Salus VS35W, VS35B Installation Manual

Page 1
L
VS35
L NSLS1 S2
NSB
INPUT
N
M
T
Note: Use the rear plate of the VS35 thermostat only with this model.
Note: In the KL06 wiring centre, the SL terminal is marked with an arrow
icon .
Installation Manual
Wired thermostat with digital display for the control of temperature in UFH & RAD systems Model: VS35W (white), VS35B (black)
Introduction
The VS35 thermostat controls temperatures of individual heating zone in underoor heating systems. Thermostat allows for signicant savings thanks to the possibility of maximum reduction the set temperature. The full version of the manual in PDF format is available on the website www.salus-controls.eu
Introduction
This product complies with the following EU Directives: Electromagnetic Compatibility 2014/30/EU, Low Voltage Directive 2014/35/EU and RoHS 2011/65/EU. Full information is available on the website www.saluslegal.com
Safety Information
Use in accordance with national and EU regulations. Use the device only as intended, keeping it in a dry condition. The product is for indoor use only. Installation must be carried out by a qualied person in accordance with national and EU regulations.
Terminals description
Terminal Description
L,N Power Supply 230 V AC
NSB Night SetBack (input 230 V AC)
SL Switched output (230 V AC)
S1, S2 External temperature sensor
Proper thermostat placement
LCD Icon description Wiring diagrams
Installation
M
M
150 cm
min 20 cm
Button
Function
Increasing / decreasing temperature or value
Selection of the operating mode, switching between values
Short press - selection conrmation Long press - entry to or exit from the menu
Long press causes blocking or unlocking the thermostat
+
Button Functions
2 3 4 5 6
7
8
9
10
11
12
13
14
1
1. Current active mode
2. Comfort mode
3. Standard mode
4. Economic mode
5. Automatic mode
6. Frost protection mode
7. Temperature unit
8. Manual mode / temp. override
9. Current / set temperature
10. Key lock
11. Settings
12. Additional temperature sensor
13. Cooling
14. Heating
Importer:
SALUS Controls plc Salus House Dodworth Business Park Whinby Road, Barnsley S75 3SP, United Kingdom
DISTRIBUTOR OF SALUS CONTROLS:
QL CONTROLS Sp. z o.o., Sp. k. Rolna 4, 43-262 Kobielice, Poland
www.salus-controls.eu
SALUS Controls is a member of the Computime Group
Maintaining a policy of continuous product development SALUS Controls plc reserve the right to change specification, design and materials of products listed in this brochure without prior notice.
VS35 thermostat in connection with actuator or pump
OR
VS30 thermostat in connection with a boiler with a “NO” voltage free terminal through the RM-16A relay
VS35 thermostat in connection with wiring centre
VS35
LLN
N
L
N
SL
SL
S1 S2
NSB
INPUT
T
LNSL
KL08NSB
KL06
VS30
L NSLS1 S2
NSB
OUTPUT
T
L N
AC 230V
In this diagram, the VS30 thermostat manages the NSB function, more details about NSB function can be found on the next page.
NSB function and an additional temperature sensor is optional.
The VS35 thermostat has been designed for ush mounting in a standard electrical box with a diameter of 60 mm.
L
AC 230V
VS35
RM-16A
L
NO COM
INPUT 230 V AC
OUTPUT
POWER SUPPLY 230 V AC / 50 Hz
NC SL N L
NSLS1 S2
NSB
INPUT
N
T
1 2
3
An additional temperature sensor is optional.
