Recommendations for Installation of Unit Functional
Blocks 10
Wiring Diagram 11
Air ow 11
Smarty 2X/3X V connection possibilities 11
Technical data 12
Filter 12
Air ow Diagrams 13
Smarty 2X V dimensions 14
Smarty 3X V dimensions 15
Mounting 16
Mounting on wall 16
Mounting on Legs 16
Connection of the unit to electric network 17
Drainage 18
Control Board and its Functions 18
Descriptions of Unit Functions 19
1.1 System modes 19
1.2 System Control 19
1.3 System status 20
1.4 Indications of Functions, Alarms and Warnings 20
1.5 Setting Date and Time 20
1.6 Weekly Schedule 20
1.7 Holiday Schedule 20
1.8 Winter/Summer Mode 20
1.9 “BOOST” Function 21
1.10 Protection against Dryness 21
1.11 Night Cooling Function (not available in Smarty
2X/3X V 1.1, 1.2 versions) 21
1.12 Air Filter Timer 21
1.13 Display and Cancellation of Alarms and Warnings
21
1.14 Event Log (History) 22
1.15 System Versions and Running Time 22
1.16 Air Flow Adjustment 22
1.17 PID Controller Adjustment 23
1.18 Manual Control of Components 23
1.19 System Monitoring 23
1.20 Stand-By Mode Blocking 23
1.21 Supply Air Temperature Control and Compensati-
on 23
1.22 Supply Air Temperature Limits 23
1.23 Mode from an External System Contactor 23
1.24 Fan Speeds from an External System Contactor
24
1.25 Filter Protections 24
1.26 Fire Protection against External System Contac-
tor 24
1.27 CO2 Reduction Function (only using additional
extract air CO2 sensors) 24
1.28 Changing Passwords 24
1.29 Restoring Factory Defaults 24
1.30 Fan Control 24
1.31 Damper Control 25
1.32 Heat Exchanger Control 25
1.33 Heaters 26
1.34 Digital Input Conguration 26
1.35 Sensor Conguration 26
1.36 Communications Line Conguration 26
Principle mounting diagram Smarty 2X/3X V 1.1 28
Principle mounting diagram Smarty 2X/3X V 1.2 29
Principle mounting diagram Smarty 2X/3X V 1.3 30
The principal connection scheme of internal and external
components 31
The principal connection scheme of internal and external
components 32
The principal connection scheme of internal and external
components 33
The principal connection scheme of internal and external
components 34
The principal connection scheme of internal and external
components 35
The principal connection scheme of internal and external
components 36
The principal connection scheme of internal and external
components 37
The principal connection scheme of internal and external
components 38
System protection 39
System protection 39
Recommendations before the start of the unit (before
the nal user) 39
Possible faults and troubleshooting 39
Sensors and their technical information 39
Fire Protection Signal Input (Fire protection input
(NC)) 44
Outdoor Air Pre-Heater 44
Pre-Heater Capacity by Regions 45
System mode ir Fan speed switch 45
Supply air CO2 or RH (input 0-10VDC) 45
Extract air CO2 or RH (input 0-10VDC) 46
Room CO
CO2 concentration according to Pettenkofer limit 47
transmitter installation recommendation 46
2
Smarty 2X/3X V 1.1 Version - Heater Control 47
Smarty 2X/3X V 1.2, 1.3 Versions - Heater Control 49
Connection of Supply and Extract Air Dampers 51
Connection of Remote Control Panel or ModBus 51
Operation and Alarm Indication (Smarty 2X/3X V 1.1)
51
Fire Place Connection (Smarty 2X/3X V 1.1) 52
2
www.salda.lt
LED indication 52
Smarty 2X V Accessories 53
Smarty 2X V Spare Parts 54
Smarty 3X V Accessories 55
Smarty 3X V Spare Parts 56
Warranty 57
Unit’s maintenance table 58
Stick the auxiliary label on the unit (on an easily accessible place) or on the
dashed place of a technical manual in order to keep the important information about the unit.
1 – Logo
2 – Internal usage code
3 – Brand name
4 – Technical data
5 – Units number
6 – Web address
STICK HERE
• All units are packed in the factory to withstand regular conditions of transportation.
• Upon unpacking, check the unit for any damages caused during transportation. It is forbidden to install damaged units!!!
• The package is only for protection purpose!
• While unloading and storing the units, use suitable lifting equipment to avoid damages and injuries. Do not lift units by holding on power supply
cables, connection boxes, air extract or exhaust anges. Avoid hits and shock overloads. Before installation units must be stored in a dry room with
the relative air humidity not exceeding 70% (at +20 °C) and with the average ambient temperature ranging between +5 °C and +30 °C. The place of
storage must be protected against dirt and water.
• The units must be transported to the storage or installation site using forklifts.
• The storage is not recommended for a period longer than one year. In case of storage longer than one year, before the installation it is necessary
to verify whether the bearings of fans and motor rotate easily (turn the impeller by hand) and if the electric circuit insulation is not damaged or the
moisture is accumulated.
8
0
0
m
m
Smarty 2X VSmarty 3X V
m
m
35
3
mm
5
2
6
485 mm
700 mm
2160 mm
755 mm
8
m
m
0
0
7
0
0
m
m
0 mm
0
7
700 mm
585 mm
585 mm
912 mm
1058 mm
700 mm
2120 mm
585 mm
4
Preparation for transportation
www.salda.lt
Smarty 2X VSmarty 3X V
Smarty 2X/3X V
1
2
3
4
Standard package (without optional accessories) includes:
1. Key - 1 pc.
2. Sealing tape FIX-PV 6x20
3. Suspension bracket - 1 pc.
4. Condensate outlet pipe G3/8 - 1 pc.
- Do not use the unit for purposes other than its’ intended.
- Do not disassemble or modify the unit in any way which may lead to mechanical failure or injury.
- Use special clothing and be careful while performing maintenance and repair jobs – the unit’s and its components’ edges may be sharp and cutting.
- Do not wear loose clothing that could be entangled in to operating unit.
- Do not place ngers or other foreign objects through inlet or exhaust guards or into connected duct. If a foreign object enters the unit, immediately
disconnect power source. Before removing object, make sure that any mechanical motion has stopped, the heater has cooled down and the restart is
not possible.
- Do not connect to any other power source than indicated on the model label.
- Do not place or operate unit on unsteady surfaces and mounting frames.
- Mount the unit rmly to ensure safe operating.
- Never use this unit in any explosive or aggressive elements containing environment.
- Do not use the unit if external connections are broken or damaged. If there are any defects, stop operating the unit and replace the damaged parts immediately. That can be performed only by qualied electrician.
- Do not use water or another liquid to clean electrical parts or connections.
- If you notice water on electrical parts or connections, stop operating the unit.
Smarty 2X/3X V are residential air handling unit with a high eciency (up to 90 %) counter ow heat exchanger. The unit provides ventilation in the
home and takes the heat from the exhausted air. AHU complies with ErP 2018 and Passivhaus requirements. The unit is operated by a separate
remote control panel or though separate MB-Gateway by PC. Remote control panel and MB-Gateway are optional and not included in standard package. Control functions depend on selected control board type: MiniMCB or MiniMCB basic.
Smarty 2X/3X V operates within the limits of the airow diagrams and is suitable for indoor operation only. Required ambient temperatures must be
from +5 oC to +40 oC. For the cold climate zones (air temperatures below -6 oC), integrated or optional pre-heater is required.
www.salda.lt
5
Smarty 2X/3X V
1
2
3
4
5
6
7
15
14
13
12
11
8
9
10
Smarty 2XV, 3XV are available in three versions:
Optional heating elements
*- only pre-heater or
Product name
Control board
Type
Heat recovery
Temperature
control
Bypass damper
(lter pollution
Pressure sensor
monitoring)
heater
Duct based
Integrated pre-
Smarty 2X V 1.1Mini MCBPremium+++-+-+
Smarty 2X V 1.2Mini MCB BasicAdvanced+++--+*
Smarty 2X V 1.3Mini MCB BasicBasic++---+*
Smarty 3X V 1.1Mini MCBPremium+++++-+
Smarty 3X V 1.2Mini MCB BasicAdvanced+++--+*
Smarty 3X V 1.3Mini MCB BasicBasic++---+*
Not suitable for swimming pools, saunas and other
similar facilities.
Smarty 2X VSmarty 3X V
8
1
2
3
4
5
6
7
9
10
11
12
13
14
15
1
2
3
4
5
6
7
Air Pre-
Heater
heater
Duct based
Air Heater
8
9
10
11
12
13
14
15
16
16
1. Flange 4 pcs.
2. Outdoor air temperature sensor (TL)
3. Outdoor air lter (G4/(F7 - optional)) and the EPP cover*
4. Extract air sensor (TA)**
5. Bypass damper (M1)**
6. Preheater (PE1)**
7. Extract air lter (G4) and the EPP cover*
10. Control board.
11. Supply air fan (PV)**
12. Exhaust air fan (IV)**
13. Galvanized steel casing
14. EPP casing
15. Heat exchanger
16. Condensate tube plugs
8. Supply air sensor
9.CE7/7 power supply cable - 3 m.
*Filter EPP cover only on Smarty 3X V.
** Depends on unit type.
• Unit is designed to operate only indoors.
• It is forbidden to use the unit in potentially explosive environment.
• Unit is designed to supply/extract only clean air (free of chemical compounds causing metal corrosion, of substances aggressive to zinc, plastic and
rubber, and of particles of solid, adhesive and bred materials).
Outdoor
- temperature min./max. [°C]
- humidity[%]90
-15 / +40**
-40 / +40***
-5/ +40*
Extract
- temperature min./max.*
- humidity[%]60
[°C]+15 / +40
* - Outdoor air temeperature without preheater (Salda Antifrost o)
** - with integrated preheater (Smarty 2X/3XV 1.1) or Smarty 2X/3XV 1.2/1.3 (Salda Antifrost on)
*** - with optional preheater on duct
Salda Antifrost uses dis-balancing of the air ow and it may cause negative pressure in premises.
6
www.salda.lt
Unplug unit from mains before opening the door (disconnect the power plug from the outlet or if there is a two-pole
automatic circuit breaker installed – disconnect it as well.
It is necessary to ensure that it won’t be turned on by third
parties) and wait until the full stop of the fans (for about 2
min.).
Smarty 2X VSmarty 3X V
Smarty 2X/3X V
Smarty 2X VSmarty 3X V
Remowing Smarty 2X V lters: key loosened and removable product
doors, removable lters. Uses G4 / (F7 - optional) lters.
Dirty lters increase air resistance, airow into the room.
Changing lters, lters reload timer control. Description
of remote control panel functions is provided in the remote
control panel technical documentation or on the website
www.salda.lt.
Allowed to operate the unit without lters!
Remowing Smarty 3X V lters: opening lter cover (pulling the strap),
It is advisable to change the lters every 3 - for 4 months,
or according to their testimony timer remote control.
• Maintenance should be performed only by experienced and trained sta.
• The fan should be inspected and cleaned at least once a year.
• Be sure the fan is disconnected from power source before performing any maintenance or repair.
• Observe sta safety regulations during maintenance and repair.
• The motor is of heavy duty ball bearing construction. The motor is completely sealed and requires no lubrication. Supplied air fan from X15, X2, X4.
Extract air fan from X16, X2, X4.
• Detach fan from the unit.
• Impeller should be specially checked for buil-up material or dirt which may cause an imbalance. Excessive imbalance can lead to accelerated wear
on motor bearings and vibration.
• Clean impeller and inside housing with mild detergent, water and damp, soft cloth.
• Do not use high pressure cleaner, abrasives, sharp instruments or caustic solvents that may scratch or damage housing and impeller.
