5.5.2. PLACE REQUIREMENTS FOR THE EQUIPMENT AND MOUNTING POSITIONS 11
5.5.3. CONNECTION OF AIR DUCTS 12
5.5.4. AIR FLOW 12
5.5.5. CONNECTION OF THE KITCHEN HOOD 12
5.5.6. SHIELD INSTALLATION 13
5.6. CONNECTION OF THE UNIT TO ELECTRIC NETWORK 13
5.7. START-UP RECOMMENDATIONS 13
5.7.1. SYSTEM PROTECTION 13
5.7.2. PRE-STARTUP RECOMENDATIONS OF THE UNIT (IN THE PRESENCE OF THE ENDUSER) 14
6. MAINTENANCE 14
6.1. SAFETY INSTRUCTION 14
6.2. COVER OPENING 14
6.3. FILTERS MAINTENANCE 15
6.4. FANS MAINTENANCE 15
6.5. HEATER MAINTENANCE 16
6.6. ROTOR MAINTENANCE 16
7. CONTROL 17
7.1. DEVICE CONTROL 17
7.2. MEANING OF THE SYMBOLS USED IN THE INSTRUCTIONS AND ON THE DEVICE 17
7.3. DESCRIPTIONS OF THE FUNCTIONS 17
7.4. DESCRIPTION OF THE UNITS FUNCTIONS 18
7.4.1. SYSTEM MODES 18
7.4.2. SYSTEM CONTROL 19
7.4.3. SYSTEM STATES 20
7.4.4. SETTING DATE AND TIME 20
7.4.5. SUPPLY AIR TEMPERATURE CONTROL AND COMPENSATION 20
7.4.6. FAN CONTROL 21
7.4.7. “BOOST“ FUNCTION 21
7.4.8. WEEKLY SCHEDULE 21
2 | EN SMARTY RV v2019.12
7.4.9. HOLIDAY SCHEDULE 21
7.4.10. WINTER/SUMMER MODE 21
7.4.11. DRYNESS PROTECTION 21
7.4.12. NIGHT COOLING FUNCTION 22
7.4.13. CO2 REDUCTION FUNCTION 22
7.4.14. FILTER PROTECTIONS 22
7.4.15. SYSTEM MODE COMMUNICATION WITH EXTERNAL CONTACTOR 22
7.4.16. FAN SPEEDS FROM AN EXTERNAL SYSTEM CONTACTOR 22
7.4.17. HEAT EXCHANGER CONTROL 23
7.4.18. SYSTEM MONITORING 23
7.4.19. STAND-BY MODE BLOCKING 23
7.4.20. AIR FLOW ADJUSTMENT 23
7.4.21. MANUAL CONTROL OF COMPONENTS 23
7.4.22. CHANGING PASSWORDS 24
7.4.23. RESTORING FACTORY DEFAULTS 24
7.4.24. INDICATIONS OF FUNCTIONS, ALARMS AND WARNINGS 24
7.4.25. DISPLAY AND CONCELLATION OF ALARMS AND WARNINGS 24
7.4.26. EVENT LOG (HISTORY) 25
7.4.27. SYSTEM VERSIONS AND RUNNING TIME 26
8. ACCESSORIES 26
8.1. CONNECTION FO ACCESSORIES 27
8.1.1. SCHEMATIC OF CONTROLLER CONNECTIONS IN MCB 27
8.1.2. CO2 SENSOR OR CONNECTION OF HUMIDITY SENSOR RH 29
8.1.3. ROOM CO
TRANSMITTER INSTALLATION RECOMMENDATION 30
2
8.1.4. CO2 CONCENTRATION ACCORDING TO PETTENKOFER LIMIT 31
8.1.5. FIRE PROTECTION INPUT (NC) 31
8.1.6. EXTERNAL SWITCHES 31
8.1.7. CONNECTION OF REMOTE CONTROL PANEL OR MODBUS 32
8.1.8. “MCB TOOL” PROGRAM DESCRIPTION 32
8.2. THE PRINCIPAL CONNECTION SCHEME OF INTERNAL AND EXTERNAL COMPONENTS 34
8.3. ELECTRICAL CONNECTION OF THE UNITS 48
9. POSSIBLE FAULTS AND TROUBLESHOOTING 49
10. SENSORS AND THEIR TECHNICAL INFORMATION 49
11. INSPECTION OF THE VENTILATION SYSTEM 49
12. ECODESIGN DATA TABLE 50
13. DECLARATION OF CONFOMITY 51
14. WARRANTY 52
14.1. LIMITED WARRANTY COUPON 52
EN | 3SMARTY RV v2019.12
2. SYMBOLS AND MARKING
LN: XX000000
2019.01.01
Stick the auxiliary label on the unit (on an easily accessible place) or on the dashed place of a technical manual in order to keep the important
information about the unit.
