Application Ventilation of houses, oces or other heated premises (classrooms, apartments, conference rooms, etc.)
Description
AIR HANDLING UNITS
A1/L2
V [m3/h]
RIS P EKO 3.0 is a range of heat recovery units with high-eciency counter-ow heat exchangers and low
height. The units are designed for mounting under ceilings in order to save space. There are 5 sizes (airow
interval 420-2500 m3/h) with separate heaters available for dierent climate zones.
RIS P EKO 3.0 units have high overall energy savings due to the highly ecient heat recovery (up to 90%),
quiet and economical EC fans, eective low-pressure-drop lters, 100% motorized bypass dampers (for the
1900 and 2500 versions) and top-level of air tightness.
Energy eciency ensures full thermal comfort for passive houses, without an additional pre-heater at
temperatures above -5°C.
All the RIS P EKO 3.0 units are fully equipped with automatic controls. Optional external sensors for CO2 and
humidity and the event planning feature will help to control automatically your climate (demand-level control).
RIS P EKO 3.0 units are service-friendly and are easy to mount. Filter pollution may be identied by timers
or contamination controls (RIS 1200-2500 P EKO 3.0).
All units are supplied tested and ready to install.
Three remote control options are available:
Remote control
Features
Construction
1. Flex, Stouch or Ptouch remote controllers.
2. Building management system connections.
3. Remote control via PC MB-Gateway.
› Ideal for ceiling installations.
› Ready for Passive House technology: high eciency.
› Easy and quick mounting.
› Water/electrical heating options.
› Fully integrated plug-and-play control system.
› Frameless construction from double-skinned panels.
› Acoustic and thermal wall insulation: RIS 400–2500 P EKO 3.0 – 30/50 mm.
› RIS 400-700 P EKO 3.0 powder-coated white housing RAL 9016; RIS 1200–2500 P EKO 3.0 powder-coated
grey housing RAL 7040.
› Integrated electrical heater or optional duct-based water heater/cooler.
› Low-pressure-drop lters: F7/M5.
› Hinged door with locks grants easy access to internal components.
› Separate compartment on the side of the unit grants quick access to the control board (plug-and-play).
› Stainless steel condensate tray.
› Fitted with mounting brackets.
› Integrated anti-frost pressure switch (RIS 1200-2500 P EKO 3.0).
RIS 400 P E 0.9 EKO 3.0
Equipped with new PRV V2 control board
AHU with EC motors and ecient heat exchanger
Electrical heater power in kW
Heater type (E - integrated electrical heater; W - prepared for water heater)
Housing type (V - vertical, H - horizontal, P - ceiling)
AHU size according to maximum airow range m3/h
AHU with plate heat exchanger
64
The company reserves the right to make changes of technical data without prior notice
Thermal eciency up to*90%
Motorized by-pass+
Max power consumption
Control boardPRV V2
Filter class
Housing insulation, mineral wool
Colour
Weight (net, without packing)
Comply with ERP2016; 2018
Operationindoors
Fresh air temperature limits**
Housing protection class IP
phase/voltage [50Hz/VAC]
phase/voltage [50Hz/VAC]
power/current[kW/A]
fan speed[min-1]
power/current[kW/A]
fan speed[min-1]
exhaust/supply
RALwhite
0.9 EKO 3.0 1.6 EKO 3.0 3.0 EKO 3.0
~1, 230~1, 230~1, 230
[kW]
[kW/A]
[mm]
[kg]
°C
0,91,63,0
0,085/0,73
0,085/0,73
1,07/5,50 1,77/8,503,17/14,50
* Calculated according EN 13141-7.
**For temperatures lower than recommended, use electrical pre-heater
to ensure balanced operation.
