KL10RF
Installation and wiring guide
www.salus-controls.com Technical Helpline 00000 000000
LN
1
2
LN
1
2
LN
1
2
LN
1
2
OUT
IN
OPTIONAL UFH ZONE VALVE
FOR RADIATORS GROUPS
FUSE
FUSE
SUPPLIED CABLES
230V TO UFH PUMP
UNDERFLOOR HEATING MANIFOLD
1.5MM2CABLE
(INSTALLER SUPPLIED)
1.5MM
2
CABLE
(INSTALLER SUPPLIED)
1.5MM
2
CABLE
(INSTALLER SUPPLIED)
1.5MM
2
CABLE
(INSTALLER SUPPLIED)
13 AMP FUSED CONNECTION UNIT
FUSED AT 3 AMPS
230V
OPTIONAL
CYLINDER STAT
1.5MM23 CORE
1.5MM
2
3 CORE
1.5MM
2
CABLE
OUT
IN
(INSTALLER SUPPLIED)
COLOURS ARE INDICATIVE ONLY.
EXTRA CONNECTIONS MAY BE REQUIRED
AS PER MANUFACTURERS INSTRUCTIONS
ZONE 1
+++++++++
---------
ZONE 2
IN
HW CYLINDER
THERMOSTAT
HW MOTORISED VALVE OVERHEAT STAT UFH PUMP BOILER ENABLE UFH MOTORISED VALVE
OUT IN OUT IN OUTBR EA N OR GR BR EA N OR GRLNE
ZONE 3 ZONE 4 ZONE 5
ZONE 6
ZONE 7
ZONE 8
LN
1
2
LNLN LNLN LNLN
THERMOSTAT NEUTRAL CONNECTIONS THERMOSTAT LIVE CONNECTIONS
L NLNLNLNLNLNLNLNLNLN
BATTERY POWERED
PROGRAMMABLE
ROOM THERMOSTAT
(MODEL VS20WRF)
OPTIONAL
HOT WATER TIMER
(MODEL VS10WRF
or VS20WRF)
MAINS POWERED
PROGRAMMABLE
ROOM THERMOSTAT
(MODEL VS10WRF)
BATTERY POWERED
PROGRAMMABLE
ROOM THERMOSTAT
MAINS POWERED
PROGRAMMABLE
ROOM THERMOSTAT
BATTERY POWERED
PROGRAMMABLE
ROOM THERMOSTAT
BATTERY POWERED
PROGRAMMABLE
ROOM THERMOSTAT
MAINS POWERED
PROGRAMMABLE
ROOM THERMOSTAT
OPTIONAL
PROGRAMMABLE
ROOM THERMOSTAT
RADIATOR ZONE
2
2
1
3
4
8
6
5
9
FACTORY
FITTED
LINK
FACTORY
FITTED
LINK
FACTORY
FITTED
LINK
These instructions are applicable to the SALUS model
stated above.
Warning
This product must be tted by a competent person, and
installation must comply with the guidance, standards and
regulations applicable to the city, country or state where the
product is installed. Failure to comply with the requirements
of the relevant guidance, standards and regulations could lead
to injury, death or prosecution.
Warning
Always isolate the AC Mains supply before installing or working
on any components that require 230 VAC 50Hz supply.
For PDF Installation guide please go to www.salus-controls.com
Meets the following EC Directives
• Electro-Magntic Compatibility directive 2004 / 108 / EC
• Low voltage Directive 2006/95/EC
Optional wireless
receiver RX10RF
7
Maintaining a policy of continued product development SALUS Controls plc reserve the right to change
specication, design and materials of products listed on this installation guide without prior notice.
Issue Date: June 2014 Document Number 00106
iT600 Wiring Centre KL10RF 004_Layout 1 05/06/2014 15:24 Page 1

KL10RF
Installation and Wiring Guide
When using option 2 refer to device
parameters on page xx of the manual.
Fuses
Coordinator
Aerial Connection
Dip Switch Set Up
In order for the wiring centre to be
able to control UFH and Radiators,
there is a need to turn o the UFH
pump for a zone when that zone is
to be used for radiators.
Eg. When tting a zone for radiators
or towel rail then the Dip Switch for
that zone should be switched to OFF.
The Dip Switches for this are located
under the front lid. When the zone
switch is in the ON position the UFH
pump will run when that zone is
calling for heat along with the boiler.
When it is in the OFF position then
the UFH pump will not run but the
boiler will re.
