Salus EP110 Installation Manual

Page 1
Model: EP110
Single channel programmable controller
Installation Manual
Page 2
Contents
Product Compliance ................................................................................................. 3
Safety Information ...................................................................................................... 3
Box content .................................................................................................................... 3
Introduction ................................................................................................................... 4
Features ............................................................................................................................. 4
Installation ....................................................................................................................... 5
Button functions and LCD icons ........................................................................ 7
Operations ....................................................................................................................... 8
Functions ......................................................................................................................... 14
Factory Reset ................................................................................................................. 16
Technical Info ................................................................................................................ 17
Warranty ........................................................................................................................... 18
Page 3
Product compliance
Installation
Jumper Settings
Input: 230V, 50Hz Output: 3A/ switch terminal
1
EP110 Volt Free application only
EP110 - 230V Application Only
Note: Please remove red link wire for this application.
Terminal Description Backplate
N Mains Neutral
L Mains Live
1 Not Used
2 Not Used
3 Volt Free Connection
4 Volt Free Connection
Earth Parking (no electrical connection)
NL1234
NL123456
Changes to the jumpers settings should only be made by the Engineer carrying out the installation or other qualified person. The installer should select the jumper positions required if changes need to be made to the factory default settings. These jumpers are found on the rear of the controller.
EP110/ EP210/ EP310 Switching Bridges
Switch
Program
5-2 days programme or
24h programme
Fully pumped system(P*)
or gravity-fed hot water
system(G*)
System
Feature EP110/310 Settings
5-2
24H
24H
5-2
NA
NA
P
G
EP210 Settings
EP110/EP310 EP210
This product complies with the essential requirements and other relevant provisions of the following EU Directives: 2014/30/EU, 2014/35/EU and 2011/65/EU. Please check www.saluslegal.com for the full information.
Safety Information
Use in accordance with the EU and national regulations. For indoor use only. Keep your device completely dry. This product must be installed by a competent person and in accordance with all the EU and national regulations.
Always isolate the AC Mains supply before installing or working on any components that require 230 VAC 50Hz supply.
Box content
The box includes the EP110 controller, 2X screws and plugs and the Quick Guide installation manual.
EP110 Controller 2x screws and plugs
Model: EP110/EP210/EP310
Installer Manual-Quick Guide
Quick Guide Installation
EP110 Installation Manual 03
Page 4
Introduction
A programmable heating controller is used to switch the heating system and/or hot water in your home as needed. It works by controlling the heating boiler according to a series of programmed settings that take effect at different times of the day. The controller can be set up to 3 programs per day, with complementary Boost actions and can operate in five different modes. Three different sets of time can be set for each day of week, resulting in a total of 21 settings applicable to the device.
When connected to a system with a non-programmable (digital) thermostat, it can switch off/on the boiler and control the heating and/or hot water in your system in a programmed manner. You can use the controller in a fully pumped and controlled system, where heating and hot water can be operated independently or in gravity-fed water system, where the central heating cannot be operated without hot water.
The heating system will not work if the programmer has switched it off. The controller does not detect the temperature or adjust the heating mode in your house, it just tells the boiler when to switch Off/On depending on our individual time settings.
With the controller you don’t have to worry about switching On/Off your system manually. All you need to do it so set up the schedules that fit your needs. The controller can be used on your system to control either the central heating OR the hot water.
Features
Single Channel Programmer for Central Heater or Hot Water
12 or 24 hour clock format
5+2 or 24 h individual program with 3 settings per day
Boost function
Holiday function
Advance function
Memory backup
Page 5
Installation
NL123456
NL123456
Wiring and terminal description
230 VAC
Terminal Description Backplate
N Mains Neutral
L Mains Live
1 NC (Output)
2 Not Used
NL1234
3 Switch Live (Output)
4 230V Common (via Link)
Earth Parking (no electrical connection)
Volt free application. Note: Please remove red link wire (like the one in the picture above) for this application.
Volt Free
Terminal Description Backplate
N Mains Neutral
L Mains Live
1 Not Used
2 Not Used
3 Volt Free Connection
4 Volt Free Connection
Earth Parking (no electrical connection)
NL1234
EP110 Installation Manual 05
Page 6
Wall mounting
Fix the backplate to the wall.
Align the front housing
at the top edge.
Jumper settings
The jumpers are found on the rear of your controller and can be used to change the settings for the program type or internal backup memory battery. If you want to change the position of your jumpers, please note that you will need to reset your device. The default position for the jumpers set a 5+2 program type and keep the internal backup battery off.
EP110 Switching Bridges
Fit the front housing. Press lightly.
Switch Feature Setting Default
Program 5-2 days program or
Memory Backup Disable/enable the
Note: Changes to the jumper settings should only be made by the engineer carrying out the installation or another qualified person. The installer should select the jumper positions required if changes need to be made to the factory default settings. These jumpers are found on the rear of the controller.