T
T
VII 2017
Page 2
Temperature setting
Manual mode - temperature settings
NSB function - automatic mode
Changing the HEATING / COOLING mode
Oset function (temperature calibration)
Installer settings
Error codes
dxx Function Value Description
Default
value
d01
Control method
temperature
0 PWM algorithm
0
1 Span ±0.5°C
2 Span ±1.0°C
d02 Oset temperature
from -3.0°C
to +3.0°C
If the thermostat indica­tes wrong temperature,
you can correct
it by ± 3.0°C
0°C
d03
Using a oor
temperature sensor
(S1, S2)
0 No sensor
0
1 Sensor is connected
d04
External sensor
used for air
or oor temperature
measurement
(Function is active,
when d03=1)
0
Thermostat measures
the temperature only on
the external sensor
0
1
The sensor is used
as a protection against
overheating the oor
d05
Cooling mode control
method
1 Span ±0.5°C
2
2 Span ±1.0°C
d06
Type of thermoelectric
actuator
0 NO - normally open
1
1 NC - normally closed
d07 Valve protection
0 OFF
1
1 ON
d08
Frost protection
temperature
5-17°C
Frost protection / Holiday
mode temperature
5°C
d12
Heating temperature
limit
5-35°C
The maximum heating
temperature that can be set
by the user
35°C
d13
Cooling temperature
limit
5-40°C
The minimum cooling temperature that can
be set by the user
5°C
d14
Maximum oor
temperature (this function is active in heating mode when
d04 = 1)
6-45°C
In order to protect the oor from overheating, heating will be turned
OFF, when the maximum
temperature of the oor
sensor will be reached
27°C
d15
Minimum oor
temperature (this function is active in heating mode when
d04 = 1)
6-45°C
In order to protect
the oor, heating will
be turned ON, when the
minimum temperature of the oor sensor will
be reached
10°C
d16
Lower oor temperature
limit for cooling
(this function is active
when d04 = 1)
6-45°C
In order to protect the
oor, cooling will
be turned OFF, when
the minimum temperatu-
re will be reached
6°C
d18
Operating mode
HEATING / COOLING
0 Heating system
0
1 Cooling system
Error code Description
Err02 The maximum / minimum oor temperature has been exceeded
Err03 Temperature sensor is faulty
Err04 Temperature sensor is shorted
1
4
3 sec
3 sec
3 sec
1
5
2
43
3 sec
Choose mode
using or buttons.
1 2
43
3 sec
Set Oset temperature value
using or buttons.
Set the temperature with
or buttons.
Select the service parameter
using or buttons.
The parameter value
is set by or .
Press to conrm the changes.
Simultaneously hold the buttons
for 3 seconds.
Press to conrm the changes.
Press to conrm the changes.
Current temperature.
Temperature set in the selected
operating mode.
Choose the temperature mode
using or buttons.
Select the automatic mode
using or buttons.
Press to conrm the changes.
Press any button to highlight the screen, then follow the steps below:
Press any button to highlight the screen, then follow the steps below:
Press any button to highlight the screen, then follow the steps below:
Press any button to highlight the screen, then follow the steps below:
Press any button to highlight the screen, then follow the steps below:
There are 4 temperature levels available. In manual mode only one temperature level is active (icon in the frame indicates which mode is currently choosen). For each temperature levels you can set a dierent temperature.
The NSB (Night SetBack) function can automatically change temperatures on VS35 daily thermostats via VS30 programmable thermostat connected to a wiring centre (or another external clock). NSB function switches between comfortable temperature and economic temperature .
The VS35 thermostat allows you to adjust the displayed temperature ± 3.0°C. You can do it according to the following steps:
To activate the automatic mode, select the icon. On display together with the icon, the controller indicates active temperature mode: or .
- Comfort mode
- Standard mode
- Economic mode
- Frost protection mode. Usually used in a longer period of absence or during the holidays (available only in heating mode).
Press any button to highlight the screen, then follow the steps below:
Note: You can also set the Oset temperature value using the service parameter d02.
Note: For the NSB function to work, it is necessary to connect the wirings properly. Connection diagrams can be found on the previous page.
2
3
Note: To restore the thermostat’s factory settings, in step 2 set the PSuu to 47 code, and conrm the selection with the button.
Note: Heating / cooling mode can also be set using the service parameter d18.
2
2
1
1
1
2
3
4