Salus FC600-M Instruction Manual

M
L
FC600
+
AIR
+
AIR
+
L
Introduction
Terminals description
Electrical diagram
DIN rail mounting
Display description and button functions
Product Compliance
Control module for FC600 thermostat Model: FC600-M 0-10V
Safety Information
Principle of operation
The FC600-M 0-10V module is dedicated to fan coils or trench heaters con­trolled by 0 ... 10V signal. It is a supplement to the main thermostat SALUS FC600. The module smoothly adjust fan speed via controling 0V...10V voltage. In addition, device can control two electric actuators (heating and cooling valve).
This product complies with essential requirements of the European Parliament Directive And Of The Council 2012/19 / EU of 4 July 2012 on waste electrical and electronic equipment (WEEE).
230V AC
2-PIPE SYSTEM
4-PIPE SYSTEM
OR
Power supply unit (PSU)
230V AC / 24V DC
1. Double-digit, 7-segment LED display
- displays parameters: F1, F1, F3, t and voltage and time values
2. Entering the menu, selecting the parameter, increasing the value
3. Conrmation of parameter selection, reduce the value
Use in accordance with national and local regulations of the country and in EU territory.
Indoor use only. Keep your equipment completely dry.
The installation must be carried out by a qualied person in accordance with the rules of the country and in the EU.
Before install, repair, maintenance or during any connection work disconnect power supply from the module and make sure the terminals and wires are free of voltage.
The electrical installation where module works should be secured with a fuse, specially selected to the applied loads.
The device can not be used with the damaged case.
Under no circumstances dont’t modify the module construction.
Do not allow access to the module to people who didn’t read this manual.
Do not install the device under voltage.
A short circuit at the output may damage the unit.
It is forbidden to operate a defective device or repaired by unauthorized service.
For module covering there is a special installation enclosure for the installation of electrical equipment. This enclosure should prevent user before access to the module wiring terminals. The module is designed to be mounted on a standard 35mm DIN rail. Before sliding the module . onto the DIN rail , slide the hook using the at sc rewdriver. When module is mounted on the rail, place the hooks at the original position. Make sure that module is mounted solidly and that it can not be removed from the rail without a tool.
NOTE: The connection wires should be protected against tearing, loosening, or built up in such a way that they can not be exposed to mechanical stress.
The module recognizes input signals from SALUS FC600 for three dierent voltage fan levels and accordingly sets the 0V...10V output voltage.
Voltage values for each levels and time of voltage incrase on output are settable by buttons and displayed on LCD. Settings are saved to the device memory. The module smoothly changes the voltage value at startup and during switching between fan speed mode.
Additionally this module recognizes the input signals for the heating valve and a cooling valve. Accordingly which signal will be received, module will send +24V voltage at the output for the heating/cooling valve.
Terminal
Name
Function
Module power supply 24V DC
Heating valve control output
Cooling valve control output
Power supply and fan control 24V DC
F1
Fan Speed control (Low level) - 230V AC input
F2
Fan Speed control (Medium level) - 230V AC input
F3
Fan Speed control (High level) - 230V AC input
V1
4 pipe: 230V AC control input - heating valve
2 pipe: 230V AC control input - heating / cooling valve
V2
4 pipe: 230V AC control input - cooling valve
2 pipe: N/A
N
Neutral
1
1
2
3
2
3
1
3
2
Instructions Manual
www.salus-controls.eu
SALUS Controls is a member of the Computime Group
Maintaining a policy of continuous product development SALUS Controls plc reserve the right to change specification, design and materials of products listed in this brochure without prior notice.
Issue Date: VII 2017
Distributor of SALUS Controls:
QL CONTROLS Sp. z o.o., Sp. k. Rolna 4 43-262 Kobielice, Poland salus@salus-controls.pl
NOTE: Before opening the casing disconnect the power supply from the terminals of FC600-M 0-10V module and FC600 controller.
NOTE: In the module should be used porcelain, slow blow 5x20 mm fuses with nominal burnout current of 8A / 230V.
Display will ashes voltage value for the selected program. Set the target value
by using button or .
On display will ashes time value.
Set the target value using
button or .
The voltage threshold settings are limited by the module:
Time of voltage increase at the output when module starts-up and switches voltage tresholds is expressed by the parameter t. This parameter is limited to the range from 0 to 50 s.
The module provides a smooth voltage increase at the output for thresholds depending on t parameter, according to the following characteristic.
A fuse is located inside the device casing. It protects module and the devices connected to it.
To open the casing of the module, you need to pry all the hooks (with a at screwdriver) and then carefully remove its upper part.
Using a at screwdriver, pry the fuse holder, replace the fuse, put the holder back in place and then snap the upper housing of the module.
The total voltage value for the F1-F3 thresholds is limited to 0 ... 10V range.
Setting voltage thresholds for fan speed Replacing the fuseSetting the increase/decrease time of the output
voltage
1
1
2
3
3
4
4
2
Press button to enter menu
Press button
to enter menu.
Press button to conrm your option.
Press button to conrm your option.
Wait 8 seconds
- the module will save settings.
Wait 8 seconds
- the module will save settings.
After saving device
will automatically
return to the menu.
After saving device
will automatically
return to the menu.
After 15 seconds
inactivity, the module
will go into sleep
mode.
After 15 seconds
inactivity, the module
will go into sleep
mode.
Using button select the appropriate parameter to set:
Select the t parameter by using button.
F1 - for the rst voltage threshold F2 - for the second voltage threshold F3 - for the third voltage threshold
NOTE: Module starts to supply voltage at the output when any threshold
is selected. The current value change causes a fan speed change - this allows you to check its operation and select adequate speed.
F1 - range from 0V to setpoint in F2 F2 - range from the setpoint in F1 to the setpoint in F3 F3 - range from setpoint in F2 to 10V
5
5
6
6
7
7
0V
50
t
10V
1
s
s
{
{
{
F1
F2
F3
SELECT
SELECT
SET
SELECT
SET
max.
min.
5x20
FUSE
0V
50
t
10V
1
s
s
{
{
{
F1
F2
F3
SELECT
SELECT
SET
F1 F2 F3 t
SELECT
SET
SELECT
SET
SELECT
SET
F1 F2 F3 t
0,1V
MENU
MENU
ZAPIS
8s
max.
min.
5x20
FUSE
Product Specication
Power supply 24V DC
Max current consumption 8A
Input voltage signals 230V AC
Output signals:
-
-
- fan
1(1)A, 24V DC 1(1)A, 24V DC 6,5(6,5)A, 24V DC
Fan control 0…10V
Mounting type DIN rail 35mm
Protection degree IP20 (build over)
Operating temperature from -10°C to 40°C
Storage temperature from -10°C to 65°C
Relative humidity
5-85% without steam condensation
Display
Double-digit, 7-segment LED display
Wires gauge 0,5 - 2,5 mm
2
Lenght of uninsulated wire 7 mm
Weight 60 g
Standards
PN-EN 60730-2-1 PN-EN 60730-1
Protection class II
Overvoltage class II
Pollution degree 2
Dimensions [mm] 65 x 90 x 52
65 mm
48,5 mm
45 mm
Loading...