• Do not plunge the motor into any uid while cleaning impeller.
www.salda.lt
7
Smarty 2X/3X V
• Make sure, that impeller ’s balance weights are not moved.
• Make sure the impeller is not hindered.
• Mount the fan back into the unit. Connect the fan to power supply source.
• If after maintenance the fan does not start or stop itself, contact the producer. Malfunction of the fan can be identied according to the pressure in the
system (when pressure switches are connected). When there is a folt in fans’ motor, any separate notice is shown on the control panel.
Be sure the unit is disconnected from power source
before performing any maintenance or repair.
- Remove the fan connectors from the control board. Supplied air fan from X15, X2, X4. Extract air fan from X16, X2, X4.
Note:
- X2, X4 are common for both fans.
- Reassembly shall be executed in the reverse order.
X2
Smarty 2X V
X15
X4
X16
Smarty 3X V
8
www.salda.lt
Smarty 2X/3X V
• Proceed to maintenance and repair after any rotation in the fan stopped.
• Clean the heat exchanger once a year.
• Firstly take out heat exchanger cassette carefully. Submerge it into a bath and wash with warm soapy water (do not use soda). Then rinse it with
weak hot water stream (too strong stream can fold the plates). Place back the heat exchanger only when it is completely dry.
Smarty 2X VSmarty 3X V
Bypass damper and pre-heater are mounted on one block. The pre-heater shall be disconnected by
removing X29 connector. The bypass damper shall be disconnected by removing X25 .
Smarty 2X VSmarty 3X V
X29
X25
www.salda.lt
9
Smarty 2X/3X V
- Unscrew the front bolt securing the control board holder to the unit casing.
- Withdraw the automation through the front part.
- Disconnect the connectors from the control board.
- The connectors are marked according to connection location. Thus during automation reassembly please observe the marking of the connection
location of connectors and controller. If the marking on the controller terminals is not visible follow the PCB information provided in this passport (see
miniMCB description: Fig. 2 and Fig. 3):
Smarty 2X VSmarty 3X V
• All the metering, control and execution units shall be mounted in freely accessible locations for maintenance, repairs or replacement.
• Prior to handover to the user, the pre-commissioning activities shall be performed to ensure proper operation of the automatic control system of the
air handling unit. Power plug socket shall be installed at a distance to ensure unstrained power cable of the unit. Standard length of the unit power
cable shall be: ~2.5 m long from the unit casing.
Prior to connecting the unit to the mains, the door shall be closed.
The installed plug socket shall be of at least the same nominal current as the unit nominal current, which is indicated in the unit rating plate.
Unit shall be connected to the mains through the current leakage relay (30mA).
After complete dismantling of the unit control automation and its reinstallation, when connecting the
automation connectors, it is necessary to check if the
connector conductors are not damaged or otherwise
broken.
• Install the control panel at the designed location.
• Connect the connection cable supplied with the remote control panel kit between the control panel and the HVAC unit. It is recommended to install
the remote control board separately from the power cables.
NOTE: If the cable is used together with other power cables, the remote control panel cable shall be shielded with grounded shielding armour.
NOTE: the remote control panel shall be connected and/or disconnected only after disconnecting power supply to HVAC unit.
10
www.salda.lt
Smarty 2X/3X V
Electrical equipment connection to the control board terminals. Control board connectors shall be of the following cross sectional area.
* Possibility to insert coupling of corresponding diameter
14
www.salda.lt
80 mm
810 mm
900,5 mm
Smarty 2X/3X V
Ø 160 mm
Ø 150 mm
110 mm
170 mm
252 mm
116 mm
110 mm
406 mm
599 mm
386 mm
Ø 150 mm/160 mm*
224 mm
G3/8
265 mm
113 mm
284 mm
G3/8
538 mm
* Possibility to insert coupling of corresponding diameter
www.salda.lt
15
Smarty 2X/3X V
40
mm
c
b
90
90
d
a
10
mm
10
mm
a
10
mm
b
c
14 mm
b
a
10
mm
10
mm
a
10
mm
b
b
a
10
mm
10
mm
• Installation should only be performed by qualied and trained sta.
• When connecting air ducts, consider the notices indicated on the casing of the unit.
• Before connecting to the air duct system, the connection openings of ventilation unit should be closed.
• When connecting the ducts , you should pay attention to the air ow direction indicated on the device housing.
• Do not connect the bends close to connection anges of the unit. The minimum distance of the straight air duct between the unit and the rst branch of
the air duct in the supply air duct must be 1xD, in air exhaust duct 3xD, where D is diameter of the air duct.
• It is recommended to use the accessories-holders. This will reduce vibration transmitted by the unit to the air duct system and environment.
• Enough space must be left for opening of the maintenance door and lter covers.
• If the installed ventilation unit is adherent to the wall, it may transmit noise vibrations to the premises. Though the level of noise caused by the fans is
admissible, it is recommended to mount the unit at the distance of 400 mm from the nearest wall. If it is not possible, the mounting of the unit is recommended on the wall of the room where the level of noise is not important.
• Ducts are connected to the unit in such way that they could be easily disassembled and the heater could be removed from the unit when performing
service or repair works.
Smarty 2X VSmarty 3X V
Unit mounting on wall:
a) To reduce the vibration stick the insulating tape on the unit‘s casing
side which touches the wall before mounting the unit on the wall.
b) The unit has to be mounted on the mounting brackets.
c) AHU mounting drawing.
Unit mounting on wall:
a) To reduce the vibration stick the insulating tape on the unit‘s casing
side which touches the wall before mounting the unit on the wall.
b) The unit has to be mounted on the mounting brackets.
c) AHU mounting drawing.
d) After the unit is mounted two wall bracket tabs has to be folded to 90o
angle by pliers to avoid the accident fall of the unit.
Legs are optional and not included in standard package.
16
www.salda.lt
400 mm
Smarty 2X/3X V
L
2xL
• Supply voltage to the unit must be connected by a qualied specialist following the manufacturer’s instructions and eective safety instructions.
• The unit’s power network voltage must correspond to electrotechnical parameters of the unit indicated in the technical decal.
• The unit’s voltage, power and other technical parameters are provided in the unit’s technical decal (on the unit casing). The unit must be connected
to the voltage plug socket of the grounded power network in compliance with the eective requirements.
• The unit must be earthed according to the rules on installing electrical equipment.
• It is prohibited to use extension wires (cables) and power network plug socket distribution devices.
• Prior to carrying out any ventilation unit installation and connection activities (until its hand-over to the customer), the unit must be disconnected from
the power network.
• After installation of the ventilation unit, the power network plug socket must be accessible at any time and disconnection from the power network is
performed through the two-pole circuit breaker (by disconnecting phase pole and neutral).
• The unit must be thoroughly checked against damages (execution, control, measurement nodes) during transportation before it is connected to the
power network.
• The power cable can be replaced only by a qualied specialist upon the evaluation of the rated power and current.
The manufacturer does not assume any liability for
personal injuries and property damage due to nonconformance with the provided instructions.
www.salda.lt
17
Smarty 2X/3X V
II
IV
I
VI
III
V
VII
VIII
It’s required to connect condensate drainage system after hanging or placement of
air handling unit. Insert condensate draining into AHU. Condensate draining must
1
2
3
Before every heating season the condensate tube shall be
lled with water as indicated during the rst start-up! Before
every heating season the condensate tube shall be lled
with water as indicated during the rst start-up!
be lubricated with sealant (I-VII). Then place plastic washer on the bottom and tighten with counter nut (VII). Pipe (3) (metal pipe should be connected with G3/8 elbow,
plastic pipe – with G3/8 elbow or rubber hose – with strap if the unit is placed on
the legs, in other cases condensate hose can be connected in any direction) should
be connected by following order: AHU (1), pipe (2), and drainage system. Pipes (3)
should be bended not less than 3° degrees (1 meter of pipe must be bended 60 mm
downwards)! Before turning on AHU (1) the draining system should be lled up with
at least 0.5 l of water (pipe loop (3) must be always lled with water), also check if
water reaches sewerage system! In other case premise can be ooded during AHU
operation!
Draining system must be installed in the premise where the temperature is not lower
than 1°C. If temperature falls below 0°C the draining system should be isolated with
thermal isolation. The pipe loop 2) not necessarily must be mounted below the AHU
(1), but below the AHU (1) level.
Note. If the collector is situated upstream, install a system with a condensate pump
(oered as an accessory).
3
D = min 150 mm
Air Handling Unit uses two types of boards, depending on the
selected product version: miniMCB or miniMCB basic. Their
functionality is dierent, thus check the board name by the
product version.
Control board functions and logics are designed according to Standards DIN 1946-6:2009-05 and EN 12098-3.
MCB control board can be controlled by: Ptouch remote control panel, Stouch remote control panel or MB - GATEWAY web application. Description of
remote control panel functions is provided in the remote control panel technical documentation or on the website www.salda.lt.
The unit can be congured only with Ptouch remote control
panel or MB-Gateway web application.
The following control board functions can be fully controlled
only with Ptouch remote control panel or MB-Gateway web
application. In case of Stouch remote control panel use the
description of remote control panel functions for MCB control
board.
18
www.salda.lt
Smarty 2X/3X V
System modes:
• Stand-by
• Building protection
• Economy
• Comfort
In stand-by mode the system is shut down for a permissible shutdown period (based on the stand-by mode blocking function settings).
The building protection mode is designed to protect a building against moisture accumulation. In this mode the system operates at speed 1. By default,
in this mode temperature maintenance is controlled (preferred temperature is indicated). However, if necessary, temperature maintenance can be
switched o.
Economy mode is designed to save energy when people are not in the room. In this mode the system operates at speed 2. By default, in this mode
temperature maintenance is controlled (preferred temperature is indicated). However, if necessary, temperature maintenance can be switched o.
Comfort mode is used when people are present in the room. In this mode the system operates at speed 3. In this mode the temperature is always
maintained.
System mode can be changed automatically by the functions (in a sequential order as indicated):
1 - Weekly Schedule
2 - Mode is activated from an external contactor
3 - User’s manual mode selection
4 - Holiday Schedule
5 - Stand-by mode blocking
Based on the weekly schedule the system decides which mode it will be operating in; however, the user may change the existing mode manually. The
system will inform when the next mode change is scheduled. After power loss the mode is selected based on the weekly schedule; however, if the
schedule is not set, the mode used before the power loss will be activated.
The user may change modes only when the mode is activated from an external contactor. The only case when the user cannot change the mode is
when the period of a holiday schedule is active. The system informs that the holiday schedule mode is active. To prevent blocking, the period of the
holiday schedule must be changed.
Stand-by mode can be blocked based on selected parameters. If at least one of the above functions changes its mode into stand-by mode, it must be
checked whether this mode is not currently blocked. If it is blocked, the previous selected mode is on.
The function order is provided below.
Start
Reading of input
data
Weekly Schedule
Mode external switch
User entered data.
Holiday Schedule
Stand-by mode block-
ing
Boost ventilation
Ventilation logics
Protections
Ventilation logics blocking
Manual control of com-
ponents
Data sending to outputs
and user interface
www.salda.lt
Protection against Dryness
End
19
Smarty 2X/3X V
The eld of a system status is designed to notify a user of the existing system status. The table below provides possible system statuses.
System statusDescription
Stand-by modeSystem operates in stand-by mode.
Building protection modeSystem operates in building protection mode.
Economy modeSystem operates in economy mode.
Comfort modeSystem operates in comfort mode.
Emergency runSystem operates in emergency mode. For more information see alarms.
PreparingSystem is preparing for operation (pre-heating water heaters, etc.).
Opening dampersDampers are opened.
BOOST function activated“BOOST” function is active.
Cooling heatersElectric heaters are cooled down prior to stopping fans.
Closing dampersDampers are closed.
Critical alarmCritical failure, system is shut down. For more information see alarms.