There are three other function
switches as well.
Pump & Boiler delay:This gives a
three minute delay to allow
actuators to open before the boiler
res.
Pump Only Delay: Delays only the
UFH pump from ring for three
minutes.
Actuator NC or NO: This refers to
Normally Open or Normally Closed.
This should be set to NC for
products.
2
Actuator Connections
Actuator connections corresponding to the thermostat connections. Up to 2
cables can be used in each connection (4 Actuators per Zone) If more, that
number needs to be connected, then an external junction box will be needed.
A maximum of xxx actuators can be connected to a zone in this manner.
Optional Cylinder Thermostat: If connecting the cylinder thermostat
directly to the timer then a link needs to be tted between IN and OUT.
Optional Hot Water Motorised Valve: Used if timed hot water is required.
Optional Overheat Thermostat:Used for connecting a pipe thermostat to
prevent over temperature water damaging sensitive oors. Remove the link
and connect the pipe thermostat so it is Normally Closed. The pipe stat will
open if overheating occurs and
the UFH pump will stop running.
Optional Boiler Enable: This Volt Free connection must come from the boiler
thermostat connection, when any zone calls for heat the Boiler enable will
close causing the boiler to run. If work is being carried out on the boiler then
power to and from the switch will
cease. (Do not connect to the boiler IN terminal by linking a 230V
feed from the wiring centre)
Optional UFH Motorised Valve: If a UFH motorised valve is
tted then remove the link between OR and GR.
Optional Heat/Cool Changeover: This connection allows heat/cool
changeover of all thermostats using a single external switch (installer supplied).
Switch: Open-Heating Closed-Cooling
Motorised Valves, Pump, Boiler & Stat Connections
This must be carefully removed
or replaced when removing or
replacing the wiring centre
cover, being careful to ensure
the correct orientation.
Ribbon Connection
Thermostat Connections
Thermostat connections are to power the thermostats only, there
is no switched live needed as this is done with a wireless signal.
Power can therefore be supplied to the thermostat locally from
any convenient power source if connecting to the wiring centre
from the thermostat is dicult. Battery powered RF thermostats
can also be used. These can be mixed with 230v RF thermostats or
as an alternative.
A Coordinator will be
needed with all RF
products.
After setting up the coordinator
will assign the wiring centre
number. This is because more than
1 wiring centre may be used on a
project. Pressing the network
button will illuminate the relevant
number. The example shown is for
wiring centre 1, if 1 & 2 are lit it
would be wiring centre 2.
3
4
5
9
6
8
1
Information Display
Thermostat Zones
Groups
1
2
NETWORK
BUTTON
7
www.salus-controls.com Technical Helpline 00000 000000
Option 2
Connect Cylinder
Thermostat to RF
Thermostat for wire
free connection. A
link will be needed
between IN & OUT
as shown by arrow.
IN
HW CYLINDER
THERMOSTAT
HW MOTORISED VALVE OVERHEAT STAT UFH PUMP BOILER ENABLE UFH MOTORISED VALVE
OUT IN OUT IN OUTBR EA N OR GR BR EA N OR GRLNE
ZONE 1 ZONE 2 ZONE 3 ZONE 4
SLNL SLNL SLNL SLNL SLNL
HW TIMER CONNECTION
THERMOSTAT CONNECTIONS 230V AC
230V AC
Sensor Terminals
Can be used for external AIR, Floor sensor
when congured as thermostat. Can also
be used for cylinder thermostat when
connected for HW.
OPTONAL HOT
WATER
MOTORISED
VALVE
OPTONAL UPH
MOTORISED
VALVE REMOVE
LINK IF USED
Option 1
Connect Cylinder
Thermostat to
wiring centre
IN
HW CYLINDER
THERMOSTAT
HW MOTORISED VALVE OVERHEAT STAT UFH PUMP BOILER ENABLE UFH MOTORISED VALVE
OUT IN OUT IN OUTBR EA N OR GR BR EA N OR GRLNE
ZONE 1 ZONE 2 ZONE 3 ZONE 4
SLNL SLNL SLNL SLNL SLNL
HW TIMER CONNECTION
THERMOSTAT CONNECTIONS 230V AC
230V AC
OPTONAL HOT
WATER
MOTORISED
VALVE
OPTONAL UPH
MOTORISED
VALVE REMOVE
LINK IF USED
Hot Water Connections
iT600 Wiring Centre KL10RF 004_Layout 1 05/06/2014 15:24 Page 2