LN: XX000000
2019.01.01
Figure 2.1 - Technical label
1 - Logo; 2 - Product code (SKU); 3 - Product name; 4 - Technical data; 5 - Production place; 6 - Batch number and production date; 7 - Serial
number.
Figure 2.2 - Indication for duct connection.Figure 2.3 - indication of kitchen hood
ODA - outdoor air; SUP - supply air; ETA - extract air; EHA - exhaust air.
3. SAFETY INSTRUCTIONS AND PRECAUTIONS
Read this instruction very carefully before installing and using this equipment. Installation, connection and maintenance should be carried out by
a qualifed technician and in accordance with the local rules and legal acts.
The company shall take no responsibility for the injuries suered by the people or for the damaged property, if the safety requirements are not
followed or the device is modifed without the permission of the manufacturer.
Warning – pay attentionAdditional information
Main safety rules
Danger
• Before performing any electricity or maintenance tasks make sure, that the device is disconnected from the mains, that all moving parts
of the device have stopped.
• Make sure that the fans can not be entered through air ducts or branch openings.
• If you notice liquids on electric parts or connections that bear voltage, stop the operation of the appliance.
• Do not plug the device into the mains, that diers from the one indicated on the label or on the housing.
• Voltage of the mains should comply with the electrotechnical parameters indicated on the label.
• The device should be earthed in accordance with the rules of installation of electric appliances. It is forbidden to turn on and use unearthed device. Follow the requirements of the device’s labels that indicate Danger.
Warnings
• Connection of electricity and maintenance of the device should be performed only by a qualied personnel, in accordance with the
manufacturer’s instructions and valid safety requirements.
• In order to reduce the risk during installation and maintenance, suitable protective clothes should be worn.
• Beware of sharp angles while performing installation and maintenance tasks.
• Do not touch heating elements until they haven’t cooled down.
• Some devices are heavy, thus one should be very careful while transporting and installing. Use suitable lifting equipment.
• While connecting electricity to the mains a circuit breaker of suitable size is necessary.
Warning!
• If the device is installed in a cold environment, make sure that all connections and tubes are properly isolated. Intake and discharge air
ducts should be isolated in all cases.
• Openings of the ducts should be covered during transportation and installation.
• Make sure not to damage the heater when connecting the piping of the water heater. For tightening up, use a wrench/spanner.
4 | EN SMARTY RV v2019.12
Before starting the equipment
320 mm
653 mm
• make sure, that there are no strange objects inside;
• manually check whether fans are not stuck or blocked;
• if rotary heat exchanger is installed in the device, make sure that it is not stuck or blocked;
• check the grounding;
• make sure that all components and accessories are connected in accordance with the project or provided instructions.
Danger: Fumes
Salda Antifrost system uses dis-balancing of the air ow and it may cause negative pressure in premises. Great care should be taken
when using at the same time in premises as another heating appliance what depend on the air in premises. Such appliances include
gas, oil, wood or coal-red boilers and heaters, replaces, continuous ow or other water heaters, gas hobs, cookers or ovens which
draw air in from the room and duct exhaust gases out through a chimney or extraction ducting. The heating appliance can be starved
of oxygen, impairing combustion. In exceptional cases harmful gases could be drawn out of the chimney or extraction ducting back
into the room. In this case we strictly recommend to turn o Salda Antifrost and use an external preheater for heat exchanger anti-frost
protection (see Salda Antifrost function on the Remote controller manual).