Fire alarmFire protection from an external contactor is activated.
Heat exchanger frost protection activatedHeat exchanger frost protection is activated.
Change ltersWarning on clogged lters. Pressure relays are activated or lter timer is activated.
Room RH 3 days average is lower than 30%. Limiting 3 speed. Protection against dryness is activated. Room 3-day humidity average is lower than
30%. Air ow is reduced.
Function indications are designed to inform a user on active functions and on the presence of at least one warning or alarm. The table below provides
indications and their descriptions.
Functions indicationsDescription
Working indication outputWorking indication output is activated
Alarm indication outputFailure indication output is activated
System mode switchMode is activated from an external contactor
Custom fans speed switchSelected fan speed from an external contactor is activated
WinterActive winter mode
Stand-by mode blocking activatedStand-by mode blocking is activated
Slowing down fansFans are slowed down
Slowing down fans by temperatureFans are slowed down based on supply air temperature
Night cooling function activatedNight cooling function is activated
Hydronic pump exercise activatedPreventive maintenance of circulation pumps is activated
Service stop functionVentilation logic operation is blocked. Service activities are carried out
HolidaysHoliday schedule interval is active. System mode can be changed only upon changing the holiday sched-
Reducing CO2 levelCO2 reduction function is activated
Full recirculationFull recirculation function is activated
Proper date and time must be set to have proper functioning of schedules, event log and winter/summer function. Fast synchronization with the computer time is possible in user and adjuster environments.
ule interval.
A weekly schedule consists of 10 weekly events. They can be added, deleted, activated and deactivated. One event indicates time, mode and days
of the week.
The system changes modes based on the weekly schedule only when the indicated time comes; therefore a user can always change the existing mode
manually. This schedule noties the user of the upcoming mode change by indicating the time remaining till the next event.
A holiday schedule is used when the unit has to operate in an indicated mode during holidays. The user interface shows when the schedule period is
active as the mode activated by this function (except for protections) can be changed by no-one. In order to control the system in a normal manner,
the holiday schedule period must be deactivated, i.e. zero values must be indicated or period dates must be changed. Up to ve holiday periods can
be indicated.
The winter/summer function is used to set upcoming cold periods, because some part of the system need to be protected against cold outdoor air.
During the winter period it is recommended to leave the unit on, therefore it is possible to set that the system switch-o is blocked during the winter
period. Water heaters must be always on during the entire winter period.
20
www.salda.lt
Smarty 2X/3X V
The winter mode may be indicated:
• Manually
• By date
• Based on 3-day mean outdoor air temperature. The mean is calculated only when the fresh air (outdoor) pre-heater is o.
Boost ventilation function is used for fast ventilation of the rooms. This function activates the maximum air ow (speed 4). Boost ventilation must be
temporary, i.e. it must be a nal condition (e.g. CO2 limit, time). The reason for this limitation is protection against dryness. The function is activated
manually and from the external system contactor.
The function is inactive in stand-by mode. Time limit shall be set to this function. Once the function is activated, the indicated time is set for the function
timer and time is counted till the function deactivation. This time may be adjusted in real-time, i.e. when the function is on.
This function is designed to protected premises against dryness. If the function is active, it calculates the 3-day mean humidity of extract air from the
premises. If the mean drops below 30%, fans start operating at speed 2 in comfort mode. A user is notied of the activated protection and limited air
ow.
If the humidity mean exceeds 30% or the function is switched o manually, fans start operating at speed 3 in comfort mode.
This function is designed to save energy which is used to cool a building in the morning by cool night air.
If the function is on but not active, activation conditions are checked:
1 - System time is between function start and function end (hours/minutes).
2 - Time is every hour since the start.
3 - If “Stand-by” mode is set, the unit operates in “Building protection” for 5 minutes so that the actual temperature data is available. Temperatures
are checked after purging. If wrong temperatures are received the unit returns to “Stand-by” mode.
4 - Outdoor temperature is higher than the set outdoor temperature.
5 - Extract air temperature is higher than the set temperature.
6 - Extract air temperature is higher than the outdoor temperature by at least 2 °C.
7 - Summer time.
If all conditions are fullled the unit starts operating in “Comfort” mode (without temperature maintenance). The main window shows that the night
cooling function is active.
Where the function is active, the deactivation conditions are regularly checked:
1 - Time does not correspond to the start/end interval.
2 - Extract air temperature drops below the set point.
3 - Outdoor air temperature drops below the set point.
4 - Mode other than “Comfort” was switched or the unit has been shut down
If at least one condition is correct, the unit switches o the night cooling function and it switches to the mode that was on prior to activating the function.
The air lter timer is designed to inform the user on lter replacement. After lters have been replaced, the timer must be reset. The user can always
see how many days remain till the lter replacement. When the time expires, the warning on lter replacement is displayed. The lter timer limit can
be set in the service environment. Maximum permissible time – 1 year. Time is calculated only when fans are rotating.
This timer also shall be automatically reset to cancel lter clogging warning.
The system noties the user of system failures by alarms and warnings. Warnings are cancelled automatically, whereas alarms must be cancelled
manually. It is recommended that alarms are cancelled by a specialist prior to nding out the causes of the alarm. If at least one alarm is active, the
system is shut down and external failure indication is activated. All possible alarms and warnings are provided in the table below.
ALARMS
NO REGISTER NAME
A1 #D2 FIREPLACE PROTECTION ACTIVATED
A2 #D5 PLATE HEAT EXCHANGER FROST PROTECTION. SYSTEM STOPPED.
A3 #D6PLATE HEAT EXCHANGER FROST PROTECTION (PRESSURE RELAY). SYSTEM STOPPED.
A4 #D7 HYDRAULIC HEATER FROST PROTECTION. SYSTEM STOPPED.
A5 #D10 TOO LOW SUPPLY TEMPERATURE. SYSTEM STOPPED.
A6 #D11 TOO HIGH SUPPLY TEMPERATURE. SYSTEM STOPPED.
A7 #D12 CHANGE SUPPLY FILTER (PRESSURE RELAY). SYSTEM STOPPED.
A8 #D13 CHANGE EXTRACT FILTER (PRESSURE RELAY). SYSTEM STOPPED.
A9 #D15 CHANGE SUPPLY AND EXTRACT FILTERS. SYSTEM STOPPED.
A10 #D24 SUPPLY AIR TEMPERATURE SENSOR FAILURE. SYSTEM STOPPED.
A11 #D25 EXTRACT AIR TEMPERATURE SENSOR FAILURE. SYSTEM STOPPED.
www.salda.lt
21
Smarty 2X/3X V
A12 #D26 EXHAUST AIR TEMPERATURE SENSOR FAILURE. SYSTEM STOPPED.
A13 #D27 OUTSIDE AIR TEMPERATURE SENSOR FAILURE. SYSTEM STOPPED.
A14 #D28 HYDRAULIC HEATER WATER TEMPERATURE SENSOR FAILURE. SYSTEM STOPPED.
A15 #D29 HYDRAULIC PREHEATER WATER TEMPERATURE SENSOR FAILURE. SYSTEM STOPPED.
A16 #D30HYDRAULIC COOLER WATER TEMPERATURE SENSOR FAILURE. SYSTEM STOPPED.
A17 #D31 CONTROLLER CABINET TEMPERATURE SENSOR FAILURE. SYSTEM STOPPED.
A18 #D34 HEATER MANUAL PROTECTION. SYSTEM STOPPED.
A19 #D36 PREHEATER MANUAL PROTECTION. SYSTEM STOPPED.
A20 #D38 SUPPLY FAN PROTECTION
A21 #D39 EXTRACT FAN PROTECTION
A22 #D40 DX COOLER PROTECTION
A23 #D41 FIRE ALARM
A24 #D42 SUPPLY AIR PRESSURE PROTECTION. SYSTEM STOPPED.
A25 #D43 EXTRACT AIR PRESSURE PROTECTION. SYSTEM STOPPED.
A26 #D44 BAD CONFIGURATION
A27 #D45 HEATER MANUAL PROTECTION: FAN BOOST ENABLED
A28 #D46PREHEATER MANUAL PROTECTION: FAN BOOST ENABLED
WARNING
NO REGISTER NAME
W1 #D1BROKEN ROTOR BELT (Applicable when a rotor heat exchanger is built in the unit).
W7 #D16 SUPPLY AIR TEMPERATURE SENSOR FAILURE. EMERGENCY RUN.
W8 #D17 EXTRACT AIR TEMPERATURE SENSOR FAILURE. EMERGENCY RUN.
W9 #D18 EXHAUST AIR TEMPERATURE SENSOR FAILURE. EMERGENCY RUN.
W10 #D19OUTSIDE AIR TEMPERATURE SENSOR FAILURE. EMERGENCY RUN.
W11 #D20 HYDRAULIC HEATER WATER TEMPERATURE SENSOR FAILURE. EMERGENCY RUN.
W12 #D21 HYDRAULIC PREHEATER WATER TEMPERATURE SENSOR FAILURE. EMERGENCY RUN.
W13 #D22 HYDRAULIC COOLER WATER TEMPERATURE SENSOR FAILURE. EMERGENCY RUN.
W14 #D23 CONTROLLER CABINET TEMPERATURE SENSOR FAILURE. EMERGENCY RUN.
W15 #D32 FIRE DAMPER TEST PASSED
W16 #D33 FIRE DAMPER TEST FAILED
W17 #D35HEATER AUTOMATIC PROTECTION
W18 #D37PREHEATER AUTOMATIC PROTECTION
The system records 50 recent events (failures, alarms, re damper testing results, etc.). The log stores the event description and time.
Every unit has a conguration version specic to this unit, which is saved in the production line. Besides the system conguration and software versions the running time is also displayed since the unit manufacture date. Running time is calculated when fans are rotating.
4 air ows are used in the system and they are dedicated to specic modes:
1. Building protection
2. Economy
3. Comfort
4. “BOOST” function
The ows are displayed in ascending order, i.e. when “Comfort” mode is set to lower air ow than that of “Economy” one, the “Economy” mode air ow
will be reduced automatically. With respect to the system conguration, air ows are indicated in percentage or pressure or amounts of air. 100% value
of air ow is indicated in service environment.
22
www.salda.lt
Smarty 2X/3X V
This function is used to adjust the coecients of the existing PID controllers. The number of coecients depends on the system conguration. If the
system operation for any reasons is unstable (uctuating), PID coecients may be adjusted. We recommend this to be done by a specialist.
The function of manual control of components is designed to activate/deactivate the components manually. Components are controlled by digital and
analogue outputs. Analogue outputs are controlled in percentage, and digital output are controlled by “on/o”. By default, all components are attributed
“Auto” status which means that a component is controlled based on ventilation logic. Components are displayed by the system conguration. Settings
must be saved so that they remain the same after power loss.
The minimum unit consumption in stand-by mode is ensured only when all the manual control components are set to “Auto” position.
Prior to using the manual control function, it is recommended to activate the force shutdown function which blocks the ventilation logic functions.
This function may be useful, if you need to check whether everything is properly connected. Moreover, in the event of failure, certain component can
be activated so that the unit operates irrespective of sensors and protections. Of course, this method should be applied in exceptional cases until the
failure is rectied.
If an external (“Remote”) type of a temperature sensor is displayed, the sensor temperature may be indicated manually, and the values may be indicated via the Modbus interface.
This function is used to monitor controller input and output values, versions of connected modules, system date and time, fan speeds, temperatures,
CO2 value, pressure, etc. The amount of information depends on the system conguration. This tool is designed for preventive maintenance of the
system.
This function is designed to protect the system against the impermissible unit shutdown. It is recommended to limit the unit shutdown up to 1 hour
within 12 hours during the winter period. Possible function modes:
• Always allow shutdown
• Block shutdown
• Block shutdown during winter period
• Block shutdown during summer period
It must be indicated for the function for how long the switch-o is permissible within 12 hours. If the switch-o is blocked and the system is shut down,
the system counts the time and informs the user on the remaining time.
