Wiring centre extension for KL08RF
Model: KL04RF
Wiring Centre Description
1. Serial Connector
2. Power Supply
3. Connection diode
4. Power supply diode
5. Work status indication of each zone
6. Output terminals for actuators
2
Manual
DISTRIBUTOR OF SALUS CONTROLS:
QL CONTROLS Sp. z o.o., Sp. k.
Rolna 4,
43-262 Kobielice,
Poland
Importer:
SALUS Controls plc
Salus House, Dodworth Business Park
Whinby Road, Barnsley S75 3SP,
United Kingdom
www.salus-controls.eu
SALUS Controls is a member of the Computime Group.
Maintaining a policy of continuous product development SALUS Controls plc reserve the right
to change specification, design and materials of products listed in this brochure without prior notice.
1
IX 2018
3 4
KL04RF
Introduction 1. Serial connector
The KL04RF module is an extension to the KL08RF wiring centre for an additional 4 heating zones. Works
only in combination with KL08RF wiring centre and increases its functionality up to 12 individual heating
zones.
It is used for communication between KL08RF wiring centre and KL04RF extension module. Combined
set increases support up to 12 zones.
Product Compliance
This product complies with the essential requirements and other relevant provisions of the following
EU Directives: EMC 2014/30/EU, Low Voltage Directive LVD 2014/35/EU, Radio directive 2014/53/EU
and RoHS directive 2011/65/EU. The full text of the EU Declaration of Conformity is available at the
following internet address: www.saluslegal.com
Safety Informations
Use in accordance with national and EU regulations. Device is intended for indoor use only in dry
conditions. Product for indoor use only. Installation must be carried out by a qualied person in
accordance to national and EU regulations.
Before attempting to setup and install, make sure that KL04RF is not connected to any power source.
Installation must be carried out by a qualied person. Incorrect installation may cause damage to the
wiring centre. The KL04RF should not be installed in areas where it may be exposed to water or damp
conditions.
Technical Information
Power Supply 230 V AC
Max load 3 A
Outputs Thermoelectric actuator 230V AC
Dimensions [mm] 163 x 85 x 67
2. Power supply
L
N
230 V AC
5
6
9
Power supply for wiring centre is 230V ~, 50Hz.
Features of the installation:
• two-wire, with PE protective conductor,
• made in accordance with applicable regulations.
9
11 12
10
11 12
10

3. Connection diode
INSTALLATION
If KL04RF module is properly connected to the KL08RF wiring centre, connection diode will
light solid red.
4. Power supply diode
After connecting the KL04RF module to the power supply, Power led diode will light solid red.
5. Work status indication of each zone
Green led diode lights up when the heating demand signal is being transmitted from the thermostat
to the given zone (with NC actuators connected).
6. Output terminals for actuators
Wires of the thermoelectric actuators should be plugged into the self-locking connectors in the
appropriate zones. You can connect 3 actuators directly to one zone. The current load of one zone is
adapted to operate with up to 6 thermoelectric actuators with a power of 2 Watts. If there is a need to
connect more than 6 actuators please use an additional relay to relieve the output of the zone.
9
11 12
10
Note: On the actuator contacts,
there is voltage 230 V AC during
their work.
1
Remove the top cover of the KL04RF. Connect the thermoelectric actuators wires.
2
When mounting on a DIN rail, open the hooks on the back of the housing.
3
KL04RF power supply
Mount the back side of the housing to the wall.
12 mm
110 mm
(min. 2x1,0 mm2 230 V
max. 2x1,5mm2 230 V)
Remove the appropriate piece
of insulation from the wires.
5
6
Connect KL08RF and KL04RF using serial connector.
7
The operation was explained on the example
of T30NC actuators.
4
Make sure that all the wires are properly connected, mount top cover and power up the wiring
centre - “Power” and “Connection” re d LED diodes will light up indicating the correct connection
with the KL08RF wiring centre.
Thread the power supply wires through and connect them to the “L” and “N” terminals.