24h program
internal backup
battery
5-2 24H 5-2 days program
OFF ON Internal backup
battery disabled
Page 7
Button functions and LCD icons
MODE
<
<
SELECT SET
Key Function
Mode Press to select ON/ONCE/AUTO/
ADV/OFF.
+1Hr Press to enter/cancel Boost override
function by setting Boost hours.
Select Press to select the setting of clock/
date/week day, etc.
Set Press to confirm the setting.
+Hr
Up arrow Press to increase clock/day, press and
hold to enter fast advance.
Down arrow Press to decrease clock/day, press
and hold to enter fast advance. Press to activate backlight.
Hardware reset
Press and hold button for 3 seconds to activate Holiday mode.
Select + Set Press and hold buttons to enter clock
setting mode.
1
2
3
4
1
Showing when relay is On
2
Boost hours
3
Daylight Saving Time On/Off
4
Program number
5
ON Mode Active (controller runs continually)
5 6
12
11
10
7 8 9
7
Auto Mode Active (controller runs in Auto)
ADV Mode Active
8
(controller runs in advance override)
9
OFF Mode Active (controller is off)
10
AM/PM
Holiday mode on
11
6
ONCE Mode Active (controller runs for 1 period a day)
Days of the week
12
EP110 Installation Manual 07
Page 8
Operations
Initial power up
After power up or after RESET is pressed, the programmer is reset to factory default settings. During system reset, all LCD icons and segments are turned on for 2 seconds and all keys are blocked. After 2 seconds and all keys are released, the programmer is initialized. First the software version is shown and after that the typical reset display is shown. The time should be 12:00am.
MODE
+Hr
<
<
SELECT SET
MODE
<
Default settings
Function Status after Reset
Operation Mode Normal mode
Clock 12:00 AM
AM/PM indicator AM
<
SELECT SET
MODE
+Hr
<
<
SELECT SET
+Hr
Date January 1, 2016
Daylight Saving Time(DST) On
Program Factory default 5+2
Program Number indicator Off
SET indicator Off
PROG indicator Off
Mode indicator(s) “Off“
Output Relay Off
CH/HW indicator(s) Off
Page 9
Setting time and date
The first thing you will have to do is to set the time and date on your controller. First you will need to set up the time and then the date. To enter clock setting mode, press and hold Select and Set buttons for 3 seconds. Please follow the instructions below.
MODE
<
<
SELECT SET
3 sec
Press and hold the
indicated buttons together for 3 sec.
MODE
<
<
SELECT SET
Press Up or Down to set
the hour. Press Select
to confirm.
+Hr
MODE
<
<
SELECT SET
Choose your clock format
Press Up/Down arrow for
12/24 hr format.
+Hr
MODE
<
<
SELECT SET
Press Up or Down to set
the minutes. Press Select
to confirm.
+Hr
MODE
24
<
<
SELECT SET
Choose your clock format Press Up/Down arrow for
12/24 hr format.
+Hr
MODE
<
<
SELECT SET
Press Up or Down to
set the year.
Press Select to confirm.
+Hr
+Hr
MODE
<
<
SELECT SET
+Hr
Press Up or Down to set the
month. Press Select
to confirm.
When Daylight saving time is enabled, the clock will automatically change from Greenwich Mean Time (GMT) to British Summer Time (BST) on the last Sunday in March. The clock will automatically change back to GMT on the last Sunday in October.
MODE
<
<
SELECT SET
+Hr
Press Up or Down to set the
day. Press Select to confirm.
MODE
<
<
SELECT SET
+Hr
Press Up or Down to set the
Daylight Saving Time On or Off.
Press Set to confirm.
EP110 Installation Manual 09
Page 10
Operating Modes
EP110 can operate in 5 different modes, described in the table below. EP110 can be set to control either the boiler OR the hot water. You can choose on which one of the channels you connect the controller. To access operating modes, please press Mode key.
Operation Mode Function
ON Continuously on
ONCE On for 1 period a day, from Program 1 ON to Program 3 OFF
AUTO Automatic program control
ADV When device is in Auto or Once mode, press the MODE
button for 3 sec for selecting Advance (ADV). This will move the unit into the next program. When the ADV function ends the device will return to normal program.
OFF Continuously off
For activating the functions described above, press the MODE button. The operating mode is cycled in the below sequence:
ON Mode
MODE
<
ONCE Mode
MODE
<
<
<
SELECT SET
SELECT SET
Pressing the Mode key once activates the ON Mode. In ON mode, the
+Hr
controller gives the boiler the ON command, so the heating or the hot water will run continuously.
The circle icon will be rotating in a sequence when the relay output is ON.