If the time has expired and stand-by mode is blocked, the user is informed by the function indication.
Temperature may be indicated for supply air or room temperature. The temperature can be maintained based on supply or extract air temperature. If
control by room temperature is selected, the function calculates the temperature to be supplied to maintain proper room temperature. Temperature is
limited based on supply air temperature permissible limits.
The ventilation unit is not designed to heat premises; therefore it is not necessary to use full capacity for low temperature dierences as the compensation in percentage is provided for in this function. This parameter indicates a percentage part of the temperature dierence (between the set point and
room temperature) to be compensated by this function. E.g. set point is 20°C, room temperature is 16°C, compensation is 50%, dierence between
the indicated and existing temperatures is 20-16=4°C. Since 50% is compensated, then 4*50%=2°C, and when the received value is added to the set
point we get the required supply air temperature 2+20=22°C. As this temperature is within the supply air temperature protection limits, it is not limited.
In this case the system will maintain the supply air temperature at 22°C. The closer room temperature is to the set point (20°C), the closer required
supply air temperature is to 20°C.
It can be also too hot in the room, therefore this function is compensating in both directions (both heats and cools). The required (compensated) temperature is displayed in the window “Monitoring” (“Required supply t.”). If it is displayed that the required temperature is equal to 0°C it means that the
supply air temperature maintenance is switched o.
The supply air temperature is maintained by the following components (in a sequential order as indicated):
• Fans (if too hot the speed is decreased)
• Cooler
• Recirculation damper (in case of favourable outdoor air temperature)
• Bypass damper (in case of favourable outdoor air temperature)
• Heater
• Fans (if too cold the speed is decreased)
The system rst of all tries to maintain the supply air temperature by means of a heat exchanger. If plate heat exchanger is used, the bypass damper is
used. The heat exchanger can both cool and heat with respect to outdoor and room air temperatures. The heat exchanger is controlled based on PID
controller assigned to it. When the heat exchanger operates at full capacity and required temperature is not reached, the recirculation damper, then
the heater or cooler is activated (if necessary) etc. Only the components congured for temperature maintenance are activated. From one component
to another one the system switches over in 60 seconds.
This function is designed to limit the supply air temperature. The minimum and maximum supply air temperatures are indicated for the function as well
as permissible time and protection actions (display only an alarm or shut down the unit). This function limits supply air temperature set by the user
and other functions. If the temperature is controlled based on room temperature, this function does not allow supplying warmer or cooler air than that
indicated in the protection.
If the system fails to maintain the right temperature, i.e. supply air temperature remains outside the limits for an indicated period of time, the unit is shut
down (if indicated) and alarm is displayed. By default, the minimum permissible supply air temperature is 16.5°C, maximum temperature is 40.0°C.
This function is designed to activate the preferred system mode by means of an external contactor. The function indicates a type of a signal to be sent
to the input.
Possible types of signals:
• Not used
www.salda.lt
23
Smarty 2X/3X V
• Button click. Selected system mode is activated. Function is activated when it receives an impulse. It is deactivated when it receives the impulse
again.
• On/o. Selected system mode is activated. Mode is active when contactor is on.
• PIR sensor. When the sensor is activated, the selected system mode is activated. If the signal is not received within 30 minutes, the mode is
deactivated.
This function is designed to activate/deactivate the boost ventilation function or preferred combination of fan speeds by means of an external contactor.
The function indicates a type of a signal to be sent to the input and components controlled by it. Possible combinations of signal types and functions:
• Not used.
• On/o. Selected fan speed combination is activated. Function is on when contactor is on.
• Button click. Selected fan speed combination is activated. Function is activated when it receives an impulse. It is deactivated when it receives
the impulse again.
• On/o. Boost ventilation function is controlled. Function is on when contactor is on. If the boost ventilation function is not terminated by means of
this function within the boost ventilation time limit, force shutdown is used after the time expires.
• Button click. Boost ventilation function is controlled. Function is activated when it receives an impulse. It is deactivated when it receives the
impulse again.
• If the boost ventilation function is not terminated by means of this function within the boost ventilation time limit, force shutdown is used after the
time expires.
It is also indicated whether boost ventilation will be activated or combination of fan speeds is preferred, i.e. it is possible to indicate preferred supply
and extract air fan speeds individually.
1.24.1 Chimney Sweep Function
When the function of fan speed from an external contactor is used, the function can be adjusted so that it helps to light a re in a replace. The external
contactor may be connected to the switch of the replace door. It must be indicated in the function that “On/O” signal will be used, minimum extract
air fan speed and maximum supply air fan speed must be indicated. This combination will create the pressure in a room, which will improve the smoke
extract through a chimney as well as burning. When the replace door is opened, the function will be activated. When the door is closed, the function
will be deactivated.
1.25.1 Filter Timer Settings
Filter timer limit is set to the function. The maximum setting can be 1 year.
1.25.2 Air Filter Protections based on Pressure Relays (only Smarty 2X/3X V 1.1)
The function checks if the lters are clogged by means of pressure switches. Available function operating combinations:
• Not available
• Supply air
• Extract air
• Supply and extract air
When pressure switches are activated an alarm is displayed.
A re protection signal can be connected to this controller. By default, the signal input is normally closed (NC). Input conguration can be changed.
When the signal is lost for an indicated period of time, the protection is activated, warning is displayed and indicated mode is performed. Protection
is terminated upon cancelling the warning. It is possible to set a timespan during which the system does not activate. It is possible to select system
behaviour when this function activates:
• Stop the system
• Run supply air fan in full speed and stop extract air fan
• Run extract air fan in full speed and stop supply air fan
• Run supply and extract air fans in full speed
This function is designed to maintain a proper quality of room air.
Where CO2 exceeds the permissible limit, CO2 reduction is activated and air ow is increased. When CO2 reaches the set point, this function is
switched o.
Login passwords can be changed in the service environment. To change passwords of service and adjuster environments the password must be
activated.
The password consists of 4 digits. If password is not necessary for parameter review and change, set the password (number “0”).
This function allows to restore the factory defaults.
The preferred air ow can be indicated in percentage or 4 xed speeds where each of them is dedicated to a relevant system mode:
1. Building protection
2. Economy
3. Comfort
4. “BOOST” function
Fan speed can be controlled based on:
• Percentage value. Speed percentage is indicated. 0% corresponds to 0V control signal voltage, 100% corresponds to 10V control signal voltage.
• Pressure. The maximum system pressure is indicated which means 100% air ow.
24
www.salda.lt
Smarty 2X/3X V
• Air ow (m3/h). Supply and extract air factor K and maximum system air ow (m3/h) is indicated which means 100% air ow.
The fans are controlled by PID controller based on air ow and pressure. Every fan is controlled individually.
It is possible to limit the minimum and maximum fan control signal voltage. By default, minimum 2V voltage is indicated which means that 0V voltage
signal is sent when fans are o, and 2V voltage signal is immediately sent when rotation is required.
1.30.1 Fan Protection based on Rotating Speed
If fans have “tacho” outputs, the fan failure can be identied based on their rotating speed. If the system sends the signal for fans to rotate and they
fail to rotate, then protection is activated, system operation is shut down and alarm is displayed.
1.30.2 Air Flow Protection based on Pressure (only in Smarty 3X V 1.1 version)
Where this protection is activated the system must reach the required pressure or air ow. If the system fails to reach the required air ow or pressure
within the indicated period of time, the protection is activated, unit is shut down and alarm is displayed. This may happen due to failures of air ow/
pressure transmitters, pressure hose defect, clogged ow, impeller defects, incorrect factor K, etc.
1.30.3 Protection of Premises with a Fireplace (only in Smarty 2X/3X V 1.1 versions)
This protection is used for premises with a replace. It protects against improper air pressure dierence which can result in presence of ue gas
(carbon black) in premises. Pressure switch must be connected to the assigned digital input to measure pressure drop in the premises and inside the
chimney. Upon activation of this protection the pressure switch will shut down the unit and display the alarm.
1.30.4 Slowing Down Air Flows based on Temperature
If supply air temperature is more important than air ow, the function of air ow slowing down based on temperature may be switched on. If full heating/cooling capacity is used to reach the desired temperature and it is not reached, the air ow is slowed down to have sucient power to maintain
the desired temperature.
1.30.5 Continuous Temperature Maintenance by Slowing Fans Down
This function is designed to save energy when air ow is changed. It is active when fans are controlled based on percentage, since PID controllers
do it automatically if it is controlled based on air ows or pressure. Fast change of air ows imbalances the temperature maintenance function and
consumes energy until it is balanced again. If a user sets a higher air ow, this function starts gradually increasing the air ow and gradually slows
down the conversion speed when it approaches the set value. In this way the temperature maintenance function suers less stress and consumes less
energy. If the user reduces the air ow, the system switches o coolers and heaters to prevent from the heat/cold wave and gradually changes the air
ow. After the air ow has been reduced, heaters and coolers continue operating as required.
The following dampers can be connected to the system:
• Supply/extract air dampers (On/O or OpenClose type). The damper is opened prior to starting fans and closed after fan shutdown.
If On/O or OpenClose type damper is indicated, proper opening time must be indicated.
1.32.1 Cold - Heat Recuperation (no bypass dampers in Smarty 2X/3X V 1.3 versions)
Cold-heat recuperation function is designed to control a heat exchanger. The plate heat exchanger power is controlled by means of a bypass damper.
When the damper is closed, the heat exchanger is used at full capacity. When opening the damper the heat exchanger power is reduced.
The heat exchanger can both heat and cool based on outdoor air temperature. If it is colder outdoors than in the room, the heat exchanger pre-heats
outdoor air by using the room air heat. If it is colder in the room than outdoors, the heat exchanger cools down the outdoor air by using the room air.
The heat exchanger power is reduced to the minimum when the system required supply air temperature is the same as outdoor air temperature. The
higher the dierence between required and supply air temperatures, the higher the heat exchanger power is used. Only when the heat exchanger is
used at full capacity, it is allowed to activate other heating/cooling components.
The coecients of the heat exchanger, heat exchanger PID controller are set to this function.
PID controller output limits are set to bypass damper from which point to start operation. If the bypass damper opens only at several percent the noise
can occur, thus its minimal opening limit is limited. This limit also applies when approaching the full opening.
1.32.2 Plate Heat Exchanger Anti-Frost Protection
This protection is designed to protect the heat exchanger against accumulation of ice as the accumulated ice can damage the structure of the heat
exchanger. Protection activation/deactivation is possible based on:
• Indicated outdoor air temperature
• Indicated extract air temperature
• ndicated extract air temperature dierence from the calculated freezing point (this temperature is calculated based on outdoor air temperature,
room air temperature and humidity)
• Based on pressure switch
Possible safeguards (performed in a sequential order as indicated):
1 - Reduction of supply air ow (-30 %)
2 - Outdoor air heating with pre-heater
3 - Bypass damper opening
4 - Unit shut down (based on supply air temperature)
Protection activation conditions and safeguards can be activated optionally. Also time is indicated to switch over from one protection to another one
after time expires. If at least one activation condition is fullled, the protection is activated and warning is displayed. It begins from the least energy
www.salda.lt
25
Smarty 2X/3X V
consuming safeguards, i.e. if allowed, the supply air ow is reduced. If the protection does not help during the indicated period of time, then the other
protection is activated. Switching over from one protection to another one is done in a sequential order.
Outdoor and extract air recirculation is eective and energy-saving protection, but supplies the extract air to the supply air ow.
Outdoor air pre-heater can be used at full capacity or to maintain the set temperature. If temperature maintenance is selected, at rst the activated
protection will switch on the pre-heater at full capacity for a certain time period and then maintain the indicated temperature.