V [m3/h]
V [l/s]
~1, 230
3200
3200
M5/F7
30
9016
74
-5 - +40
34
66
Temperature eciency (balanced mass ow) EN 13141-7:
Lwa total,
dB(A)
125 Hz 250 Hz 500 Hz 1 kHz 2 kHz 4 kHz 8 kHz
V [m3/h]
RIS 400PE EKO 3.0
Supply6754596458575447
Extract5848505351484641
Surrounding5140434645403936
Measured at 395 m3/h, 100 Pa
The company reserves the right to make changes of technical data without prior notice
Extract air = 20°C/60%RH
Outdoor air = -7°C / 2°C / 7°C
LWA, dB(A)
RIS P EKO
50%
50%
RIS 400PW EKO 3.0
Supply air
Δ Pstat [Pa]Δ Pstat [Pa]
Exhaust air
Performance
Power consumption
V [l/s]
V [m3/h]
V [l/s]
P [W]
P [W]
AIR HANDLING UNITS
RIS 400PW EKO 3.0
Specic fan power
Δ Pstat [Pa]
total power for supply & exhaust fans kW
SFP=
air ow m3/h
Temperature eciency
η [%]
x 3600
View from inspection side
Extract airExhaust airOutdoor airSupply air
Article No.Version
GAGRIS1748_0019A400PW EKO 3.0 Optional water heater
fan speed[min-1]3200
Thermal eciency up to*90%
Motorized by-pass+
Max power consumption [kW/A]0,17/1,50
Control boardPRV V2
Filter classexhaust/supplyM5/F7
Housing insulation, mineral wool[mm]30
ColourRALwhite9016
Weight (net, without packing) [kg]73
Comply with ERP2016; 2018
Operationindoors
Fresh air temperature limits**°C-5 - +40
Housing protection classIP34
* Calculated according EN 13141-7.
**For temperatures lower than recommended, use electrical pre-heater
to ensure balanced operation.
V [m3/h]
V [l/s]
400PW EKO 3.0
Temperature eciency (balanced mass ow) EN 13141-7:
Outdoor air = -7°C / 2°C / 7°C
LWA, dB(A)
V [m3/h]
RIS 400PW EKO 3.0
Supply6754596458575447
Extract5848505351484641
Surrounding5140434645403936
Measured at 395 m3/h, 100 Pa
Lwa total,
dB(A)
125 Hz 250 Hz 500 Hz 1 kHz 2 kHz 4 kHz 8 kHz
The company reserves the right to make changes of technical data without prior notice
Thermal eciency up to*90%
Motorized by-pass+
Max power consumption
Control boardPRV V2
Filter class
Housing insulation, mineral wool
Colour
Weight (net, without packing)
Comply with ERP2016;2018
Operationindoors
Fresh air temperature limits**
Housing protection class IP
phase/voltage [50Hz/VAC]
phase/voltage [50Hz/VAC]
power/current[kW/A]
fan speed[min-1]
power/current[kW/A]
fan speed[min-1]
exhaust/supply
RALwhite
* Calculated according EN 13141-7.
**For temperatures lower than recommended, use electrical pre-heater
to ensure balanced operation.
air ow m3/h
The company reserves the right to make changes of technical data without prior notice
x 3600
V [m3/h]
V [l/s]
V [m3/h]
Temperature eciency (balanced mass ow) EN 13141-7:
RIS 700PE EKO 3.0
Supply7564666870666059
Extract6253555756524945
Surrounding5645475050474342
Measured at 700 m3/h, 100 Pa
Lwa total,
dB(A)
View from inspection side
1.2 EKO 3.0 3.0 EKO 3.0 4.5 EKO 3.0
~1, 230~1, 230~3, 400
[kW]
[kW/A]
[mm]
[kg]
°C
125 Hz 250 Hz 500 Hz 1 kHz 2 kHz 4 kHz 8 kHz
1,23,04,5
~1, 230
0,168/1,4
3230
0,168/1,4
3230
1,54/8,34 3,34/15,844,84/9,3
M5/F7
30
9016
103,5104104,5
-5 - +40
34
Extract air = 20°C/60%RH
Outdoor air = -7°C / 2°C / 7°C
LWA, dB(A)