4. INFORMATION ABOUT THE PRODUCT
4.1. DESCRIPTION
HRU Residential is a residential air handling unit with a high eciency (up to 75 %) rotor heat exchanger with integrated electrical heater. The unit
provides ventilation in the home and takes the heat from the exhausted air. AHU complies with ErP 2018 requirements. The unit is operated by a
separate remote control panel or though separate MB-Gateway by PC. Remote control panel and MB-Gateway are optional and not included in
standard package.
HRU Residential operates within the limits of the airow diagrams and is suitable for indoor operation only. Required ambient temperatures must
be from -20 oC to +40 oC. For the cold climate zones (air temperatures below -20 oC), optional pre-heater is required.
Unsuitable for operation in pools, saunas and other similar premises.
4.2. DIMENSIONS AND WEIGHT
620 mm
224,5 mm
98 mm
320 mm
116,3 mm
105,7 mm
84 mm
Ø 125 mm
276,3 mm
598 mm
598 mm
273,1 mm
237,7 mm
100,4 mm
653 mm
320 mm
160 mm
620 mm
286 mm
598 mm
Ø 175 mm
SMARTY
2R VER2R VER PLUS
m[kg]3636
4.3. TECHNICAL DATA
SMARTY
Heat exchange
- phase/voltage[f/VAC/Hz]~1/230/50~1/230/50
2R VER2R VER PLUS
EN | 5SMARTY RV v2019.12
- power/current[kW/A]0,006/0,10,006/0,02
-thermal eciency up to75%75%
Heater
- power/current[kW/A]0,6/2,610,6/2,61
Exhaust air fan
- phase/voltage
- power/current
- speed
- protection classIP44IP54
- control imput[VDC]0-100-10
Supply air fan
- phase/voltage
- power/current
- speed
- protection classIP44IP54
- control imput[VDC]0-100-10
Total
- power/current[kW/A]0,75/3,910,77/4,13
Automatic control integrated
Insulation of walls
Weight
Exhaust air lter
class classePM10 55%ePM10 65%
width[mm]270270
height[mm]8685
depth[mm]46173
modelMPLFMK
Supply air lter
classePM10 55%ePM10 65%
width[mm]270270
height[mm]8685
depth[mm]46173
modelMPLFMK
[f/VAC/Hz]~1/230/50~1/230/50
[kW/A]0,07/0,60,084/0,75
[min-1]13803200
[f/VAC/Hz]~1/230/50~1/230/50
[kW/A]0,07/0,60,084/0,75
[min-1]13803200
++
[mm]2020
[kg]3636
SMARTY 2R VER
Outdoor622254614841272014
Supply 702961685960554943
Extract622254614936281914
Exhaust692860675858524841
Surrounding491040483631303029
Measured at 140 m3/h, 50 Pa
SMARTY 2R VER PLUS
Outdoor601850585544281612
Supply 662355636156554840
Extract601950585440352417
Exhaust662355626056534636
Surrounding48334444532313029
Measured at 180 m3/h, 50 Pa
NOTE. Subject to technical modication
LWA TOTAL,
DB(A)
LWA TOTAL,
DB(A)
63 Hz125 Hz250 Hz500 Hz1 kHz2 kHz4 kHz8 kHz
63 Hz125 Hz250 Hz500 Hz1 kHz2 kHz4 kHz8 kHz
LWA, DB(A)
LWA, DB(A)
6 | EN SMARTY RV v2019.12
4.3.1. AIR FLOW DIAGRAMS
Performance
Power consumption
SMARTY 2R VERSMARTY 2R VER PLUS
Supply airSupply air
Exhaust airExhaust air
Temperature eciencyTemperature eciency
Temperature eciency (balanced mass ow):
Extract air = - 20 °C / 90 % RH
4.4. OPERATING CONDITIONS
• Unit is designed to operate only indoors.
• It is forbidden to use the unit in potentially explosive environment.
• Unit is designed to supply/extract only clean air (free of chemical compounds causing metal corrosion, of substances aggressive to zinc,
plastic and rubber, and of particles of solid, adhesive and bred materials).
OUTDOOR AIR
- temperature min./max.*[°C]-23 / +40
- humidity[%]90
EXTRACT AIR
- temperature min./max.*
- max. humidity
[°C]+15 / +40
[%]60
* Can be used at temperatures below -23 °C with pre-heater, the power of which is over 600W.