When using the bypass damper the supply air heater must be connected. The opening of the damper will reduce the cold air ow through the heat
exchanger, but it will cool down the supply air which must be heated up by the supply air heater. This protection slowly opens the bypass damper as
far as activation conditions are fullled. When suitable conditions are met the damper will be stopped for 5 min. and then slowly closed. If the supply
air temperature drops below the permissible limit (insucient heater power), then the damper will be closed by force based on supply air temperature.
Only either pre-heater or heater can be connected to
MiniMCB basic board.
1.33.1 Supply Air Heater
Supply air heaters are designed to additionally pre-heat the supply air when the heat exchanger heating power is insucient. The heater is controlled
by means of a PID controller based on temperature indicated by the system and data of the supply air temperature sensor. One supply air heater can
be connected to this system.
Possible options of supply air heaters in this system:
• Supply air heater is not used.
• Electric heater is controlled by 0..10VDC signal
• Electric heater is controlled by On/O signal. PWM control interval in seconds is indicated to control this heater.
Also it is possible to swap the connectors of pre-heater and heater protections and control signals.
1.33.2 Electric Heater Thermal Protections
The electric heater can have two protections. One is automatic, another one is manual. The automatic protection is automatically o when the heater
cools down, whereas the manual protection must be deactivated by pressing the switch on the heater.
When the automatic protection is activated, the heater and its power circuit are o, warning is displayed. Minimum switch-o time – 5 minutes. When
the protection is restored, the warning is no longer displayed.
If the manual protection is activated, the heater and its power circuit are o, an alarm is displayed, the indicated protection action is performed. By default, full speed blowing is performed so that maximum cooling of the heater is ensured as there is a probability that the manual protection can jam and
leave the heater running. Of course, if the manual protection is properly activated, the supply air temperature can quickly drop to critical temperature
during winter period if full speed blowing is on and the system would be shut down in any case.
1.33.3 Electric Heater Cooling
If an electric heater is used and the system wants to stop the fan, heaters are switched o prior to shutting fans down and they are cooled down by
blowing for an indicated period of time. A user is notied of heater cooling.
1.33.4 Outdoor Air Pre-Heater (not applicable to Smarty 2X/3X V 1.1 versions as they have integrated internal pre-heater)
Outdoor air pre-heaters are controlled based on anti-frost protection. Possible options of outdoor air heaters in this system:
• Supply air pre-heater is not used.
• Electric pre-heater is controlled by 0..10VDC signal
• Electric pre-heater is controlled by On/O signal. PWM control interval in seconds is indicated to control this heater.
In this system it is possible to indicate a normal status of every digital input, i.e. indicate whether the contactor is normally open or closed (Normally
Open (NO), Normally Closed (NC)). The re protection contactor must be NC as in case of re the contactor may break if a cable burns.
In this system two 0-10VDC air quality sensors and eight temperature sensors may be used.
The following can be connected to two 0-10VDC inputs:
• Supply air RH sensor
• Extract air CO2 sensor
• Extract air RH sensor
• Supply air pressure sensor
• Extract air pressure sensor
0V and 10V values are indicated for these sensors. Types of temperature sensors:
• “None” – sensor is not connected
• “Remote” – remote sensor. Sensor temperature can be indicated via Modbus.
• “NTC 10K 3997” – NTC sensor is connected.
In this system all types of sensors and failure action are indicated. Possible failure actions:
• Do nothing – only warning is displayed
• Shut down the system – the system is shutdown, alarm is displayed.
• Emergency mode – operation is continued, but sensor-dependent functions are switched o. Warning is displayed.
MiniMCB controller has two independent communications lines. One line is dedicated for remote control panels, another one is for BMS network.
The line dedicated to the BMS network is galvanized. Used communication protocol – Modbus RTU.
26
www.salda.lt
By default:
• Modbus address: 1
• Baudrate: 19200
• Frame: E,8,1 (parity: Even)
If necessary, a complete description of miniMCB functions can be downloaded from www.salda.lt.
Smarty 2X/3X V
www.salda.lt
27
Smarty 2X/3X V
KE
(EKA)
+
TA
PE
Ptouch
Stouch
*
TE**
T
inklas
TA
PE*
(EKA
NIS/
EKA)
AKS***
AKS***
AKS***
MBGateway
KE
(EKA)
+
TA
PE
PtouchStouch
*
TE**
T
inklas
TA
PE*
(EKA
NIS/
EKA)
AKS***
AKS***
AKS***
*
*
MB-Gateway
outdoor airsupply airexhaust airextract air
Separate power supply source
Transmitter 1
CO2 or RH
Transmitter 2
CO2 or RH
- It’s recommended to insulate by 50 mm mineral wool
- It’s recommended to insulate by 25 mm mineral wool
- Possibility to choose a direction of the drainage pipe
WSGSupply and exhaust air grillesIFFilter for extract air (G4)
PIRMotion detectorTAExtract air temperature sensor
KE (EKA)Electric heaterPVSupply air fan
TJSupply air temperature sensorPRPlate heat exchanger
M2
M3Exhaust air damper actuatorRS485Control panel connection place
TE**
Fresh air damper actuator. Recommended to use with
return spring
Exhaust air temperature sensor (** - shall be ordered
separately)
IVExtract air fan
PtouchControl panel
TLOutdoor air temperature sensorStouchControl panel
PFFilter for supply air (G4/(F7 - optional))MBGateway Net module
PEElectric preheaterPCPersonal computer
CEE7/7Power cable with plugAKS***Silencer (*** - recomendet)
DJSmoke detectorM1ByPass motor
28
Network
www.salda.lt
Smarty 2X/3X V
KE*
(EKA)
TA
*
TE**
PE*
(EKA
NIS/
EKA)
TA
PE*
(EKA
NIS/
EKA)
AKS***
AKS***
AKS***
Ptouch
Stouch
T
inklas
MBGateway
KE
(EKA)
+
TA
PE
PtouchStouch
*
TE**
T
inklas
TA
PE*
(EKA
NIS/
EKA)
AKS***
AKS***
AKS***
*
*
MB-Gateway
outdoor airsupply airexhaust airextract air
Separate power supply source
Transmitter 1
CO2 or RH
Transmitter 2
CO2 or RH
Network
- It’s recommended to insulate by 50 mm mineral wool
- It’s recommended to insulate by 25 mm mineral wool
- Possibility to choose a direction of the drainage pipe
KE* or PE* - either pre-heater PE or heater KE shall be connected.
WSGSupply and exhaust air grillesIFFilter for extract air (G4)
IVExtract air fan
PIRMotion detectorTAExtract air temperature sensor
KE (EKA)Electric heaterPVSupply air fan
TJSupply air temperature sensorPRPlate heat exchanger
M2
Fresh air damper actuator. Recommended to use with
return spring
M3Exhaust air damper actuatorRS485Control panel connection place
TE**
Exhaust air temperature sensor (** - shall be ordered
separately)
PE* (EKA
NIS or EKA)
Electric preheater
TLOutdoor air temperature sensorStouchControl panel
PFFilter for supply air (G4/(F7 - optional))PtouchControl panel
M1ByPass motorMBGateway Net module
CEE7/7Power cable with plugAKS***Silencer (*** - recomendet)
DJSmoke detectorPCPersonal computer
www.salda.lt
29
Smarty 2X/3X V
KE*
(EKA)
TA
*
TE**
PE*
(EKA
NIS/
EKA)
AKS***
AKS***
Ptouch
Stouch
T
inklas
MBGateway
KE
(EKA)
+
TA
PE
PtouchStouch
*
TE**
T
inklas
TA
PE*
(EKA
NIS/
EKA)
AKS***
AKS***
AKS***
*
*
MB-Gateway
outdoor airsupply airexhaust airextract air
Separate power supply source
Transmitter 1
CO2 or RH
Transmitter 2
CO2 or RH
- It’s recommended to insulate by 50 mm mineral wool
- It’s recommended to insulate by 25 mm mineral wool
- Possibility to choose a direction of the drainage pipe
KE* or PE* - either pre-heater PE or heater KE shall be connected.
WSGSupply and exhaust air grillesIFFilter for extract air (G4)
IVExtract air fan
PIRMotion detectorTAExtract air temperature sensor
KE (EKA)Electric heaterPVSupply air fan
TJSupply air temperature sensorPRPlate heat exchanger
M2
Fresh air damper actuator. Recommended to use with
return spring
M3Exhaust air damper actuatorRS485Control panel connection place
TE**
Exhaust air temperature sensor (** - shall be ordered
separately)
PE* (EKA
NIS or EKA)
Electric preheater
TLOutdoor air temperature sensorStouchControl panel
PFFilter for supply air (G4/(F7 - optional))PtouchControl panel
PCPersonal computerMBGateway Net module
CEE7/7Power cable with plugAKS***Silencer (*** - recomendet)
DJSmoke detector
30
Network
www.salda.lt
Smarty 2X/3X V
X23:8 - 12VDC
X23:7 - DI4
miniEX1 V0.3
02-1
02-1
02-1
-N3
X23:6 - 12VDC
X23:5 - DI3
-Fire Place II
(for versions 1.1)
-Fire Place I
Fire place
1
01
Drawing #
Book #
UAB"SALDA"
X4:6 - 3.3V_1W
-N1
miniMCB V0.3
-N1
miniMCB V0.3
X4:5 - DI4
-FA
X6:6 - GND
X6:5 - AI3(NTC)
X6:4 - GND
X6:3 - AI2(NTC)
X6:2 - GND
X6:1 - AI1(NTC)
TATL
TJ
Fire alarm
Jumper 7
air temp.
sensor
Extract
air temp.
sensor
Fresh
air temp.
sensor
Supply
2016-03-22
2016-03-22
2016-03-22
SIGNATUREDUTIES / NAMEDATE
EI D. Aleksandravičius
EI A. Šklenikas
CHECKED BY
CHECKED BY
DRAWN BY
X3:6 - 24VDC
X3:5 - STEP_A
X3:4 - STEP_A/
X3:3 - STEP_B
(for versions 1.1 and 1.2)
Bypass actuator
X3:2 - STEP_B/
-N1
miniMCB V0.3
PE N L
1
1
1
-X2
1
2
3
2
2
2
X3:1 - 24VDC
PE -+
-G1
24VDC
X9:3 - PE
-N1
miniMCB V0.3
X5:6 - +12VDC
X5:5 - DI7
(for versions 1.1 and 1.2)
Bypass position switch
219.1017.0.1.1-PS
Principle connection scheme
Power in
Components and cables marked with the dash line connected by SALDA or customer.
X9:2 - GND
PE
N
L1
-X1
1123445677
-N1
miniMCB V0.3
X9:1 - 24VDC_IN
Punktyrine linija pažymėtus komponentus ir kabelius pajungia SALDA arba vartotojas.
www.salda.lt
Power supply
1f, 230VAC
Aut. 219.1017E
31
Smarty 2X/3X V
1
02
Drawing #
X8:8 - I2C_SCL
X8:7 - I2C_CDA
X8:6 - GND
X8:5 - 2.5VDC_REF
X8:4 - 3.3VDC
miniMCB V0.3
-N1
X8:3 - 12VDC
X8:2 - 24VDC_P
X8:1 - GND
X22:1 - I2C_SCL
X22:2 - I2C_SDA
X22:3 - GND
X22:4 - 2.5VDC
X22:5 - 3.3VDC
miniEX1 V0.2
X22:6 - 12VDC
X22:7 - 24VDC
X22:8 - GND
EX1 module power, control.
