 and WQ610RF thermostats are Boiler Plus compatible thermostats,
designed specically to control central heating boilers and also in the case of the RF versions,
electrical panel heaters. They have our new load compensation (ITLC) software with Volt free
switch and also Opentherm 4.0 connections, so you can choose the method of control to suit
your boiler / installation. Please note that the Boilers need to have an OpenTherm Association
license to be fully compatible with WQ610 range(should you wish to connect to the OpenTherm
terminals A and B). Please verify if this requirement is met with your Boiler Manufacturer.
Product Compliance
This product complies with the essential requirements and other relevant provisions of the following EU
Directives: RED:2014/53/EU and RoHS 2011/65/EU. Full text of the EU Declaration of Conformity is available on:
www.saluslegal.com
Safety Information
Use in accordance with national and EU regulations. Use the device as intended, keeping it in
a dry condition. Product is for indoor use only. Installation must be carried out by a qualied
person in accordance with national and EU regulations.
Technical Specication
Thermostat supply 230VAC Lithium Battery (Rechargable)
Thermostat rating max 3 (1) A -
OpenTherm terminals A / B -
Outputs
Temperature range 5°C – 35°C 5°C – 35°C
Thermostat display accuracy 0.5°C 0.5°C
ErP control class Class V Class V
Radio Frequency -- 2.4 GHz
Dimension [mm] 86 x 86 x 27 [mm] 86 x 86 x 11[mm]
Receiver supply 230 V AC
Receiver rating max 16 (5) A
OpenTherm terminals A / B
Outputs Voltage free NO / COM terminals
Radio frequency 2.4 GHz
Dimension [mm] 98 x 98 x 32[mm]
WQ610RF: 2405-2480MHz; <14dBm
WARNING! Always ensure the AC mains power is switched off before installing or working
on any components.
WQ610
Thermostat
Voltage free
NO / COM terminals
WQ610 Receiver
WQ610RF
Thermostat
-
2 3
1
1. MENU - enter the menu options, press and hold
for 3 seconds to return to main screen without
saving changes.
2. DOWN - decrease the temperature and move
through the menus.
3. UP - increase the temperature and move through
the menus.
4. TICK - conrm changes and enter menus.
Press and hold for 3 seconds to exit User Menu
and save changes. Press and hold to cancel
BOOST feature or temporary override (whilst in
normal screen).
4
5
7
5. ON - When in Manual Mode, ON will
turn the boiler on.
6. OFF - When in Manual Mode, OFF
will turn the boiler o.
7. AUTO - Receiver operates in automatic
mode according to the thermostat.
8. MANUAL - Receiver output is
controlled by the On/O slide switch.
6
8
TX thermostat
If you select NO, thermostat will use
dafult settings and revert to normal
screen.
OPENTHERM
Accessing Advanced Settings Menu
Receiver
Advanced Settings allow the installer / landlord to adjust the thermostat to suit individual installation
requirements. Do not adjust the settings unless you are competent to do so. The Advanced Settings may be
locked by the creation and activation of a 4 digit PIN code. Please keep your PIN safe and secure.
1
230 V
Once you have properly connected your
thermostat with the OpenTherm terminals
the OT message will be shown on the
screen. For more Opentherm details, go
to the Opentherm: Conguration section.
2
LCD Icon Description
TX thermostat
1
2
3
4
13
12
11
679108
1. Menu/Settings description
2. Clock 24hr/AM/PM
3. Temperature unit
4. Heating indicator (icon is animating
when there is heating demand)
5. RF Connection indicator
6. Current Temperature / Setpoint
Temperature
7. Holiday mode indicator
8. Temporary override mode
9. Settings icon
10. Battery indicator
11. Schedule program number
12. Schedule mode icon
13. Day indicator/ SET information
5
WQ610 Thermostat Terminals Description
Please ensure the boiler has 230 V switching before wiring in this way.
Power Up and Conguration
The WQ610RF thermostat contains a re-chargeable Lithium battery. When the battery level
is below 10%, the thermostat will display “PLEASE RE-CHARGE BATTERY”. Please re-charge
for a full 24 hours using a standard Micro USB charger. Thermostat operation will not be
aected during the charging period
1
2
Press TICK to enter Daylight Saving Time
Menu.
Press TICK to select the type of heating
control you prefer.
Press MENU.
3
5
Terminal Description
A/B OpenTherm Communication Wires only
NO Volt free connection (Switch)
COM Volt free connection (Common)
L;N Supply (230 V AC)
WQ610RX Receiver Terminals Description
To activate thermostat, press TICK button
for 3 seconds (RF version) only.
3
Language ”ENGLISH” is flashing, press
UP or DOWN, choose your language, then
TICK to confirm.
4
SALUS Controls plc
SALUS House
Dodworth Business Park South,
Using UP or DOWN, navigate to Advanced
submenu and press TICK.
4
Using UP or DOWN, select ON or OFF.
Press TICK to confirm.
6
ITLC helps to improve system efficiency
and end user comfort. Default is ITLC
Radiators (disabled if Opentherm
connected). Press TICK to confirm or
DOWN to see the next option.
Whinby Road, Dodworth,
Terminal Description
B / A OpenTherm Communication Wires only
NO Volt free connection (Switch)
COM Volt free connection (Common)
L; N Supply (230 V AC)
Using UP or DOWN, choose the time
format between 24 hr and 12 hr format.
Using UP or DOWN, set the hour and
then press TICK, which will then move
to minutes, that can be changed in the
same way.