EN | 7SMARTY RV v2019.12
+40 C
10
9
10
9
o
+5 C
o
o
+40 C
o
-23 C
Figure 5.4.1 - operating conditions
4.5. STANDARD PACKAGE OF COMPONENTS
Standard package (without optional accessories) includes:
• Mounting brackets (mural and unit parts), Rubber seal for vibration damping.
• Screws M5x25 DIN7985 CT for mounting brackets - 3 pcs.; 5. Spring washers DIN127 5 - 3 pcs.
• Bushing caps - 8 pcs.
• Antivibration stick - 2 pcs.
• Key - 1 pcs.
4.6. DESCRIPTION OF COMPONENTS
+40 C
+15 C
o
o
9
9
Figure 5.3.1 - Smarty 2R VER constructionFigure 5.3.2 - Smarty 2R VER plus construction
Rotor boxRotor boxGPURSD085_330
Temperature sensor 3 mTJPJUT0063
Temperature sensor 1,5 mTL/TAPJUT0062
ControlerMCB V1.0ZED00985
Hall sensorHall H1A-D12P24-1PJUT0006
Electrical heater
SRR 0,6-1f EC-1k
(Smarty 2R VER)
SRR V-0,6-1f
(Smarty 2R VER plus)
ZESSRR028
ZESSRR032
5. INSTALATION
5.1. RECEPTION OF GOODS
Each device is thoroughly checked before transportation. When receiving goods it is recommended to check whether devices were damaged
during transportation. If damage to the device is identied, immediately inform the representatives of a transport company. Please inform a representative of the manufacturer, if any deviation from the order is noticed.
5.2. TRANSPORTATION AND STORAGE
• All units are packed in the factory to withstand regular conditions of transportation.
• Upon unpacking, check the unit for any damages caused during transportation. It is forbidden to install damaged units!!!
• The package is only for protection purpose!
• While unloading and storing the units, use suitable lifting equipment to avoid damages and injuries. Do not lift units by holding on power sup-
ply cables, connection boxes, air extract or exhaust anges. Avoid hits and shock overloads. Before installation units must be stored in a dry
room with the relative air humidity not exceeding 70% (at +20 °C) and with the average ambient temperature ranging between +5 °C and +30
°C. The place of storage must be protected against dirt and water.
• The units must be transported to the storage or installation site using forklifts.
• The storage is not recommended for a period longer than one year. In case of storage longer than one year, before the installation it is necessary to verify whether the bearings of fans and motor rotate easily (turn the impeller by hand) and if the electric circuit insulation is not damaged
or the moisture is accumulated.
2020 mm
1200 mm
780 mm
EN | 9SMARTY RV v2019.12
5.3. UNPACKING
M
CO
2
5.4. MOUNTING DIAGRAM
Figure 5.4.1 - Smarty RV (** Only one sensor can be used at a time)
Figure 5.4.2 - Indication for duct connection.Figure 5.4.3 - Ventilated premisesFigure 5.4.4 - Air from cooing hood
LIST OF COMPONENTS
CPlate heat exchangerA1Fire alarm damper actuator I
PVSupply air fanA2Fire alarm damper actuator II
IFExtract air lterTJSupply air temperature sensor
PFSupply air lterTLOutdoor air temperature sensor
IVExhaust fanTEExhaust air temperature sensor
KE1Electric heaterDTJExtract air temperature and RH sensor
PE1Electric pre-heaterT2Cooler changeover thermostat
KV2Water pre-heaterTV2Water preheater temperature sensor
KV3Water coolerTV3Water cooler temperature sensor
DXDX coolerU3PV pressure transmitter
M1By-pass damperU4IV pressure transmitter
M2Outdoor air damper actuatorCO
M3Exhaust air damper actuatorRHRH sensor*
M5Water cooler valve motorPCComputer
M12Water pre-heater valve actuatorRC1Stouch or SA-Control remote control panel
M14Water cooler circulation pumpRC2Stouch, Flex or SA-Control remote control panel
M15DX cooler valve actuatorMB-GatewayNetwork module
M16Water pre-heater circulation pumpNETNetwork
RRotor heat exchanger
System mode switch (START/STOP)Fans speed switch (BOOST)
* Compone
5.5. MOUNTING
• Installation should only be performed by qualied and trained sta.