Book #
UAB"SALDA"
2016-03-22
2016-03-22
2016-03-22
X5:4 - +12VDC
X5:3 - DI6
X5:2 - +12VDC
miniMCB V0.3
Electrical preheater
DI5 - automatic protection
DI6 - manual protection
-N1
-N1
miniMCB V0.3
-N1
miniMCB V0.3
X5:1 - DI5
X12:3 - DO2(L(L2))
X12:2 - N(L1)
X12:1 - PE
X10:3 - N(L1)
X10:2 - DO1(L(L2))
X10:1 - PE
RT1
RT1
AT1
AT1
L1
N
PE
L
N
PE
Control ON/OFF
Internal or external preheater
-PE1
Power up to 2kW, 1f/230V
KE1
EKA ...-1F
EI D. Aleksandravičius
EI A. Šklenikas
CHECKED BY
CHECKED BY
DRAWN BY
219.1017.0.1.2-PS
Principle connection scheme
SIGNATUREDUTIES / NAMEDATE
32
Electrical heater max. 0,6kW
X11:3 - PE
X11:2 - L(L2)
-N1
miniMCB V0.3
Power in
-N1
miniMCB V0.3
1123445677
X11:1 -N(L1)
X17:3 - PE
X17:2 - N(L1)
X17:1 - L(L2)
Components and cables marked with the dash line connected by SALDA or customer.
Punktyrine linija pažymėtus komponentus ir kabelius pajungia SALDA arba vartotojas.
01-7
01-7
01-7
Aut. 219.1017E
www.salda.lt
Smarty 2X/3X V
1
03
Drawing #
Book #
X19:3 - 24VDC
AO1
miniEX1 V0.3
-N2
miniEX1 V0.3
-N2
X19:2 - GND
X19:1 - AI(0-10V)
X21:4 - 24VDC
X21:3 - DO2
X21:2 - 24VDC
X21:1 - DO1
GND
Vin
Alarm
2928
indication
Transmitter 2
Supply air CO2 or
RH (input 0-10VDC)
output
(STOP)
UAB"SALDA"
2016-03-22
2016-03-22
2016-03-22
SIGNATUREDUTIES / NAMEDATE
Working
2726
output
(START)
indication
(for versions 1.1)
=MCB1-H1=MCB1-H2
EI D. Aleksandravičius
X6:8 - GND
-N1
miniMCB V0.3
X6:7 - AI4(NTC)
X7:4 - 3.3V_1W
TE
temperature sensor
Optional.
Extract air
EI A. Šklenikas
CHECKED BY
CHECKED BY
DRAWN BY
X7:3 - DI10
miniMCB V0.3
X7:2 - 3.3V_1W
X7:1 - DI9
-N1
X7:7 - +24VDC
X7:6 - GND
miniMCB V0.3
-N1
X7:5 - AI4(0-10V)
X14:3 - PE
X13:4 - DO4(L(L2))
X13:3 - DO3(L(L2))
X13:2 - N(L1)
32
-Fan speed switch
3031
-System mode switch
AO1
GND
Vin
L1
L1
N
33
L1
L1
N
219.1017.0.1.3-PS
Principle connection scheme
Transmitter 1
Extract air CO2 or
RH (input 0-10VDC)
M3
230VAC
ON/OFF
M2
230VAC
ON/OFF
Components and cables marked with the dash line connected by SALDA or customer.
Punktyrine linija pažymėtus komponentus ir kabelius pajungia SALDA arba vartotojas.
1123445677
www.salda.lt
-N1
miniMCB V0.3
X13:1 - PE
J3J4
Aut. 219.1017E
33
Smarty 2X/3X V
6
01
Drawing #
Book #
UAB"SALDA"
2015-11-19
2015-11-19
2015-11-19
SIGNATUREDUTIES / NAMEDATE
794941-1
X25
EI D. Aleksandravičius
EI A. Šklenikas
CHECKED BY
CHECKED BY
DRAWN BY
8
7
6
5
4
3
2
1
Blue
0.22
Red
0.22
Yellow
0.22
Violet
0.22
Black
0.22
Blue
0.22
White
0.35
White
0.35
+24
A
A/
B
B/
+24
COM
NC NO
X5
M1
Bypass actuator motor
Bypass
switch
position
221.1007.0.1.1-PS-0k
Principal connection scheme
34
1123445677
Pynė l. SMARTY ZP3XV-0k
www.salda.lt
KF2EDGKD-5.0/3P
Smarty 2X/3X V
8
01
Drawing #
Book #
UAB"SALDA"
2015-11-24
2015-11-24
2015-11-24
SIGNATUREDUTIES / NAMEDATE
8
White
0.35
White
0.35
White
0.35
White
3
X12
2
1
0.35
Brown
0.75
Blue
0.75
Green-yellow
0.75
7
6
5
4
794821-1
Preheater
3
2
X29
1
EI D. Aleksandravičius
EI A. Šklenikas
CHECKED BY
CHECKED BY
DRAWN BY
8
7
6
5
4
KF2EDGKD-2.5/8P
3
2
X5
1
6
5
4
3
2
X3 KF2EDGKD-2.5/6P
1
White
0.35
White
0.35
White
0.35
White
0.35
White
0.35
White
0.35
White
0.35
White
0.35
8
7
6
5
4
794821-1
3
Bypass
2
X25
1
221.1011.0.1.0-PS-0k
Principle connection scheme
1123445677
www.salda.lt
Pynė l. Smarty 3XV-PE-0k
35
Smarty 2X/3X V
01
12
Drawing #
Book #
UAB"SALDA"
WH - White - Baltas
GY - Grey - Pilkas
BK - Black - Juodas
BN - Brown - Rudas
Cable for control
GN/YE - Green/Yellow - Žalias/Geltonas
BU - Blue - Mėlynas
RD - Red - Raudonas
2016-03-22
2016-03-22
2016-03-22
0-10V in
GND
Tach
+10V
H4)
X16:3 - PE
X16:2 - N(L1)
N1
miniMCB V0.3
miniMCB V0.3
N1
miniMCB V0.3
N1
N1
miniMCB V0.3
X16:1 - DO6(L(L2))
X4:4 -Tacho2_K
X4:3 - DI3(Tacho2_A)
X4:2 -Tacho1_K
X4:1 - DI2(Tacho1_A)
X2:4 - AO2(0-10V)
X2:3 - GND
X2:2 - AO1(0-10V)
X2:1 - GND
X15:3 - DO6(L(L2))
X15:2 - N(L1)
X15:1 - PE
Green-yellow
0.5
Blue
0.5
Brown | Black
0.5
White
0.35
Red
0.35
White
0.35
Red
0.35
Yellow
0.35
Blue
0.35
Yellow
0.35
Blue
0.35
Brown | Black
0.5
Blue
0.5
Green-yellow
0.5
L1
N
PE
IV
Cable for power supply
Cable for control
0-10V in
GND
Tach
+10V
H4)
L1
N
PE
PV
SIGNATUREDUTIES / NAMEDATE
EI D. Aleksandravičius
EI A. Šklenikas
CHECKED BY
CHECKED BY
DRAWN BY
SP42
Principle connection scheme
36
Cable for power supply
1123445677
Fans (MiniMCB)
www.salda.lt
Smarty 2X/3X V
13
Drawing #
Book #
UAB"SALDA"
2015-11-24
2015-11-24
SIGNATUREDUTIES / NAMEDATE
01
2015-11-24
794941-1
X29
CHECKED BY
CHECKED BY
DRAWN BY
8
7
6
5
4
3
2
1
White
0.5
White
0.5
White
0.5
White
0.5
Brown
1
Blue
1
Green-yellow
1
RT1
1
2
AT1
1
2
EK1
SP35
Principle connection scheme
J2
1123445677
www.salda.lt
Heater
37
Smarty 2X/3X V
1
01
Drawing #
Book #
UAB"SALDA"
-K1
X12:3 - DO2(L(L2))
-N2
miniMCB V0.3
X12:2 - N(L1)
X12:1 - PE
230VAC
A1
A2
1114
-K1
2016-03-22
2016-03-22
SIGNATUREDUTIES / NAMEDATE
X2:6 - AO3(0-10V)
-N2
miniMCB V0.3
X2:5 - GND
2
1
3
4
-K1
PE
L1
L2
12-0-10V
11-GND
L2
L1
PE
EKS NIS ... -2f
-PE1
Control 0-10V
External preheater.
Power over 2kW, 2f/400V
CHECKED BY
APPROVED BY
DRAWN BY
38
SP45
X2:6 - AO3(0-10V)
-N1
miniMCB V0.3
-N1
miniMCB V0.3
X2:5 - GND
X12:3 - DO2(L(L2))
X12:2 - N(L1)
X12:1 - PE
GND
0-10V
L1
N
PE
EKA NIS ... -1F
PE1
Control 0-10V
External preheater.
Power up to 2kW, 1f/230V
Max. 2kW/230V
12345678910
External preheater
www.salda.lt
Smarty 2X/3X V
Unit controller miniMCB has integrated protection against short-circuit.
F1 - 1A (5x20) controller power supply 230VAC/24VDC protection.
To ensure safe maintenance of the unit, it is necessary to
remove the plug from the power network.
Prior to start-up the system must be thoroughly cleaned. Check whether:
• operation systems and unit elements as well as automation and automation devices were not damaged during installation,
• all consumers are connected to power supply and t for service,
• all necessary automation elements are installed and connected to power supply and miniMCB basic, EX1 terminal blocks,
• cable connection to miniMCB basic, EX1 terminal blockscomply with the existing power connection diagrams,
• all electrical equipment protection elements are properly connected (if they are additionally used),
• cables and wires correspond to all applicable safety and functional requirements, diameters, etc.,
• earthing and protection systems are properly installed,
• condition of all seals and sealing surfaces is proper.
FailureCauseExplanation / corrective actions
Unit is not operatingNo supply voltages
Two-pole protection device is o or a current
leakage relay is active (if installed by the installer)
Air supply heater or heater is not operating or
malfunctioning (if installed)
Too low air ow at rated fan speed Clogged supply and/or extract air lter(s)Filter replacement needed
Filters are clogged and no message is shown
on the remote control
The controller is used with NTC sensors.
Default sensor NTC
10 kΩ β (25/85) 3977
Limits for temperature measurement -30 ...105 °C.
Accuracy - ± 0,2 %
Safety class – IP-54
Too low air ow in air ducts activates automatic
protection
Manual protection is activated
Wrong time in lter timers
Check whether the device is connected to the
plug socket
Switch on only if the unit condition has been
evaluated by a qualied electrician. If the system failed, the failure MUST BE rectied prior
to switching it on.
Check if air lters are not clogged
Check if fans are rotating
Possible heater or unit failure. MUST address
the servicing sta for failure detection and its
elimination.