+Hr
Pressing the Mode key twice activate the ONCE Mode. In ONCE mode, the controller gives the boiler the command to run only for one period per day (from program 1 ON to program 3 OFF)
Page 11
ON Mode
MODE
OFF Mode
Pressing the Mode key 3 times activates the AUTO. In AUTO mode, the
+Hr
controller gives the boiler the ON/OFF command depending on your schedule.
<
<
SELECT SET
MODE
+Hr
Pressing the Mode key 4 times activates the OFF Mode. In OFF mode, the controller gives the boiler the OFF command, so the heating or the hot water will be turned off.
<
<
SELECT SET
ADV Mode
Note: In ONCE or AUTO mode, by long pressing the MODE button, the controller will switch automatically to ADV. You can cancel the ADV by long pressing the MODE key. The device will then return to ONCE or AUTO mode. You can’t select ADV by pressing Mode key.
When in Auto mode selecting ADV, the controller will simply toggle the current auto setting (ON or OFF). For example, if the current program is
MODE
+Hr
set as:
08:00 ON 09:00 OFF 10:00 ON 11:00 OFF
<
<
SELECT SET
Selecting ADV between 8:00 and 8:59 will change the output to OFF, from 9:00 onwards back to AUTO (which is also OFF). Selecting ADV between 9:00 and 09:59 will change the output to ON, from 10:00 onwards back to AUTO (which is also ON). If the ADV puts the relay ON then the boost
Long press Mode while
in Auto or Once
would apply immediately at the next OFF change, if the ADV puts the relay OFF then the boost would apply immediately and turn the relay ON.
08:00 OFF 10:00 ON 12:00 OFF 14:00 ON
If ADV occurs at 08:30 and the relay is ON from 08:30 to 12:00. During this period, if at 08:45 +1Hr (Boost) is pressed, the relay will be ON from 08:30 to 12:00. Boost is applied immediately ie. from 08:45 to 09:45 at the next change, ie. 12:00. If ADV occurred at 10:30 the relay will be ON from 10:00, OFF from 10:30 (ADV) to 14:00 if no +1Hr Override. During ADV, if at 10:45 +1Hr (Boost) is pressed, the relay will go ON again at 10:45 (boost starts), OFF at 11:45 (Boost ends) until ends at 14:00, then ON again at 14:00.
EP110 Installation Manual 11
Page 12
Programming the EP110
2 types of programs can be set:
5+2 (Mo to Fri same and Sat, Sun same)
Different programs for each 24h. There are 3 different time sets for each day.
5-2 Days Program Individual Days Program
Weekdays
3 sets of time/channel
Weekends
3 sets of time/channel
Total: 6 settings/week
Setting the 5+2 program
MODE
<
<
SELECT SET
Press Set to start programming.
+Hr
MODE
<
<
SELECT SET
Press Up or Down to select
weekdays or weekends.
Press Select to confirm.
1 Day
3 sets of time/channel
Total: 21 settings/week
+Hr
MODE
<
<
SELECT SET
Press Up or Down to
set start time for prog 1.
Press Select to confirm.
+Hr
MODE
<
<
SELECT SET
Press Up or Down to set
the minutes. Press Select to
confirm.
MODE
<
<
SELECT SET
Press Up or Down to
set start time for prog 2.
Press Select to confirm.
+Hr
MODE
<
<
SELECT SET
Press Up or Down to set
end time for prog 1. Press
Select to confirm.
+Hr
+Hr
MODE
<
<
SELECT SET
+Hr
Press Up or Down to set
the minutes. Press Select to
confirm.
Once you have finished setting the start/end time for the first program, the device will jump into the second program, and then into third and
2
afterwards into Sat-Sun. Please follow the same steps for each of the 3 programs. Press SET at any time to confirm the setting and return for program set selection.
Page 13
Setting dierent programs for each 24h
Note: Don’t forget to move the jumpers to 24h in order to have the individual program active. After that please follow the same instructions as for the 5-2 days program.
MODE
<
<
SELECT SET
Press Set to start
MODE
programming.
<
<
SELECT SET
Press Up or Down to set
the minutes. Press Select
to confirm.
+Hr
MODE
<
<
SELECT SET
Monday will flash. Press Select
to confirm.
+Hr
MODE
<
<
SELECT SET
Press Up or Down to set start time for prog 1. Press
+Hr
Select to confirm.
+Hr
MODE
<
<
SELECT SET
Press Up or Down to set end time for prog 1. Press
Select to confirm.
+Hr
MODE
<
<
SELECT SET
+Hr
Press Up or Down to set the
minutes. Press Select
to confirm.
MODE
<
<
SELECT SET
+Hr
2
Press Up or Down to
set start time for prog 2.
Press Select to confirm.
Once you have finished setting the start/end time for the first program, the device will jump into the second program, and then into third and afterwards into next day. Please follow the same steps for each of the 3 programs. Press SET at any time to confirm the setting and return for program set selection.