• When connecting air ducts, consider the notices indicated on the casing of the unit.
• Before connecting to the air duct system, the connection openings of ventilation unit should be closed.
• Do not connect the bends close to connection anges of the unit. The minimum distance of the straight air duct between the unit and the rst
branch of the air duct in the supply air duct must be 1xD, in air exhaust duct 3xD, where D is diameter of the air duct.
• It is recommended to use the accessories-holders. This will reduce vibration transmitted by the unit to the air duct system and environment.
• Enough space must be left for opening of the maintenance door and lter covers.
• If the installed ventilation unit is adherent to the wall, it may transmit noise vibrations to the premises. Though the level of noise caused by the
fans is admissible, it is recommended to mount the unit at the distance of 400 mm from the nearest wall. If it is not possible, the mounting of
the unit is recommended on the wall of the room where the level of noise is not important.
• Ducts are connected to the unit in such way that they could be easily disassembled and the heater could be removed from the unit when
performing service or repair works.
5.5.1. MOUNTING ON THE WALL
90
90
30 mm
acd
b
Mounting on the wall:
a) To reduce the vibration stick the insulating tape on the unit‘s casing side which touches the wall before mounting the unit on the wall.
b) The unit has to be mounted on the mounting brackets.
c) AHU mounting drawing.
d) After the unit is mounted two wall bracket tabs has to be folded to 90o angle by pliers to avoid the accident fall of the unit.
5.5.2. PLACE REQUIREMENTS FOR THE EQUIPMENT AND MOUNTING POSITIONS
1. The installation position only in the horizontal direction.
2. Install the supporting legs.
3. AmberAir Compact are assembled from separate sections.
4. They must be adjusted without a gradient.
5. Leave space in the front (2xL) that it would be sucient to open the doors and to remove or install a required component.
EN | 11SMARTY RV v2019.12
5.5.3. CONNECTION OF AIR DUCTS
• Connected air ducts must be straight and have their own xing.
• Make sure that the fans can not be accessed through air duct heads. If it is possible to access the fan, protective grid should be installed. You
can choose it in our website.
• Do not reduce the diameter of the piping near air inlet or exhaust ducts. If you want to reduce the speed of air in the system, drop of pressure
and noise level, you can increase the diameter.
• In order to reduce the level of the noise in the air supply system, install silencers (see chapter on their installation).
• In order to reduce air loss in the system, the air ducts and prole parts should be of class C and higher. Their catalog can be found in our
website.
• If air handling unit is installed in heated premises, outdoor and exhaust air ducts must be insulated in order to avoid heat loses and condensing.
If AHU is installed outdoors, it’s recommended to insulate all the air ducts.
• It is recommended to maintain a distance of up to 8 meters between air intake and air exhaust ducts. Air supplying system should be installed
further from potential air pollution sources.
• Use holders while installing air ducts next to the ventilation equipment. They suppress vibration and ensure a rm installation of various system
parts.
• Necessary holders can be found in our catalog or website.
• A common mistake is that air ducts are attached to improper airow connection. On the ventilation equipment there are signs, indicating the air
duct to be connected. Before starting the system carefully check whether the work was performed properly.
5.5.4. AIR FLOW
The maintenance side can be changed for the ventilation unit, i.e. it can be mounted with the left ambient air inlet or the right ambient air inlet. That
can be implemented by switching over the back door and the front door. The default version of the ventilation unit is right.
• Installation works must be performed only by trained and qualied personnel.
• If you have any questions regarding the save installation and use of the product, please contact the manufacturer or the representative.
• Before installing the unit, unscrew the lid a covering the opening for connection of the kitchen hood and remove the middle part of the insulating ring.
• Cut the connecting opening as indicated on the insulation material.
• Carefully remove the lid, which covers the electric connection for the connection of the electrical part of the kitchen hood to the ventilation unit.
• Mount the hood to the ventilation unit. Fasten with self-tapping screws to the designated connection points.
• It is necessary to ensure the tight and reliable connection of the air ducts of the kitchen hood to the ventilation unit and the electrical contact
of the control circuit.