Shorten lter timer time till the message of
clogged lters
www.salda.lt
39
Smarty 2X/3X V
Fig. 1. Unit automation:
A
F
B
C
E
Fig. 2. miniMCB controller zones:
A
GND
GND
+24VDC
DI1
2 3 41 2 3 4 5 6
1
D
D
AO1 (0-10V)
AO2 (0-10V)
GND
GND
AO3 (0-10V)
STEP_B/
STEP_B
STEP_A/
+24VDC_P
1 2 3 4 5 6
STEP_A
+24VDC_P
DI2 (TACHO1_A)
(TACHO1_K)
DI3 (TACHO2_A)
(TACHO2_K)
1 2 3 4 5 6
AI1 (NTC)
AI2 (NTC)
AI3 (NTC)
GND
GND
AI4 (NTC)
GND
DI4
+3.3V_1W
DI5
+12VDC
DI6
+12VDC
DI7
+12VDC
3
2
4 5 6 7 81 2 3 4 5 6 7 81 2 3 4 5 6 7 8
1
GND
DI8
+12VDC
AI4 (0-10V)
GND
DI9
+3.3V_1W
DI10
GND
+3.3V_1W
+24VDC
40
F
PE
+24VDC PCB
POWER SUPPLY
GND
PE
2 3
1
PE
PE
N(L1)
DO6 (L(L2))
PE
L(L2)
N(L1)
DO6 (L(L2))
PE
PE
N(L1)
4 3 2 13 2 13 2 13 2 1
N(L1)
DO5 (L(L2))
DO4 (L(L2))
DO3 (L(L2))
PE
N(L1)
DO2 (L(L2)_2)
N(L1)_2
3213 2 13 2 13 2 1
PE
PE
N(L1)_2
L(L2)_2
DO1 (L(L2)_2)
N(L1)_2
D
www.salda.lt
A
ConnectorContactor No.Contactor nameFunctional block name
miniMCB
1PE
X1
X2
X3
X4
X5
X6
2GND
324VDC
4DI1 (HOLO)
1GND
2AO1 (0-10V)
3GND
4AO2 (0-10V)
5GND
6AO3 (0-10V)
124VDC_P
2STEP_B/
3STEP_B
4STEP_A/
5STEP_A
624VDC_P
1DI2 (TACHO1_A)
2 (TACHO1_K)
3DI3 (TACHO2_A)
4 (TACHO2_K)
5DI4
63.3V_1W
1DI5
212VDC
3DI6
412VDC
5DI7
612VDC
7DI8
812VDC
1AI1 (NTC)
2GND
3AI2 (NTC)
4GND
5AI3 (NTC)
6GND
7AI4 (NTC)
8GND
Not used
Supply air fan control (output 0-10VDC)
Extract air fan control (output 0-10VDC)
Electric/Water preheater control (output 0-10VDC)
Bypass step motor control
Supply fan speed RPM
Extract fan speed RPM
Fire protection input (NC)
Electric Preheater automatic protection (NC)
Electric Preheater manual protection (NC)
Bypass closed (NC)
Not used
Supply air temperature sensor
Fresh air temperature sensor
Extract air temperature sensor
Exhaust air temperature sensor (optional)
Smarty 2X/3X V
www.salda.lt
41
Smarty 2X/3X V
1DI9
23.3V_1W
3DI10
X7
ConnectorContactor No.Contactor nameFunctional block name
X9
X10
X11
X12
X13
X14
X15
X16
X17
43.3V_1W
5AI4 (0-10V)
6GND
724VDC
8GND
124VDC POWER
3PE
1PE
3N(L1)_2
1N(L1)_2
3PE
1PE
3DO2 (L(L2)_2)
1PE
2N(L1)
3DO3 (L(L2))
4DO4 (L(L2))
1DO5 (L(L2))
3PE
1PE
3DO6 (L(L2))
1DO6 (L(L2))
3PE
1L(L2)
3PE
System mode switch
Fan speed switch
A2-Extract air CO2 or RH (input 0-10VDC)
24VDC Power supply for Air quality transmitter I
D
miniMCB
24VDC power supply input2GND
Electric/Water Heater power line/circulation pump (max.0,6kW)2DO1 (L(L2)_2)
230VAC Power supply for X10 and X122L(L2)_2
Preheater power line (max. 2kW)2N(L1)_2
Supply/extract air damper control output
DO3 (Open) DO4 (Close) 0,5A
Not used2N(L1)
Supply fans power line - PV2N(L1)
Extract fans power line - IV2N(L1)
230VAC Power supply for X13, X14, X15, X162N(L1)
42
www.salda.lt
F
ConnectorContactor No.Contactor nameFunctional block name
miniMCB
1RS422_Z
2RS422_Y
3-
X18
Fig. 3. EX1 controller zones
4RS422/485_A
5RS422/485_B
6RS_GND
724VDC
8GND
RS422/485 communication port
B
Smarty 2X/3X V
C
B
ConnectorContactor No.Contactor nameFunctional block name
miniEX1
1AI1 (0-10V)
X19
X20
X21
www.salda.lt
324VDC
1GND
2AO1 (0-10V)
3GND
4AI2 (NTC)
1DO1
224VDC
3DO2
424VDC
A1-Supply air CO2 or RH (input 0-10VDC) 2GND
Electric/Water heater control (output 0-10VDC)
Hydraulic heater water temperature sensor
Working indication output (START). 24VDC; 1,2W max.
Alarm indication output (STOP). 24VDC; 1,2W max.
43
Smarty 2X/3X V
12345678910
KE*
(EKA)
TA
TE**
PE*
(EKA
NIS/
EKA)
AKS***
AKS***
C
ConnectorContactor No.Contactor nameFunctional block name
miniEX1
1DI1
212VDC
3DI2
X23
412VDC
5DI3
612VDC
7DI4
812VDC
Fire protection signal input must be normally closed, until the re protection system is not connected a jumper is installed in the factory.
Automation controller A zone X4.
Electric heater manual protection (NC)
Electric heater automatic protection (NC)
Filter relay/Fire place I, DI (NC)
Filter relay/Fire place II, DI (NC)
1 2 3 4 5 6
In product versions 1.1 pre-heater is integrated inside the product. In product versions 1.2 and 1.3 pre-heater is
integrated on the outdoor air channel. Pre-heater is controlled by 0-10V signal.
Installation diagram.
Installation based on air direction Air Damper M2 -> Pre-Heater PE -> Recuperator.
Wiring diagram.
Automation controller A (X2) and D (X12) zones
PE
-N1
miniMCB V0.3
Max. 2kW/230V
X12:1 - PE
X12:2 - N(L1)
-N1
miniMCB V0.3
X2:5 - GND
X12:3 - DO2(L(L2))
X2:6 - AO3(0-10V)
L1
L2
-K1
-N2
miniMCB V0.3
X2:5 - GND
X2:6 - AO3(0-10V)
123
4
-N2
miniMCB V0.3
X12:1 - PE
X12:2 - N(L1)
X12:3 - DO2(L(L2))
A1
-K1
230VAC
A2
44
N
L1
PE
PE1
0-10V
EKA NIS ... -1F
External preheater.
Control 0-10V
Power up to 2kW, 1f/230V
GND
L1
L2
PE
-PE1
EKS NIS ... -2f
External preheater.
Control 0-10V
Power over 2kW, 2f/400V
External pre-heater is not necessary, unit 1.1 version with internal
pre-heater 0.6 kW is suitable
EKA 125-1,2-1fGKOEKA051219.1017.0.1.2-PS-0k
EKA 125-1,8-1fGKOEKA047219.1017.0.1.2-PS-0k
External pre-heater is not necessary, unit 3.1 version with internal
pre-heater 1.2 kW is suitable
-
-
Functions are activated with external switches.
Automation controller A zone.
System mode switch X7: 1, 2
Fan speed switch X7: 3, 4
Supply air CO2 or RH (input 0-10VDC) connection. This connection is possible for unit version 1.1 miniMCB basic with EX1
controller.
Installation diagram.
Transmitter shall be installed inside supply air duct.
Wiring diagram.
Automation controller B zone X19.
Supply air CO2 or
RH (input 0-10VDC)
Transmitter 2
AO1
GND
AI1(0-10V)
GND
+24VDC
Vin
www.salda.lt
1 2 3
45
Smarty 2X/3X V
Extract air CO2 or RH (input 0-10VDC) connection.
Installation diagram.
Transmitter shall be installed inside extract air duct or room.
Wiring diagram.
Automation controller A zone X7.
Transmiter 1
AO1
Vin
GND
AI4 (0-10V)
GND
+24VDC
1 2 3 4 5 6 7 8
max. 400m
min. 50 cm
150 cm
2
Where the channel CO2 transmitter is used: it must be
installed in the extract air duct. Tool for drilling holes are
required for its installation.
min. 60 cm
46
www.salda.lt
3000Eect on an individual
2500
Reduced concentration, drowsi-
2000
concentration [ppm]
2
CO
1500
1000Pettenkofer limit
500Pleasant
0
01234
C
d
e
s
o
l
C
d
e
l
l
o
r
t
n
o
s
w
o
d
n
i
w
n
io
t
a
l
ti
n
e
v
Outdoor air
Duration of the presence in the room in hours
ness, headache, etc.
Pettenkofer limit Disturbs
Smarty 2X/3X V
Product Smarty 2X/3X V 1.1 version can be equipped with either electric or water heater.
The electric heater can be controlled by:
- On/O – control of electric heater up to 0.6kW/230V or the circulation pump.
- 0-10V – control of electric or water heater.
- Electric heater control by On/O.
Installation diagram.
Electric heater shall be installed inside air duct. Arrangement based on air direction Electric Heater -> Supply Air Sensor (TJ).
KE
TJ
Mini MCB
Wiring diagram.
On/O heater connection. Automation controller D zone X10
and C zone X23. This control method is suitable only to electric
heaters up to 0.6 kW/230 V. In order to control more powerful
heater above 0.6 kW by On/O method, intermediate relay shall
be used where power circuit shall be connected to a separate
power supply.
32 1
DO1 (L(L2)_2)
N(L1)_2
PE
DI3
DI4
+12VDC
+12VDC
1 2 3 4 5 6 7 8
DI2
DI1
+12VDC
+12VDC
www.salda.lt
N
PE
max. 0,6kW;
2,6A; 230V
EKA ... -1F
L
AT1
AT1
RT1
RT1
EKA ... -1F
47
Smarty 2X/3X V
1 2 3 4 5 6 7 8
• Automatic and manual protection shall be connected to EX1 controller X23 connector if the electric heater is
equipped with these connection terminals.
• Otherwise jumpers are installed on X23 connector protection inputs.
DI4
DI3
+12VDC
+12VDC
- Electric heater control 0-10V.
Installation diagram.
Electric heater shall be installed inside air duct. Arrangement based on air
direction Electric Heater -> Supply Air Sensor (TJ).
EKA NIS ... -1F
PE
+12VDC
N
L1
GND
-Q1
DI1
DI2
+12VDC
Wiring diagram.
0-10V heater connection. Automation controller B zone, X20 connector.
0-10V
KE
0-10V
TJ
Mini MCB
PE N L1
1f, 230VAC
AO1 (0-10V)
GND
1 2 3 4
When using the supply air heater, the supply air sensor
(SS) shall be installed downstream the heater (or cooler) as the sensor cable allows or until the rst branching, bend of the air transportation system.
TJ
EKA
48
www.salda.lt
Smarty 2X/3X V
Smarty 2X/3X V 1.2 and 1.3 versions of the product can be connected which an electrical heater, which can be controlled by
- On/O signal EKA;
- 0-10V signal EKA NIS.
Installation diagram
The electrical heater shall be installed in the air duct. The arrangement procedure in the direction of air: electrical heater -> TJ supply air sensor.
KE
TJ
Mini MCB
Connection diagrams SP55 and SP56:
=miniMCB1=miniMCB1
miniMCB V0.2
miniMCB V0.2
miniMCB V0.2
X10:1 - PE
X10:2 - DO1(L(L2))
X10:3 - N(L1)
X5:1 - DI5
X5:2 - +12VDC
X5:3 - DI6
X5:4 - +12VDC
X2:5 - GND
X2:6 - AO3(0-10V)
L
N
PE
AT1
AT1
RT1
RT1
GND
0-10V
miniMCB V0.2
X10:1 - PE
-K1
miniMCB V0.2
miniMCB V0.2
X10:2 - DO1(L(L2))
X10:3 - N(L1)
A1
A2
X5:1 - DI5
X5:2 - +12VDC
X5:3 - DI6
X5:4 - +12VDC
X2:5 - GND
-K1
12345
6
L
N
PE
AT1
AT1
X2:6 - AO3(0-10V)
RT1
RT1
GND
0-10V
=miniMCB1=miniMCB1
miniMCB V0.2
miniMCB V0.2
X10:1 - PE
X10:2 - DO1(L(L2))
X10:3 - N(L1)
X5:1 - DI5
X5:2 - +12VDC
X5:3 - DI6
X5:4 - +12VDC
L
N
PE
AT1
AT1
RT1
RT1
miniMCB V0.2
X10:1 - PE
-K1
miniMCB V0.2
X10:2 - DO1(L(L2))
X10:3 - N(L1)
A1
A2
X5:1 - DI5
X5:2 - +12VDC
X5:3 - DI6
-K1
12345
L
N
PE
X5:4 - +12VDC
6
AT1
AT1
RT1
RT1
KE1
External heater
Control 0-10V
Power up to 0,6 kW - 1f
KE1
External heater
Control 0-10V
Power over 0,6 kW - 1f
KE1
External heater
Control on/off
Power up to 0,6 kW - 1f
KE1
External heater
Control on/off
Power over 0,6 kW - 1f
Since a pre-heater is to be connected according to the factory settings, settings should be changed in the environment of the MB-Gateway WEB application service or on the Ptouch control panel1.