EP110 Installation Manual 13
Page 14
Functions
Temporary Override
Boost Override (+1Hr override)
Boost Override (+1Hr override) is available in ONCE/AUTO/OFF modes. Boost mode can be activated even in ADV mode. When boost mode is activated, ADV is canceled. Press +1Hr at current mode to activate the Boost Override (+1Hr override) setting mode. Boost mode increases the time of the active program by 1-9 hours. The new setting hour “+x” (x=last boost hour+1 hour) is displayed. Subsequent press of +1Hr will increase the duration by 1 hour. Maximum duration is 9 hours. If the number rolls back to blank, this will disable the Boost Override.
MODE
<
<
Press +1Hr to enter
Boost override.
SELECT SET
+Hr
MODE
<
<
SELECT SET
The number of boost hours
will be displayed.
+Hr
MODE
<
<
SELECT SET
+Hr
To exit boost override, press
mode button until number
+x dissapears.
ADV Override
ADV only works in AUTO or ONCE mode. During ADV, press MODE once to cancel ADV and go back to AUTO /ONCE mode after LCD backlight is turned off. +1Hr override and ADV cannot co-exist in same channel. During ADV mode, when +1Hr is pressed, override mode will cancel ADV mode then change to Boost mode. If +1Hr override (Boost) is running, then ADV is selected, ADV will be activated and the previous +1Hr override will be cancelled.
MODE
<
<
SELECT SET
3 sec 1 sec
Long press Mode while in
Auto or Once to enter ADV
override Mode
+Hr
MODE
<
<
SELECT SET
+Hr
Short press Mode while in ADV to
exit mode back to auto or Once
Page 15
Holiday Override
During the period of holiday override, relay should be always Off. Press and hold at current mode for 3 seconds to activate the Holiday Override setting mode. The plane icon will be displayed on the LCD and the user’s only option will be to set the number of holiday days (up to 31). To exit Holiday Override and turn On the relay, long press the key.
Enter Holiday Mode
3 sec
Exit Holiday Mode
MODE
<
<
Press for 3 seconds.
3 sec
MODE
<
<
SELECT SET
SELECT SET
+Hr
MODE
<
<
SELECT SET
+Hr
Press Up/Down keys
to select days.
+Hr
MODE
<
<
SELECT SET
+Hr
Press for 3 seconds.
LCD Backlight
If AC is powered, LCD backlight is activated when or any key is pressed. The backlight will be turned off in 15 seconds after all keys are released.
Controller in current mode.
EP110 Installation Manual 15
Page 16
Factory Reset
If you want to return to the factory settings please press the Reset button once (use a pin for this action).
MODE
+Hr
<
<
SELECT SET
MODE
<
Press reset button. LCD will turn OFF.
MODE
+Hr
<
<
SELECT SET
MODE
<
<
<
+Hr
SELECT SET
+Hr
SELECT SET
All icons will be displayed. Software version.
MODE
<
<
Normal Mode.
+Hr
SELECT SET
Page 17
Technical Info
Product Specication
Model: EP110 Type: Surface Mounted Wired Single Channel Programmable Timer Memory Backup Lithium battery (CR2032 x1pc) Power control Rating 230V/50Hz/3(1)A Relay SPDT Protection Rating: IP 30 Environment Operating Temperature/
0°C ~ 50°C, 10% – 90% non-condensing
Humidity: Storage Temperature/
-20°C~- 60°C, 10% – 90% non-condensing
Humidity Programs Program 5-2 or 24hr individual program (selectable by jumper),
3 settings/day, with holiday override. Boost Override Yes, max 9 hours(selectable by software) Holiday Override Yes, max 31 days (selectable by software) Clock Clock Format 12 or 24 hour (selectable by software) Clock Accuracy +/-1 min/month Daylight Saving Time (DST) Yes, Clock automatically adjusted if DST is enabled.
EP110 Installation Manual 17
Page 18
Warranty
SALUS Controls warrants that this product will be free from any defect in materials or workmanship, and shall perform in accordance with its specification, for a period of two years from the date of installation. SALUS Controls sole liability for breach of this warranty will be (at its option) to repair or replace the defective product.
Customer Name: ..................................................................................................................................................................
Customer Address: .............................................................................................................................................................
................................................................................................................ Post Code: ...............................................................
Tel No: ................................................................... Email: ......................................................................................................
Company Name: ...................................................................................................................................................................
Tel No: .................................................................. Email: ........................................................................................................
Installation Date: ...................................................................................................................................................................
Installer Name: .......................................................................................................................................................................
Installer Signature: ...............................................................................................................................................................
Page 19
SALUS Controls PLC SALUS House
Dodworth Business Park South, Whinby Road, Dodworth, Barnsley S75 3SP, UK.