• The subsequent installation of the device is performed according the description in chapter “Mechanic installation”.
• Properties, assembly, control, use and maintenance of the kitchen hood are described in its instalation manual.
12 | EN SMARTY RV v2019.12
Use cooker hood supplied by our company only. Equipment is not tested with other cooker hoods and company holds no
responsibility for malfunction or failures of the equipment in this case.
5.5.6. SHIELD INSTALLATION
5.6. CONNECTION OF THE UNIT TO ELECTRIC NETWORK
• Supply voltage to the unit must be connected by a qualied specialist following the manufacturer’s instructions and eective safety instructions.
• The unit’s power network voltage must correspond to electrotechnical parameters of the unit indicated in the technical decal.
• The unit’s voltage, power and other technical parameters are provided in the unit’s technical decal (on the unit casing). The unit must be con-
nected to the voltage plug socket of the grounded power network in compliance with the eective requirements.
• The unit must be earthed according to the rules on installing electrical equipment.
• It is prohibited to use extension wires (cables) and power network plug socket distribution devices.
• Prior to carrying out any ventilation unit installation and connection activities (until its hand-over to the customer), the unit must be disconnected from the power network.
• After installation of the ventilation unit, the power network plug socket must be accessible at any time and disconnection from the power network is performed through the two-pole circuit breaker (by disconnecting phase pole and neutral).
• The unit must be thoroughly checked against damages (execution, control, measurement nodes) during transportation before it is connected
to the power network.
• The power cable can be replaced only by a qualied specialist upon the evaluation of the rated power and current.
The manufacturer does not assume any liability for personal injuries and property damage due to non-conformance with
the provided instructions.
5.7. START-UP RECOMMENDATIONS
5.7.1. SYSTEM PROTECTION
Control system of the unit has an integrated protection against short-circuit for these functional components. The controllers have the following
protections:
MCB
F1, F2 - 1A(5x20) MCB protection
To ensure safe maintenance of the unit, it is necessary to remove the plug from the power network.
EN | 13SMARTY RV v2019.12
5.7.2. PRE-STARTUP RECOMENDATIONS OF THE UNIT (IN THE PRESENCE OF THE ENDUSER)
Prior to start-up the system must be thoroughly cleaned. Check whether:
• operation systems and unit elements as well as automation and automation devices were not damaged during installation,
• all consumers are connected to power supply and t for service,
• all necessary automation elements are installed and connected to power supply and MCB terminal blocks,
• cable connection to MCB terminal blocks comply with the existing power connection diagrams,
• all electrical equipment protection elements are properly connected (if they are additionally used),
• cables and wires correspond to all applicable safety and functional requirements, diameters, etc.,
• earthing and protection systems are properly installed,
• condition of all seals and sealing surfaces is proper.
6. MAINTENANCE
Unplug unit from mains before opening the door (disconnect the power plug from the outlet or if there is a two-pole automatic
circuit breaker installed – disconnect it as well. It is necessary to ensure that it won’t be turned on by third parties) and wait
until the full stop of the fans (for about 2 min.).
6.1. SAFETY INSTRUCTION
• Do not use the unit for purposes other than its’ intended.
• Do not disassemble or modify the unit in any way which may lead to mechanical failure or injury.
• Use special clothing and be careful while performing maintenance and repair jobs – the unit’s and its components’ edges may be sharp and cutting.
• Do not wear loose clothing that could be entangled in to operating unit.
• If a outside object enters the unit, immediately disconnect power source. Before removing object, make sure that any mechanical motion has
stopped, the heater has cooled down and the restart is not possible.
• Do not connect to any other power source than indicated on the model label.
• Do not place or operate unit on unsteady surfaces and mounting frames.
• Mount the unit rmly to ensure safe operating.
• Never use this unit in the environment containing any explosive or aggressive elements.
• Do not use the unit if external connections are broken or damaged. If there are any defects, stop operating the unit and replace the damaged parts
immediately. That can be performed only by qualied electrician.
• Do not use water or another liquid to clean electrical parts or connections.
• If you notice condensat on electrical parts or connections, stop operating the unit.