Settings in the environment of the MB-Gateway WEB application service
Change the settings as follows:
• Service password 4444;
• Service -> Heaters -> Heater and pre-heater position;
• Select either the heater or pre-heater to be switched on MiniMCB basic.
1
With the Stouch control panel, it is impossible to change the settings
www.salda.lt
49
Smarty 2X/3X V
• Service -> Digital inputs -> Heaters protection inputs
Set the manual and automated protection statuses of the heater or pre-heater – according to the standards, it should be NC.
• Service -> Heaters -> Supply air heater or Fresh air pre-heater
Set whether it is a heater or pre-heater as well as the type of the heater or pre-heater and actions to be performed in case of the activation of a danger
signal.
Settings with the Ptouch control panel
1. Go to Menu/Service/Heaters. Enter the password (the initial password – 4444);
2. Select Control Position in the settings “Heater on basic” or “Pre-heater on basic”.
3. Go to Menu/Service/Heaters/Heater Set type “E010” 0-10 control, EONOFF On/O control, NONE – heater switch-o, and also specify the
system’s response to danger.
4. Go to Menu/Service/Heaters/Preheater. Set type “E010” 0-10 control, EONOFF On/O control, NONE – heater, pre-heater switch-o. Set the
system’s response to danger.
5. Go to Menu/Service/Digital inputs/Heater protection. Set the manual and automated protection statuses – according to the standards, it should
be NC.
6. Go to Menu/Service/Digital inputs/Preheater protection. Set the manual and automated protection statuses – as a standard, it should be NC.
When using the supply air heater, the supply air sensor
(SS) shall be installed downstream the heater (or cooler) as the sensor cable allows or until the rst branching, bend of the air transportation system.
TJ
EKA
50
www.salda.lt
Smarty 2X/3X V
Product Smarty 2XV and Smarty 3XV all versions can be equipped with fresh air damper and extract air drives. They are controlled by 3-point.
Installation diagram.
See “Principle mounting diagram” - 28-30 p.
Wiring diagram.
Automation controller D zone. Upon activation of output X13:3 the dampers shall open, Upon activation of output X13:4 the dampers shall close.
4 3 2 1
DO3 (L(L2))
DO4 (L(L2))
N(L1)
PE
Wiring diagram.
Automation controller F zone, X18 connector.
Switch positions for X18 connector conguration
SwitchPositionPurpose
1A+Y (RS422->RS485)
2B+Z (RS422->RS485)
3120R line termination resistor
S2
41kR line pull-up resistor
51kR line pull-down resistor
Galvanic isolation disable (turn ON when connecting
6
Remote Controller - RS_GND will be shorted to GND,
OFF - when connecting to BMS)
Wiring diagram.
Automation controller B zone, X21 connector.
N
230VAC
ON/OFF
M2
L1
L1
PEPE
N
230VAC
ON/OFF
M3
Working
indication
output
(START)
L1
Alarm
indication
output
(STOP)
L1
www.salda.lt
H1
H2
+24VDC
DO1
1 2 3 4
+24VDC
DO2
51
Smarty 2X/3X V
Wiring diagram.
Automation controller C zone, X23 connector.
LED indication
miniMCBminiEX1
LED13.3V miniMCB power indication (1W mode)LED1EX1 status LED
LED212V miniMCB power indication
LED33.3V miniMCB power indication (ON mode)
LED4MiniMCB status LED
LED5Communication line Transmit indication
LED6Communication line Receive indication
LED724V peripheral POWER ON indication
1 2 3 4 5 6 7 8
DI3
DI4
+12VDC
+12VDC
-Fire Place II
-Fire Place I
52
www.salda.lt
Smarty 2X/3X V
Electric heater
EKA 125-0,3-1f*
GKOEKA063
Temperature sensor 3 m
TE
PJUT0063
Condensate pump
MAXI BLUE SET
PRGSIK002
Electric preheater
EKA 125-1,2-1f*
GKOEKA051
CO2 sensor
S-RCO2-F2
ZAKKT0048
Remote control panel with
rj45 cable
Ptouch
PRGPU081_rj45
Electric preheater
EKA 125-1,8-1f*
GKOEKA047
CO2 sensor
S-KCO2
ZAKKT0049
Remote control panel with
rj45 cable
Stouch
PRGPU051_rj45
Electric preheater
EKA NIS 125-1,8-1f*
PSIEKANIS22
Channel humidity transmit-
ter
S-KFF-U
ZAKKT0051
Net module
MB Gateway
GAUMBGATEWAY001
Electric preheater
EKA NIS 125-1,2-1f*
PSIEKANIS20
Humidity transmitter
S-RFF-U-D-F2
ZAKKT0050
Actuator for damper
CM230-F-L
ZAKP0076
Legs
Smarty legs
GAGKSMARTY168_1004
Damper
SKG 125
GSKSKG002
www.salda.lt
Filters 270x121x25/F7
* Smarty 2X V 1.1 has an integrated electrical pre-heater, which is intended for the use only up to -15 °C. In order to
operate the product at temperatures below -15 °C, it is recommended to use a duct-mounted pre-heater (see the table). Smarty 2X V 1.1 version can control a pre-heater and heater at the same time. Smarty 2X V 1.2 and 1.3 versions
do not have an integrated pre-heater, and can control only either a pre-heater or heater at a time.
MPL
ZFEPF127
(optional)
Filters 270x121x25/G4
MPL
ZFEPF129
Filters 270x187x25/G4
MPL
ZFEPF128
Silencer
AKS 125-9
GSOAKS004
53
Smarty 2X/3X V
Bypass damper
Damper***
GPUSK227_1016_1016
Heat exchanger
Heat exchanger
ZSLPLGS0024
Electrical heater
Heater
ZSIS220_1017_1017
Temperature sensor 3 m
TJ
PJUT0063
Control board without
presure sensores
Mini MCB*
GAUSM219_1017_1045
Temperature sensor 1,5 m
TL/TA
PJUT0062
Control board
Mini MCB Basic**
GAUSM219_1017_1020
Supply/extract air fan
Fan
GPUVM224_1026_1026
Smarty 2X V door
Door
GPUD232_1027_0
* Smarty 2X V 1.1 version only
** Smarty 2X V 1.2 and V 1.3 versions only.
*** Smarty 2X V 1.1 and V 1.2 versions only.
54
www.salda.lt
Smarty 2X/3X V
Electrical heater
EKA 160 0.3-1f*
PSIEKA075
Temperature sensor 3 m
TE
PJUT0063
Condensate pump
MAXI BLUE SET
PRGSIK002
Electrical preheater
EKA NIS 160-5,0-2f*
PSIEKANIS27
CO2 sensor
S-RCO2-F2
ZAKKT0048
Damper
SKG 160
GSKSKG003
CO2 sensor
S-KCO2
ZAKKT0049
Remote control panel with
rj45 cable
Ptouch
PRGPU081_rj45
Silencer
AKS 160-9
GSOAKS006
Channel humidity transmit-
ter
S-KFF-U
ZAKKT0051
Remote control panel with
rj45 cable
Stouch
PRGPU051_rj45
Supply and extract air
grating
WSG
GGRWSG0126_509
Humidity transmitter
S-RFF-U-D-F2
ZAKKT0050
Net module
MB Gateway
GAUMBGATEWAY001
Actuator for damper
CM230-F-L
ZAKP0076
Legs
Smarty legs
GAGKSMARTY168_1004
* Smarty 3X V 1.1 has an integrated electrical pre-heater, which is intended for the use only up to -15 °C. In order to operate the product at temperatures below -15 °C, it is recommended to use a duct-mounted pre-heater (see the table). Smarty 3X V 1.1 version can control a pre-heater and heater
at the same time. Smarty 3X V 1.2 and 1.3 versions do not have an integrated pre-heater, and can control only either a pre-heater or heater at a time.
www.salda.lt
Filter 475x134x25 G4 with
band
MPL
ZFEPF120
Filer 475x180x25 G4 with
band
MPL Z
ZFEPF121
Filer 475x134x25 F7 with
band
MPL
ZFEPF119
(optional)
55
Smarty 2X/3X V
Damper
Damper***
GPUSK227_1016_1016
Heat exchanger
Heat exchanger
ZSLPLGS0023
Temperature sensor 3 m
TJ
PJUT0063
Electric heater
Heater
ZSIS220_1017_1018
Supply/extract air fan
Fan**
GPUVM224_1021_1021
Temperature sensor 1,5 m
TL/TA
PJUT0062
Control board
Mini MCB*
GAUSM219_1017_1017
Supply/extract air fan
Fan*
GPUVM224_1020_1020
Control board
Mini MCB Basic**
GAUSM219_1017_1020
Supply/extract air fan
Fan*
GPUVM224_1032_1032
Smarty 3X V door
Door
ZSIS220_1017_1018
Supply/extract air fan
Fan**
GPUVM224_1034_1021
* Smarty 3X V 1.1 version only.
** Smarty 3X V 1.2 and 1.3 versions only.
*** Smarty 3X V 1.1 and 1.2 versions only.
56
www.salda.lt
Smarty 2X/3X V
1. All equipment manufactured in our factory is checked in operating conditions and tested befor delivery. Test protocol is supplied together with the
unit. The equipment is shipped in good working order and condition to the direct client. The unit is warrantied for the period of two years from the
invoice date.
2. If equipment is found to have been damaged during transportation, a claim should be made against carrier, as we assume no responsibility for such
damage.
3. This warranty does not apply:
3.1. when transportation, storage, installation and maintenance instructions of the unit are violated;
3.2. when the equipment is improperly maintained, mounted - inadequate maintenance;
3.3. when the equipment without our knowledge and permission has been upgraded or unskilled repairs were made;
3.4. when the unit was used not for its original purpose.
4. This warranty does not apply at these malfunction cases:
4.1. mechanical damage;
4.2. damage caused by entering outside objects, materials, liquids;
4.3. damage caused by natural disaster, accident (voltage change in the electricity network, lightning, etc..).
5. The company assumes no liability for its products either directly or indirectly damage, if the damage is caused by failure to comply with installation
and mounting regulations, deliberate or careless users or third-party behavior.
These conditions are readily discernable when the equipment is returned to our factory for inspection.
If the direct client determines that equipment is found to be faulty, or a breakdown occurred, he should inform the manufacturer within ve working days
and deliver the equipment to manufacturer. Delivery costs should be covered by customer.
www.salda.lt
57
Smarty 2X/3X V
NOTE. The purchaser is required to ll in the “Product maintenance table”.
*
2
- At least.
*
1
-Look at the product label.
Filter replacementEvery 3-4 months
*
2
Heat exchanger cleaningOnce a year
*
2
Fan cleaningOnce a year
*
2
Instalation
IntervalDate
gu/lu number
*
1
Product name
*
1
58
www.salda.lt
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.