Barnsley S75 3SP, UK
E: sales@salus-tech.com
E: techsupport@salus-tech.com
www.salus-tech.com
WQ610 Wiring Diagram
DO NOT connect to OpenTherm terminals unless your boiler is OpenTherm Association approved and
has the OpenTherm Logo.
VOLT FREE OPENTHERM
5 6
Using UP or DOWN, set the year and then
press TICK.
Using UP or DOWN, set the month and
then press TICK, which will then move
to days, that can be changed in the same
way.
SALUS Controls is a member of the Computime Group.
Maintaining a policy of continuous product development SALUS Controls plc reserve
the right to change specification, design and materials of products listed in this brochure
without prior notice.
Issue Date: Nov 2019
V006
7
8
19
20
3
4
WQ610RF: Pairing with the Receiver
This option is only for electrical radiators.
Press TICK to confirm or DOWN to see the
next option.
9
Using TICK, then UP and DOWN you can
select FROST value . (5 - 17 degrees C).
Press TICK to conrm or DOWN to see the
next option.
11
This is a simple ON/OFF algortihm
control based on the set point. Using UP
or DOWN, you can select the SPAN value.
Press TICK to confirm or DOWN to go to
next option.
10
Using TICK, then UP and DOWN you can
set the maximum and the minimum
room temperature.
12
Press TICK and enter installer’s phone
number using UP and DOWN buttons.
21
This option will allow you to lock your
advanced settings using your access
PIN. Using UP or DOWN, create your lock
advanced settings, then TICK to conrm.
23
Allows you to create a PIN which may
be used to limit access to your settings.
Using UP or DOWN, create your PIN access, then TICK to conrm.
22
Using UP or DOWN, enter the PIN code
number. Press TICK to confirm every
digit.
Temporary Manual Override
For overriding the schedule to bring the
HEAT on, use the UP button to increase the
temperature and press TICK to accept the
change.
Using UP or DOWN, adjust the
temperature and then press TICK.
5
OpenTherm related errors:
1
Press TICK to enter menu. Using UP or
DOWN, set the maximum opentherm
central heating temperature.
Using UP or DOWN, set the value then press TICK for 3
sec to confirm and exit to main screen.
2
1
ON
AUTO
2
Turn the receiver OFF and ON
twice to reset. Ensure receiver
switches are ON and AUTO.
Red LED should be ashing.
Enter thermostat MENU and
scroll down until you will see
“PAIR WITH RECEIVER” option.
Select YES to proceed with
Pairing.
The pairing between the thermostat and the
receiver is already done at the factory. However,
should you need to re-pair the units then this can
be done using the User Menu. The link may also
be tested from the User Menu to show pairing link
has been successful. Before pairing, the Receiver
should be unplugged, then plugged back in.
During the pairing process, the distance between
the Thermostat and the Receiver should be
at least 1m.
3
Now your thermostat is
looking for the receiver. A 10
minute counter will appear on
the screen.
4
Upon connecting to the
receiver, the thermostat will
display the message “PAIRING
SUCCESSFUL” and return to
normal operation afterwards.
The red LED will stop ashing
when the pairing is successful.
If you think that the temperature
displayed on the thermostat is not
accurate due to its location, you can
calibrate it using this menu with values
between -3.5 / +3.5 degree.
13
This will stop your boiler early to improve
energy saving.
15
Using UP or DOWN, you can select YES
and press TICK to confirm,or you can
select NO and go to point 20.
17 18
This will start your boiler early to improve energy saving.
14
Press TICK to allow installer or landlord
to set service reminder and lock
temperature level.
16
Using UP or DOWN, select the number of
days service alert should last for.
This setting will be valid until
the next scheduled program.
Use your created PIN to lock access to
advanced settings menu.
OpenTherm: Conguration
This menu will only be visible if your boiler is OpenTherm compatible and you have connected to
terminals A and B.
OpenTherm is a method of control used by modern heating systems. Instead of switching a boiler on and off at
intervals, modulating control allows the amount of heat provided by the boiler to be controlled to match the
varying demand from the thermostat. This means the customer has greater system efficiency, energy saving
and room comfort from our heating controls.
Temperature Values for Opentherm
Please note that below values can be manually set only if the boiler allows it.
CH (Central Heating) HW (Hot Water)
MIN TEMP: 25 °C MIN TEMP: 40 °C
MAX TEMP: 80 °C MAX TEMP: 80 °C
DEFAULT TEMP: 75 °C DEFAULT TEMP: 60 °C
1
2
SERVICE REQUEST ERROR LOCKOUT RESET ERROR
3 4
LOW WATER PRESSURE ERROR GAS FLAME FAULT ERROR
5 6
AIR PRESSURE FAULT ERROR WATER OVER TEMPERATURE ERROR
WQ610RF: Testing Link
1
Enter MENU and scroll down
until you nd „TEST LINK”
option. Press TICK button to
continue.
2 3
Now your thermostat is
sending a TEST message to the
receiver with the expectation
of receiving a response. While
testing, both red and green
LED will be intermittently
ashing.
Additional installation notes for WQ610:
GRAB
TOP
AND
BOTTOM
TO OPEN
Your thermostat will indicate
that the connection has been
tested successfully and will
return to normal operation.
Using UP or DOWN, select the warning
period before the service alert will be
activated, then press TICK.
Using UP or DOWN, select the lock
temperature and then press TICK.
This screen display will be displayed
when OT is connected. To change the
settings for DHW and/or CH - press
MENU and go to ADVANCED SETTINGS.
Using UP or DOWN, navigate to HW
SETPOINT and press TICK.
MENU /
If an Opentherm fault is detected on the boiler, the thermostat will display the above
messages. These errors are not related to the thermostat.