Application Ventilation of houses, oces or other heated premises (classrooms, apartments, conference rooms, etc.)
Description
AIR HANDLING UNITS
A1/L2
1900
1200
700
V [m3/h]
RIS V EKO 3.0 is a range of heat recovery units with high-eciency counter-ow heat exchangers and vertical duct connections. Units are designed for placement on the oor. Due to vertical ducting, the units are
suitable for installation in various premises (basements, boiler rooms, etc). There are 4 sizes (airow interval
700-2200 m3/h) with left/right connection sides.
RIS V EKO 3.0 units have high overall energy savings due to the highly ecient heat recovery (up to 90%),
quiet and economical EC fans, eective low-pressure-drop lters and top-level of air tightness.
Energy eciency ensures full thermal comfort for passive houses, without an additional pre-heater at
temperatures above -5°C.
All the RIS V EKO 3.0 units are fully equipped with automatic controls. Optional external sensors for CO2
and humidity and so the event planning feature will help to control automatically your climate (demandlevel control).
RIS V EKO 3.0 units are service-friendly and are easy to mount. Filter pollution may be identied by timers
or contamination controls (RIS 1200-2200 V EKO 3.0).
All units are supplied tested and ready to install.
Three remote control options are available:
Remote control
Features
Construction
1. Flex, Stouch or Ptouch remote controllers.
2. Building management system connections.
3. Remote control via PC MB-Gateway.
› Vertical mounting with left/right versions.
› Ready for Passive House technology: high eciency.
› Easy and quick mounting.
› Water/electrical heating options.
› Fully integrated plug-and-play control system.
› Construction from double-skinned steel, with powder coated paint, panels.
› Acoustic and thermal wall insulation: RIS 700 V EKO 3.0 – 30 mm, RIS1200-2200 V EKO 3.0 – 50 mm.
› RIS 700 V EKO 3.0 powder-coated white housing RAL 9016; RIS 1200–2200 V EKO 3.0 powder-coated
grey housing RAL 7040.
› Integrated electrical heater or optional water heater/cooler on the duct.
› Low-pressure-drop lters: F7/M5.
› Hinged door with locks grants easy access to internal components by.
› Stainless steel condensate tray.
› Fitted with mounting brackets (optional).
› Integrated anti-frost pressure switch (RIS 1200-2200 V EKO 3.0).
RIS 700 V E L EKO 3.0
Equipped with new PRV V2 control board
AHU with EC motors and ecient heat exchanger
Air intake side (L - left; R - right)
Heater type (E - integrated electrical heater; W - prepared for water heater)
Housing type (V - vertical, H - horizontal, P - ceiling)
AHU size according to maximum airow range m3/h
AHU with plate heat exchanger
80
The company reserves the right to make changes of technical data without prior notice
RIS 700VE EKO 3.0 (vertical) version with electrical heater
AVA
IV - exhaust air fan
PV - supply air fan
PR - plate heat exchanger
KE - electrical heater
PF - lter for fresh air (class M5)
IF - lter for extract air (class M5)
M1 - actuator of by-pass damper
TL - temperature sensor for fresh air
TJ - temperature sensor for supply air
TE - temperature sensor for exhaust air
DTJ 100.1 - humidity + temperature sensor
EKA NV PH -optional fresh air pre-heater
AVA - optionally supplied water cooler
IV - exhaust air fan
PV - supply air fan
PR - plate heat exchanger
KE - electrical heater
PF - lter for fresh air (class F7)
IF - lter for extract air (class M5)
M1 - actuator of by-pass damper
TE - temperature sensor for exhaust air
TL - temperature sensor for fresh air
TJ - temperature sensor for supply air
DTJ100.1 - humidity + temperature sensor
PS1 - supply air dierential pressure switch
PS2 - extract air dierential pressure switch
PS3 - heat exchanger antifrost pressure switch
EKA NV PH -optional fresh air pre-heater
AVA - optionally supplied water cooler
86
The company reserves the right to make changes of technical data without prior notice
RIS 700VW EKO 3.0 (vertical) version with water heater
AVA
EKANV
PH
DTJ
100.1
AVS - optionally supplied water heater
AVA - optionally supplied water cooler
IV - exhaust air fan
PV - supply air fan
PR - plate heat exchanger
PF - lter for fresh air (class M5)
IF - lter for extract air (class M5)
M1 - actuator of by-pass damper
M6 - optionally supplied mixing valve and motor
M4 - water heater circulation pump
TJ - temperature sensor for supply air
TE - temperature sensor for exhaust air
TL - temperature sensor for fresh air
DTJ 100.1 - humidity + temperature sensor
TV - antifrost sensor
T1 - antifrost thermostat
EKA NV PH -optional fresh air pre-heater
RIS V EKO
AIR HANDLING UNITS
RIS 1200VW EKO 3.0 (vertical) version with water heater
AVA
PS3
EKANV
PH
DTJ
100.1
AVS - optionally supplied water heater
AVA - optionally supplied water cooler
IV - exhaust air fan
PV - supply air fan
PR - plate heat exchanger
PF - lter for supply air (class F7)
IF - lter for extract air (class M5)
M1 - actuator of by-pass damper
M4 -
optionally supplied
pump
M6 - optionally supplied mixing valve and motor
TJ - temperature sensor for supply air
TE - temperature sensor for exhaust air
TL - temperature sensor for fresh air
TV - antifrost sensor
T1 - antifrost thermostat
DTJ100.1 - humidity + temperature sensor
PS1 - supply air dierential pressure switch
PS2 - extract air dierential pressure switch
PS3 - heat exchanger antifrost pressure switch
EKA NV PH -optional fresh air pre-heater
water heater circulation
The company reserves the right to make changes of technical data without prior notice
87
RIS V EKO
RIS 1900VW EKO 3.0 / RIS 2200VW EKO 3.0 (vertical) versions with water heater
AIR HANDLING UNITS
AVA
TE
PS3
EKANV
PH
DTJ
100.1
AVS - optionally supplied water heater
AVA - optionally supplied water cooler
IV - exhaust air fan
PV - supply air fan
PR - plate heat exchanger
PF - lter for supply air (class F7)
IF - lter for extract air (class M5)
TL - temperature sensor for fresh air
TE - temperature sensor for exhaust air
M1 - actuator of by-pass damper
M6 - optionally supplied mixing valve and motor
M4 -
optionally supplied
water heater circulation
pump
TJ - temperature sensor for supply air
TV - antifrost sensor
T1 - antifrost thermostat
DTJ100.1 - humidity + temperature sensor
PS1 - supply air dierential pressure switch
PS2 - extract air dierential pressure switch
PS3 - heat exchanger antifrost pressure switch
EKA NV PH -optional fresh air pre-heater
88
The company reserves the right to make changes of technical data without prior notice
FUNCTIONS
Description of the functions
Functions
Date and time settings
4 speeds for easy and user-friendly control (“Stop” – the unit is stopped; “Low”, medium”, and “High”. Service menu allows adjusting each
BOOST function (Fans operate at highest speed)
Comfortable air temperature function
User and service control levels
CO2 level indication and reduction function
Relative humidity (RH) level indication and reduction function
Software and conguration update possibility