6.2. COVER OPENING
14 | EN SMARTY RV v2019.12
6.3. FILTERS MAINTENANCE
Figure 6.3.1 - Smarty 2R VERFigure 6.3.2 - Smarty 2R VER plus
Dirt increases air resistance in the lter, therefore less air is supplied into the premises.
Taking o the lters:
• Open cover.
• Remove the lter.
Changing lters, lters reload timer control. Description of remote control panel functions is provided in the remote control
panel technical documentation or on the website www.salda.lt.
Allowed to operate the unit without lters!
It is recommended to change the lters every 3-4 months, or in accordance to lter timer.
6.4. FANS MAINTENANCE
• Maintenance should be performed only by experienced and trained sta.
• The fan should be inspected and cleaned at least once a year.
• Be sure the fan is disconnected from power source before performing any maintenance or repair.
• Proceed to maintenance and repair after any rotation in the fan is stopped.
• Observe sta safety regulations during maintenance and repair.
• The motor is of heavy duty ball bearing construction. The motor is completely sealed and requires no lubrication for the life of the motor.
• Detach fan from the unit.
• Impeller should be specially checked for buil-up material or dirt which may cause an imbalance. Excessive imbalance can lead to accelerated
wear on motor bearings and noise, vibration.
• Clean impeller and inner housing with mild detergent, water and damp, soft cloth.
• Do not use high pressure cleaner, abrasives, sharp instruments or caustic solvents that may scratch or damage housing and impeller.
• Do not plunge the motor into any uid while cleaning impeller.
• Make sure, that impeller ’s balance weights are not moved.
• Make sure the impeller is not hindered.
• Mount the fan back into the unit. Connect the fan to power supply source.
• If after maintenance the fan does not start or stop itself, contact the producer. Malfunction of the fan can be identied according to the pressure
in the system (when pressure switches are connected). When there is a fault in fans’ motor, any separate notice is shown on the control panel.
Figure 6.4.1 - Smarty 2R VER
EN | 15SMARTY RV v2019.12
Figure 6.4.2 - Smarty 2R VER plus
Be sure the unit is disconnected from power source before performing any maintenance or repair.
6.5. HEATER MAINTENANCE
• Electrical heater does not need to be serviced additionally. It is compulsory to change lters as described above.
• Heaters have 2 thermal protections: automatically self-resetting, which activates at +50°C and the manually restored, which activates at
+100°C.
• After the activation of the manually restored protection, the unit must be disconnected from the power supply. Wait until the heating elements
cool down and the fans stop rotating. After identifying and removing the reason of failure, to start the unit, press the “reset” button. The failure
can be identied only by a qualied professional.
• If necessary, the electric heater can be removed. Disconnect the electrical connector from the heater and remove the heater.
Figure 6.5.1 - Smarty 2R VER
1
a
b
a
2
3
Figure 6.5.2 - Smarty 2R VER plus
6.6. ROTOR MAINTENANCE
• Rotor heat exchanger must be serviced once a year.
• Ensure that the gaps of the heat exchanger are clean, the brushes are not worn, the belt drive is not worn and the clamping nodes of the rotor
heat exchanger are tight.
• Rotor heat exchanger can be easily removed from the unit. The power cord of the motor of the heat exchanger is disconnected. The clamp of
rotor heat exchanger section is released and raised and the heat exchanger is removed.
• The heat exchanger is cleaned using the solution of warm water and non-corrosive toward aluminum alkaline agent or the air stream. It is not
recommended to apply direct stream of liquid as it can harm the device.
16 | EN SMARTY RV v2019.12
• While cleaning, protect the motor of heat exchanger from entry of moisture and uids.
• After reinstalling the heat exchanger, fasten the heat exchanger section with the clamp. Connect the heat exchanger motor.
CAUTION: the heat exchanger can not be used when the lters are removed!
7. CONTROL
7.1. DEVICE CONTROL
Ventilation unit can be controlled using a remote control, web interface via MB-Gateway and building management system. More information about
the possibilities of controlling is provided in the table below.
MB-Gateway + WIFI + SALDA AIR appStouchFLEX MCBSA-ControlMB-GatewayBMS
+++++Modbus RTU
7.2. MEANING OF THE SYMBOLS USED IN THE INSTRUCTIONS AND ON THE DEVICE